132/11kV Substation Standard Cable Schedule

CABLE INDENTIFICATION

E/F XX C / CT / VT XXX

Three numerical represents cable number

Alphabet 'C' represents control / Protection / Signalling / Metering / Indication,


and 'CT' Represents Current Transformer Cables and 'VT' Represents Voltage

Two numerical represents Bay / Feeder Reference (Note:'00' Represents no Bay


Identification)

Alphabet represents the Voltage Level (e.g. 'E' 132kV and 'F' For 11kV)

DCDB1/2 XXX

Three numerical represents cable number

Cable from DCDB1 / DCDB2

HLDB XXX
Three numerical represents cable number

Heating & Lighting Distribution for Panels

TYPES OF CABLES

For Power Cables (main DC supply from DCDB) - XLPE

For Power Cables (main LVAC supply from ACDB)- XLPE

For CT/VT Circuits - XLPE / PVC

For DC Circuits (control /Tripping/Alarm)- PVC

Rev.2 Page 1 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

AC Incoming Supply (Heater & 2 Red, Yellow,


1 HLDB xxx AC 4 HLDB 132kV M1BZP Panel DZ1 4C x 4 mm 20*
Lighting circuit) Blue & Black

2
2 DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV M1BZP Panel DZ1 2C x 6 mm Red & Black 20*

132kV M1BZP Panel


2
3 DCDB1 xxx DC Incoming Supply-2 DC 2 DCDB-1 2C x 6 mm Red & Black 20*
DZ-2

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ1 E01
4 E01 C007 19C x 2.5 mm2 White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ1 E01

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
5 E01 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E01

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
6 E01 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E01

132kV M1BZP Panel


132kV LCC 2 Red, Yellow,
7 E01 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ
E01

132kV M1BZP Panel 132kV LCC


2
8 E01 C010 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ1 E01

132kV Relay panel


132kV M1BZP Panel
50BF1 Back Trip DC 6
E02
DZ1 2
9 E02 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ1 E02

132kV M1BZP Panel


132kV LCC
2 Red, Yellow,
10 E02 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
DZ1 Blue & Black
E02

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
11 E02 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E02

Rev.2 Page 2 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
12 E02 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E02

132kV M1BZP Panel 132kV LCC


2
13 E02 C029 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ1 E02

132kV Relay panel


50BF1 Back Trip DC 6 132kV M1BZP Panel
DZ1 E03
2
14 E03 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ1 E03

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
15 E03 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E03

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
16 E03 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E03

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
17 E03 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E03

132kV M1BZP Panel 132kV LCC


2
18 E03 C010 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ1 E03

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ1 E04
2
19 E04 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ1 E04

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
20 E04 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E04

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
21 E04 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E04

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
22 E04 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E04

Rev.2 Page 3 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

132kV M1BZP Panel 132kV LCC


2
23 E04 C029 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ1 E04

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ1 E05
2
24 E05 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ1 E05

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
25 E05 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E05

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
26 E05 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E05

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
27 E05 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E05

132kV M1BZP Panel 132kV LCC


2
28 E05 C010 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ1 E05

132kV M1BZP Panel 132kV Relay panel


2
29 E06 C07A 50BF1 Back Trip DC 6 7Cx 2.5 mm White 20*
DZ1 E06

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 3
DZ2 E06
2
30 E06 C07B 12C x 2.5 mm White 25*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ2 E06

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
31 E06 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E06

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
32 E06 CT05 M1BZP CT Circuit - DZ2 CT 4 4C x 4 mm 20*
Blue & Black
DZ2 E06

Rev.2 Page 4 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ2 E07
2
33 E07 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ2 E07

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
34 E07 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E07

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
35 E07 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E07

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
36 E07 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E07

132kV M1BZP Panel 132kV LCC


2
37 E07 C010 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ2 E07

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ2 E08
2
38 E08 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ2 E08

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
39 E08 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E08

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
40 E08 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E08

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
41 E08 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E08

132kV M1BZP Panel 132kV LCC


2
42 E08 C029 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ2 E08

Rev.2 Page 5 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ2 E09
2
43 E09 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ2 E09

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
44 E09 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E09

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
45 E09 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E09

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
46 E09 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E09

132kV M1BZP Panel 132kV LCC


2
47 E09 C010 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ2 E09

132kV M1BZP Panel 132kV Relay panel


50BF1 Back Trip DC 6
DZ2 E10
2
48 E10 C007 19C x 2.5 mm White 32*
132kV M1BZP Panel 132kV Relay panel
TC-1 & CB Fail Initi. DC 7
DZ2 E10

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
49 E10 CT04 M1BZP CT Circuit - DZ1 CT 4 4C x 4 mm 20*
Blue & Black
DZ1 E10

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
50 E10 CT05 M1BZP CT Circuit - DZ2 CT 3 4C x 4 mm 20*
Blue & Black
DZ2 E10

132kV M1BZP Panel 132kV LCC


2 Red, Yellow,
51 E10 CT06 M1BZP CT Circuit - CZ CT 4 4C x 4 mm 20*
Blue & Black
CZ E10

132kV M1BZP Panel 132kV LCC


2
52 E10 C010 Islolator Status (M1BZP) DC 3 4C x 2.5 mm White 20*
DZ2 E10

Rev.2 Page 6 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-1 Busbar Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

2
53 M1BZP C001 Check Zone Operated DC 2 132kV M1BZP Panel-CZ 132kV DFR Panel-2 4C x 2.5 mm White 20*

Disc. Zone1 Operated & M1BZP Trip 2


53 M1BZP C002 DC 4 132kV M1BZP Panel-DZ1 132kV DFR Panel-2 7C x 2.5 mm White 25*
Relay Operated F94A.E06

Disc. Zone2 Operated & M1BZP Trip 2


54 M1BZP C003 DC 6 132kV M1BZP Panel-DZ2 132kV DFR Panel-2 7C x 2.5 mm White 25*
Relay Operated F94B.E06, F94.E08

M1BZP Trip Relay Operated


2
55 M1BZP C004 (F94.E01, F94.E02, F94.E03, DC 8 132kV M1BZP Panel-DZ1 132kV DFR Panel-1 12C x 2.5 mm White 25*
F94.E05)

M1BZP Trip Relay Operated 2


56 M1BZP C005 DC 2 132kV M1BZP Panel-DZ1 132kV DFR Panel-2 4C x 2.5 mm White 20*
(F94.E04)

M1BZP Trip Relay Operated 2


57 M1BZPC005 DC 4 132kV M1BZP Panel-DZ2 132kV DFR Panel-2 7C x 2.5 mm White 25*
(F94.E07, F94.E09)

M1BZP Trip Relay Operated 2


58 M1BZPC006 DC 2 132kV M1BZP Panel-DZ2 132kV DFR Panel-2 7C x 2.5 mm White 25*
(F94.E10)

132kV M1BZP Panel


BCU Faulty DC 3 132kV M2BZP Panel
CZ

132kV M1BZP Panel


2
59 M1BZPC007 M2BZP Faulty DC 3 132kV M2BZP Panel 12C x 2.5 mm White 25*
CZ

132kV M1BZP Panel


Panel AC MCB Trip DC 3 132kV M2BZP Panel
CZ

Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection

Rev.2 Page 7 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Centralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
AC Incoming Supply (Heater & 2 Red, Yellow,
1 HLDB xxx AC 4 HLDB 132kV M2BZP Panel-1 4C x 4 mm 20
Lighting circuit) Blue & Black

2
2 DCDB2 xxx DC Incoming Supply-1 DC 2 DCDB-2 132kV M2BZP Panel-1 2C x 6 mm Red & Black 20

2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV M2BZP Panel-2 2C x 6 mm Red & Black 20

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E01 2
4 E01 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E01

2 Red, Yellow,
5 E01 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 132kV LCC 4C x 4 mm 20*
Blue & Black
E01

132kV LCC 2
6 E01 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E01

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E02 2
7 E02 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E02

132kV LCC 2 Red, Yellow,


8 E02 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E02 Blue & Black

132kV LCC 2
9 E02 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E02

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E03 2
10 E03 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E03

132kV LCC 2 Red, Yellow,


11 E03 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E03 Blue & Black

132kV LCC 2
12 E03 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E03

Rev.2 Page 8 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Centralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV Relay Panel
50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E04 2
13 E04 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E04

132kV LCC 2 Red, Yellow,


14 E04 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E04 Blue & Black

132kV LCC 2
15 E04 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E04

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E05 2
16 E05 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E05

132kV LCC 2 Red, Yellow,


17 E05 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E05 Blue & Black

132kV LCC 2
18 E05 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E05

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E06
2
19 E06 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi. DC 7 132kV M2BZP Panel-2
E06

132kV LCC 2 Red, Yellow,


20 E06 CT06 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E06 Blue & Black

132kV LCC 2 Red, Yellow,


21 E06 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E06 Blue & Black

132kV LCC 2
22 E06 C010 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E06

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E07 2
23 E07 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E07

Rev.2 Page 9 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Centralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV LCC 2 Red, Yellow,
24 E07 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E07 Blue & Black

132kV LCC 2
25 E07 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E07

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E08 2
26 E08 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E08

132kV LCC 2 Red, Yellow,


27 E08 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E08 Blue & Black

132kV LCC 2
28 E08 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E08

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E09 2
29 E09 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E09

132kV LCC 2 Red, Yellow,


30 E09 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E09 Blue & Black

132kV LCC 2
31 E09 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E09

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Pane-2
E10 2
32 E10 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E10

132kV LCC 2 Red, Yellow,


33 E10 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E10 Blue & Black

132kV LCC 2
34 E10 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E10

2
35 M2BZP C001 M2BZP Zone1 & 2 Operated DC 3 132kV M2BZP Panel-1 132kV DFR Panel - 2 4C x 2.5 mm White 20

Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection

Rev.2 Page 10 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Decentralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
AC Incoming Supply (Heater & 2 Red, Yellow,
1 HLDB xxx AC 4 HLDB 132kV M2BZP Panel-1 4C x 4 mm 20
Lighting circuit) Blue & Black

2
2 DCDB2 xxx DC Incoming Supply-1 DC 2 DCDB-2 132kV M2BZP Panel-1 2C x 6 mm Red & Black 20

2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV M2BZP Panel-2 2C x 6 mm Red & Black 20

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-1
E01 2
4 E01 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-1
E01

2 Red, Yellow,
5 E01 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 132kV LCC 4C x 4 mm 20*
Blue & Black
E01

132kV LCC 2
6 E01 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E01

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-1
E02 2
7 E02 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-1
E02

132kV LCC 2 Red, Yellow,


8 E02 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E02 Blue & Black

132kV LCC 2
9 E02 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E02

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-1
E03 2
10 E03 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-1
E03

132kV LCC 2 Red, Yellow,


11 E03 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E03 Blue & Black

132kV LCC 2
12 E03 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel-1 7C x 2.5 mm White 20*
E03

Rev.2 Page 11 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Decentralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV Relay Panel
50BF2 Back Trip DC 6 132kV M2BZP Panel-1
E04 2
13 E04 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-1
E04

132kV LCC 2 Red, Yellow,


14 E04 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-1 4C x 4 mm 20*
E04 Blue & Black

132kV LCC 2
15 E04 C030 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -1 7C x 2.5 mm White 20*
E04

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E05 2
16 E05 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E05

132kV LCC 2 Red, Yellow,


17 E05 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Pane-2 4C x 4 mm 20*
E05 Blue & Black

132kV LCC 2
18 E05 C011 Islolator Status (M2BZP ) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E05

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E06
2
19 E06 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi. DC 7 132kV M2BZP Panel-2
E06

132kV LCC 2 Red, Yellow,


20 E06 CT06 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E06 Blue & Black

132kV LCC 2 Red, Yellow,


21 E06 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E06 Blue & Black

132kV LCC 2
22 E06 C010 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E06

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E07 2
23 E07 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E07

Rev.2 Page 12 Of 28
132/11kV Substation Standard Cable Schedule
132kV Main-2 Busbar Protection Panel (Decentralized)
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)
132kV LCC 2 Red, Yellow,
24 E07 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E07 Blue & Black

132kV LCC 2
25 E07 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E07

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E08 2
26 E08 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E08

132kV LCC 2 Red, Yellow,


27 E08 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E08 Blue & Black

132kV LCC 2
28 E08 C030 Islolator Status (M2BZ) DC 6 132kV M2BZP Panel-2 7C x 2.5 mm White 20*
E08

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E09 2
29 E09 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E09

132kV LCC 2 Red, Yellow,


30 E09 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E09 Blue & Black

132kV LCC 2
31 E09 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E09

132kV Relay Panel


50BF2 Back Trip DC 6 132kV M2BZP Panel-2
E10 2
32 E10 C008 19C x 2.5 mm White 32*
132kV Relay Panel
TC-2 & CB Fail Initi DC 7 132kV M2BZP Panel-2
E10

132kV LCC 2 Red, Yellow,


33 E10 CT07 M2BZP CT Circuit CT 4 132kV M2BZP Panel-2 4C x 4 mm 20*
E10 Blue & Black

132kV LCC 2
34 E10 C011 Islolator Status (M2BZP) DC 6 132kV M2BZP Panel -2 7C x 2.5 mm White 20*
E10

2
35 M2BZP C001 M2BZP Zone1 & 2 Operated DC 3 132kV M2BZP Panel-1 132kV DFR 4C x 2.5 mm White 20

Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection

Rev.2 Page 13 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

AC Incoming Supply (Heater & ACDB 2 Red, Yellow,


1 HLDB xxx AC 4 132kV DFR Panel-1 4C x 4 mm 20*
Lighting circuit) (HLDB) Blue & Black

2
2 DCDB1 xxx DC Incoming Supply DC 2 DCDB-1 132kV DFR Panel-1 2C x 6 mm Red & Black 20*

Main-1 & Main2 Protection


3 E01 C009 DC 3 132kV DFR Panel-X 132kV Feeder Relay panel-E01 4C x 2.5 mm2 White 20*S Future Bay
Opereated to trigger DFR

2 Red, Yellow,
6 E01 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-X 132kV LCC-E01 4C x 4 mm 20* Future Bay
Blue & Black

2 Red, Yellow,
7 E01 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-X 132kV LCC-E01 4C x 2.5 mm 20* Future Bay
Blue & Black

2
8 E01 C012 CB Status (for DFR) DC 2 132kV DFR Panel-X 132kV LCC-E01 4C x 2.5 mm White 20S* Future Bay

Main-1 & Main2 Protection 2


9 E02 C009 DC 3 132kV DFR Panel-1 132kV IDT Relay panel-E02 4C x 2.5 mm White 20S*
Opereated to trigger DFR

2 Red, Yellow,
10 E02 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-1 132kV LCC-E02 4C x 4 mm 20*
Blue & Black

2
11 E02 C031 CB Status (for DFR) DC 2 132kV DFR Panel-1 132kV LCC-E02 4C x 2.5 mm White 20S*

2 Red, Yellow,
12 Fxx CT02 DFR CT Circuit (LV) CT 4 132kV DFR Panel-1 11kV SWGR- INCOMER-1 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
13 FxxVT01 DFR VT Circuit (LV) VT 4 132kV DFR Panel-1 11kV SWGR.-INCOMER -1 4C x 2.5 mm 20*
Blue & Black

O/C EF Protection Operated DC 2 132kV DFR Panel-1 11kVSWGR-INCOMER-1

14 FxxC008 7C x 2.5 mm2 White 20S*

11kV Incomer CB Status DC 2 132kV DFR Panel-1 11kV SWGR-INCOMER-1

Rev.2 Page 14 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

Main-1 & Main2 Protection


15 E03C009 DC 3 132kV DFR Panel-1 132kV Feeder Relay panel-E03 4C x 2.5 mm2 White 20*S
Opereated to trigger DFR

2 Red, Yellow,
16 E03 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-1 132kV LCC-E03 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
17 E03 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-1 132kV LCC-E03 4C x 2.5 mm 20*
Blue & Black

2
18 E03 C012 CB Status (for DFR) DC 2 132kV DFR Panel-1 132kV LCC-E03 4C x 2.5 mm White 20S*

Main-1 & Main2 Protection 2


19 E04 C009 DC 3 132kV DFR Panel-2 132kV IDT Relay panel-E04 4C x 2.5 mm White 20S*
Opereated to trigger DFR

2 Red, Yellow,
20 E04 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E04 4C x 4 mm 20*
Blue & Black

2
21 E04 C031 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E04 4C x 2.5 mm White 20S*

2 Red, Yellow,
22 Fxx CT02 DFR CT Circuit (LV) CT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-2 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
23 FxxVT01 DFR VT Circuit (LV) VT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-2 4C x 2.5 mm 20*
Blue & Black

O/C EF Protection Operated DC 2 132kV DFR Panel-2 11kV SWGR-INCOMER-2

24 Fxx C008 7C x 2.5 mm2 White 20S*

11kV Incomer CB Status DC 2 132kV DFR Panel-2 11kV SWGR-INCOMER-2

Main-1 & Main2 Protection


25 E05 C009 DC 3 132kV DFR Panel-1 132kV Feeder Relay panel-E05 4C x 2.5 mm2 White 20*S
Opereated to trigger DFR

Rev.2 Page 15 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

Applicable for
Main-1 & Main2 Protection 132kV Feeder Reactor Relay 2
26 E05 C018 DC 3 132kV DFR Panel-1 4C x 2.5 mm White 20S* Feeder with
Opereated to trigger DFR panel-E05
Reactor

2 Red, Yellow,
27 E05 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-1 132kV LCC-E05 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
28 E05 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-1 132kV LCC-E05 4C x 2.5 mm 20*
Blue & Black

2
29 E05 C012 CB Status (for DFR) DC 2 132kV DFR Panel-1 132kV LCC-E05 4C x 2.5 mm White 20S*

Main-1 & Main2 Protection 132kV Buscoupler Relay panel- 2


30 E06 C009 DC 3 132kV DFR Panel-2 4C x 2.5 mm White 20*S
Opereated to trigger DFR E06

2 Red, Yellow,
31 E06 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E06 4C x 4 mm 20*
Blue & Black

2
32 E06 C011 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E06 4C x 2.5 mm White 20S*

Main-1 & Main2 Protection


33 E07 C009 DC 3 132kV DFR Panel-2 132kV Feeder Relay panel-E07 4C x 2.5 mm2 White 20*S
Opereated to trigger DFR

Applicable for
Main-1 & Main2 Protection 132kV Feeder Reactor Relay 2
34 E07 C018 DC 3 132kV DFR Panel-2 4C x 2.5 mm White 20S* Feeder with
Opereated to trigger DFR panel-E07
Reactor

2 Red, Yellow,
35 E07 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E07 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
36 E07 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-2 132kV LCC-E07 4C x 2.5 mm 20*
Blue & Black

2
37 E07 C012 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E07 4C x 2.5 mm White 20S*

Main-1 & Main2 Protection 2


38 E08 C009 DC 3 132kV DFR Panel-2 132kV IDT Relay panel-E08 4C x 2.5 mm White 20S*
Opereated to trigger DFR

Rev.2 Page 16 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

2 Red, Yellow,
39 E08 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E08 4C x 4 mm 20*
Blue & Black

2
40 E08 C031 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E08 4C x 2.5 mm White 20S*

2 Red, Yellow,
41 Fxx CT02 DFR CT Circuit (LV) CT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-3 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
42 Fxx VT01 DFR VT Circuit (LV) VT 4 132kV DFR Panel-2 11kV SWGR-INCOMER-3 4C x 2.5 mm 20*
Blue & Black

O/C EF Protection Operated DC 2 132kV DFR Panel-3 11kV SWGR-INCOMER-3

43 FxxC008 7C x 2.5 mm2 White 20S*

11kV Incomer CB Status DC 2 132kV DFR Panel-3 11kV SWGR-INCOMER-3

Main-1 & Main2 Protection


44 E09C009 DC 3 132kV DFR Panel-2 132kV Feeder Relay panel-E09 4C x 2.5 mm2 White 20*S
Opereated to trigger DFR

2 Red, Yellow,
45 E09 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-2 132kV LCC-E09 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
46 E09 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-2 132kV LCC-E09 4C x 2.5 mm 20*
Blue & Black

2
47 E09 C012 CB Status (for DFR) DC 2 132kV DFR Panel-2 132kV LCC-E09 4C x 2.5 mm White 20S*

Main-1 & Main2 Protection


48 E10 C009 DC 3 132kV DFR Panel-X 132kV Feeder Relay panel-E10 4C x 2.5 mm2 White 20*S Future Bay
Opereated to trigger DFR

Rev.2 Page 17 Of 28
132/11kV Substation Standard Cable Schedule
132kV DFR Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

2 Red, Yellow,
49 E1 0 CT03 DFR & BCU CT Circuit CT 4 132kV DFR Panel-X 132kV LCC-E10 4C x 4 mm 20* Future Bay
Blue & Black

2 Red, Yellow,
50 E10 VT03 VT Circuit (DFR) VT 4 132kV DFR Panel-X 132kV LCC-E10 4C x 2.5 mm 20* Future Bay
Blue & Black

2
51 E1 0C012 CB Status (for DFR) DC 2 132kV DFR Panel-X 132kV LCC-E10 4C x 2.5 mm White 20S* Future Bay

LVAC PANEL 2
52 DFRC001 LVAC Protn Operated DC 2 132kV DFR Panel-1 4C x 2.5 mm White 20*S
(Cubicle -2)

LVAC PANEL 2
53 DFRC002 LVAC Protn Operated DC 2 132kV DFR Panel-2 4C x 2.5 mm White 20*S
(Cubicle -4)

LVAC PANEL 2
54 DFRC003 LVAC Protn Operated DC 2 132kV DFR Panel-2 4C x 2.5 mm White 20*S
(Cubicle -8)

2
55 DFRC004 Fault Recorder Operated DC 4 132kV DFR Panel-2 SCS Panel 7C x 2.5 mm White 20*S

Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
-E01 and E10 are considered as Future Bays
-All Feeder Bay are considered with Reactor

Rev.2 Page 18 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Protection Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description Equipment Description Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
material)

AC Incoming Supply (Heater & ACDB 2 Red, Yellow,


1 HLDB xxx AC 4 132kV Feeder Relay panel 4C x 4 mm 20*
Lighting circuit) (HLDB) Blue & Black

2
2 DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV Feeder Relay panel 2C x 6 mm Red & Black 20*

2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV Feeder Relay panel 2C x 6 mm Red & Black 20*

2 Red, Yellow,
4 Exx CT01 Main-1 CT Circuit CT 4 132kV Feeder Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
5 Exx CT02 Main-2 CT Circuit CT 4 132kV Feeder Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
6 Exx VT01 Main-1 VT Circuit VT 4 132kV Feeder Relay panel 132kV LCC 4C x 2.5 mm 20*
Blue & Black

2 Red, Yellow,
7 Exx VT02 Main-2 VT Circuit VT 4 132kV Feeder Relay panel 132kV LCC 4C x 2.5 mm 20*
Blue & Black

132kV LCC
CB Trip Coil-1 DC 4 132kV Feeder Relay panel
2
8 Exx C001 12C x 2.5 mm White 20*
132kV LCC
SF6 Lockout-1 DC 4 132kV Feeder Relay panel

MAIN 1 CB Status DC 3 132kV Feeder Relay panel 132kV LCC


2
9 Exx C002 7C x 2.5 mm White 20*

VT MCB Trip DC 2 132kV Feeder Relay panel 132kV LCC

CB Open relay (TC-1) DC 3 132kV Feeder Relay panel 132kV LCC

2
10 Exx C003 CB Close Interlock DC 2 132kV Feeder Relay panel 132kV LCC 12C x 2.5 mm White 25*

Panel AC MCB Trip & CB Close


DC 3 132kV Feeder Relay panel 132kV LCC
Interlock

Rev.2 Page 19 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Protection Panel
Type of Cable From Cable To Proposed Cable Details
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description Equipment Description Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
material)

CB Trip Coil-2 DC 4 132kV Feeder Relay panel 132kV LCC


2
11 Exx C004 12C x 2.5 mm White 20*

SF6 Lockout-2 DC 4 132kV Feeder Relay panel 132kV LCC

MAIN 2 CB Status DC 3 132kV Feeder Relay panel 132kV LCC


2
12 Exx C005 7C x 2.5 mm White 20*

VT MCB Trip DC 2 132kV Feeder Relay panel 132KV LCC

CB Open relay (TC-2) DC 3 132kV Feeder Relay panel 132kV LCC


2
13 Exx C006 7C x 2.5 mm White 20*

CB Close relay (M2FP) DC 2 132kV Feeder Relay panel 132KV LCC

Applicable only
2
14 Exx C013 Cable box oil pressure Low/High Trip DC 3 132kV Feeder Relay panel Cable box Oil pressure device 4C x 2.5 mm White 20S* if available (oil
filled cables)

Applicable only
2
15 Exx C014 Cable box oil Low/High Alarm DC 2 132kV Feeder Relay panel Cable box Oil pressure device 4C x 2.5 mm White 20S* if available (oil
filled cables)

Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Cables from 132kV Feeder panel to DFR panel, M1BZP panel and M2BZP panel are available in DFR panel, M1BZP panel and M2BZP panel cable schedule

Rev.2 Page 20 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Reactor Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

1
132kV Feeder Reactor Relay 2
DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 2C x 6 mm Red & Black 20*
panel

2
132kV Feeder Reactor Relay 2
DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 2C x 6 mm Red & Black 20*
panel

132kV Feeder Reactor Relay 2 Red, Yellow,


3 Exx CT01 Main-1 CT Circuit (132kV Bus Side) CT 4 Reactor-MK 4C x 4 mm 20*
panel Blue & Black

Main-1 CT Circuit (Reactor Neutral 132kV Feeder Reactor Relay 2 Red, Yellow,
4 Exx CT02 CT 4 Reactor-MK 4C x 4 mm 20*
Side) panel Blue & Black

Main-1 CT Circuit (Reactor Earthing 132kV Feeder Reactor Relay 2


5 Exx CT03 CT 2 Reactor-MK 2C x 4 mm Red & Black 20*
Side) panel

132kV Feeder Reactor Relay 2 Red, Yellow,


6 Exx CT04 Main-2 CT Circuit CT 4 Reactor-MK 4C x 4 mm 20*
panel Blue & Black

This cable is
not applicable
if M2RP is
Main-2 CT Circuit (Reactor Neutral 132kV Feeder Reactor Relay 2 Red, Yellow,
7 Exx CT05 CT 4 Reactor-MK 4C x 4 mm 20* High
Side) panel Blue & Black
Impedance
REF.
Protection

Main-2 CT Circuit (Reactor Earthing 132kV Feeder Reactor Relay 2


8 Exx CT06 CT 2 Reactor-MK 2C x 4 mm Red & Black 20*
Side) panel

132kV Feeder Reactor Relay 2


9 Exx C013 M1RP Trip & CB Fail Initi. DC 7 132kV Feeder Relay panel 12C x 2.5 mm White 25*
panel

132kV Feeder Reactor Relay 2


10 Exx C014 MAIN 1 CB Status DC 4 132kV LCC Panel 7C x 2.5 mm White 20*
panel

Rev.2 Page 21 Of 28
132/11kV Substation Standard Cable Schedule
132kV Feeder Reactor Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

132kV Feeder Reactor Relay 2


11 Exx C015 Panel AC MCB Trip DC 2 132kV LCC Panel 4C x 2.5 mm White 20S*
panel

132kV Feeder Reactor Relay 2


12 Exx C016 M2RP Trip & CB Fail Initi. DC 7 132kV Feeder Relay panel 12C x 2.5 mm White 25*
panel

132kV Feeder Reactor Relay 2


13 Exx C017 MAIN 2 CB Status DC 4 132kV LCC Panel 7C x 2.5 mm White 25*
panel

M1RP Mechanical Trip circuit (63T, 132kV Feeder Reactor Relay 2


14 Exx C019 DC 5 Reactor-MK 7C x 2.5 mm White 20*
49OTT, 63T Cable Box) panel

M2RP Mechanical Trip circuit 132kV Feeder Reactor Relay 2


15 Exx C020 DC 5 Reactor-MK 7C x 2.5 mm White 20*
(PRV, PRV-CABLE, 49WTT) panel

M1RP Mechanical Alarm circuit (63A, 132kV Feeder Reactor Relay 2


16 Exx C021 DC 6 Reactor-MK 12C x 2.5 mm White 25*
49OTA,OLA, 63A-Cable box) panel

M2RP Mechanical Alarm circuit


132kV Feeder Reactor Relay 2
17 Exx C022 (49WTA, BRA) DC 4 Reactor-MK 7C x 2.5 mm White 20*
panel

Note:
* In accordance with BS:6121 actual cable dimensions must be used for gland selection
Cables from 132kV Feeder Reactor panel to DFR panel available in DFR panel cable schedule

Rev.2 Page 22 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)

AC Incoming Supply (Heater & 2 Red, Yellow, Applicable if it


1 HLDB xxx AC 4 HLDB 132kV IDT Relay panel 4C x 4 mm 20*
Lighting circuit) Blue & Black is first panel

2
2 DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV IDT Relay panel 2C x 6 mm Red & Black 20*

2
3 DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV IDT Relay panel 2C x 6 mm Red & Black 20*

2 Red, Yellow,
4 Exx CT01 Main-1 CT Circuit CT 4 132kV IDT Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
5 Exx CT02 Main-2 CT Circuit CT 4 132kV IDT Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black

M1 IDT HV Nutral CT Circuit (IDT- 2


6 Exx CT08 CT 2 132kV IDT Relay panel IDT-MK 2C x 4 mm Red & Black 20*
MK)

M2 IDT HV Nutral CT Circuit (IDT- 2


7 Exx CT09 CT 2 132kV IDT Relay panel IDT-MK 2C x 4 mm Red & Black 20*
MK)

2
8 Exx CT10 M1 ET Nutral CT Circuit (ET-MK) CT 2 132kV IDT Relay panel ET-MK 2C x 4 mm Red & Black 20*

2
9 Exx CT11 M2 ET Nutral CT Circuit (ET-MK) CT 2 132kV IDT Relay panel ET-MK 2C x 4 mm Red & Black 20*

2 Red, Yellow,
10 Exx CT12 Main-1 CT Circuit CT 4 132kV IDT Relay panel 11kV Swgr. Incomer 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
11 Exx CT13 Main-2 CT Circuit CT 4 132kV IDT Relay panel 11kV Swgr. Incomer 4C x 4 mm 20*
Blue & Black

Rev.2 Page 23 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)

CB Trip Coil-1 DC 4 132kV IDT Relay panel 132kV LCC

2
12 Exx C001 12C x 2.5 mm White 20*

SF6 Lockout-1 DC 4 132kV IDT Relay panel 132kV LCC

2
13 Exx C002 MAIN 1 CB Status DC 4 132kV IDT Relay panel 132kV LCC 7C x 2.5 mm White 20*

CB Open relay (TC-1) DC 3 132kV IDT Relay panel 132kV LCC

2
14 Exx C003 CB Close Interlock DC 2 132kV IDT Relay panel 132kV LCC 12C x 2.5 mm White 25*

Panel AC MCB Trip & CB Close


DC 3 132kV IDT Relay panel 132kV LCC
Interlock

CB Trip Coil-2 DC 4 132kV IDT Relay panel 132kV LCC

2
15 Exx C004 12C x 2.5 mm White 20*

SF6 Lockout-2 DC 4 132kV IDT Relay panel 132kV LCC

2
16 Exx C005 MAIN 2 CB Status DC 4 132kV IDT Relay panel 132kV LCC 7C x 2.5 mm White 20*

2
17 Exx C006 CB Open relay (TC-2) DC 3 132kV IDT Relay panel 132kV LCC 4C x 2.5 mm White 20S*

M1 IDT Mechanical Trip circuit (63T,


18 Exx C010 DC 6 132kV IDT Relay panel IDT-MK 7C x 2.5 mm2 White 20*
63TC, 49OTT, 63T Cable Box)

M2 IDT Mechanical Trip circuit


19 Exx C011 DC 6 132kV IDT Relay panel IDT-MK 7C x 2.5 mm2 White 20S*
(PRV, PRV-TC, PRV-CABLE 49WTT)

Rev.2 Page 24 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)

M1 IDT Mechanical Alarm circuit


2
20 Exx C012 (63TA, 49OTA,OLA-Main Tank, OLA- DC 7 132kV IDT Relay panel IDT-MK 12C x 2.5 mm White 20*
OLTC, 63T Cable Box))

M2 IDT Mechanical Alarm circuit


2
21 Exx C013 (49WTA, BRA) DC 4 132kV IDT Relay panel IDT-MK 7C x 2.5 mm White 20*

M1 ET Mechanical Trip circuit (63T, 2


22 Exx C014 DC 4 132kV IDT Relay panel ET-MK 7C x 2.5 mm White 20*
49OTT)

M2 ET Mechanical Trip circuit (PRV, 2


23 Exx C015 DC 4 132kV IDT Relay panel ET-MK 7C x 2.5 mm White 20*
49WTT)

M1 ET Mechanical Alarm circuit 2


24 Exx C016 DC 4 132kV IDT Relay panel ET-MK 7C x 2.5 mm White 20*
(49OTA, OLA)

M2 ET Mechanical Alarm circuit 2


25 Exx C017 DC 4 132kV IDT Relay panel ET-MK 7C x 2.5 mm White 20*
(63TA, 49WTA)

2
26 Exx C018 M1IDTP Trip Intertrip Send DC 3 132kV IDT Relay panel LVAC 4C x 2.5 mm White 20S*

Trip & 50BF Initi. From LVAC DC 3 132kV IDT Relay panel LVAC

2
27 Exx C019 M2IDTP Trip Intertrip Send DC 3 132kV IDT Relay panel LVAC 12C x 2.5 mm White 25*

LVAC Protn. Fail DC 3 132kV IDT Relay panel LVAC

2
28 Exx C020 11kV Incomer CBF Protn. Optd.- M1 DC 4 132kV IDT-1 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*

2
29 Exx C021 11kV Incomer CBF Protn. Optd.- M2 DC 4 132kV IDT-1 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*

Rev.2 Page 25 Of 28
132/11kV Substation Standard Cable Schedule
132kV IDT Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores x
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) Cable Size
LCC) material)

2
30 Exx C020 11kV Incomer CBF Protn. Optd.- M1 DC 4 132kV IDT-3 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*

2
31 Exx C021 11kV Incomer CBF Protn. Optd.- M2 DC 4 132kV IDT-3 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*

2
32 Exx C020 11kV Incomer CBF Protn. Optd..- M1 DC 4 132kV IDT-2 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*

2
33 Exx C021 11kV Incomer CBF Protn. Optd..- M2 DC 4 132kV IDT-2 Relay panel 11kV Bussection-1 7C x 2.5 mm White 20*

2
34 Exx C022 11kV Incomer CBF Protn. Optd..- M1 DC 4 132kV IDT-2 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*

2
35 Exx C023 11kV Incomer CBF Protn. Optd..- M2 DC 4 132kV IDT-2 Relay panel 11kV Bussection-2 7C x 2.5 mm White 20*

M1IDTP Trip DC 2 132kV IDT Relay panel 11kV Swgr. Incomer

2
36 Exx C024 7C x 2.5 mm White 20*

LV CB Status - Main 1 DC 3 132kV IDT Relay panel 11kV Swgr. Incomer

M2IDTP Trip DC 2 132kV IDT Relay panel 11kV Swgr. Incomer

2
37 Exx C025 7C x 2.5 mm White 20*

LV CB Status - Main 2 DC 3 132kV IDT Relay panel 11kV Swgr. Incomer

CB Close Interlock - 11kV CB DC 2 132kV IDT Relay panel 11kV Swgr. Incomer

2
38 Exx C026 7C x 2.5 mm White 20*

CB Close Interlock - Alarm DC 3 132kV IDT Relay panel 11kV Swgr. Incomer

Note: * In accordance with BS:6121 actual cable dimensions must be used for gland selection
Cables from DFR panel, M1BZP panel, M2BZP panel and 11kV BZP are available in DFR panel, M1BZP panel M2BZP panel and 11kV BZP cable schedule

Rev.2 Page 26 Of 28
132/11kV Substation Standard Cable Schedule
132kV Bus Coupler Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

1
2
DCDB1 xxx DC Incoming Supply-1 DC 2 DCDB-1 132kV BC Relay panel 2C x 6 mm Red & Black 20*

2
2
DCDB2 xxx DC Incoming Supply-2 DC 2 DCDB-2 132kV BC Relay panel 2C x 6 mm Red & Black 20*

2 Red, Yellow,
3 Exx CT01 Main-1 CT Circuit CT 4 132kV BC Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black

2 Red, Yellow,
4 Exx CT02 Main-2 CT Circuit CT 4 132kV BC Relay panel 132kV LCC 4C x 4 mm 20*
Blue & Black

CB Trip Coil-1 DC 4 132kV BC Relay panel 132kV LCC

2
5 Exx C001 12C x 2.5 mm White 20*

SF6 Lockout DC 4 132kV BC Relay panel 132kV LCC

2
6 Exx C002 MAIN 1 CB Status DC 4 132kV BC Relay panel 132kV LCC 7C x 2.5 mm White 20*

CB Open relay (TC-1) DC 3 132kV BC Relay panel 132kV LCC

2
7 Exx C003 CB Close Interlock DC 2 132kV BC Relay panel 132kV LCC 12C x 2.5 mm White 25*

Panel AC MCB Trip & CB Close


DC 3 132kV BC Relay panel 132kV LCC
Interlock

Rev.2 Page 27 Of 28
132/11kV Substation Standard Cable Schedule
132kV Bus Coupler Protection Panel
Cable From Cable To Proposed Cable Details
Type of
Cable Route Cable Length
Sl. Cable Tag. / Cable circuit No. of cores
Circuit Description Equipment Description Gland size (To be filled (To be filled Remarks
No. Reference number (AC/DC/ required No. of Cores
Equipment Description (Exist.SS PJB instead of Color code (Brass - by contractor) by contractor)
CT/VT) x Cable Size
LCC) material)

CB Trip Coil-2 DC 4 132kV BC Relay panel 132kV LCC

2
8 Exx C004 12C x 2.5 mm White 20*

SF6 Lockout DC 4 132kV BC Relay panel 132kV LCC

2
9 Exx C005 MAIN 2 CB Status DC 4 132kV BC Relay panel 132kV LCC 7C x 2.5 mm White 20*

2
10 Exx C006 CB Open relay (TC-2) DC 3 132kV BC Relay panel 132kV LCC 4C x 2.5 mm White 20S*

Note:
* In accordance with BS:6121 actual cable dimensions* In
must
accordance
be used for
with
gland
BS:6121
selection
actual cable dimensions must be used for gland selection
Cables from DFR panel, M1BZP panel, M2BZP panel and 11kV BZP are available in DFR panel, M1BZP panel M2BZP panel and 11kV BZP cable schedule

Rev.2 Page 28 Of 28