Calculation Size of Neutral Earthing Transformer (NET)

Generator Details:
Generator Voltage (VL) (L-L) 66 KV
Maximum Over Voltage 85.8 KV
Frequency 50 Hz
Generator Transformer Details:
Transformer Primary Voltage 132 KV
Transformer Secondary Voltage 66 KV
Capacitance Per Phase:
Generator Winding Capacitance / Phase 0.22 µ Farad
Generator Connection Capacitance / Phase 0.001 µ Farad
Generator Transformer Capacitance / Phase 0.006 µ Farad
Generator Transformer Connection Capacitance / Phase 0 µ Farad
Transformer Cabale Capacitance / Phase 0.0003 µ Farad
Surge Arrestor Capacitance / Phase 0.25 µ Farad
Other Capacitance / Phase µ Farad
Total Zero Sequence Capacitance (C): 0.47730 µ Farad
Total Zero Sequence Capacitance Reactance to Ground (Xc): 6672.35 Ω/Phase
Neutral Earthing Transformer Size:
Primary Voltage of the Grounding Transformer (Vp) 66 KV
Secondary Voltage of the Grounding Transformer (Vs) 415 Volt
Turns Ratio of the Grounding Transformer (N) 159.04
Neutral Earthing Transformer % Reactance (X%) 4% 0.04
Neutral Earthing Transformer Reactance in PU (Xpu) 0.04 PU
Neutral Earthing Transformer Base KV (Bv) 0.24 KV

Jignesh.Parmar, www.electricalnotes.wordpress.com, jiguparmar@yahoo.com

1
al Earthing Transformer (NET)

:Calculate Size of Neutral Earthing Transformer:


Phase to Neutral Voltage (Vp1) 38.11 KV VL/1.732
% of Force field condition for Neutral Earthing Transformer 30% 1.3
Phase to Neutral Voltage under Force Field Condition (Vf) 49.54 KV Vf=Vp1x 1.3
Capacitive charging current/phase (Ic) 7.42 Amp Ic=Vf / Xc
Total Capacitive charging current (It) 22.27 Amp It=3xIc
Rating of Neutral Earthing Transformer (Pr) 1470.03 KVA Pr=VpxIt
Neutral Earthing Transformer overloading factor 2.6
Size of Neutral Earthing Transformer (P) 565 KVA P=Pr/ 2.6
Residual Capacitive reactance (Xct) 2224.12 Ω Xct=Xc / 3
Required Resistance value at secondary side (Rsec) 0.088 Ω Rsec=Xct / (NxN)
Required Grounding Resistor value at primary side (Rp) 2224.12 Ω Rp=Xct
Neutral Earthing Transformer Secondary Current 1362.40 Amp
Neutral Earthing Transformer Secondary Resistor Current (for 30 Seconds) 4604.91 Amp
Neutral Earthing Transformer Reactance Base(Base X): 0.10 Ω
Neutral Earthing Transformer Reactance (X) 0.00 Ω X=Xpu x Base X
Neutral Earthing Transformer X/R Ratio 0.05
Fault current through Neutral (single line to ground fault) (If) 17.13 Amp If=Vp1/Rp
:Results:
Rating of Neutral Earthing Transformer (P) 565 KVA
Short time Rating of Neutral Earthing Transformer 1470 KVA
Ratio of Neutral Earthing Transformer 66000 /415 Volt
Neutral Earthing Transformer Secondary Current 1362.40 Amp
Required Grounding Resistor value at primary side (Rp) 2224.12 Ω
Required Resistance at secondary side (Rsec) 0.09 Ω
Neutral Earthing Transformer Secondary Resistor Current (for 30 Seconds) 4604.91 Amp