COLUMN

DESIGN

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
THIRD FLOOR
COLUMNS

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN A1
I. DESIGN CRITERIA
'
f c =21 MPa
f y =2 75 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )


W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 26.22 +43.089


Total Reaction R= 69.31 kN

Pu=W u+ R

Pu=12.234 +69.31

Pu=81.64 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=323 8.75 kN > 81.64 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN A2
I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 63.39 +26.22 +28.12


Total Reaction R= 117.73 kN

Pu=W u+ R

Pu=12.234 +117.73

Pu=129.96 kN
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
III. SOLVE FOR STEEL AREA
Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=323 8.75 kN >129.96 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN A3
I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 28.12 +43.83


Total Reaction R= 71.95 kN
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Pu=W u+ R

Pu=12.234 +71.95

Pu=84.284 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π
A st = ( 20 )2 ( 11 ) =3455.75 mm2
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN > 84.284 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN B1


I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
W U =12.234 kN

Total Reaction R= 26.22 + 43.089 + 46.40


Total Reaction R= 115.71 kN

Pu=W u+ R

Pu=12.234 +115.71

Pu=128.044 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π
A st = ( 20 )2 ( 11 ) =3455.75 mm2
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >1 28.044 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
VI. DESIGN OF TIES
Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN B2


I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )


DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 46.40 +47.61 +63.39 + 50.45


Total Reaction R= 207.85 kN

Pu=W u+ R

Pu=12.234 +207.85

Pu=220.184 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >220.184 kN ( ok !)

V. SPACING OF BARS

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN B3


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 43.83 + 50.45 + 26.22


Total Reaction R= 125.5 kN

Pu=W u+ R

Pu=12.234 +125.5

Pu=137.734 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >137. 734 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN C1


I. DESIGN CRITERIA

f ' c =21 MPa

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 2( 26.22)


Total Reaction R= 52.44 kN

Pu=W u+ R

Pu=12.234 +52.44

Pu=64.77 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
IV. SOLVE FOR ACTUAL A st
π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >64.67 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN C2
I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 26.22+47.61+28.01


Total Reaction R= 101.84 kN

Pu=W u+ R

Pu=12.234 +101.84

Pu=114.074 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π
A st = ( 20 )2 ( 11 ) =3455.75 mm2
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >1 14.074 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN C3
I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 28.01+26.22


Total Reaction R= 54.23 kN

Pu=W u+ R

Pu=12.234 +54.23

Pu=66.464 kN

III. SOLVE FOR STEEL AREA


DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >66.464 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
SECOND FLOOR
COLUMNS
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN A1
I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 53.05 +81.99


Total Reaction R= 135.04 kN

Pu=W u+ R + PU (3 rd)
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Pu=12.234 +135.04 +81.46

Pu=228.73 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >228.73 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN A2


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Total Reaction R= 53.05 + 122.06 +51.97
Total Reaction R= 227.08 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +227.08 +129.96

Pu=369.27 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >369.27 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN A3


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 51.978 + 76.18


Total Reaction R= 128.15 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +128.15 + 84.284

Pu=224.664 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >224.64 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN B1


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 81.99 + 60.60 + 88.13


Total Reaction R= 230.72 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +230.72 + 128.044

Pu=370.994 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∅ Pn=3238.75 kN >370.994 kN ( ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN B2


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Column Size=400 mm x 400 mm
Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 88.13 + 122.06 +60.60 +53.26


Total Reaction R= 324.05 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +324.75 + 220.184

Pu=556.564 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >556.564 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN B3
I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 53.26 +76.18 +25.49


Total Reaction R= 154.93 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +154.93 +137.734

Pu=304.90 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π
A st = ( 20 )2 ( 11 ) =3455.75 mm2
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >304.90 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN C1
I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 2 (60.60)


Total Reaction R= 121.20 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +121.20+ 64.674

Pu=198.104 kN

III. SOLVE FOR STEEL AREA

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >198.104 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN C2
I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 2(60.60)+ 26.48


Total Reaction R= 147.68 kN

Pu=W u+ R +¿ PU (3 rd)
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Pu=12.234 +147.68 +114.074

Pu=273.98 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >273.98 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN C3


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Total Reaction R= 26.48 + 25.49
Total Reaction R= 51.97 kN

Pu=W u+ R +¿ PU (3 rd)

Pu=12.234 +51.97 +66.469

Pu=130.70 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >130.70 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
GROUND FLOOR
COLUMNS

DESIGN FOR COLUMN A1


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 75.29 +49.07


Total Reaction R= 124.36 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +124.36+228.73

Pu=365.32 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >365.42 kN (ok !)

V. SPACING OF BARS

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN A2


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 49.07 + 51.97 + 115. 35


Total Reaction R= 216.39 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.23+216.23+ 369.27

Pu=597.89 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π
A st = ( 20 )2 ( 11 ) =3455.75 mm2
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >597.89 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN A3


I. DESIGN CRITERIA

f ' c =21 MPa

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 51.97 + 76.11


Total Reaction R= 128.08 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +128.08+224.664

Pu=364.974 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
IV. SOLVE FOR ACTUAL A st
π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >364.974 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN B1
I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 75.29 +51.08 + 74.66


Total Reaction R= 201.23 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +201.23+370.994

Pu=584.254 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π
A st = ( 20 )2 ( 11 ) =3455.75 mm2
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >584.254 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN B2
I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 115.35 + 51.08 + 74.66 + 53.26


Total Reaction R= 294.35 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +294.35+556.46

Pu=863.04 kN

III. SOLVE FOR STEEL AREA


DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN > 863.04 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
DESIGN FOR COLUMN B3
I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 53.26 + 76.11 + 25.49


Total Reaction R= 154.86 kN

Pu=W u+ R +¿ PU (2 rd)
DIEGA , Michael Hechona
COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Pu=12.234 +154.86+304.90

Pu=471.99 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN > 471.99 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN C1


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Total Reaction R= 51.08 + 51.08
Total Reaction R= 102.16 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +102.16+198.104

Pu=312. 494 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN >312.494 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN C2


I. DESIGN CRITERIA

f ' c =21 MPa


f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 2(51.08) + 26.48


Total Reaction R= 128.64 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +128.64+273.98

Pu=414.85 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)

A st =3200 m m2

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

∅ Pn=3238.75 kN > 414.85 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DESIGN FOR COLUMN C3


I. DESIGN CRITERIA
'
f c =21 MPa
f y =275 MPa

Column Size=400 mm x 400 mm


Main Bars =20 mm
Column Ties = 10 mm
Height of Column =2.7 m

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
II. LOADINGS
W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=23.6 ( 2.7 ) ( 0.4 ) (0.4 )

W DL=10.195 kN

W U =1.2W DL

W U =1.2(10.195)
W U =12.234 kN

Total Reaction R= 26.48 + 25.49


Total Reaction R= 51.97 kN

Pu=W u+ R +¿ PU (2 rd)

Pu=12.234 +51.97+130.70

Pu=194.90 kN

III. SOLVE FOR STEEL AREA


Assume A st =0.02 A g

A st =0.02 ( 400 ) ( 400)


2
A st =3200 m m

A st 3200
N= =
Ab π
¿¿
4

IV. SOLVE FOR ACTUAL A st


π 2 2
A st = ( 20 ) ( 11 ) =3455.75 mm
4
V. CHECK IF∅ Pn > Pu
∅ Pn=Ø 0.80 ¿

∅ Pn=( 0.65 ) ( 0.80) [0.85 ( 21 ) ( 250000−3455.75 ) ]+(275)(3455.75)

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace
∅ Pn=3238.75 kN >19 4.90 kN (ok !)

V. SPACING OF BARS
h−2 ( cc )−2 ( d t ) −4 (d b )
S=
3
400−2 ( 40 )−2 (10 )−4 (20)
S=
3
S=73 mm<150 mm(ok !)

VI. DESIGN OF TIES


Least of :
48 dt =48(10)=480 mm

16 d b =16(20)=32 mm ←

least column dimension=400 mm


∴ Use10 mm ties spaced at 320 mm

DIEGA , Michael Hechona


COMPUTATIONS CE 108-RCD
LAXAMANA , Joan Grace