You are on page 1of 1

Project Name: Camp-2,Galfar IN-House Project Standby Hours: 24

Project ID: CAMP-2-SLD-FA Alarm Mins: 15


Prepared By: Viswanath Derating Factor: 1.2
Date: 23-Mar-2022 Number of Loop: 4

Addressable Fire Alarm Panel


Panel ID: AA504 Model: AA504 (4-Loop Panel)
Location: Accommodation Block-A

Current Draw
Model Description Qty REFERENCE
Standby Alarm
AA504 Control Panel 1 0.420 2.700
DD501 Smoke Detector 182 0.127 0.364 NFPA 72 : 2007 ; 4.4.1.5.30* Capacity
DD502 Heat Detector 14 0.010 0.028 1. The Fire Alarm Systems require 24 Hours of Standby
CP312 Manual Call Point 38 0.027 0.114 time and in alarm for 5 minutes (Evacuate)
SA340A Sounder 25 0.018 0.075 2. The Fire Alarm Systems require 24 Hours of Standby
SA340 Sounder -W/P 1 0.001 0.003 time and in alarm for 15 minutes (Emergency Voice/Alarm
ST805 Sounder base 124 0.087 0.372 3. Auxiliary and Remote Station Fire Alarm System require
S-A4045 Input/Output Module 2 0.001 0.006 60 Hours of Standby time
0 0.000 0.000
0 0.000 0.000 BS 5839 Part 1
0 0.000 0.000 1. The Fire Alarm Systems require 24 Hours of Standby
0 0.000 0.000 time and in alarm for 30 minutes (Evacuate/ Emergency
0 0.000 0.000 Voice)
0 0.000 0.000
0 0.000 0.000
Total Standby Current (Amps) 0.690 3.662 Total Alarm Current (Amps)
Standby Time In Hours 24 0.250 Alarm Time In Minutes / 60 (15 Mins)
Total Standby AH Require d 16.565 0.916 Total Alarm AH Required
Total Combined AH Required 17.48
Multiply By The Derating Factor 1.20
Minimum Battery AmpHours Required 20.98

Wire resistance is taken from Chapter 9 Table 8 of the National Electric Code (NFPA70).