CABLE INDENTIFICATION
E/F XX C / CT / VT XXX
Alphabet represents the Voltage Level (e.g. 'E' 132kV and 'F' For 11kV)
DCDB1/2 XXX
HLDB XXX
Three numerical represents cable number
TYPES OF CABLES
Rev.2 Page 1 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2
2 DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV M1BZP Panel DZ1 2C x 6 mm Red & Black 20*
Rev.2 Page 2 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
Rev.2 Page 3 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
Rev.2 Page 4 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
Rev.2 Page 5 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
Rev.2 Page 6 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2
53 M1BZP C001 Check Zone Operated DC 2 132kV M1BZP Panel-CZ 132kV DFR Panel-2 4C x 2.5 mm White 20*
Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Rev.2 Page 7 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Centralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
AC Incoming Supply (Heater & 2 Red, Yellow,
1 HLDB xxx AC 4 HLDB 132kV M2BZP Panel-1 4C x 4 mm 20
Lighting circuit) Blue & Black
2
2 DCDB2 xxx DC Incoming Supply-1 DC 2 DCDB-2 132kV M2BZP Panel-1 2C x 6 mm Red & Black 20
2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV M2BZP Panel-2 2C x 6 mm Red & Black 20
2 Red, Yellow,
5 E01 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 132kV LCC 4C x 4 mm 20*
Blue & Black
E01
132kV LCC 2
6 E01 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E01
132kV LCC 2
9 E02 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E02
132kV LCC 2
12 E03 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E03
Rev.2 Page 8 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Centralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV Relay Panel
50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E04 2
13 E04 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E04
132kV LCC 2
15 E04 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E04
132kV LCC 2
18 E05 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E05
132kV LCC 2
22 E06 C010 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E06
Rev.2 Page 9 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Centralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV LCC 2 Red, Yellow,
24 E07 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E07 Blue & Black
132kV LCC 2
25 E07 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E07
132kV LCC 2
28 E08 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E08
132kV LCC 2
31 E09 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E09
132kV LCC 2
34 E10 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E10
2
35 M2BZP C001 M2BZP Zone1 & 2 Operated DC 3 132kV M2BZP Panel-1 132kV DFR Panel - 2 4C x 2.5 mm White 20
Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Rev.2 Page 10 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Decentralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
AC Incoming Supply (Heater & 2 Red, Yellow,
1 HLDB xxx AC 4 HLDB 132kV M2BZP Panel-1 4C x 4 mm 20
Lighting circuit) Blue & Black
2
2 DCDB2 xxx DC Incoming Supply-1 DC 2 DCDB-2 132kV M2BZP Panel-1 2C x 6 mm Red & Black 20
2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV M2BZP Panel-2 2C x 6 mm Red & Black 20
2 Red, Yellow,
5 E01 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 132kV LCC 4C x 4 mm 20*
Blue & Black
E01
132kV LCC 2
6 E01 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E01
132kV LCC 2
9 E02 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E02
132kV LCC 2
12 E03 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E03
Rev.2 Page 11 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Decentralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV Relay Panel
50BF2 Back Trip DC 6 132kV M2BZP Panel-1
E04 2
13 E04 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-1
E04
132kV LCC 2
15 E04 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E04
132kV LCC 2
18 E05 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E05
132kV LCC 2
22 E06 C010 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E06
Rev.2 Page 12 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Decentralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV LCC 2 Red, Yellow,
24 E07 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E07 Blue & Black
132kV LCC 2
25 E07 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E07
132kV LCC 2
28 E08 C030 Islolator Status (M2BZ) DC 6 132kV M2BZP Panel-2 7C x 2.5 mm White 20*
E08
132kV LCC 2
31 E09 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E09
132kV LCC 2
34 E10 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E10
2
35 M2BZP C001 M2BZP Zone1 & 2 Operated DC 3 132kV M2BZP Panel-1 132kV DFR 4C x 2.5 mm White 20
Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Rev.2 Page 13 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2
2 DCDB1 xxx DC Incoming Supply DC 2 DCDB-1 132kV DFR Panel-1 2C x 6 mm Red & Black 20*
2 Red, Yellow,
6 E01 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-X 132kV LCC-E01 4C x 4 mm 20* Future Bay
Blue & Black
2 Red, Yellow,
7 E01 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-X 132kV LCC-E01 4C x 2.5 mm 20* Future Bay
Blue & Black
2
8 E01 C012 CB Status (for DFR) DC 2 132kV DFR Panel-X 132kV LCC-E01 4C x 2.5 mm White 20S* Future Bay
2 Red, Yellow,
10 E02 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-1 132kV LCC-E02 4C x 4 mm 20*
Blue & Black
2
11 E02 C031 CB Status (for DFR) DC 2 132kV DFR Panel-1 132kV LCC-E02 4C x 2.5 mm White 20S*
2 Red, Yellow,
12 Fxx CT02 DFR CT Circuit (LV) CT 4 132kV DFR Panel-1 11kV SWGR- INCOMER-1 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
13 FxxVT01 DFR VT Circuit (LV) VT 4 132kV DFR Panel-1 11kV SWGR.-INCOMER -1 4C x 2.5 mm 20*
Blue & Black
Rev.2 Page 14 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2 Red, Yellow,
16 E03 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-1 132kV LCC-E03 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
17 E03 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-1 132kV LCC-E03 4C x 2.5 mm 20*
Blue & Black
2
18 E03 C012 CB Status (for DFR) DC 2 132kV DFR Panel-1 132kV LCC-E03 4C x 2.5 mm White 20S*
2 Red, Yellow,
20 E04 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E04 4C x 4 mm 20*
Blue & Black
2
21 E04 C031 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E04 4C x 2.5 mm White 20S*
2 Red, Yellow,
22 Fxx CT02 DFR CT Circuit (LV) CT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-2 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
23 FxxVT01 DFR VT Circuit (LV) VT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-2 4C x 2.5 mm 20*
Blue & Black
Rev.2 Page 15 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
Applicable for
Main-1 & Main2 Protection 132kV Feeder Reactor Relay 2
26 E05 C018 DC 3 132kV DFR Panel-1 4C x 2.5 mm White 20S* Feeder with
Opereated to trigger DFR panel-E05
Reactor
2 Red, Yellow,
27 E05 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-1 132kV LCC-E05 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
28 E05 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-1 132kV LCC-E05 4C x 2.5 mm 20*
Blue & Black
2
29 E05 C012 CB Status (for DFR) DC 2 132kV DFR Panel-1 132kV LCC-E05 4C x 2.5 mm White 20S*
2 Red, Yellow,
31 E06 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E06 4C x 4 mm 20*
Blue & Black
2
32 E06 C011 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E06 4C x 2.5 mm White 20S*
Applicable for
Main-1 & Main2 Protection 132kV Feeder Reactor Relay 2
34 E07 C018 DC 3 132kV DFR Panel-2 4C x 2.5 mm White 20S* Feeder with
Opereated to trigger DFR panel-E07
Reactor
2 Red, Yellow,
35 E07 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E07 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
36 E07 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-2 132kV LCC-E07 4C x 2.5 mm 20*
Blue & Black
2
37 E07 C012 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E07 4C x 2.5 mm White 20S*
Rev.2 Page 16 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2 Red, Yellow,
39 E08 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E08 4C x 4 mm 20*
Blue & Black
2
40 E08 C031 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E08 4C x 2.5 mm White 20S*
2 Red, Yellow,
41 Fxx CT02 DFR CT Circuit (LV) CT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-3 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
42 Fxx VT01 DFR VT Circuit (LV) VT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-3 4C x 2.5 mm 20*
Blue & Black
2 Red, Yellow,
45 E09 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E09 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
46 E09 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-2 132kV LCC-E09 4C x 2.5 mm 20*
Blue & Black
2
47 E09 C012 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E09 4C x 2.5 mm White 20S*
Rev.2 Page 17 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2 Red, Yellow,
49 E1 0 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-X 132kV LCC-E10 4C x 4 mm 20* Future Bay
Blue & Black
2 Red, Yellow,
50 E10 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-X 132kV LCC-E10 4C x 2.5 mm 20* Future Bay
Blue & Black
2
51 E1 0C012 CB Status (for DFR) DC 2 132kV DFR Panel-X 132kV LCC-E10 4C x 2.5 mm White 20S* Future Bay
LVAC PANEL 2
52 DFRC001 LVAC Protn Operated DC 2 132kV DFR Panel-1 4C x 2.5 mm White 20*S
(Cubicle -2)
LVAC PANEL 2
53 DFRC002 LVAC Protn Operated DC 2 132kV DFR Panel-2 4C x 2.5 mm White 20*S
(Cubicle -4)
LVAC PANEL 2
54 DFRC003 LVAC Protn Operated DC 2 132kV DFR Panel-2 4C x 2.5 mm White 20*S
(Cubicle -8)
2
55 DFRC004 Fault Recorder Operated DC 4 132kV DFR Panel-2 SCS Panel 7C x 2.5 mm White 20*S
Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
-E01 and E10 are considered as Future Bays
-All Feeder Bay are considered with Reactor
Rev.2 Page 18 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Protection Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description Equipment Description Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
material)
2
2 DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV Feeder Relay panel 2C x 6 mm Red & Black 20*
2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV Feeder Relay panel 2C x 6 mm Red & Black 20*
2 Red, Yellow,
4 Exx CT01 Main-1 CT Circuit CT 4 132kV Feeder Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
5 Exx CT02 Main-2 CT Circuit CT 4 132kV Feeder Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
6 Exx VT01 Main-1 VT Circuit VT 4 132kV Feeder Relay panel 132kV LCC 4C x 2.5 mm 20*
Blue & Black
2 Red, Yellow,
7 Exx VT02 Main-2 VT Circuit VT 4 132kV Feeder Relay panel 132kV LCC 4C x 2.5 mm 20*
Blue & Black
132kV LCC
CB Trip Coil-1 DC 4 132kV Feeder Relay panel
2
8 Exx C001 12C x 2.5 mm White 20*
132kV LCC
SF6 Lockout-1 DC 4 132kV Feeder Relay panel
2
10 Exx C003 CB Close Interlock DC 2 132kV Feeder Relay panel 132kV LCC 12C x 2.5 mm White 25*
Rev.2 Page 19 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Protection Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description Equipment Description Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
material)
Applicable only
2
14 Exx C013 Cable box oil pressure Low/High Trip DC 3 132kV Feeder Relay panel Cable box Oil pressure device 4C x 2.5 mm White 20S* if available (oil
filled cables)
Applicable only
2
15 Exx C014 Cable box oil Low/High Alarm DC 2 132kV Feeder Relay panel Cable box Oil pressure device 4C x 2.5 mm White 20S* if available (oil
filled cables)
Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Cables from 132kV Feeder panel to DFR panel, M1BZP panel and M2BZP panel are available in DFR panel, M1BZP panel and M2BZP panel cable schedule
Rev.2 Page 20 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Reactor Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
1
132kV Feeder Reactor Relay 2
DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 2C x 6 mm Red & Black 20*
panel
2
132kV Feeder Reactor Relay 2
DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 2C x 6 mm Red & Black 20*
panel
Main-1 CT Circuit (Reactor Neutral 132kV Feeder Reactor Relay 2 Red, Yellow,
4 Exx CT02 CT 4 Reactor-MK 4C x 4 mm 20*
Side) panel Blue & Black
This cable is
not applicable
if M2RP is
Main-2 CT Circuit (Reactor Neutral 132kV Feeder Reactor Relay 2 Red, Yellow,
7 Exx CT05 CT 4 Reactor-MK 4C x 4 mm 20* High
Side) panel Blue & Black
Impedance
REF.
Protection
Rev.2 Page 21 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Reactor Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Cables from 132kV Feeder Reactor panel to DFR panel available in DFR panel cable schedule
Rev.2 Page 22 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)
2
2 DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV IDT Relay panel 2C x 6 mm Red & Black 20*
2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV IDT Relay panel 2C x 6 mm Red & Black 20*
2 Red, Yellow,
4 Exx CT01 Main-1 CT Circuit CT 4 132kV IDT Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
5 Exx CT02 Main-2 CT Circuit CT 4 132kV IDT Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black
2
8 Exx CT10 M1 ET Nutral CT Circuit (ET-MK) CT 2 132kV IDT Relay panel ET-MK 2C x 4 mm Red & Black 20*
2
9 Exx CT11 M2 ET Nutral CT Circuit (ET-MK) CT 2 132kV IDT Relay panel ET-MK 2C x 4 mm Red & Black 20*
2 Red, Yellow,
10 Exx CT12 Main-1 CT Circuit CT 4 132kV IDT Relay panel 11kV Swgr. Incomer 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
11 Exx CT13 Main-2 CT Circuit CT 4 132kV IDT Relay panel 11kV Swgr. Incomer 4C x 4 mm 20*
Blue & Black
Rev.2 Page 23 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)
2
12 Exx C001 12C x 2.5 mm White 20*
2
13 Exx C002 MAIN 1 CB Status DC 4 132kV IDT Relay panel 132kV LCC 7C x 2.5 mm White 20*
2
14 Exx C003 CB Close Interlock DC 2 132kV IDT Relay panel 132kV LCC 12C x 2.5 mm White 25*
2
15 Exx C004 12C x 2.5 mm White 20*
2
16 Exx C005 MAIN 2 CB Status DC 4 132kV IDT Relay panel 132kV LCC 7C x 2.5 mm White 20*
2
17 Exx C006 CB Open relay (TC-2) DC 3 132kV IDT Relay panel 132kV LCC 4C x 2.5 mm White 20S*
Rev.2 Page 24 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)
2
26 Exx C018 M1IDTP Trip Intertrip Send DC 3 132kV IDT Relay panel LVAC 4C x 2.5 mm White 20S*
Trip & 50BF Initi. From LVAC DC 3 132kV IDT Relay panel LVAC
2
27 Exx C019 M2IDTP Trip Intertrip Send DC 3 132kV IDT Relay panel LVAC 12C x 2.5 mm White 25*
2
28 Exx C020 11kV Incomer CBF Protn. Optd.- M1 DC 4 132kV IDT-1 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*
2
29 Exx C021 11kV Incomer CBF Protn. Optd.- M2 DC 4 132kV IDT-1 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*
Rev.2 Page 25 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)
2
30 Exx C020 11kV Incomer CBF Protn. Optd.- M1 DC 4 132kV IDT-3 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*
2
31 Exx C021 11kV Incomer CBF Protn. Optd.- M2 DC 4 132kV IDT-3 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*
2
32 Exx C020 11kV Incomer CBF Protn. Optd..- M1 DC 4 132kV IDT-2 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*
2
33 Exx C021 11kV Incomer CBF Protn. Optd..- M2 DC 4 132kV IDT-2 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*
2
34 Exx C022 11kV Incomer CBF Protn. Optd..- M1 DC 4 132kV IDT-2 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*
2
35 Exx C023 11kV Incomer CBF Protn. Optd..- M2 DC 4 132kV IDT-2 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*
2
36 Exx C024 7C x 2.5 mm White 20*
2
37 Exx C025 7C x 2.5 mm White 20*
CB Close Interlock - 11kV CB DC 2 132kV IDT Relay panel 11kV Swgr. Incomer
2
38 Exx C026 7C x 2.5 mm White 20*
CB Close Interlock - Alarm DC 3 132kV IDT Relay panel 11kV Swgr. Incomer
Note: * In accordance with BS:6121 actual cable dimensions must be used for gland selection
Cables from DFR panel, M1BZP panel, M2BZP panel and 11kV BZP are available in DFR panel, M1BZP panel M2BZP panel and 11kV BZP cable schedule
Rev.2 Page 26 Of 28
132/11kV Substation Standard Cable Schedule
132kV Bus Coupler Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
1
2
DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV BC Relay panel 2C x 6 mm Red & Black 20*
2
2
DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV BC Relay panel 2C x 6 mm Red & Black 20*
2 Red, Yellow,
3 Exx CT01 Main-1 CT Circuit CT 4 132kV BC Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black
2 Red, Yellow,
4 Exx CT02 Main-2 CT Circuit CT 4 132kV BC Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black
2
5 Exx C001 12C x 2.5 mm White 20*
2
6 Exx C002 MAIN 1 CB Status DC 4 132kV BC Relay panel 132kV LCC 7C x 2.5 mm White 20*
2
7 Exx C003 CB Close Interlock DC 2 132kV BC Relay panel 132kV LCC 12C x 2.5 mm White 25*
Rev.2 Page 27 Of 28
132/11kV Substation Standard Cable Schedule
132kV Bus Coupler Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
2
8 Exx C004 12C x 2.5 mm White 20*
2
9 Exx C005 MAIN 2 CB Status DC 4 132kV BC Relay panel 132kV LCC 7C x 2.5 mm White 20*
2
10 Exx C006 CB Open relay (TC-2) DC 3 132kV BC Relay panel 132kV LCC 4C x 2.5 mm White 20S*
Note:
* In accordance with BS:6121 actual cable dimensions* In
must
accordance
be used for
with
gland
BS:6121
selection
actual cable dimensions must be used for gland selection
Cables from DFR panel, M1BZP panel, M2BZP panel and 11kV BZP are available in DFR panel, M1BZP panel M2BZP panel and 11kV BZP cable schedule
Rev.2 Page 28 Of 28