Mode -1 Dectection Phase - To raise a pressure differential in the protection space - stair case by the
required amount when all doors are closed.
Mode -2 Fire fighting phase - To maintain a specified Air velocity (1.0 m/sec) through the open doors in to
the fire floor with various other doors open.
Staircase- 1
Leakage Area Calculations:
2
Air leakage Area through all single leaf doors opening into a pressurized space = 0.02 M
2
Air leakage Area through all single leaf doors opening outwards from a pressurized space = 0.02 M
2
Air leakage Area through all double leaf doors opening into a pressurized space = 0.42 M
2
Leakage Area through pivoted and weather stripped window per m length = 3.60E-05 M
( Reference Table D.2 BS 5588)
2
Air leakage Area through all windows = 0.0003 M
2
Leakage Area through exterior stair walls ( Tight wall tightness ) per sq. meter = 7.00E-05 M
( Reference Table D.3 BS 5588)
2
Leakage Area through internal stair walls ( Tight wall tightness ) per sq. meter = 1.40E-05 M
( Reference Table D.3 BS 5588)
2
Air leakage Area through exterior stair wall = 0.038 M
2
Air leakage Area through internal stair wall = 0.001 M
2
Total leakage Area (Door + window + wall) = 0.500 M
As per QCDD the Stairwell pressurisation system required to maintain minimum 25 Pa pressure
1
difference between stairwell and the occupant area (Lobby) for buildings that are non-sprinklered.
To calculate the staircase pressurisation we required to maintain 37.5 Pa with all doors closed.
The formula for doing the calculation of supply air volume
1/n
Q = 0.83 A E P
3
Where Q= Voume of air required (M / Sec)
AE = Leakage area from the space (M 2 )
P= Pressure differential (Pa) ( 37.5 Pa)
n= Leakage factor (For door n=2 & window cracks n =1.6)
1/2 3
There fore, Q= 0.83 x 0.500 x 37.5 = 2.541 M /Sec
3
Total Airflow from calculation 1 and 2 = 7.541 M /Sec
One wall adjoins the pressurised space so there will not be any leakage where they have common wall
The length of lobby walls not adjoining a protected space = 1.936+5.13+1.377+3.66 m = 12.103 M
2
Total Leakage Area from doors in the lobby = .06+.06+.015 = 0.135 M
1/2 3
Air supply to typical floor lobby = 0.83 x.135 x12.5 = 0.396 M /Sec
3
Total Air supply for all floors from 1st to 5th including lower roof = 2.3769394 M /Sec
b Ground Floor
The length of lobby walls not adjoining a protected space = 1.936+5.13+1.377+3.66+1.54+1.54 m = 15.183 M
2
Total Leakage Area from doors in the lobby = .06+.06+.015+.02+.02 = 0.175 M
1/2 3
Air supply required to ground floor lobby = 0.83 x.175 x 12.5 = 0.514 M /Sec
c Basement Floor
The length of lobby walls not adjoining a protected space =
1.936+5.674+3+1.578+5.22+4+8.873+11.425+3.575+3+3.93 m = 52.211 M
^-4 2
leakage area through walls = 52.211 x 3.6 x 0.14 x 10 = 0.003 M
2
Total Leakage Area from doors in the lobby = .06+.06+.015+.02+.03+.03 = 0.215 M
1/2 3
Air supply required tobasement floor lobby = 0.83 x.215 x 12.5 = 0.631 M /Sec
3
Total Volume of supply air requied for all floors lobby based on BS = 3.52 M /Sec
3
Total Volume of Supply air requied for the complete system = 11.06 M /Sec