BATTERY CAPACITY CALCULATION.


The following battery capacity calculation are base on specification set for the Fire
Alarm System to be operational during main AC and essential power supply failure.
Capacity of this 24V DC standby battery set shall be satisfied the following 2
condition:-

a) 72 hours full system operational during main AC and essential power supply failure.
b) 3 hours alarm load, i.e. bells/sounders energisation and control outputs actuation.

Assumptions:
a) Total alarm zones actuation shall not be more than 10 zones at any one time.
b) Battery effectiveness is only 80%.

MAIN FIRE ALARM PANEL


LOCATION : RECEPTION

Item Description Total Current (A) Standby Total battery


quantity per unit hours (H) capacity (AH)

1 CPU Central controller 1 0.25 72 18

2 Alarm zone sensing current 15 0.0015 72 1.62

3 Alarm zone actuation current 5 0.025 72 9

4 Bell ringing 4 0.06 3 0.72

29.34
Add 10% safety factor 32.27

Therefore battery capacity shall be 32.27 x (100/80) AH


= 40.34 AH

Hence, battery capacity = 40 AH

BATTERY B/1 PERUNDING AZFAR


CADANGAN UBAHSUAI DALAMAN 1 UNIT KEDAI PEJABAT 3 TINGKAT KEPADA
HOTEL BAJET PADA TINGKAT 1, 2 & SEBAHAGIAN TINGKAT BAWAH, NO. PT 435,
H.S(D) 18061, NO. P36 PUSAT PERNIAGAAN MUTIARA GEMILANG, MUKIM &
DAERAH BENTONG, PAHANG DARUL MAKMUR UNTUK TETUAN YES LUXURY
HOTEL SDN BHD

BATTERY CAPACITY CALCULATION.

The following battery capacity calculation are base on specification set for the Fire Alarm System to be
operational during main AC and essential power supply failure. Capacity of this 24V DC standby battery set
shall be satisfied the following 2 condition:-

a) 72 hours full system operational during main AC and essential power supply failure.
b) 3 hours alarm load, i.e. bells/sounders energisation and control outputs actuation.

Assumptions:
a) Total alarm zones actuation shall not be more than 10 zones at any one time.
b) Battery effectiveness is only 80%.

Item Description Total Current (A) Standby Total battery


quantity per unit hours (H) capacity (AH)

1 CPU Central Controller 1 0.25 72 18

2 Alarm zone sensing current 10 0.0015 72 1.08

3 Bell ringing 4 0.06 3 0.72

19.8
Add 20% safety factor 23.76

Therefore battery capacity shall be 23.76 x (100/80) AH


29.7 AH

Hence, battery capacity selection ≈ 40 AH