You are on page 1of 3

MODEL CODE OF SAFE PRACTICE PART 19: FIRE PRECAUTIONS AT PETROLEUM REFINERIES AND BULK STORAGE INSTALLATIONS

from the fire. Once a need for cooling has been identified, the
Generally, applying water to equipment not minimum application rates given in Table D.1 should be
immediately involved in the fire may divert resources used.
from other more critical tasks. This should be continually
assessed during the emergency and tactics should be
changed where necessary to optimise available resources. D.3 CONTROL OF BURNING
The rates shown below are for guidance only. If the
applied water does not evaporate from the surface it is In some cases, water only may be used to control a fire
supposed to be protecting, the surface may not be hot until extinguishment is possible. Although not usually
enough to warrant protection. If resources are limited and fully effective at extinguishing flammable liquid fires, the
under strain at the time, concentration on other, more water may slow fire development and spread as well as
critical areas should then be considered. providing valuable cooling to exposed equipment.
Cooling may be required if the equipment is likely to Although it is not possible to specify application rates for
be exposed to heat fluxes in excess of 8-12 kW/m2. all fire types (since these will depend on the petroleum
Usually, the most appropriate way of determining the need product type, fire size and presence of obstacles as well as
for cooling will be to carry out fire modelling calculations application equipment), the minimum application rate
as part of the fire scenario analysis to identify exposures range given in Table D.1 should be used.
(see section 3.2).

Table D.1: Minimum application rates for water based systems

Application rate
(l/min./m2)
Process areas (Application rates based on ground area)
Process unit blocks 4
High density - stacked equipment 6-8
Cooling uninsulated equipment enveloped in flame
Process vessels, equipment, structural steel, pipe racks, fin-fan coolers etc. 10
Pumps handling flammable liquids in isolated areas [Note 1] 10
Pumps handling flammable liquids adjacent to cable runs, fin-fans, pressure equipment, pipe 20
racks etc. [Note 2]
Compressors handling flammable gases 10
Electrical and instrument cable trays, transformers, switchgear etc. 10
Cooling equipment exposed to radiant heat
Miscellaneous process equipment 2
Fixed [Note 3] and floating roof [Note 4] tanks containing Classes I, II and III liquids 2
Pressurised tanks (general) 10
LPG tanks 10
Buildings such as warehouses, offices and laboratories 2
Control of burning
Water spray for control of fire (application rate depends on product type) 10-20

Notes
1 Per square metre of horizontal area extending 0,6 m from the pump and driver's periphery
2 Total water application rate based on application equipment and run time
3 Consider roof and shell of fixed roof tanks
4 See D.5 for considerations on cooling tanks. Water spray should not be applied to the roof

102

Licenced to: Mrs Melissa van Velzen. Single user licence only.
IMPORTANT: This file is subject to a licence agreement issued by the Energy Institute, London, UK. All rights reserved. It may only be used in accordance with
the licence terms and conditions. It must not be forwarded to, or stored or accessed by, any unauthorised user. Enquiries: e: pubs@energyinst.org.uk t: +44 (0)207 467 7100
ANNEX D

D.4 EXTINGUISHMENT USING WATER ONLY (ii) Cooling adjacent tanks

The application rate of spray water for extinguishment will Cooling of heat-exposed tanks can be achieved through
depend on the circumstances of the fire and no precise the use of fixed or semi-fixed water spray systems, or by
guidance can be given. If necessary, trials with actual mobile means. Table D.1 provides a summary of
application equipment should be conducted to establish minimum application rates.
required application rates. Actual application rates will For adjacent tank cooling, the required water flow
depend on factors such as nozzle type, spacing and depends on the distance from the fire, wind direction, the
location, water pressure and flowrate etc. As noted in D.3, area exposed to radiation, the type of tank (e.g. fixed or
water is not generally an effective extinguishing material floating roof) and the intensity of the fire. The need for
for fires involving Class I petroleum and its products. fixed water-cooling can, if necessary, be assessed by using
appropriate fire modelling techniques, or otherwise at the
time of an incident if no fixed protection is provided.
D.5 STORAGE TANKS Various publications provide guidance on water
cooling requirements for exposed tanks but a practical fire
(i) Considerations regarding the use of cooling water ground method of checking whether an adjacent tank or
for tanks on fire other plant/equipment is affected by radiant heat is to
sweep a water stream across the exposed structure or tank
The need for cooling a fire-affected tank shell above the shell above the liquid level; if it steams off, it needs
product level has been much debated. There is no known cooling. If not, heat input is minimal or non-existent and
incidence of tank shell failure leading to product release therefore is not a hazard at that time. Regular checks
under full surface fire conditions where cooling water was should clearly be made if in doubt about prolonged
not applied to the shell. However, there have been some exposure to radiant heat.
cases where it is thought that uneven application of water To avoid unnecessary wastage of water and the
to the tank shell has caused distortion in some areas and potential problems of bund flooding or oil/water separator
consequent loss of product. overflow, if the water applied does not steam off, its
Tank shells are intended to fold inward under full application should be stopped and tried again at regular
surface fire conditions instead of folding outward with intervals.
potential loss of burning product. Another factor is that Overall, the final decision as to whether or not to
cooling the involved tank shell with uneven or erratic apply cooling water should be the responsibility of the
water streams will lead to hot and cool zones on the shell person in charge of fire attack, and should be based on the
surface area which may lead to distortion and possible prevailing conditions.
product spill or overflow. Therefore, cooling water should Lessons learned from incidents include many cases
not be applied to the tank on fire. where water has been over-applied for cooling adjacent
However, it should be remembered that if tanks, leading to bund flooding, carry-over of product to
extinguishment is to be attempted, tank shell folds may other areas and excessive discharge of contaminated water
trap pockets of burning product that the foam blanket offsite, as well as a shortage of water for more critical use.
cannot flow over. This may cause some difficulty in For tank fire design events, radiant heat should be
achieving complete extinguishment. In addition, cooling calculated. Any exposures receiving more than 32 kW/m2
may be required to gain full extinguishment by giving the should be provided with fixed cooling water systems. Any
foam a better chance to seal against the tank wall. (The exposures receiving 8-32 kW/m2 may require cooling, but
hotter the wall, the more difficult it is to seal against it.) this can be provided by mobile/portable means providing
Therefore, cooling water, applied evenly around the that it can be deployed in a reasonable time.
complete tank shell may be required towards the end of an A water application rate of 2 l/min./m2 is normally
incident and calculations to determine maximum water sufficient; this removes 43 kW/m2 thermal radiation at
requirements should make allowance for it. In practice, it 50% efficiency, 30 kW/m2 at 35%, or 69 kW/m2 at 80%
may only be required at the latter stages of the fire in respectively. At many sites this may be the maximum
which case cooling water on adjacent installations may no practical rate determined by supply and drainage
longer be required, thus reducing total water flow demand. considerations. Rates higher than 2 l/min./m2 do not
provide a proportionate increase in protection.

103

Licenced to: Mrs Melissa van Velzen. Single user licence only.
IMPORTANT: This file is subject to a licence agreement issued by the Energy Institute, London, UK. All rights reserved. It may only be used in accordance with
the licence terms and conditions. It must not be forwarded to, or stored or accessed by, any unauthorised user. Enquiries: e: pubs@energyinst.org.uk t: +44 (0)207 467 7100
MODEL CODE OF SAFE PRACTICE PART 19: FIRE PRECAUTIONS AT PETROLEUM REFINERIES AND BULK STORAGE INSTALLATIONS

Box D.1: Example calculations sheet

Note: Data are nominal only and should not be used for design purposes

1. Spillage fire foam quantity:


Spillage area = 50 m2
Foam application rate (e.g. 3% FP foam) = 6,5 l/min./m2
Total application rate = 325 l/min.
Run time = 15 min.
Total foam concentrate = 325 x 0,03 x 15 = 146,25 l
Water requirement for foam application = 325 x 15 = 4 875 l (~5 m3)

2. Foam systems:
Tank area = 346 m2
Foam application rate (NFPA 11) = 4,1 l/min./m2
Total application rate = 346 x 4,1 = 1 420 l/min.
System run time (NFPA 11) = 55 min.
Foam concentrate quantity = 1 420 x 0,03 x 55 = 2 343 l
Foam solution quantity (water) = 1 420 x 0,97 x 55 = 75,8 m3 (~76 m3)

3. Water for cooling four adjacent tanks, based on typical tank dimensions of 20 m diameter x 10 m height and a
minimum application rate of 2 l/min./m2 over 50% of the height:

Each segment shell area = B x 20 x 10 = 157 m2


4
Each segment roof area = B x 202 = 78,5m2
4x4
Cooling on shell/segment = 0,5 x 157 x 2 = 157 l/min.
Cooling on roof segment = 78,5 x 2 = 157 l/min.
Total cooling/segment = 314 l/min.
Total for four segments = 1 256 l/min.

Run time = 2 hr.


Total quantity = 1 256 x 120 = 150 720 l (~ 151 m3)

Total quantities:
Maximum water flow for foam solution = 1 420 l/min.
(Bund spill extinguished first)
Total quantity of water for foam solution = 76 m3
Foam concentrate = 2 343 l
Maximum water flow for cooling = 1 256 l/min.
Total quantity of water for cooling = 150,72 m3 (~ 151 m3)

Therefore, calculation of required resources results in the following quantities required onsite:

Foam systems:
Foam concentrate = 2 350 l
Foam solution (water) flow = 1 420 l/min.
Foam solution quantity = 78,1 m3 (includes approximately 76 m3 water)

Water cooling:
Water cooling flow = 1 256 l/min.
Water cooling quantity = 151 m3

104

Licenced to: Mrs Melissa van Velzen. Single user licence only.
IMPORTANT: This file is subject to a licence agreement issued by the Energy Institute, London, UK. All rights reserved. It may only be used in accordance with
the licence terms and conditions. It must not be forwarded to, or stored or accessed by, any unauthorised user. Enquiries: e: pubs@energyinst.org.uk t: +44 (0)207 467 7100

You might also like