FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 1:
 Pressure drop after through Alarm Valve.
Follow Table 7, point 10.6 Standard 7336:2003
We calculator as formular:
hb  Sb  qb  qb
qb : Water flow through Alarm Valve (l/s)
Sb: Resistance values of Alarm Valve

Alarm Valve Sb
Type
100A 0.00302
150A 0.00368

1
LOGO
FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 2:
 Pressure drop after through Alarm Valve.
Follow “Water supply & Drainage Water” of author Tran
Hieu Nhue
We calculator as formular:
hb  Sb  qb  qb
qb : Water flow through Alarm Valve (l/s)
Sb: Resistance values of Alarm Valve

Alarm Valve Sb
Type
100A 0.00302
150A 0.000869

2
LOGO
FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 3: Follow catalouge Viking ( Deluge Valve Type FSX-A )

3
LOGO
FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 4: Follow catalouge Viking ( Alarm Check Valve Model J1 )

4
LOGO
FIRE SPRINKLER SYSTEM

* COMPARE WITH 4 OPTION:


Example with Alarm Check Valve 150A ( 6 inches ), water
flow 6500 l/min:
OPTION 1:
Follow Table 7, point 10.6 Standard 7336:2003
 Pressure drop after through Alarm Valve

hb  Sb  qb  qb
 0.00368 108 108  42.9(m)

5
LOGO
FIRE SPRINKLER SYSTEM

* COMPARE WITH 4 OPTION:


Example with Alarm Check Valve 150A ( 6 inches ), water flow
6500 l/min:
OPTION 2:
Follow “Water supply & Drainage Water” of author Tran Hieu Nhue
 Pressure drop after through Alarm Valve

hb  Sb  qb  qb
 0.000869 108 108  10.1(m)

6
LOGO
FIRE SPRINKLER SYSTEM
OPTION 3: Follow catalouge Viking ( Deluge Valve Type FSX-A )

Pressure
drop
through
Alarm
Valve:
0.6 bar
= 6(m)

7
LOGO
FIRE SPRINKLER SYSTEM

OPTION 4: Follow catalouge Viking ( Alarm Check Valve Model J1 )

Pressure
drop
through
Alarm
Valve:
6m

8
LOGO
FIRE SPRINKLER SYSTEM

* COMPARE WITH 4 OPTION:


Example with Alarm Check Valve 150A ( 6 inches ), water
flow 6500 l/min:
Option 1 2 3 4
Total 42.9 10.1 9.0 6.0
Friction
loss (m)

1- Use Option 1, Total friction loss is too big (but follow VN


Standard)
2- Use Option 3 & 4 (follow catalouge) Total friction loss
can be smaller, but many type of Alarm Check Valve, so
difficult to choose for Calculation.
3- Use Option 2, Total friction loss isn’t too big, same
Option 3,4. Now Estimation Department follow this Option.

9