Definitions Of Terms:
All forces in units 'kN' and 'm'
All reinforcement details like area, spacing in 'mm'
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of columns
1 βdns =
due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in 'kN'
4 ∑Pu = Total factored vertical load in 'kN'. (Clause 6.6.4.4)
5 δu = Design displacement in 'mm'
Modification factor reflecting the reduced mechanical
6 λ =
properties Of concrete
Coefficient defining the relative contribution Of
7 ac =
concrete strength To nominal wall shear strength
Cross-sectional area of a structural member measured
8 Ach = to the outside edges of transverse reinforcement in
'sqmm'
Gross area of concrete section bounded by web
9 Acv = thickness And length of section in the direction Of
shear force considered in 'sqmm'
Effective cross-sectional area within a joint In a plane
10 Aj = parallel To plane Of reinforcement generating shear
In the joint in 'sqmm'
Area Of non-prestressed longitudinal tension
11 As =
reinforcement in 'sqmm'
Minimum area Of shear reinforcement within spacing
12 Avmin =
's' in 'sqmm'
13 B = Width of column/ wall in 'mm'
Cross-sectional dimension of member core measured
14 bc1 and dc1 = to the outside edges of the transverse reinforcement
composing area Ash in 'mm'
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 2 of 244
42 Mux =
Factored moment acting on a section along D in
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 3 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 4 of 244
Code References:
ACI 318M - 14
Sr.No Element Clause / table
Minimum area of longitudinal reinforcement
1 : 18.7.4
for column
Maximum area of longitudinal
2 : 18.7.4
reinforcement for column
Minimum longitudinal and transverse
3 : 18.10.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 25.7.2
5 Minimum spacing of transverse ties : 25.7.2
Maximum spacing of longitudinal and
6 : 18.10.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 18.10.6
Area and spacing of special confining
8 : 18.7.5
reinforcement
9 Slenderness Moments : 6.2.5
10 : 22.5.5
Shear Strength provided by concrete for
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 5 of 244
column
11 Design of shear for non-ductile wall : 11.5.4
12 Design of shear for ductile wall : 18.10.4.1
13 Minimum Flexural Strength of Columns : 18.7.3
14 Shear Check at Column Joint : 18.8.4.1
15 Shear Strength of Column : 18.3.3, 18.4 & 18.6.5
16 fs,perm : 10.6.4
17 fc,perm : 10.2.7.1
18 Wcr : Eq 4.2(a)
Sway Calculation (Stability Index)
For Global-X Direction
Lateral Load case is not been considered in analysis in Global-X Direction
General Data
Column No. : C3
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 6 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 7 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 11.55
M1 = -467.98 kNm
M2 = -647.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.33
11.55 < 25.33, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 17.32
M1 = 0.39 kNm
M2 = 0.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.01
17.32 < 26.01, Column not slender along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 8 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 9 of 244
φ Pn = 8865.75 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 10 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 11 of 244
Location Bottom
Critical Analysis Load
1501
Combination
Critical Load Combination 10667
Member Force
P (kN) 396.46
Mx (kNm) 4.91
My (kNm) 0.66
Max Corner Stress (C1) 0.81
Min Corner Stress (C2) 0.66
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C3
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 12 of 244
Along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 13 of 244
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 17.03 kNm
M2 = -468.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.44
30.79 < 34.44, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.11 kNm
M2 = 0.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.49
46.19 > 30.49, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 3.11 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.01
Mc1 = 3.14 kNm
1.4 MuyB = 0.54 kNm
Mc1 = Min (3.14, 0.54) kNm
= 0.54 kNm
Mc2 = 3.14 kNm
1.4 MuyT = 0.16 kNm
Mc2 = Min (3.14, 0.16) kNm
= 0.16 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 14 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 15 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 16 of 244
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = 251.21 kNm
φVcy = 370.7 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 17 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C3
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 18 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 19 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -106.89 kNm
M2 = -145.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.21
2.31 < 25.21, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.58
3.46 < 35.58, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 20 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 21 of 244
Final Pt = 1 %
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 22 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 23 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C4
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 24 of 244
Vuyt = 197.09 kN
Pub = 794.57 kN
Muxb = 996.71 kNm
Muyb = 14.39 kNm
Vuxb = -2.74 kN
Vuyb = 197.09 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 25 of 244
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 11.55
M1 = 701.27 kNm
M2 = 996.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.56
11.55 < 25.56, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 17.32
M1 = 10.29 kNm
M2 = 14.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.42
17.32 < 25.42, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 26 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 27 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 28 of 244
deff = 530 mm
ρw (50% of As provided) = 0.014
Mm = -23.2 kNm
φVcx = 622.22 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 29 of 244
General Data
Column No. : C4
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 30 of 244
Vuyt = 196.15 kN
Pub = 766.58 kN
Muxb = 701.41 kNm
Muyb = 10.29 kNm
Vuxb = -2.47 kN
Vuyb = 196.15 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 31 of 244
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -88.44 kNm
M2 = 701.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.51
30.79 < 35.51, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.45 kNm
M2 = 10.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.48
46.19 > 33.48, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 25.3 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.06
Mc1 = 26.77 kNm
1.4 MuyB = 14.41 kNm
Mc1 = Min (26.77, 14.41) kNm
= 14.41 kNm
Mc2 = 26.77 kNm
1.4 MuyT = 0.63 kNm
Mc2 = Min (26.77, 0.63) kNm
= 0.63 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 32 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 33 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 34 of 244
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = 435.98 kNm
φVcy = 360.23 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 35 of 244
General Data
Column No. : C4
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 36 of 244
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 37 of 244
Axis = 2
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -88.55 kNm
M2 = -142.89 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.56
2.31 < 26.56, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = -0.01 kNm
M2 = 0.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.16
3.46 < 34.16, Column not slender along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 38 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 39 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 40 of 244
φ = 0.75
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = -94.76 kNm
φVcy = 694.04 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 41 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C5
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 42 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 43 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 11.55
M1 = 812.68 kNm
M2 = 1149.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.52
11.55 < 25.52, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 17.32
M1 = 1.95 kNm
M2 = 2.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 24.74
17.32 < 24.74, Column not slender along B
Where
A = Moments from analysis
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 44 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 45 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 46 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 47 of 244
General Data
Column No. : C5
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 48 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 49 of 244
axis
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -82.25 kNm
M2 = 812.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.21
30.79 < 35.21, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.05 kNm
M2 = 1.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.72
46.19 > 33.72, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 22.15 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.05
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 50 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 51 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 52 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 53 of 244
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 54 of 244
General Data
Column No. : C5
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 55 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -82.34 kNm
M2 = -145.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.2
2.31 < 27.2, Column not slender along D
Column Is Braced Along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 56 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 57 of 244
Pt Calculated = 1.28
φ Pn, Max = 8865.75 kN
Pu < φ Pn, Max Hence, OK
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 58 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 59 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C6
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 60 of 244
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 61 of 244
(Length x (Length x
Width x Depth) Width x Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 1112.1 No Beam No Beam - - 1
Top 1112.1 No Beam No Beam - - 1
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Minor
= 2
axis
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 11.55
M1 = 560.99 kNm
M2 = 794.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.53
11.55 < 25.53, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 17.32
M1 = 7.16 kNm
M2 = 10.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.45
17.32 < 25.45, Column not slender along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 62 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 63 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 64 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 65 of 244
General Data
Column No. : C6
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 66 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 67 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -61.02 kNm
M2 = 561.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.31
30.79 < 35.31, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.33 kNm
M2 = 7.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.45
46.19 > 33.45, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
Ig ( x 10 9) = 16.2 mm4
= 120387854.39 Nsqmm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 68 of 244
EI ( x 10 6)
M2min = 19.89 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.05
Mc1 = 20.79 kNm
1.4 MuyB = 10.03 kNm
Mc1 = Min (20.79, 10.03) kNm
= 10.03 kNm
Mc2 = 20.79 kNm
1.4 MuyT = 0.46 kNm
Mc2 = Min (20.79, 0.46) kNm
= 0.46 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 69 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 70 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 71 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 72 of 244
General Data
Column No. : C6
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 73 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 74 of 244
M1 = -61.21 kNm
M2 = -104.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.95
2.31 < 26.95, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = -0.01 kNm
M2 = 0.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.43
3.46 < 35.43, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 75 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 76 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 77 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C9
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 78 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 79 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 11.55
M1 = -556.73 kNm
M2 = -786.69 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.51
11.55 < 25.51, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 17.32
M1 = 2.07 kNm
M2 = 2.99 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 80 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 81 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 82 of 244
φ = 0.75
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = 583.11 kNm
φVcy = 346.56 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 83 of 244
General Data
Column No. : C9
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 84 of 244
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 85 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 55.17 kNm
M2 = -556.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.19
30.79 < 35.19, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.15 kNm
M2 = 2.07 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.13
46.19 > 33.13, Column slender along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 86 of 244
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 18.48 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = 19.25 kNm
1.4 MuyB = 2.9 kNm
Mc1 = Min (19.25, 2.9) kNm
= 2.9 kNm
Mc2 = 19.25 kNm
1.4 MuyT = 0.21 kNm
Mc2 = Min (19.25, 0.21) kNm
= 0.21 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 87 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 88 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 89 of 244
deff = 530 mm
ρw (50% of As provided) = 0.014
Mm = 9.52 kNm
φVcx = 385.53 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 90 of 244
General Data
Column No. : C9
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 91 of 244
Vuyt = -142.84 kN
Pub = 485.37 kN
Muxb = 55.24 kNm
Muyb = 0.15 kNm
Vuxb = -0.49 kN
Vuyb = -142.84 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 92 of 244
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 55.24 kNm
M2 = 97.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.18
2.31 < 27.18, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.76
3.46 < 33.76, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 93 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 94 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 95 of 244
Mm = -25.36 kNm
φVcx = 585.58 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 96 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 97 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 98 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 99 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 100 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 101 of 244
General Data
Column No. : C10
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 102 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 103 of 244
Along D
Q = 0.004
0.004< 0.05, Column shall be designed as non-sway frame
(Braced)
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 104 of 244
Pt Calculated = 1.28
φ Pn, Max = 8865.75 kN
Pu < φ Pn, Max Hence, OK
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 105 of 244
Nu = 577.91 kN
Muy = 555.98 kNm
Vuy = -154.69 kN
λ = 1
φ = 0.75
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = 355.88 kNm
φVcy = 359.11 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 106 of 244
General Data
Column No. : C10
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 107 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 108 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 66.43 kNm
M2 = 108.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.65
2.31 < 26.65, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 109 of 244
Klux /r = 3.46
M1 = 0 kNm
M2 = 0.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.74
3.46 < 33.74, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 110 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 111 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 112 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C11
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 113 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 114 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 115 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 116 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 117 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 118 of 244
General Data
Column No. : C11
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 119 of 244
Vuxb = -0.38 kN
Vuyb = 161.54 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 120 of 244
A B C
Major Axis Mux (top) -50.15 - -50.15
Major Axis Mux (bottom) 598.15 - 598.15
Minor Axis Muy (top) 0.08 - 0.08
Minor Axis Muy (bottom) 1.59 - 1.59
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 121 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 122 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 123 of 244
Link Rebar
10 --- --- 10 ---
Number
Spacing 300 --- --- 300 ---
General Data
Column No. : C11
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 124 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 125 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 77.44 kNm
M2 = 131.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.91
2.31 < 26.91, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0.01 kNm
M2 = 0.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.58
3.46 < 33.58, Column not slender along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 126 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 127 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 128 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 129 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C12
Level : 99.8 m To 101.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 130 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 131 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 11.55
M1 = -523.43 kNm
M2 = -744.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.56
11.55 < 25.56, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 17.32
M1 = 1.81 kNm
M2 = 2.57 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.56
17.32 < 25.56, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 132 of 244
Pu = 602.05 kN
Mux = -744.6 kNm
Muy = 2.57 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 133 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 134 of 244
Nu = 281.99 kN
Mux = 91.26 kNm
Vux = -17.54 kN
λ = 1
φ = 0.75
deff = 530 mm
ρw (50% of As provided) = 0.014
Mm = 25.34 kNm
φVcx = 345.84 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 135 of 244
General Data
Column No. : C12
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 136 of 244
N-DOZ)
Critical Location = Bottom Joint
Put = 499.51 kN
Muxt = 65.63 kNm
Muyt = 0.19 kNm
Vuxt = -0.4 kN
Vuyt = -146.45 kN
Pub = 574.06 kN
Muxb = -523.51 kNm
Muyb = 1.81 kNm
Vuxb = -0.4 kN
Vuyb = -146.45 kN
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 137 of 244
(Braced)
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 65.63 kNm
M2 = -523.51 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.5
30.79 < 35.5, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.19 kNm
M2 = 1.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.75
46.19 > 32.75, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 18.94 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = 19.76 kNm
1.4 MuyB = 2.53 kNm
Mc1 = Min (19.76, 2.53) kNm
= 2.53 kNm
Mc2 = 19.76 kNm
1.4 MuyT = 0.26 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 138 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 139 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 140 of 244
Vuy = -146.45 kN
λ = 1
φ = 0.75
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = 324.75 kNm
φVcy = 360.3 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 141 of 244
General Data
Column No. : C12
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 142 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 143 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 65.69 kNm
M2 = 105.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.55
2.31 < 26.55, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0.19 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 144 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 145 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 146 of 244
φ = 0.75
Deff = 830 mm
ρw (50% of As provided) = 0.014
Mm = 69.47 kNm
φVcy = 347.77 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 147 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C13
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 148 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 149 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -29.25 kNm
M2 = 595.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.59
30.79 < 34.59, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.1 kNm
M2 = 1.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.33
46.19 > 33.33, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 20.26 kNm
Cm = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 150 of 244
Pc = 18565.32 kN
δns = 1.05
Mc1 = 21.19 kNm
1.4 MuyB = 2.39 kNm
Mc1 = Min (21.19, 2.39) kNm
= 2.39 kNm
Mc2 = 21.19 kNm
1.4 MuyT = 0.13 kNm
Mc2 = Min (21.19, 0.13) kNm
= 0.13 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 151 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 152 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 153 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 154 of 244
General Data
Column No. : C13
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 155 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -29.29 kNm
M2 = -66.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.74
2.31 < 28.74, Column not slender along D
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 156 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 157 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 158 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 159 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C14
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 160 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 161 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -30.91 kNm
M2 = 571.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.65
30.79 < 34.65, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.1 kNm
M2 = 1.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.33
46.19 > 33.33, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 162 of 244
βdns = 0.6
Ec = 25742.96 N/sqmm
Ig ( x 10 9) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 19.15 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = 19.99 kNm
1.4 MuyB = 2.59 kNm
Mc1 = Min (19.99, 2.59) kNm
= 2.59 kNm
Mc2 = 19.99 kNm
1.4 MuyT = 0.14 kNm
Mc2 = Min (19.99, 0.14) kNm
= 0.14 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 163 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 164 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 165 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 166 of 244
General Data
Column No. : C14
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 167 of 244
Vuxb = -0.33 kN
Vuyb = 141.1 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 168 of 244
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -30.94 kNm
M2 = -66.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.43
2.31 < 28.43, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0.01 kNm
M2 = 0.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.36
3.46 < 33.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 169 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 170 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 171 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C15
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 172 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 173 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -35.87 kNm
M2 = 569.65 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.76
30.79 < 34.76, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.16 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 174 of 244
M2 = 2.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.33
46.19 > 33.33, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 22.37 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.05
Mc1 = 23.52 kNm
1.4 MuyB = 3.97 kNm
Mc1 = Min (23.52, 3.97) kNm
= 3.97 kNm
Mc2 = 23.52 kNm
1.4 MuyT = 0.22 kNm
Mc2 = Min (23.52, 0.22) kNm
= 0.22 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 175 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 176 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 177 of 244
Nu = 263.57 kN
Mux = 0.76 kNm
Vux = -13.88 kN
λ = 1
φ = 0.75
deff = 530 mm
ρw (50% of As provided) = 0.014
Mm = -60.85 kNm
φVcx = 607.14 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 178 of 244
General Data
Column No. : C15
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 179 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 180 of 244
(Braced)
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -35.9 kNm
M2 = -70.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.89
2.31 < 27.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.21
3.46 < 34.21, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 181 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 182 of 244
Pt Calculated = 1.28
Reinforcement Provided = 22-#20
Load Angle = Tan-1(Muy/Mux)
= 0 deg
Corresponding NA angle ( β ) = 0 deg
MRes = 70.55 kNm
( φ ) MCap = 1340.13 kNm
Capacity Ratio = MRes/ MCap
= 0.053 < 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 183 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 184 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C16
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 185 of 244
Vuxb = -0.99 kN
Vuyb = 134.81 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 186 of 244
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = -35.76 kNm
M2 = 521.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.82
30.79 < 34.82, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0.16 kNm
M2 = 4.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.53
46.19 > 33.53, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 19.44 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = 20.3 kNm
1.4 MuyB = 5.74 kNm
Mc1 = Min (20.3, 5.74) kNm
= 5.74 kNm
Mc2 = 20.3 kNm
1.4 MuyT = 0.23 kNm
Mc2 = Min (20.3, 0.23) kNm
= 0.23 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 187 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 188 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 189 of 244
φVcy = 358.38 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 190 of 244
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar
10 --- --- 10 ---
Number
Spacing 300 --- --- 300 ---
General Data
Column No. : C16
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 191 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 192 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = -35.77 kNm
M2 = -65.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.47
2.31 < 27.47, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.19
3.46 < 34.19, Column not slender along B
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 193 of 244
A B C
Major Axis Mux (top) -65.7 - -65.7
Major Axis Mux (bottom) -35.77 - -35.77
Minor Axis Muy (top) 0 - 0
Minor Axis Muy (bottom) 0.16 - 0.16
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 194 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 195 of 244
Mm = -110.54 kNm
φVcy = 669.46 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 196 of 244
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar
10 --- --- 10 ---
Number
Spacing 300 --- --- 300 ---
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C17
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 197 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 198 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 23.36 kNm
M2 = -517.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.54
30.79 < 34.54, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0 kNm
M2 = -0.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.06
46.19 > 34.06, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 16.74 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = -17.38 kNm
1.4 MuyB = -0.55 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 199 of 244
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 200 of 244
Pt Calculated = 1.28
φ Pn, Max = 8865.75 kN
Pu < φ Pn, Max Hence, OK
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 201 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 202 of 244
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C17
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 203 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 204 of 244
(Length x (Length x
Width x Depth) Width x Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 12511.08 No Beam No Beam - - 1
Top 12511.08 No Beam No Beam - - 1
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Major
= 2
Axis
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 23.39 kNm
M2 = 54.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.86
2.31 < 28.86, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 205 of 244
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
3.46 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 206 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 207 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 208 of 244
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C18
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 209 of 244
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 210 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 21.51 kNm
M2 = -516.65 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.5
30.79 < 34.5, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = 0 kNm
M2 = -0.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.96
46.19 > 33.96, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
Ig ( x 10 9) = 16.2 mm4
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 211 of 244
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 17.59 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = -18.29 kNm
1.4 MuyB = -0.62 kNm
Mc1 = Min (-18.29, -0.62) kNm
= -0.62 kNm
Mc2 = -18.29 kNm
1.4 MuyT = 0 kNm
Mc2 = Min (-18.29, 0) kNm
= 0 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 212 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 213 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 214 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 215 of 244
Epsilon-deff, ε1 0.0001 0
Wcr (mm) 0.0195 0
WcrPerm (mm) 0.15 0.15
General Data
Column No. : C18
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 216 of 244
Vuyb = -125.34 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 217 of 244
r = 259.81 mm
Kluy /r = 2.31
M1 = 21.55 kNm
M2 = 52.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 29.12
2.31 < 29.12, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 22.36
3.46 < 22.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 218 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 219 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 220 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C19
Level : 101.3 m To 105.3 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 221 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 222 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 22.07 kNm
M2 = -572.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.46
30.79 < 34.46, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 46.19
M1 = -0.03 kNm
M2 = -0.94 kNm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 223 of 244
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
9
Ig ( x 10 ) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 17.46 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = -18.15 kNm
1.4 MuyB = -1.32 kNm
Mc1 = Min (-18.15, -1.32) kNm
= -1.32 kNm
Mc2 = -18.15 kNm
1.4 MuyT = -0.04 kNm
Mc2 = Min (-18.15, -0.04) kNm
= -0.04 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 224 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 225 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 226 of 244
deff = 530 mm
ρw (50% of As provided) = 0.014
Mm = 9.97 kNm
φVcx = 381.36 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 227 of 244
General Data
Column No. : C19
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 228 of 244
Vuyt = -138.23 kN
Pub = 454.4 kN
Muxb = 22.09 kNm
Muyb = -0.03 kNm
Vuxb = 0.1 kN
Vuyb = -138.23 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 229 of 244
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 22.09 kNm
M2 = 56.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 29.31
2.31 < 29.31, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = -0.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.8
3.46 < 34.8, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 230 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 231 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 232 of 244
φVcx = 582.72 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
General Data
Column No. : C20
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 233 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 234 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 30.79
M1 = 23.61 kNm
M2 = -561.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.5
30.79 < 34.5, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 235 of 244
r = 173.2 mm
Klux /r = 46.19
M1 = -0.06 kNm
M2 = -2.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.65
46.19 > 33.65, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 25742.96 N/sqmm
Ig ( x 10 9) = 16.2 mm4
EI ( x 10 6) = 120387854.39 Nsqmm
M2min = 17.09 kNm
Cm = 1
Pc = 18565.32 kN
δns = 1.04
Mc1 = -17.75 kNm
1.4 MuyB = -2.98 kNm
Mc1 = Min (-17.75, -2.98) kNm
= -2.98 kNm
Mc2 = -17.75 kNm
1.4 MuyT = -0.09 kNm
Mc2 = Min (-17.75, -0.09) kNm
= -0.09 kNm
Note : The Slenderness Moment (Mc1 and Mc2) is greater than 1.4 Mu. Hence 1.4 Mu is
considered for Design.
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 236 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 237 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 238 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 239 of 244
General Data
Column No. : C20
Level : 105.3 m To 105.6 m
Frame Type = Non-Ductile
Response Modification Coefficient = 1
Design Code = ACI 318M - 14
Grade Of Concrete (f'c) = C30 N/sqmm
Grade Of Steel (fy) = Fy500 N/sqmm
Consider Ductile = No
Column B = 600 mm
Column D = 900 mm
Clear Cover, Cc = 60 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 240 of 244
Put = 437.62 kN
Muxt = 56.06 kNm
Muyt = 0 kNm
Vuxt = 0.21 kN
Vuyt = -135.18 kN
Pub = 443.21 kN
Muxb = 23.62 kNm
Muyb = -0.06 kNm
Vuxb = 0.21 kN
Vuyb = -135.18 kN
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 241 of 244
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 2
r = 259.81 mm
Kluy /r = 2.31
M1 = 23.62 kNm
M2 = 56.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.94
2.31 < 28.94, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 2
r = 173.2 mm
Klux /r = 3.46
M1 = 0 kNm
M2 = -0.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.3
3.46 < 34.3, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 242 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 243 of 244
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022
Column Design: Design Calculations Page 244 of 244
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Link Rebar Number = 10
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
Minimum corner stress in all load cases is more than Zero,Hence Section is Uncracked.
file:///C:/Users/akshayp/AppData/Local/Temp/tmpF505.tmp 10/10/2022