Professional Documents
Culture Documents
Search...
HOME INTRODUCTION CHECKLISTS VALVE COMPONENTS USED IN PIPING PDMS HOW TO PIPING LAYOUT
1. Process Plant
1. Refineries
2. Petrochemicals
3. Specialty chemicals
2. Terminals
3. Administration buildings
4. Material Handling Plants
Storage tank are containers used for storage of fluids for the short or long term. Cluster of tanks together
in a same are termed as “Tank Farms”.
Underground Tanks:
Commonly used for drain collection of the plant at atmospheric pressure.
FRP Tanks:
Commonly used for corrosive fluid at atmospheric pressure.
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 1/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 2/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
Underground tanks
General considerations:
Local codes and regulations
Client specification
Topography
Adjacent process units
Neighbouring commercial and residential property
Maintenance and operation
Detail design:
Identification of storage based on fluid stored.
Safety considerations/Statutory requirements
General / Plot plan arrangement
General piping layout
Material of Construction.
Apart from this, local rules and regulations pertaining to State and local industrial requirement should be
taken into consideration.
Safety ensures proper protection and safe operation- Lifetime.
Insurance Premium.
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 3/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
plot plan.
Plot plan is a spatial arrangement of equipment considering proper flow sequence, system grouping,
safety, statutory requirements, maintenance, operation, erection and construction with logistical
economy.
General classification of petroleum products for storage.
1. Larger installations: Aggregate capacity of Class A and Class B petroleum product is more than 5000
cu.m or diameter of Class A or Class B product tank is more than 9m.
2. Smaller installations: Aggregate capacity of Class A and Class B petroleum product is less than 5000
cu.m or diameter of Class A or Class B product tank is less than 9m.
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 4/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
Separation distances between the nearest tanks located in separate dykes shall not be less than the
diameter of the larger of the two tanks or 30 meters, whichever is more.
All process units and dyked enclosures of storage tanks shall be planned in separate blocks with roads
all around for access and safety.
In a dyked enclosure where more than one tank is located, firewalls of minimum height 600mm shall be
provided to prevent spills from one tank endangering any other tank in the same enclosure.
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 5/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
Typical tank farm arrangement
For larger installation, minimum separation distances shall be as specified in following tables.
Table 1: Inter unit Distances for large installations (D>9m or Agg. Cap > 5000cu.m)
Table 1 notes
Table 2: Interunit Distances for smaller installations (D<9m or Agg. Cap < 5000cu.m)
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 6/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
Table 2: Interunit Distances for smaller installations (D<9m or Agg. Cap < 5000cu.m)
6 COMMENTS
buildtrade
August 28, 2014 at 8:03 am
Hi,
1. Temp.
In the API std. 2.5 psig is mentioned but in the above datas, I believe that there is a formula of
deciding Press and Vac for the data sheet.
At API 2000, we can decide only the venting capacity but we are not sure yet the safety relief valve
Vendors the we cannot decide the Press and Vac to be used in our design.
Piping engineering
August 28, 2014 at 8:04 am
Hi there,
http://www.piping-engineering.com/pressure-vacuum-relief-valves-part-1.html
http://www.piping-engineering.com/pressure-vacuum-relief-valves-part-2.html
Cheers
AJ
mohanrao.k
November 21, 2014 at 8:04 am
The
NIce.
Harshit
December 12, 2014 at 4:36 pm
Flash point temperature for fluid should be 23 65 and 93 C instead of 230 650 and 930C
Piping engineering
December 19, 2014 at 11:13 am
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 7/8
7/5/2021 Tankfarm: Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure
Hi Harshit,
Thank you for suggesting correction. I have updated the flash point temperatures.
Much appreciated.
Regards,
AJ
Gajendrasingh Rajput
March 17, 2015 at 7:23 pm
NFPA 30 and API 2030 shall be followed for tank farm fire protection system.
Copyright 2021
www.piping-engineering.com/tankfarm-types-design-considerations-plot-plan-arrangement-dyke-enclosure.html 8/8