Definitions Of Terms:
All forces in units 'kN' and 'm'
All reinforcement details like area, spacing in 'mm'
Neutral axis angle for resultant design moment is with respect to local major axis.
1 βdns = Ratio to account for reduction of stiffness of columns due to sustained axial loads
2 δns = Moment magnification factor for frames not braced against sidesway
First-order relative deflection between the top and bottom of the story due to Vu
3 Δo =
in 'kN'
4 ∑Pu = Total factored vertical load in 'kN'. (Clause 406.6.4.4)
5 δu = Design displacement in 'mm'
6 λ = Modification factor reflecting the reduced mechanical properties Of concrete
Coefficient defining the relative contribution Of concrete strength To nominal wall
7 ac =
shear strength
Cross-sectional area of a structural member measured to the outside edges of
8 Ach =
transverse reinforcement in 'sqmm'
Gross area of concrete section bounded by web thickness And length of section
9 Acv =
in the direction Of shear force considered in 'sqmm'
Effective cross-sectional area within a joint In a plane parallel To plane Of
10 Aj =
reinforcement generating shear In the joint in 'sqmm'
11 As = Area Of non-prestressed longitudinal tension reinforcement in 'sqmm'
12 Avmin = Minimum area Of shear reinforcement within spacing 's' in 'sqmm'
13 B = Width of column/ wall in 'mm'
14 beff = Effective Width of column/ wall in 'mm'
Cross-sectional dimension of member core measured to the outside edges of the
15 bc1 and dc1 =
transverse reinforcement composing area Ash in 'mm'
16 c = Distance from extreme compression fiber to neutral axis in 'mm'
17 Cc = Clear cover to longitudinal reinforcement in 'mm'
Factor relating actual moment diagram to an equivalent uniform moment
18 Cm =
diagram
19 D = Depth / diameter of column in 'mm'
20 deff = Effective Depth / diameter of column in 'mm'
Distance from extreme compression fiber to centroid of longitudinal tension
21 d =
reinforcement in 'mm'
Distance from extreme compression fiber to centroid of longitudinal compression
22 d' =
reinforcement,'mm'
23 Ec = Modulus of elasticity of concrete in 'N/sqmm'
24 EI = Flexural stiffness of compression member in 'Nsqmm'
25 f'c = Specified compressive strength of concrete cylinder in 'N/sqmm'
26 fy = Specified yield strength of reinforcement in 'N/sqmm'
27 fyt = Specified yield strength fy of transverse reinforcement in 'N/sqmm'
28 hw = Height of entire wall from base to top of wall segment considered in 'mm'
29 Icr = Moment of Inertia of concrete crack section
30 k = Effective length factor for compression member
Length of compression member in a frame, measured center-to-center of the
31 lc =
joints in the frame in 'mm'
Moment of inertia of gross concrete section about centroidal axis neglecting
32 lg =
reinforcement in 'mm4'
33 lw = Length of entire wall in 'mm'
34 lux = Un-supported length for compression member along D in 'mm'
35 luy = Un-supported length for compression member along B in 'mm'
36 MCap = Moment capacity of section for a given NA angle at design Pu in 'kNm '
37 Mcr = Cracking Moment
38 MRes = Resultant design moment at a given load angle to local major axis in 'kNm '
Factored moment amplified for the effects of member curvature used for design
39 Mc =
of compression member in 'kNm'
40 Mm = Factored moment modified to account for effect of axial compression in 'kNm'
Factored moment along D of column modified to account for effect of axial
41 Mmx =
compression in 'kNm'
Factored moment along D of column modified to account for effect of axial
42 Mmy =
compression in 'kNm'
43 Mur = Sqrt (Mmy^2 + Mmx^2) for circular column in 'kNm'
Factored moment acting on a section along D in 'kNm' from Analysis (Momemt
44 Mux =
About Major Axis)
Factored moment acting on a section along B in 'kNm' from Analysis (Momemt
45 Muy =
About Minor Axis)
46 M1 = Smaller factored end moment on a compression member in 'kNm'
Factored end moment on a compression member at the end at which M1 acts,
47 M1ns =
due to loads that cause no appreciable sidesway in 'kNm'
Factored end moment on compression member at the end at which M1 acts, due
48 M1s =
to loads that cause appreciable sidesway in 'kNm'
Smaller factored end moment on a compression member due to slenderness
49 M1sldr =
effect in 'kNm'
50 M2 = Larger factored end moment on compression member in 'kNm'
51 M2min = Minimum value of moment M2 as per minimum eccentricity of column
Factored end moment on compression member at the end at which M2 acts, due
52 M2ns =
to loads that cause no appreciable sidesway in 'kNm'
Factored end moment on compression member at the end at which M2 acts, due
53 M2s =
to loads that cause appreciable sidesway in 'kNm'
Largest factored end moment on a compression member due to slenderness
54 M2sldr =
effect in 'kNm'
55 Mnb = Flexure Capacity for Beam
56 Mnc = Flexure Capacity for Column
57 Mnty = Nominal Flexure strength of column at top along depth in 'kNm'
58 Mnby = Nominal Flexure strength of column at bottom along depth in 'kNm'
59 Mntx = Nominal Flexure strength of column at top along width in 'kNm'
60 Mnbx = Nominal Flexure strength of column at bottom along width in 'kNm'
Factored axial force normal to cross section occurring simultaneously with Vu in
61 Nu =
'kN'
62 Pc = Critical buckling load in 'kN'
Ratio of area of distributed transverse reinforcement to gross concrete area
63 pt =
perpendicular to that reinforcement
64 Pω = Ratio of As to B x d
65 Q = Stability index for storey
66 r = Radius of gyration of cross section of a compression member in 'mm'
67 Vc = Nominal shear strength provided by concrete in 'kN'
68 Vj = Shear Force acting at the joint in 'kN'
69 Vn = Nominal shear strength in 'kN'
70 Vn' = Nominal shear strength at joint in 'kN'
71 Vs = nominal shear strength provided by shear reinforcement in 'kN'
72 Vs permissible = Maximum nominal shear strength provided by shear reinforcement in 'kN'
73 Vur = Factored resultant shear force acting on the column in 'kN'
74 Vus = Factored horizontal shear in a storey in 'kN'
75 Vux = Factored shear at section along B in 'kN' (From Analysis)
76 Vux1 = Shear induced due to column flexural capacity along width,'kN'
77 Vux2 = Shear due to enhanced earthquake factor along width, 'kN'
78 Vuy = Factored shear at section along D in 'kN' (From Analysis)
79 Vuy1 = Shear induced due to column flexural capacity along depth, 'kN'
80 Vuy2 = Shear due to enhanced earthquake factor along depth, 'kN'
81 y = Neutral axis depth.
82 β = It is a Neutral Axis angle corresponding to load angle to find out MCap
83 So = Center to center spacing of transverse reinforcement within the length lo in 'mm'
Length, measured from joint face along axis of member, over which special
84 lo =
transverse reinforcement must be provided in 'mm'
Code References:
NSCP C101 - 2015
Sr.No Element Clause / table
1 Minimum area of longitudinal reinforcement for column : 418.7.4
2 Maximum area of longitudinal reinforcement for column : 418.7.4
3 Minimum longitudinal and transverse reinforcement for wall : 418.10.2.1
4 Minimum diameter of transverse ties : 425.7.2
5 Minimum spacing of transverse ties : 425.7.2
Maximum spacing of longitudinal and transverse reinforcement for
6 : 418.10.2.1
wall
7 Applicability of boundary element : 418.10.6
8 Area and spacing of special confining reinforcement : 418.7.5
9 Slenderness Moments : 406.2.5
10 Shear Strength provided by concrete for column : 422.5.5
11 Design of shear for non-ductile wall : 411.5.4
12 Design of shear for ductile wall : 418.10.4.1
13 Minimum Flexural Strength of Columns : 418.7.3
14 Shear Check at Column Joint : 418.8.4.1
15 Shear Strength of Column : 418.3.3, 418.4 & 418.6.5
16 fs,perm : 424.3.2.1
17 fc,perm : A.3.1 (ACI 318-99)
18 Wcr : Eq 1-2 ( ACI 224R-01)
Sway Calculation (Stability Index)
For Global-X Direction
Level Load Combination Storey Height Gravity Load P Relative Storey Shear Stability Index Sway Condition
Analysis (m) (kN) Displacements (mm) (kN) (Q)
A B C D B x C / (A x D)
0 m to 2.1 m 104 2.1 10613.19 3.21 290.97 0.056 Sway
2.1 m to 2.3 m 104 0.2 11858.66 0.9 379.17 0.14 Sway
2.3 m to 4.6 m 104 2.3 231345.14 3.36 9401.73 0.036 Non Sway
4.6 m to 6.1 m 104 1.5 8907.96 1.94 465.46 0.025 Non Sway
6.1 m to 6.3 m 104 0.2 10044.7 1.79 616.21 0.146 Sway
6.3 m to 8.6 m 103 2.3 196811.51 2.83 9031.99 0.027 Non Sway
8.6 m to 10.1 m 104 1.5 7231.71 2.35 327.23 0.035 Non Sway
10.1 m to 10.3
104 0.2 8029.27 2.87 447.46 0.258 Sway
m
10.3 m to 12.6
104 2.3 161775.91 3.33 8330.15 0.028 Non Sway
m
12.6 m to 14.1
104 1.5 5622.21 1.37 314.92 0.016 Non Sway
m
14.1 m to 14.3
104 0.2 6118.39 3.93 429.64 0.28 Sway
m
14.3 m to 16.6
104 2.3 126740.31 2.22 7302.23 0.017 Non Sway
m
16.6 m to 18.1
104 1.5 4063.48 0.62 266.25 0.006 Non Sway
m
18.1 m to 18.3
104 0.2 4305.26 4.85 364.78 0.286 Sway
m
18.3 m to 20.6
103 2.3 91729.89 0.19 5949.33 0.001 Non Sway
m
20.6 m to 22.1
104 1.5 2553.49 0.51 211.63 0.004 Non Sway
m
22.1 m to 22.3
104 0.2 2678.36 5.6 283.64 0.264 Sway
m
22.3 m to 24.6
m 103 2.3 56947.87 1.36 4283.31 0.008 Non Sway
24.6 m to 26.1
104 1.5 1192.92 0.29 102.01 0.002 Non Sway
m
26.1 m to 26.3
104 0.2 1258.82 6.16 152.1 0.255 Sway
m
26.3 m to 28.6
104 2.3 22978.14 1.69 2346 0.007 Non Sway
m
28.6 m to 32.1
103 3.5 409.51 8.61 936.23 0.001 Non Sway
m
General Data
Column No. : C1
Level : 0 m To 2.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.035
0.035< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 1.74
r = 223.72 mm
Kluy /r = 11.67
Permissible slenderness ratio = 22
11.67 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 5.77
M1 = 109.66 kNm
M2 = -406.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.24
5.77 < 37.24, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.95
r = 223.72 mm
Kluy /r = 8.07
M1 = -9.52 kNm
M2 = -9.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 22.54
8.07 < 22.54, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.97
r = 223.72 mm
Klux /r = 8.24
M1 = -215.05 kNm
M2 = 474.69 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.44
8.24 < 39.44, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Pu = 5579.15 kN
Ag = 600625 sqmm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD3 = 413.66 sqmm
AshD (Max (AshD1, AshD2, AshD3)) = 413.66 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Pu = 5579.15 kN
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB3 = 413.66 sqmm
AshB (Max (AshB1, AshB2, AshB3)) = 413.66 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C1
Level : 4.6 m To 6.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.95
r = 223.72 mm
Kluy /r = 3.82
M1 = -1.93 kNm
M2 = -12.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.21
3.82 < 32.21, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.97
r = 223.72 mm
Klux /r = 3.9
M1 = 32.63 kNm
M2 = -509.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.77
3.9 < 34.77, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 561.69 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.94
r = 223.72 mm
Kluy /r = 7.98
M1 = -5.52 kNm
M2 = 12.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.24
7.98 < 39.24, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.49
r = 223.72 mm
Klux /r = 29.64
Permissible slenderness ratio = 22
29.64 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 595.37 kNm
δns x M2s = -298.9 kNm
M1ns = 36.37 kNm
M2ns = -2.85 kNm
δns = 1.06
M1sldr = 631.74 kNm
1.4 MuyT = 839.99 kNm
M1sldr = Min (631.74, 839.99) kNm
= 631.74 kNm
M2sldr = -301.75 kNm
1.4 MuyB = -400.14 kNm
M2sldr = Min (-301.75, -400.14) kNm
= -301.75 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 55.77 26.61 574.7 791.7 153.89 27.41 574.7 791.7 154.04 153.89 0 154.04 0
400 x 600 270 0.88 266.24 1420.04 1470.3 274.86 275.41 1473.57 1583.4 294.62 0 274.86 0 294.62
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 8.6 m To 10.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.88
r = 173.2 mm
Kluy /r = 4.57
M1 = -3.14 kNm
M2 = -14.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.34
4.57 < 31.34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.96
r = 173.2 mm
Klux /r = 4.99
M1 = 88.21 kNm
M2 = -340.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.1
4.99 < 37.1, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 3782.61 kN
Mux = -3.14 kNm
Muy = -340.99 kNm
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 918.42 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
No of bars along B = 7
S1 = 100 mm
Pu = 3782.61 kN
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB3 = 383.36 sqmm
AshB (Max (AshB1, AshB2, AshB3)) = 383.36 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C1
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = -6.36 kNm
M2 = 11.86 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
Along B
δns x M1s = 451.91 kNm
δns x M2s = -267.81 kNm
M1ns = 19.08 kNm
M2ns = 1.1 kNm
δns = 1.05
M1sldr = 470.99 kNm
1.4 MuyT = 627.26 kNm
M1sldr = Min (470.99, 627.26) kNm
= 470.99 kNm
M2sldr = -266.72 kNm
1.4 MuyB = -354.37 kNm
M2sldr = Min (-266.72, -354.37) kNm
= -266.72 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 268.8 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
S1 = 100 mm
Pu = 3774.75 kN
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD3 = 382.56 sqmm
AshD (Max (AshD1, AshD2, AshD3)) = 382.56 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Pu = 3774.75 kN
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB3 = 382.56 sqmm
AshB (Max (AshB1, AshB2, AshB3)) = 382.56 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C1
Level : 12.6 m To 14.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.029
0.029< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 6.05 kNm
M2 = -9.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
4.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = 71.01 kNm
M2 = -330.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.58
4.94 < 36.58, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 807.12 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 12.66 kNm
M2 = -12.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.54 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 10.42
M1 = -219.54 kNm
M2 = 403.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.42 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 16.6 m To 18.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.025
0.025< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 59.76 kNm
M2 = 264.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.29
4.52 < 31.29, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -7.39 kNm
M2 = -52.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.31
4.94 < 32.31, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 690.76 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 11.68 kNm
M2 = -19.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.54 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 10.42
M1 = -169.09 kNm
M2 = 332.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.42 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 2037.64 kN
Mux = -19.33 kNm
Muy = 332.76 kNm
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 20.6 m To 22.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.018
0.018< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 42.77 kNm
M2 = 208.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.54
4.52 < 31.54, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -7.41 kNm
M2 = -53.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.34
4.94 < 32.34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Rebar Number of bundled bar, D1 = 20
Diameter of bundled bar, D1 = 20 mm
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 581.19 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 10.96 kNm
M2 = -29.57 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.45
9.54 < 38.45, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 10.42
M1 = -110.34 kNm
M2 = 255.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.18
10.42 < 39.18, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 19.55 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C1
Level : 24.6 m To 26.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.023
0.023< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 36.83 kNm
M2 = 120.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.34
4.52 < 30.34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -12.91 kNm
M2 = -47.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.77
4.94 < 30.77, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 470.47 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 173.2 mm
Kluy /r = 9.32
M1 = 35.7 kNm
M2 = -104.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.12
9.32 < 38.12, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 10.2
M1 = -7.27 kNm
M2 = 61.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.41
10.2 < 35.41, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C1
Level : 28.6 m To 32.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.91
r = 173.2 mm
Kluy /r = 16.81
M1 = -25.35 kNm
M2 = 36.4 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.81 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 17.18
M1 = 56.31 kNm
M2 = -431.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.57
17.18 < 35.57, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 250 --- 100 250 100
General Data
Column No. : C2
Level : 0 m To 2.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.035
0.035< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 1.74
r = 223.72 mm
Kluy /r = 11.67
Permissible slenderness ratio = 22
11.67 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 5.77
M1 = -116.95 kNm
M2 = 406.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.46
5.77 < 37.46, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.95
r = 223.72 mm
Kluy /r = 8.07
M1 = 7.65 kNm
M2 = -17 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.4
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
500 x 750 0 10.12 684.49 2935.24 2940.6 685.61 327.1 1569.51 1583.4 388.5 685.61 0 388.5 0
400 x 600 90 7.54 502.98 2945.62 3053.7 517.81 178 1472.81 1583.4 294.62 0 517.81 0 294.62
400 x 600 180 0.74 353.6 1945.85 2035.8 367.94 80.51 972.93 1017.9 195.58 367.94 0 195.58 0
400 x 600 270 0.24 396.89 2220.94 2262 403.21 136.75 1110.47 1131 215.93 0 403.21 0 215.93
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 4.6 m To 6.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.95
r = 223.72 mm
Kluy /r = 3.82
M1 = 109.1 kNm
M2 = 447.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.07
3.82 < 31.07, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.97
r = 223.72 mm
Klux /r = 3.9
M1 = 2.03 kNm
M2 = 8.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.14
3.9 < 31.14, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 473.85 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.94
r = 223.72 mm
Kluy /r = 7.98
M1 = -13.71 kNm
M2 = 15.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
7.98 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.49
r = 223.72 mm
Klux /r = 29.64
Permissible slenderness ratio = 22
29.64 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = -463.94 kNm
δns x M2s = 276.04 kNm
M1ns = -22.79 kNm
M2ns = 6.97 kNm
δns = 1.06
M1sldr = -486.73 kNm
1.4 MuyT = -646.79 kNm
M1sldr = Min (-486.73, -646.79) kNm
= -486.73 kNm
M2sldr = 283 kNm
1.4 MuyB = 375.6 kNm
M2sldr = Min (283, 375.6) kNm
= 283 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 8.6 m To 10.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.88
r = 173.2 mm
Kluy /r = 4.57
M1 = 69.4 kNm
M2 = 311.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.33
4.57 < 31.33, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.96
r = 173.2 mm
Klux /r = 4.99
M1 = 1.25 kNm
M2 = 2.94 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.91
4.99 < 28.91, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 870.91 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 15.62 kNm
M2 = -17.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.54 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.61
r = 173.2 mm
Klux /r = 28.63
Permissible slenderness ratio = 22
28.63 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = -393.01 kNm
δns x M2s = 257.79 kNm
M1ns = -17.93 kNm
M2ns = 7.96 kNm
δns = 1.05
M1sldr = -410.95 kNm
1.4 MuyT = -547.39 kNm
M1sldr = Min (-410.95, -547.39) kNm
= -410.95 kNm
M2sldr = 265.75 kNm
1.4 MuyB = 353.73 kNm
M2sldr = Min (265.75, 353.73) kNm
= 265.75 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
λ 1 1
φ 0.75 0.75
Deff (mm) 540 540
ρw (50% of As provided) 0.012 0.012
Mm (kNm) -118.05 -58.38
φVc (kN) 509.72 502.04
Check Vu < φVc Vu > φVc
Link For Shear Design Not Required Required
Shear Links Design
Vs (kN) (Vu - φVc) / φVc
- 31.84
Vs Permissible (kN) 0.66 x sqrt(f'c) x b x deff
- 972.44
Vs Permissible Check - Vs < Vs permissible; Hence, OK
Check for Minimum Shear -
Reinforcement
0.5 x φVc (kN) - 251.02
Minimum Shear Reinforcement - Vu > 0.5 x φVc; Hence ,
Check Minimum Shear reinforcement
required
Av/s minimum (sqmm/m) - 507.25
Av/s shear (sqmm/m) - 142.4
Av/s required (sqmm/m) max (Av/s minimum , Av/s shear)
- 507.25
Link Rebar Number - 10
Diameter of link (mm) - 10
Numbers of legs provided - 7
Spacing of Link Provided (mm) - 250
Av/s provided (sqmm/m ) - 2199.12
Av/s provided check - Av/s required < Av/s provided;
Hence, OK
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 31.84 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 70.15 kNm
M2 = 301.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.21
4.52 < 31.21, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -1.22 kNm
M2 = 16.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.88
4.94 < 34.88, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 801.95 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 14.93 kNm
M2 = -20.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.54 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 10.42
M1 = 224.57 kNm
M2 = -356.02 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.42 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 3.59 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 16.6 m To 18.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Along B
Q = 0.025
0.025< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 54.37 kNm
M2 = 248.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.38
4.52 < 31.38, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -2.29 kNm
M2 = 22.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.23
4.94 < 35.23, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 675.78 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [6] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 7: EQPZ)
Pu = 2052.02 kN
Check for Ash
0.3 x Ag x f'c = 2233.44 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 7
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C2
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 12.95 kNm
M2 = -23.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.54 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 10.42
M1 = 178.12 kNm
M2 = -297.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.42 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
500 x 750 0 13.97 443.19 1824.22 1922.7 465.46 104.18 916.1 1017.9 254.69 465.46 0 254.69 0
400 x 600 90 14.31 357.66 2130.43 2148.9 385.72 8.98 1065.21 1131 215.93 0 385.72 0 215.93
400 x 600 180 1 280.94 1505.98 1583.4 294.03 52.09 752.99 791.7 154.04 294.03 0 154.04 0
400 x 600 270 0.49 305.84 1653.89 1696.5 312.93 64.76 826.94 904.8 174.94 0 312.93 0 174.94
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 20.6 m To 22.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Along B
Q = 0.018
0.018< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 37.42 kNm
M2 = 188.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.62
4.52 < 31.62, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -4.25 kNm
M2 = 28.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.78
4.94 < 35.78, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 37.42 - 37.42
Major Axis Mux (bottom) 188.64 - 188.64
Minor Axis Muy (top) -4.25 - -4.25
Minor Axis Muy (bottom) 28.73 - 28.73
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 556.98 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 135 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C2
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1900 mm
Clear Floor Height @ luy = 1900 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 9.54
M1 = 11.33 kNm
M2 = -23.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.75
9.54 < 39.75, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 10.42
M1 = 123.05 kNm
M2 = -234.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
10.42 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Level : 24.6 m To 26.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Along B
Q = 0.023
0.023< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.87
r = 173.2 mm
Kluy /r = 4.52
M1 = 28.21 kNm
M2 = 97.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.52
4.52 < 30.52, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 4.94
M1 = -0.29 kNm
M2 = 25.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.13
4.94 < 34.13, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 444.89 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C2
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 173.2 mm
Kluy /r = 9.32
M1 = 29.33 kNm
M2 = -85.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.1
9.32 < 38.1, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 10.2
M1 = 12.48 kNm
M2 = -41.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.59
10.2 < 37.59, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
154.04 154.04
Lu (mm) 1900 1900
Vu2 (kN) 380.07 336.64
Critical Analysis Load 104 105
Combination
Critical Load Combination [5] : 1.2 (LOAD 1: DL) +(LOAD 2: [6] : 1.2 (LOAD 1: DL) +(LOAD 2:
LL) +(LOAD 6: EQNX) LL) +(LOAD 7: EQPZ)
Nu (kN) 588.91 571.01
Mu (kNm) 85.87 61.34
Vu3 (kN) -46.09 57.34
Vu' (kN) Minimum(Vu1, Vu2)
380.07 336.64
Design Shear, Vu (kN) Maximum(Vu', Vu3)
380.07 336.64
λ 1 1
φ 0.75 0.75
Deff (mm) 540 540
ρw (50% of As provided) 0.012 0.012
Mm (kNm) -51.05 -71.42
φVc (kN) 389.12 387.22
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C2
Level : 28.6 m To 32.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.91
r = 173.2 mm
Kluy /r = 16.81
M1 = -26.17 kNm
M2 = 43.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.81 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 17.18
M1 = -57.81 kNm
M2 = 418.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.66
17.18 < 35.66, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 250 --- 100 250 100
General Data
Column No. : C3
Level : 2.1 m To 2.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.04
0.04< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 2.15
r = 223.72 mm
Kluy /r = 16.34
Permissible slenderness ratio = 22
16.34 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.87
r = 223.72 mm
Klux /r = 6.61
M1 = 160.35 kNm
M2 = -403.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.77
6.61 < 38.77, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.99
r = 223.72 mm
Kluy /r = 7.52
M1 = -23.16 kNm
M2 = 411.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.68
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.04 408.36 2295.66 2375.1 420.42 136.92 1147.83 1244.1 236.02 0 420.42 0 236.02
500 x 750 0 17.75 756.03 3532.37 3619.2 822.27 425.81 1766.19 1809.6 440.48 822.27 0 440.48 0
400 x 600 180 0.04 353.95 1948.03 2035.8 367.94 109.48 974.01 1017.9 195.58 367.94 0 195.58 0
400 x 600 270 22.33 334.53 1972.11 2035.8 367.94 70.75 986.05 1017.9 195.58 0 367.94 0 195.58
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 6.1 m To 6.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 5
r = 223.72 mm
Kluy /r = 24.58
Permissible slenderness ratio = 22
24.58 > 22, Column slender along D
Column Is Braced Along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.98
r = 223.72 mm
Kluy /r = 7.45
M1 = 114.51 kNm
M2 = -604.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.27
7.45 < 36.27, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 5
r = 223.72 mm
Klux /r = 37.99
Permissible slenderness ratio = 22
37.99 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 33.5 kNm
δns x M2s = -11.15 kNm
M1ns = 55.96 kNm
M2ns = -30.93 kNm
δns = 1.06
M1sldr = 89.46 kNm
1.4 MuyT = 122.74 kNm
M1sldr = Min (89.46, 122.74) kNm
= 89.46 kNm
M2sldr = -42.08 kNm
1.4 MuyB = -58.08 kNm
M2sldr = Min (-42.08, -58.08) kNm
= -42.08 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 0 68.77 103.39 761.8 791.7 153.89 0 574.7 791.7 154.04 153.89 0 154.04 0
400 x 600 270 0.79 300.95 1624.6 1696.5 312.93 237.37 1253.82 1357.2 255.82 0 312.93 0 255.82
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 10.1 m To 10.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.57
r = 173.2 mm
Kluy /r = 22.67
Permissible slenderness ratio = 22
22.67 > 22, Column slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 27.92 kNm
M2 = -49.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
6.29 < 40, Column not slender along B
Moment Magnification:
For Sway Frame:
Along D
δns x M1s = 60.02 kNm
δns x M2s = 488.45 kNm
M1ns = -34.55 kNm
M2ns = 30.25 kNm
δns = 1.35
M1sldr = 14 kNm
1.4 MuxT = 14 kNm
M1sldr = Min (14, 14) kNm
= 14 kNm
M2sldr = 518.7 kNm
1.4 MuxB = 549.91 kNm
M2sldr = Min (518.7, 549.91) kNm
= 518.7 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 420.56 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 268.8 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 86.28 kNm
M2 = -426.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.43
9.52 < 36.43, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 5
r = 173.2 mm
Klux /r = 49.07
Permissible slenderness ratio = 22
49.07 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 25.86 kNm
δns x M2s = -11.53 kNm
M1ns = 36.29 kNm
M2ns = -25.34 kNm
δns = 1.05
M1sldr = 62.15 kNm
1.4 MuyT = 85.17 kNm
M1sldr = Min (62.15, 85.17) kNm
= 62.15 kNm
M2sldr = -36.87 kNm
1.4 MuyB = -50.8 kNm
M2sldr = Min (-36.87, -50.8) kNm
= -36.87 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 268.8 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 14.1 m To 14.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 26.32 kNm
M2 = -60.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.24
6.29 < 39.24, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 404.18 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 268.8 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 89.36 kNm
M2 = -403.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.66
9.52 < 36.66, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 9.72
M1 = -32.99 kNm
M2 = 56.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.72 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -403.14 - -403.14
Major Axis Mux (bottom) 89.36 - 89.36
Minor Axis Muy (top) 56.38 - 56.38
Minor Axis Muy (bottom) -32.99 - -32.99
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
No of bars along D = 7
S1 = 100 mm
Pu = 3096.14 kN
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD3 = 313.79 sqmm
AshD (Max (AshD1, AshD2, AshD3)) = 313.79 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Pu = 3096.14 kN
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB3 = 313.79 sqmm
AshB (Max (AshB1, AshB2, AshB3)) = 313.79 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C3
Level : 18.1 m To 18.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.002
0.002< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Minimum Pt required = 1 %
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 292.89 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 125 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 78.48 kNm
M2 = -331.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.84
9.52 < 36.84, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 9.72
M1 = -29.59 kNm
M2 = 53.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <= 0.33*Sqrt
Check
(f'c)*B*d
d/2 = 270 mm
600 = 600 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 300 --- 100 300 100
General Data
Column No. : C3
Level : 22.1 m To 22.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 23.89 kNm
M2 = -52.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.41
6.29 < 39.41, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 229.2 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 59.59 kNm
M2 = -256.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.79
9.52 < 36.79, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 9.72
M1 = -26.33 kNm
M2 = 48.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 26.1 m To 26.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.025
0.025< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 19.58 kNm
M2 = -48.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.87
6.29 < 38.87, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 203.78 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Pub = 578.26 kN
Muxb = 58.98 kNm
Muyb = -26.85 kNm
Vuxb = -35.58 kN
Vuyb = -74.45 kN
Effective Length Calculation
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.9
r = 173.2 mm
Kluy /r = 8.83
M1 = 58.98 kNm
M2 = -112.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.83 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 9.13
M1 = -26.85 kNm
M2 = 54.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.86
9.13 < 39.86, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 0 17.7 88.73 737.2 791.7 153.89 0 574.7 791.7 154.04 153.89 0 154.04 0
400 x 600 270 0.44 86.12 577.61 791.7 153.89 40.19 574.7 791.7 154.04 0 153.89 0 154.04
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C3
Level : 28.6 m To 32.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.91
r = 173.2 mm
Kluy /r = 16.81
M1 = 57.77 kNm
M2 = -459.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.51
16.81 < 35.51, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 17.18
M1 = 24.99 kNm
M2 = -49.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.18 < 40, Column not slender along B
A B C
Major Axis Mux (top) 57.77 - 57.77
Major Axis Mux (bottom) -459.8 - -459.8
Minor Axis Muy (top) 24.99 - 24.99
Minor Axis Muy (bottom) -49.78 - -49.78
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 2.1 m To 2.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.04
0.04< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 2.15
r = 223.72 mm
Kluy /r = 16.34
Permissible slenderness ratio = 22
16.34 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.87
r = 223.72 mm
Klux /r = 6.61
M1 = -152.15 kNm
M2 = 413.07 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.42
6.61 < 38.42, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.99
r = 223.72 mm
Kluy /r = 7.52
M1 = -31.41 kNm
M2 = 403.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.93
7.52 < 34.93, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 1
r = 223.72 mm
Klux /r = 7.6
M1 = 8.9 kNm
M2 = 33.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.79
7.6 < 30.79, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 6.1 m To 6.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 5
r = 223.72 mm
Kluy /r = 24.58
Permissible slenderness ratio = 22
24.58 > 22, Column slender along D
Column Is Braced Along B
Slenderness Check along B
k = 1
r = 223.72 mm
Klux /r = 4.92
M1 = -17.88 kNm
M2 = -31.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.26
4.92 < 27.26, Column not slender along B
Moment Magnification:
For Sway Frame:
Along D
δns x M1s = 93.49 kNm
δns x M2s = 646.56 kNm
M1ns = -45.88 kNm
M2ns = -4.73 kNm
δns = 1.17
M1sldr = 47.54 kNm
1.4 MuxT = 47.54 kNm
M1sldr = Min (47.54, 47.54) kNm
= 47.54 kNm
M2sldr = 641.83 kNm
1.4 MuxB = 766.33 kNm
M2sldr = Min (641.83, 766.33) kNm
= 641.83 kNm
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 33.96 47.54 47.54
Major Axis Mux (bottom) 547.38 641.83 641.83
Minor Axis Muy (top) -31.83 - -31.83
Minor Axis Muy (bottom) -17.88 - -17.88
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 0 70.95 104.37 774.42 791.7 153.89 0 574.7 791.7 154.04 153.89 0 154.04 0
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD3 = 356.95 sqmm
AshD (Max (AshD1, AshD2, AshD3)) = 356.95 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Pu = 4814.27 kN
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB3 = 356.95 sqmm
AshB (Max (AshB1, AshB2, AshB3)) = 356.95 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C4
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Along B
δns x M1s = 9.22 kNm
δns x M2s = -8.58 kNm
M1ns = -6.57 kNm
M2ns = 31.27 kNm
δns = 1.06
M1sldr = 2.65 kNm
1.4 MuyT = 3.02 kNm
M1sldr = Min (2.65, 3.02) kNm
= 2.65 kNm
M2sldr = 23.15 kNm
1.4 MuyB = 32.41 kNm
M2sldr = Min (23.15, 32.41) kNm
= 23.15 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 300 --- 100 300 100
General Data
Column No. : C4
Level : 10.1 m To 10.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.57
r = 173.2 mm
Kluy /r = 22.67
Permissible slenderness ratio = 22
22.67 > 22, Column slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 0.44 kNm
M2 = -28.94 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.18
6.29 < 34.18, Column not slender along B
Moment Magnification:
For Sway Frame:
Along D
δns x M1s = 60.2 kNm
δns x M2s = 497.33 kNm
M1ns = -35.84 kNm
M2ns = 17.39 kNm
δns = 1.35
M1sldr = 12.38 kNm
1.4 MuxT = 12.38 kNm
M1sldr = Min (12.38, 12.38) kNm
= 12.38 kNm
M2sldr = 514.72 kNm
1.4 MuxB = 541.14 kNm
M2sldr = Min (514.72, 541.14) kNm
= 514.72 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 500.73 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs >0.33*Sqrt
Check
(f'c)*B*d
b/4 = 134.4 mm
300 = 300 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Critical Location = Top Joint
Put = 3748.6 kN
Muxt = -418.58 kNm
Muyt = -8.24 kNm
Vuxt = 13.89 kN
Vuyt = -219.87 kN
Pub = 3748.6 kN
Muxb = 87 kNm
Muyb = 23.7 kNm
Vuxb = 13.89 kN
Vuyb = -219.87 kN
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 87 kNm
M2 = -418.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.49
9.52 < 36.49, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 5
r = 173.2 mm
Klux /r = 49.07
Permissible slenderness ratio = 22
49.07 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 11.34 kNm
δns x M2s = -9.48 kNm
M1ns = -19 kNm
M2ns = 32.7 kNm
δns = 1.05
M1sldr = -8.24 kNm
1.4 MuyT = -11.53 kNm
M1sldr = Min (-8.24, -11.53) kNm
= -8.24 kNm
M2sldr = 23.7 kNm
1.4 MuyB = 33.19 kNm
M2sldr = Min (23.7, 33.19) kNm
= 23.7 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 268.8 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 14.1 m To 14.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 15.07 kNm
M2 = -33.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.4
6.29 < 39.4, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 460.7 kN
0.33*Sqrt (f'c)*Aeff = 483.97 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 268.8 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 88.94 kNm
M2 = -391.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.73
9.52 < 36.73, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 9.72
M1 = -12.98 kNm
M2 = 24.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
515.98 -
Link Rebar Number 10 -
Diameter of link (mm) 10 -
Numbers of legs provided 7 -
Spacing of Link Provided (mm) 250 -
Av/s provided (sqmm/m ) 2199.12 -
Av/s provided check Av/s required < Av/s provided; -
Hence, OK
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 18.1 m To 18.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.002
0.002< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 20.78 kNm
M2 = -34.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 349.6 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [6] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 7: EQPZ)
Pu = 2098.44 kN
Check for Ash
0.3 x Ag x f'c = 2233.44 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 7
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C4
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 75.48 kNm
M2 = -334.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.71
9.52 < 36.71, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 9.72
M1 = -20.39 kNm
M2 = 29.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
500 x 750 0 12.75 540.34 2259.61 2262 540.86 99.16 1129.81 1131 281.89 540.86 0 281.89 0
400 x 600 90 7.58 290.47 1562.23 1583.4 294.03 59.99 781.11 791.7 154.04 0 294.03 0 154.04
400 x 600 180 0.09 286.24 1537.21 1583.4 294.03 90.33 768.6 791.7 154.04 294.03 0 154.04 0
400 x 600 270 1.35 248.7 1318.63 1357.2 255.4 102.01 687.32 791.7 154.04 0 255.4 0 154.04
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
General Data
Column No. : C4
Level : 22.1 m To 22.3 m
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 27.73 kNm
M2 = -35.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
6.29 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 244.06 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 125 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.97
r = 173.2 mm
Kluy /r = 9.52
M1 = 64.23 kNm
M2 = -248.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.1
9.52 < 37.1, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 9.72
M1 = -25.1 kNm
M2 = 32.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 26.1 m To 26.3 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1100 mm
Clear Floor Height @ luy = 1100 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.025
0.025< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Un-Braced Along D
Slenderness Check along D
k = 3.46
r = 173.2 mm
Kluy /r = 21.97
Permissible slenderness ratio = 22
21.97 < 22,Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.99
r = 173.2 mm
Klux /r = 6.29
M1 = 32.98 kNm
M2 = -35.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
6.29 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 186.06 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C4
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1700 mm
Clear Floor Height @ luy = 1700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.9
r = 173.2 mm
Kluy /r = 8.83
M1 = 57.49 kNm
M2 = -93.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
8.83 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 9.13
M1 = 37.11 kNm
M2 = -46.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
9.13 < 40, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Pu = 506.5 kN
Check for Ash
0.3 x Ag x f'c = 2233.44 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 7
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C4
Level : 28.6 m To 32.1 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3200 mm
Clear Floor Height @ luy = 3200 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.91
r = 173.2 mm
Kluy /r = 16.81
M1 = 59.16 kNm
M2 = -470.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.51
16.81 < 35.51, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.93
r = 173.2 mm
Klux /r = 17.18
M1 = 22.84 kNm
M2 = -25.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.18 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
@B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
200 x 300 90 0.04 57.82 691.94 791.7 64.42 11.71 345.97 452.4 40.27 0 64.42 0 40.27
200 x 300 0 0.16 59.32 714.13 791.7 64.42 14.4 357.07 452.4 40.27 64.42 0 40.27 0
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
General Data
Column No. : C5
Level : 2.3 m To 4.6 m
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = -161.97 kNm
M2 = 251.64 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 17.76 kNm
M2 = 20.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 23.7
15.38 < 23.7, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C5
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Critical Location = Bottom Joint
Put = 1806.08 kN
Muxt = 171.75 kNm
Muyt = 113.29 kNm
Vuxt = 56.2 kN
Vuyt = -87 kN
Pub = 1806.08 kN
Muxb = -176.15 kNm
Muyb = -111.47 kNm
Vuxb = 56.2 kN
Vuyb = -87 kN
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 171.75 kNm
M2 = -176.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 9.58 kNm
δns x M2s = -10.48 kNm
M1ns = 104.22 kNm
M2ns = -101.55 kNm
δns = 1.06
M1sldr = 113.8 kNm
1.4 MuyT = 158.6 kNm
M1sldr = Min (113.8, 158.6) kNm
= 113.8 kNm
M2sldr = -112.02 kNm
1.4 MuyB = -156.05 kNm
M2sldr = Min (-112.02, -156.05) kNm
= -112.02 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C5
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 725
Critical Analysis Load Combination : 104
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Critical Location = Top Joint
Put = 1412.33 kN
Muxt = 180.38 kNm
Muyt = 81.46 kNm
Vuxt = 37.49 kN
Vuyt = -88.7 kN
Pub = 1412.33 kN
Muxb = -174.32 kNm
Muyb = -68.47 kNm
Vuxb = 37.49 kN
Vuyb = -88.7 kN
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = -174.32 kNm
M2 = 180.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 16.09 kNm
δns x M2s = -16.94 kNm
M1ns = 66.19 kNm
M2ns = -52.39 kNm
δns = 1.05
M1sldr = 82.28 kNm
1.4 MuyT = 114.05 kNm
M1sldr = Min (82.28, 114.05) kNm
= 82.28 kNm
M2sldr = -69.33 kNm
1.4 MuyB = -95.86 kNm
M2sldr = Min (-69.33, -95.86) kNm
= -69.33 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Pu = 1412.33 kN
Check for Ash
0.3 x Ag x f'c = 2233.44 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 7
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C5
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -144.86 kNm
M2 = 162.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -89.27 kNm
M2 = 90.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.2 238.58 1260.73 1357.2 255.4 165.77 855.92 904.8 174.94 255.4 0 174.94 0
400 x 600 270 0.18 377.45 2096.05 2148.9 385.72 86.6 1048.03 1131 215.93 0 385.72 0 215.93
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C5
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 18.1 kNm
M2 = -18.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -162.57 kNm
M2 = 200.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 18.1 - 18.1
Major Axis Mux (bottom) -18.41 - -18.41
Minor Axis Muy (top) 200.46 - 200.46
Minor Axis Muy (bottom) -162.57 - -162.57
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C5
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 21.74 kNm
M2 = -24.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -131.55 kNm
M2 = 171.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.25 183.03 950.06 1017.9 195.34 101.57 684.24 791.7 154.04 195.34 0 154.04 0
400 x 600 270 0.11 334.22 1825.98 1922.7 349.89 37.56 912.99 1017.9 195.58 0 349.89 0 195.58
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C5
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -33.31 kNm
M2 = 40.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -108.33 kNm
M2 = 151.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C6
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 223.72 mm
Kluy /r = 15.2
M1 = 273.61 kNm
M2 = -372.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.2 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -18.19 kNm
M2 = 42.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.19
15.38 < 39.19, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
0 0
Lu (mm) 4000 4000
Vu2 (kN) 161.29 105.11
Critical Analysis Load 108 110
Combination
Critical Load Combination [9] : 0.9 (LOAD 1: DL) +(LOAD 6: [11] : 0.9 (LOAD 1: DL) +(LOAD
EQNX) 8: EQNZ)
Nu (kN) 883.25 1799.18
Mu (kNm) 372.37 171.23
Vu3 (kN) -140.47 84.74
Vu' (kN) Minimum(Vu1, Vu2)
161.29 105.11
Design Shear, Vu (kN) Maximum(Vu', Vu3)
161.29 105.11
λ 1 1
φ 0.75 0.75
Deff (mm) 715 715
ρw (50% of As provided) 0.009 0.009
Mm (kNm) 109.05 -365.15
φVc (kN) 370.16 749.22
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Ag = 600625 sqmm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD (Max (AshD1, AshD2)) = 312.45 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB (Max (AshB1, AshB2)) = 312.45 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C6
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.94
r = 223.72 mm
Kluy /r = 14.29
M1 = -306.41 kNm
M2 = 319.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.29 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 7.15 kNm
δns x M2s = -7.99 kNm
M1ns = 95.7 kNm
M2ns = -92.76 kNm
δns = 1.06
M1sldr = 102.85 kNm
1.4 MuyT = 143.46 kNm
M1sldr = Min (102.85, 143.46) kNm
= 102.85 kNm
M2sldr = -100.75 kNm
1.4 MuyB = -140.45 kNm
M2sldr = Min (-100.75, -140.45) kNm
= -100.75 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Pu-max from all Combinations = 2003.67 kN
Pt required for Pu-max = 0 %
Pt min (User Defined) = 1 %
Minimum Pt required = 1 %
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.88
r = 173.2 mm
Kluy /r = 17.27
M1 = -244.63 kNm
M2 = 261.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.27 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 12.73 kNm
δns x M2s = -13.58 kNm
M1ns = 61.84 kNm
M2ns = -48.71 kNm
δns = 1.05
M1sldr = 74.57 kNm
1.4 MuyT = 103.5 kNm
M1sldr = Min (74.57, 103.5) kNm
= 74.57 kNm
M2sldr = -62.28 kNm
1.4 MuyB = -86.23 kNm
M2sldr = Min (-62.28, -86.23) kNm
= -62.28 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C6
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -232.95 kNm
M2 = 247.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -81.79 kNm
M2 = 82.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 955.66 kN
Mux = 247.92 kNm
Muy = 82.36 kNm
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C6
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -196.36 kNm
M2 = 218.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -80.17 kNm
M2 = 84.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
General Data
Column No. : C6
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -152.77 kNm
M2 = 177.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = 74.27 kNm
M2 = -77.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C6
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.83
r = 173.2 mm
Kluy /r = 16.29
M1 = -112.15 kNm
M2 = 142.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.29 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -76.79 kNm
M2 = 91.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
= 0.281 < 1
Beam Capacity At Joint:
Beam Table For Shear Along B & Shear Along D
Level = 28.6 m
Analysis Reference Number = C6
Beams at Level: Top Joint
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.49 167.23 863.83 904.8 174.75 0 574.7 791.7 154.04 174.75 0 154.04 0
400 x 600 180 0.25 2.09 574.7 791.7 153.89 13.41 574.7 791.7 154.04 153.89 0 154.04 0
400 x 600 270 0.33 158.09 814.35 904.8 174.75 0 574.7 791.7 154.04 0 174.75 0 154.04
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Pu = 216.75 kN
Check for Ash
0.3 x Ag x f'c = 2233.44 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 7
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C7
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 197.67 kNm
M2 = -281.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -13.59 kNm
M2 = 54.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 37
15.38 < 37, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.45 334.08 1825.13 1922.7 349.89 86.01 912.57 1017.9 195.58 349.89 0 195.58 0
400 x 600 180 0.63 315.03 1709.18 1809.6 331.55 102.7 854.59 904.8 174.94 331.55 0 174.94 0
400 x 600 270 0.63 397.82 2226.93 2262 403.21 153.19 1113.47 1131 215.93 0 403.21 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C7
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = -208.49 kNm
M2 = 213.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 5.08 kNm
δns x M2s = -5.21 kNm
M1ns = 98.56 kNm
M2ns = -95.09 kNm
δns = 1.06
M1sldr = 103.64 kNm
1.4 MuyT = 144.71 kNm
M1sldr = Min (103.64, 144.71) kNm
= 103.64 kNm
M2sldr = -100.3 kNm
1.4 MuyB = -140.03 kNm
M2sldr = Min (-100.3, -140.03) kNm
= -100.3 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C7
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = -198.17 kNm
M2 = 210.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 8.42 kNm
δns x M2s = -8.63 kNm
M1ns = 64.41 kNm
M2ns = -50.59 kNm
δns = 1.05
M1sldr = 72.83 kNm
1.4 MuyT = 101.36 kNm
M1sldr = Min (72.83, 101.36) kNm
= 72.83 kNm
M2sldr = -59.22 kNm
1.4 MuyB = -82.3 kNm
M2sldr = Min (-59.22, -82.3) kNm
= -59.22 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.31 318.76 1731.69 1809.6 331.55 75.43 865.85 904.8 174.94 331.55 0 174.94 0
400 x 600 180 0.63 300.69 1623.06 1696.5 312.93 98.51 811.53 904.8 174.94 312.93 0 174.94 0
400 x 600 270 0.64 381.13 2119.57 2148.9 385.72 132.35 1059.79 1131 215.93 0 385.72 0 215.93
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C7
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 926
Critical Analysis Load Combination : 104
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Critical Location = Top Joint
Put = 1540.45 kN
Muxt = 199.05 kNm
Muyt = 82.87 kNm
Vuxt = 41.43 kN
Vuyt = -95.02 kN
Pub = 1540.45 kN
Muxb = -180.95 kNm
Muyb = -82.8 kNm
Vuxb = 41.43 kN
Vuyb = -95.02 kN
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -180.95 kNm
M2 = 199.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -82.8 kNm
M2 = 82.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 199.05 - 199.05
Major Axis Mux (bottom) -180.95 - -180.95
Minor Axis Muy (top) 82.87 - 82.87
Minor Axis Muy (bottom) -82.8 - -82.8
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
286.9 221.66
λ 1 1
φ 0.75 0.75
Deff (mm) 540 540
ρw (50% of As provided) 0.012 0.012
Mm (kNm) -49.94 -183.5
φVc (kN) 435.17 494.55
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C7
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Critical Location = Top Joint
Put = 1116.82 kN
Muxt = 177.04 kNm
Muyt = 84.76 kNm
Vuxt = 41.69 kN
Vuyt = -82.43 kN
Pub = 1116.82 kN
Muxb = -152.58 kNm
Muyb = -81.94 kNm
Vuxb = 41.69 kN
Vuyb = -82.43 kN
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -152.58 kNm
M2 = 177.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -81.94 kNm
M2 = 84.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C7
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -115.79 kNm
M2 = 142.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -82.59 kNm
M2 = 82.7 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C7
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Pub = 272.75 kN
Muxb = -83.64 kNm
Muyb = -88.18 kNm
Vuxb = 46.81 kN
Vuyb = -50.62 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 401.45 No Beam No Beam - - 3.913
Top 401.45 6000 x 400 x 600 6000 x 400 x 600 102.59 102.59 1.957
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.86
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -83.64 kNm
M2 = 118.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -88.18 kNm
M2 = 99.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
General Data
Column No. : C8
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 195.01 kNm
M2 = -284.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -6.23 kNm
M2 = 43.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.72
15.38 < 35.72, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
General Data
Column No. : C8
Level : 6.3 m To 8.6 m
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = -197.56 kNm
M2 = 200.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 0.38 kNm
δns x M2s = -0.42 kNm
M1ns = 86.98 kNm
M2ns = -83.6 kNm
δns = 1.06
M1sldr = 87.36 kNm
1.4 MuyT = 122.28 kNm
M1sldr = Min (87.36, 122.28) kNm
= 87.36 kNm
M2sldr = -84.02 kNm
1.4 MuyB = -117.59 kNm
M2sldr = Min (-84.02, -117.59) kNm
= -84.02 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <= 0.33*Sqrt
Check
(f'c)*B*d
d/2 = 357.5 mm
600 = 600 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 300 --- 100 300 100
General Data
Column No. : C8
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = -18.52 kNm
M2 = 19.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 163.18 kNm
δns x M2s = -155.13 kNm
M1ns = 57.63 kNm
M2ns = -45.1 kNm
δns = 1.05
M1sldr = 220.81 kNm
1.4 MuyT = 297.54 kNm
M1sldr = Min (220.81, 297.54) kNm
= 220.81 kNm
M2sldr = -200.23 kNm
1.4 MuyB = -269.3 kNm
M2sldr = Min (-200.23, -269.3) kNm
= -200.23 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C8
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -167.38 kNm
M2 = 184.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = 68.65 kNm
M2 = -69.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C8
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -137.42 kNm
M2 = 161.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -69.2 kNm
M2 = 71.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C8
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -99.59 kNm
M2 = 126.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = 69.23 kNm
M2 = -70.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Column No. : C8
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 9.41 kNm
M2 = -15.07 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -104.88 kNm
M2 = 154.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C9
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 188.79 kNm
M2 = -284 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 0.52 kNm
M2 = 38.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.84
15.38 < 33.84, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 186.34 kNm
M2 = -190.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 2.15 kNm
δns x M2s = -2.74 kNm
M1ns = 86.4 kNm
M2ns = -83.16 kNm
δns = 1.06
M1sldr = 88.54 kNm
1.4 MuyT = 123.8 kNm
M1sldr = Min (88.54, 123.8) kNm
= 88.54 kNm
M2sldr = -85.9 kNm
1.4 MuyB = -120.05 kNm
M2sldr = Min (-85.9, -120.05) kNm
= -85.9 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.77 335.13 1831.52 1922.7 349.89 82.93 915.76 1017.9 195.58 349.89 0 195.58 0
400 x 600 180 0.68 338.39 1851.6 1922.7 349.89 79.98 925.8 1017.9 195.58 349.89 0 195.58 0
400 x 600 270 0.55 376.02 2087.01 2148.9 385.72 153.28 1043.5 1131 215.93 0 385.72 0 215.93
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = 25.49 kNm
M2 = -26.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 154.69 kNm
δns x M2s = -147.62 kNm
M1ns = 56.84 kNm
M2ns = -44.6 kNm
δns = 1.05
M1sldr = 211.53 kNm
1.4 MuyT = 285.14 kNm
M1sldr = Min (211.53, 285.14) kNm
= 211.53 kNm
M2sldr = -192.22 kNm
1.4 MuyB = -258.62 kNm
M2sldr = Min (-192.22, -258.62) kNm
= -192.22 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 162.21 kNm
M2 = -179.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = 69.47 kNm
M2 = -69.86 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 132.79 kNm
M2 = -156.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -69.54 kNm
M2 = 71.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 95.08 kNm
M2 = -121.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = 69.38 kNm
M2 = -70.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -121.96 - -121.96
Major Axis Mux (bottom) 95.08 - 95.08
Minor Axis Muy (top) 69.38 - 69.38
Minor Axis Muy (bottom) -70.47 - -70.47
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 180 0.5 239.78 1267.57 1357.2 255.4 0 633.79 791.7 154.04 255.4 0 154.04 0
400 x 600 270 0.58 246.73 1307.32 1357.2 255.4 0 653.66 791.7 154.04 0 255.4 0 154.04
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C9
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 60.15 kNm
M2 = -91.4 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -78.2 kNm
M2 = 90.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C10
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Load Combination = [4] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 5: EQPX)
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = -197.62 kNm
M2 = 275.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -14.61 kNm
M2 = 53.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.26
15.38 < 37.26, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Pu = 3189.78 kN
Check for Ash
0.3 x Ag x f'c = 3726.2775 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 9
S1 = 100 mm
Ag = 600625 sqmm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD (Max (AshD1, AshD2)) = 312.45 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB (Max (AshB1, AshB2)) = 312.45 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C10
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 197.46 kNm
M2 = -204.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 5.26 kNm
δns x M2s = -6.33 kNm
M1ns = 96.98 kNm
M2ns = -93.8 kNm
δns = 1.06
M1sldr = 102.24 kNm
1.4 MuyT = 142.74 kNm
M1sldr = Min (102.24, 142.74) kNm
= 102.24 kNm
M2sldr = -100.13 kNm
1.4 MuyB = -139.71 kNm
M2sldr = Min (-100.13, -139.71) kNm
= -100.13 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 0 0.52 320.23 1740.61 1809.6 331.55 99.14 870.31 904.8 174.94 331.55 0 174.94 0
400 x 600 180 0.51 328.54 1791.23 1809.6 331.55 89.86 895.61 904.8 174.94 331.55 0 174.94 0
400 x 600 270 0.21 385.26 2145.99 2148.9 385.72 138.55 1073 1131 215.93 0 385.72 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C10
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = 194.48 kNm
M2 = -205.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 8.7 kNm
δns x M2s = -9.16 kNm
M1ns = 62.7 kNm
M2ns = -49.46 kNm
δns = 1.05
M1sldr = 71.4 kNm
1.4 MuyT = 99.34 kNm
M1sldr = Min (71.4, 99.34) kNm
= 71.4 kNm
M2sldr = -58.62 kNm
1.4 MuyB = -81.42 kNm
M2sldr = Min (-58.62, -81.42) kNm
= -58.62 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C10
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 176.16 kNm
M2 = -194.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -79.92 kNm
M2 = 80.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 0 0.49 304.82 1647.73 1696.5 312.93 95.76 823.86 904.8 174.94 312.93 0 174.94 0
400 x 600 180 0.46 313.85 1702.02 1809.6 331.55 78.85 851.01 904.8 174.94 331.55 0 174.94 0
400 x 600 270 0.03 370.67 2053.05 2148.9 385.72 118.56 1026.53 1131 215.93 0 385.72 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C10
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Pub = 1116.04 kN
Muxb = 148.45 kNm
Muyb = -78.46 kNm
Vuxb = 39.96 kN
Vuyb = 80.32 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 401.45 No Beam No Beam - - 3.913
Top 401.45 6000 x 400 x 600 6000 x 400 x 600 102.59 102.59 3.913
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.89
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 148.45 kNm
M2 = -172.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -78.46 kNm
M2 = 81.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
General Data
Column No. : C10
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 111.82 kNm
M2 = -138.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -78.75 kNm
M2 = 79.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C10
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 79.42 kNm
M2 = -113.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -82.79 kNm
M2 = 92.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C11
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 223.72 mm
Kluy /r = 15.2
M1 = -272.53 kNm
M2 = 367.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.2 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -19.88 kNm
M2 = 40.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.9
15.38 < 39.9, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Pu = 2308.13 kN
Check for Ash
0.3 x Ag x f'c = 3726.2775 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 9
S1 = 100 mm
Ag = 600625 sqmm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD (Max (AshD1, AshD2)) = 312.45 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB (Max (AshB1, AshB2)) = 312.45 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C11
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.94
r = 223.72 mm
Kluy /r = 14.29
M1 = 293.6 kNm
M2 = -308.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.29 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 8.24 kNm
δns x M2s = -9.8 kNm
M1ns = 89.58 kNm
M2ns = -86.49 kNm
δns = 1.06
M1sldr = 97.82 kNm
1.4 MuyT = 136.33 kNm
M1sldr = Min (97.82, 136.33) kNm
= 97.82 kNm
M2sldr = -96.29 kNm
1.4 MuyB = -134.08 kNm
M2sldr = Min (-96.29, -134.08) kNm
= -96.29 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Ag = 600625 sqmm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD (Max (AshD1, AshD2)) = 312.45 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB (Max (AshB1, AshB2)) = 312.45 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C11
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.88
r = 173.2 mm
Kluy /r = 17.27
M1 = 239.99 kNm
M2 = -255.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.27 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 13.95 kNm
δns x M2s = -14.76 kNm
M1ns = 58.49 kNm
M2ns = -46.01 kNm
δns = 1.05
M1sldr = 72.44 kNm
1.4 MuyT = 100.43 kNm
M1sldr = Min (72.44, 100.43) kNm
= 72.44 kNm
M2sldr = -60.77 kNm
1.4 MuyB = -84.03 kNm
M2sldr = Min (-60.77, -84.03) kNm
= -60.77 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Pu-max from all Combinations = 1487.57 kN
Pt required for Pu-max = 0 %
Pt min (User Defined) = 1 %
Minimum Pt required = 1 %
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C11
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 227.28 kNm
M2 = -242.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -78.37 kNm
M2 = 79.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C11
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 191.37 kNm
M2 = -213.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -76.77 kNm
M2 = 81.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C11
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 148 kNm
M2 = -172.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = 70.76 kNm
M2 = -73.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C11
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.83
r = 173.2 mm
Kluy /r = 16.29
M1 = 107.13 kNm
M2 = -136.89 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.29 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -73.84 kNm
M2 = 91.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 1983
Critical Analysis Load Combination : 108
Load Combination = [9] : 0.9 (LOAD 1: DL) +(LOAD 6: EQNX)
Critical Location = Bottom Joint
Put = 74.44 kN
Muxt = 161.76 kNm
Muyt = 20.76 kNm
Vuxt = 0.56 kN
Vuyt = -90.65 kN
Pub = 74.44 kN
Muxb = -255.11 kNm
Muyb = 18.19 kNm
Vuxb = 0.56 kN
Vuyb = -90.65 kN
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 161.76 kNm
M2 = -255.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 18.19 kNm
M2 = 20.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 23.49
15.38 < 23.49, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 161.76 - 161.76
Major Axis Mux (bottom) -255.11 - -255.11
Minor Axis Muy (top) 20.76 - 20.76
Minor Axis Muy (bottom) 18.19 - 18.19
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = -163.27 kNm
M2 = 165.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.86
r = 223.72 mm
Klux /r = 58.66
Permissible slenderness ratio = 22
58.66 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 10.69 kNm
δns x M2s = -12.31 kNm
M1ns = 103.23 kNm
M2ns = -100.31 kNm
δns = 1.06
M1sldr = 113.93 kNm
1.4 MuyT = 158.7 kNm
M1sldr = Min (113.93, 158.7) kNm
= 113.93 kNm
M2sldr = -112.62 kNm
1.4 MuyB = -156.75 kNm
M2sldr = Min (-112.62, -156.75) kNm
= -112.62 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 180 0.27 322.72 1755.77 1809.6 331.55 300.15 1619.8 1696.5 313.6 331.55 0 313.6 0
400 x 600 270 0.51 386.56 2154.31 2262 403.21 113.7 1077.15 1131 215.93 0 403.21 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = 170.85 kNm
M2 = -175.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 3.03
r = 173.2 mm
Klux /r = 59.48
Permissible slenderness ratio = 22
59.48 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 17.35 kNm
δns x M2s = -18.15 kNm
M1ns = 65.92 kNm
M2ns = -52.2 kNm
δns = 1.05
M1sldr = 83.27 kNm
1.4 MuyT = 115.35 kNm
M1sldr = Min (83.27, 115.35) kNm
= 83.27 kNm
M2sldr = -70.35 kNm
1.4 MuyB = -97.2 kNm
M2sldr = Min (-70.35, -97.2) kNm
= -70.35 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 140.29 kNm
M2 = -157.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -89.38 kNm
M2 = 90.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 180 0.04 274.43 1467.82 1470.3 274.86 232.73 1227.46 1244.1 236.02 274.86 0 236.02 0
400 x 600 270 0.66 369.41 2045.1 2148.9 385.72 94.77 1022.55 1131 215.93 0 385.72 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 111.25 kNm
M2 = -135.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -86.42 kNm
M2 = 90.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 38.39 kNm
M2 = -39.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.95
r = 173.2 mm
Klux /r = 18.65
M1 = -118.33 kNm
M2 = 155.77 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.65 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C12
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 44.23 kNm
M2 = -56.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.92
r = 173.2 mm
Klux /r = 18.06
M1 = -95.29 kNm
M2 = 132.2 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 2.3 m To 4.6 m
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 29.13 kNm
M2 = -32.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -269.64 kNm
M2 = 397.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C13
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = -41.04 kNm
M2 = 45.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = -277.86 kNm
δns x M2s = 257.2 kNm
M1ns = -0.93 kNm
M2ns = 2.87 kNm
δns = 1.06
M1sldr = -278.78 kNm
1.4 MuyT = -369.55 kNm
M1sldr = Min (-278.78, -369.55) kNm
= -278.78 kNm
M2sldr = 260.07 kNm
1.4 MuyB = 344.9 kNm
M2sldr = Min (260.07, 344.9) kNm
= 260.07 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
No of bars along B = 9
S1 = 100 mm
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB (Max (AshB1, AshB2)) = 312.45 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C13
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = -34.71 kNm
M2 = 41.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = -256.55 kNm
δns x M2s = 238.36 kNm
M1ns = 3.03 kNm
M2ns = -1.62 kNm
δns = 1.05
M1sldr = -253.52 kNm
1.4 MuyT = -336.69 kNm
M1sldr = Min (-253.52, -336.69) kNm
= -253.52 kNm
M2sldr = 236.74 kNm
1.4 MuyB = 314.49 kNm
M2sldr = Min (236.74, 314.49) kNm
= 236.74 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C13
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -44.92 kNm
M2 = 47.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = 190.24 kNm
M2 = -214.2 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
= 0.328 < 1
Beam Capacity At Joint:
Beam Table For Shear Along B & Shear Along D
Level = 16.6 m
Analysis Reference Number = C13
Beams at Level: Top Joint
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.65 345.86 1897.75 1922.7 349.89 88.15 948.87 1017.9 195.58 0 349.89 0 195.58
400 x 600 0 1.12 254.94 1354.57 1357.2 255.4 172.44 892.15 904.8 174.94 255.4 0 174.94 0
400 x 600 270 0.24 344.29 1888 1922.7 349.89 90.31 944 1017.9 195.58 0 349.89 0 195.58
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Special confining reinforcement as per NSCP C101 -
2015
Load Combination = [5] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 6: EQNX)
Pu = 1560.57 kN
Check for Ash
0.3 x Ag x f'c = 2233.44 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 7
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C13
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -46.18 kNm
M2 = 49.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = 147.79 kNm
M2 = -178.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.63 297.84 1606.05 1696.5 312.93 46.28 803.03 904.8 174.94 0 312.93 0 174.94
400 x 600 0 1.08 197.16 1027.97 1131 215.64 106.9 721.28 791.7 154.04 215.64 0 154.04 0
400 x 600 270 0.15 302.59 1634.41 1696.5 312.93 49.91 817.2 904.8 174.94 0 312.93 0 174.94
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C13
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 1330
Critical Analysis Load Combination : 106
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Critical Location = Top Joint
Put = 568.43 kN
Muxt = 31.22 kNm
Muyt = 146.97 kNm
Vuxt = 65.38 kN
Vuyt = -16.29 kN
Pub = 568.43 kN
Muxb = -33.93 kNm
Muyb = -114.5 kNm
Vuxb = 65.38 kN
Vuyb = -16.29 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 31.22 kNm
M2 = -33.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -114.5 kNm
M2 = 146.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 31.22 - 31.22
Major Axis Mux (bottom) -33.93 - -33.93
Minor Axis Muy (top) 146.97 - 146.97
Minor Axis Muy (bottom) -114.5 - -114.5
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
108.73 269.64
λ 1 1
φ 0.75 0.75
Deff (mm) 540 540
ρw (50% of As provided) 0.012 0.012
Mm (kNm) -28.45 54.35
φVc (kN) 392.93 305.57
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C13
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Critical Location = Top Joint
Put = 212.3 kN
Muxt = 52.57 kNm
Muyt = 123.15 kNm
Vuxt = 50.4 kN
Vuyt = -23.92 kN
Pub = 212.3 kN
Muxb = -43.1 kNm
Muyb = -78.39 kNm
Vuxb = 50.4 kN
Vuyb = -23.92 kN
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -43.1 kNm
M2 = 52.57 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -78.39 kNm
M2 = 123.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C14
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 223.72 mm
Kluy /r = 15.2
M1 = -212.87 kNm
M2 = 368.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.2 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -15.51 kNm
M2 = 29.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Load Combination = [4] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 5: EQPX)
Pu = 3560.34 kN
Check for Ash
0.3 x Ag x f'c = 3726.2775 kN
Pu <= 0.3 x Ag x f'c
f'c = 20.68 N/sqmm
f'c <= 70
Along D
No of bars along D = 9
S1 = 100 mm
Ag = 600625 sqmm
bc1 = 695 mm
Ach = 483025 sqmm
AshD1 = 253.57 sqmm
AshD2 = 312.45 sqmm
AshD (Max (AshD1, AshD2)) = 312.45 sqmm
AshD Provided = 706.86 sqmm
Along B
No of bars along B = 9
S1 = 100 mm
Ag = 600625 sqmm
dc1 = 695 mm
Ach = 483025 sqmm
AshB1 = 253.57 sqmm
AshB2 = 312.45 sqmm
AshB (Max (AshB1, AshB2)) = 312.45 sqmm
AshB Provided = 706.86 sqmm
General Data
Column No. : C14
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.94
r = 223.72 mm
Kluy /r = 14.29
M1 = -339.9 kNm
M2 = 355.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.29 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 17.71 kNm
δns x M2s = -16.46 kNm
M1ns = 12.78 kNm
M2ns = -10.1 kNm
δns = 1.06
M1sldr = 30.49 kNm
1.4 MuyT = 41.36 kNm
M1sldr = Min (30.49, 41.36) kNm
= 30.49 kNm
M2sldr = -26.56 kNm
1.4 MuyB = -35.96 kNm
M2sldr = Min (-26.56, -35.96) kNm
= -26.56 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.75 402.81 2259.4 2262 403.21 159.7 1129.7 1131 215.93 0 403.21 0 215.93
400 x 600 0 1.13 370.78 2053.73 2148.9 385.72 78.1 1026.86 1131 215.93 385.72 0 215.93 0
400 x 600 180 0.36 318.71 1731.41 1809.6 331.55 311.45 1687.57 1696.5 313.6 331.55 0 313.6 0
400 x 600 270 0.38 410.41 2309.07 2375.1 420.42 151.53 1154.54 1244.1 236.02 0 420.42 0 236.02
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
General Data
Column No. : C14
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Vuyb = -21.3 kN
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.88
r = 173.2 mm
Kluy /r = 17.27
M1 = -36.4 kNm
M2 = 48.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.27 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 253.63 kNm
δns x M2s = -235.39 kNm
M1ns = 11.29 kNm
M2ns = -8.36 kNm
δns = 1.05
M1sldr = 264.93 kNm
1.4 MuyT = 352.87 kNm
M1sldr = Min (264.93, 352.87) kNm
= 264.93 kNm
M2sldr = -243.75 kNm
1.4 MuyB = -324.52 kNm
M2sldr = Min (-243.75, -324.52) kNm
= -243.75 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C14
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -258.89 kNm
M2 = 274.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -30.55 kNm
M2 = 32.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C14
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -221.7 kNm
M2 = 245.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -30.48 kNm
M2 = 33.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C14
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -174.43 kNm
M2 = 196.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -27.54 kNm
M2 = 27.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C14
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Vuyt = -40.51 kN
Pub = 282.37 kN
Muxb = -78.33 kNm
Muyb = -83.14 kNm
Vuxb = 52.27 kN
Vuyb = -40.51 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 401.45 No Beam No Beam - - 2.609
Top 401.45 6000 x 400 x 600 3000 x 400 x 600 102.59 205.18 1.304
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.83
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.83
r = 173.2 mm
Kluy /r = 16.29
M1 = -78.33 kNm
M2 = 83.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.29 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -83.14 kNm
M2 = 125.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.54 202.87 1059.69 1131 215.64 34.61 574.7 791.7 154.04 0 215.64 0 154.04
400 x 600 0 2.31 272.26 1455.14 1470.3 274.86 0.44 727.57 791.7 154.04 274.86 0 154.04 0
400 x 600 180 0.07 45.45 574.7 791.7 153.89 93.13 625.85 791.7 154.04 153.89 0 154.04 0
400 x 600 270 0.14 232.78 1227.76 1244.1 235.66 26.71 613.88 791.7 154.04 0 235.66 0 154.04
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C15
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Pub = 4468.33 kN
Muxb = 25.72 kNm
Muyb = -399.73 kNm
Vuxb = 163.06 kN
Vuyb = 10.45 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 1117.46 No Beam No Beam - - 1
Top 1117.46 6000 x 400 x 600 6000 x 400 x 600 102.59 102.59 10.892
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.86
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = -22.35 kNm
M2 = 25.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 350.13 kNm
M2 = -399.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
d/2 = 357.5 mm
600 = 600 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 300 --- 100 300 100
General Data
Column No. : C15
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 11.23 kNm
M2 = -11.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 419.76 kNm
δns x M2s = -398.2 kNm
M1ns = 45.83 kNm
M2ns = -39.7 kNm
δns = 1.06
M1sldr = 465.59 kNm
1.4 MuyT = 620.5 kNm
M1sldr = Min (465.59, 620.5) kNm
= 465.59 kNm
M2sldr = -437.9 kNm
1.4 MuyB = -583.34 kNm
M2sldr = Min (-437.9, -583.34) kNm
= -437.9 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C15
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = -10.79 kNm
M2 = 12.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 320.79 kNm
δns x M2s = -293.95 kNm
M1ns = 33.1 kNm
M2ns = -25.81 kNm
δns = 1.05
M1sldr = 353.89 kNm
1.4 MuyT = 472.64 kNm
M1sldr = Min (353.89, 472.64) kNm
= 353.89 kNm
M2sldr = -319.76 kNm
1.4 MuyB = -426.77 kNm
M2sldr = Min (-319.76, -426.77) kNm
= -319.76 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C15
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 5.53 kNm
M2 = -5.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -303.28 kNm
M2 = 324.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C15
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 1.45 kNm
M2 = -2.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -256.49 kNm
M2 = 284.52 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Hence, OK
General Data
Column No. : C15
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = -5.68 kNm
M2 = 8.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -202.35 kNm
M2 = 233.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 983.07 kN
Mux = 8.62 kNm
Muy = 233.85 kNm
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0 269.37 1438.25 1470.3 274.86 46.99 719.12 791.7 154.04 0 274.86 0 154.04
400 x 600 0 0.1 266.78 1423.19 1470.3 274.86 24.6 711.59 791.7 154.04 274.86 0 154.04 0
400 x 600 180 0.19 287.01 1541.81 1583.4 294.03 39.71 770.9 791.7 154.04 294.03 0 154.04 0
400 x 600 270 10.13 392.3 2350.45 2375.1 420.42 32.75 1175.23 1244.1 236.02 0 420.42 0 236.02
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 7.99 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C15
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = -91.56 kNm
M2 = 125.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = 55.93 kNm
M2 = -65.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C16
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 1987
Critical Analysis Load Combination : 106
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Critical Location = Bottom Joint
Put = 4424.78 kN
Muxt = -19.45 kNm
Muyt = 346.22 kNm
Vuxt = 159.9 kN
Vuyt = 9.98 kN
Pub = 4424.78 kN
Muxb = 26.46 kNm
Muyb = -389.11 kNm
Vuxb = 159.9 kN
Vuyb = 9.98 kN
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = -19.45 kNm
M2 = 26.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 346.22 kNm
M2 = -389.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.53 362.64 2002.4 2035.8 367.94 145.8 1001.2 1017.9 195.58 0 367.94 0 195.58
400 x 600 0 0.42 370.37 2051.17 2148.9 385.72 77.44 1025.59 1131 215.93 385.72 0 215.93 0
400 x 600 180 0.15 336.57 1840.42 1922.7 349.89 96.63 920.21 1017.9 195.58 349.89 0 195.58 0
400 x 600 270 14.25 500.65 3088.05 3166.8 533.06 165.23 1544.03 1583.4 294.62 0 533.06 0 294.62
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
General Data
Column No. : C16
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Pub = 3727.95 kN
Muxb = 6.77 kNm
Muyb = -419.28 kNm
Vuxb = 216.19 kN
Vuyb = 4.19 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 1117.46 No Beam No Beam - - 10.892
Top 1117.46 6000 x 400 x 600 6000 x 400 x 600 102.59 102.59 7.403
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.96
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 6.77 kNm
M2 = -9.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 405.93 kNm
δns x M2s = -386.51 kNm
M1ns = 60.98 kNm
M2ns = -53.38 kNm
δns = 1.06
M1sldr = 466.9 kNm
1.4 MuyT = 623.36 kNm
M1sldr = Min (466.9, 623.36) kNm
= 466.9 kNm
M2sldr = -439.89 kNm
1.4 MuyB = -586.99 kNm
M2sldr = Min (-439.89, -586.99) kNm
= -439.89 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C16
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = -14.95 kNm
M2 = 14.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 308.52 kNm
δns x M2s = -283.16 kNm
M1ns = 42.95 kNm
M2ns = -33.73 kNm
δns = 1.05
M1sldr = 351.47 kNm
1.4 MuyT = 470.13 kNm
M1sldr = Min (351.47, 470.13) kNm
= 351.47 kNm
M2sldr = -316.89 kNm
1.4 MuyB = -423.52 kNm
M2sldr = Min (-316.89, -423.52) kNm
= -316.89 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C16
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 12.63 kNm
M2 = -13.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -303.09 kNm
M2 = 324.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C16
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 11.32 kNm
M2 = -12.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.47 250.34 1328.08 1357.2 255.4 54.72 664.04 791.7 154.04 0 255.4 0 154.04
400 x 600 0 0.35 302.54 1634.09 1696.5 312.93 11.36 817.05 904.8 174.94 312.93 0 174.94 0
400 x 600 180 0.88 267.72 1428.62 1470.3 274.86 25.11 714.31 791.7 154.04 274.86 0 154.04 0
400 x 600 270 13.43 393.92 2360.95 2375.1 420.42 8.61 1180.48 1244.1 236.02 0 420.42 0 236.02
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C16
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 1333
Critical Analysis Load Combination : 106
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Critical Location = Top Joint
Put = 1013.87 kN
Muxt = -9.21 kNm
Muyt = 238.62 kNm
Vuxt = 111.46 kN
Vuyt = 4.42 kN
Pub = 1013.87 kN
Muxb = 8.48 kNm
Muyb = -207.13 kNm
Vuxb = 111.46 kN
Vuyb = 4.42 kN
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 8.48 kNm
M2 = -9.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 250 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C16
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 9.27 kNm
M2 = -14.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -139.28 kNm
M2 = 146.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -14.87 - -14.87
Major Axis Mux (bottom) 9.27 - 9.27
Minor Axis Muy (top) 146.41 - 146.41
Minor Axis Muy (bottom) -139.28 - -139.28
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Rebar Number of bundled bar, D1 = 20
Diameter of bundled bar, D1 = 20 mm
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 28.02 kNm
M2 = -28.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 259.49 kNm
M2 = -363.82 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 24.97 kNm
M2 = -28.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 257.03 kNm
δns x M2s = -238.94 kNm
M1ns = 33.95 kNm
M2ns = -30.36 kNm
δns = 1.06
M1sldr = 290.98 kNm
1.4 MuyT = 388.19 kNm
M1sldr = Min (290.98, 388.19) kNm
= 290.98 kNm
M2sldr = -269.3 kNm
1.4 MuyB = -359.18 kNm
M2sldr = Min (-269.3, -359.18) kNm
= -269.3 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = 23.95 kNm
M2 = -25.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 234.79 kNm
δns x M2s = -216.89 kNm
M1ns = 23.88 kNm
M2ns = -18.7 kNm
δns = 1.05
M1sldr = 258.67 kNm
1.4 MuyT = 345.45 kNm
M1sldr = Min (258.67, 345.45) kNm
= 258.67 kNm
M2sldr = -235.59 kNm
1.4 MuyB = -314.41 kNm
M2sldr = Min (-235.59, -314.41) kNm
= -235.59 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.36 332.6 1816.04 1922.7 349.89 130.53 908.02 1017.9 195.58 0 349.89 0 195.58
400 x 600 0 0.09 335.97 1836.69 1922.7 349.89 82.87 918.34 1017.9 195.58 349.89 0 195.58 0
400 x 600 180 1.68 352.68 1940.09 2035.8 367.94 70.73 970.05 1017.9 195.58 367.94 0 195.58 0
400 x 600 270 0.3 376.52 2090.15 2148.9 385.72 90.31 1045.08 1131 215.93 0 385.72 0 215.93
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 936
Critical Analysis Load Combination : 106
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Critical Location = Top Joint
Put = 2237.55 kN
Muxt = -26.55 kNm
Muyt = 230.82 kNm
Vuxt = 109.56 kN
Vuyt = 12.96 kN
Pub = 2237.55 kN
Muxb = 25.26 kNm
Muyb = -207.29 kNm
Vuxb = 109.56 kN
Vuyb = 12.96 kN
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 25.26 kNm
M2 = -26.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.33 290 1559.48 1583.4 294.03 101.17 779.74 791.7 154.04 0 294.03 0 154.04
400 x 600 0 0.14 312.02 1690.99 1696.5 312.93 60.09 845.49 904.8 174.94 312.93 0 174.94 0
400 x 600 180 1.81 330.05 1800.46 1809.6 331.55 47.72 900.23 904.8 174.94 331.55 0 174.94 0
400 x 600 270 0.35 348.23 1912.39 1922.7 349.89 59.38 956.2 1017.9 195.58 0 349.89 0 195.58
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 1135
Critical Analysis Load Combination : 106
Load Combination = [7] : 1.2 (LOAD 1: DL) +(LOAD 2: LL) +(LOAD 8: EQNZ)
Critical Location = Top Joint
Put = 1615.32 kN
Muxt = -25.87 kNm
Muyt = 201.74 kNm
Vuxt = 93.24 kN
Vuyt = 12.53 kN
Pub = 1615.32 kN
Muxb = 24.22 kNm
Muyb = -171.14 kNm
Vuxb = 93.24 kN
Vuyb = 12.53 kN
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 24.22 kNm
M2 = -25.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -171.14 kNm
M2 = 201.74 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.28 243.71 1290.03 1357.2 255.4 62.12 645.02 791.7 154.04 0 255.4 0 154.04
400 x 600 0 0.23 279.5 1497.55 1583.4 294.03 29.04 748.77 791.7 154.04 294.03 0 154.04 0
400 x 600 180 1.88 298.86 1612.12 1696.5 312.93 16.16 806.06 904.8 174.94 312.93 0 174.94 0
400 x 600 270 0.39 310.26 1680.38 1696.5 312.93 20.23 840.19 904.8 174.94 0 312.93 0 174.94
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 22.58 kNm
M2 = -24.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -127.71 kNm
M2 = 160.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -24.28 - -24.28
Major Axis Mux (bottom) 22.58 - 22.58
Minor Axis Muy (top) 160.58 - 160.58
Minor Axis Muy (bottom) -127.71 - -127.71
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Rebar Number of bundled bar, D1 = 20
Diameter of bundled bar, D1 = 20 mm
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C17
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 21.35 kNm
M2 = -22.69 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -87.87 kNm
M2 = 120.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = -19.03 kNm
M2 = 27.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 238.57 kNm
M2 = -352.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = 6.49 kNm
M2 = -11.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 250.04 kNm
δns x M2s = -232.56 kNm
M1ns = 5.89 kNm
M2ns = -3.05 kNm
δns = 1.06
M1sldr = 255.93 kNm
1.4 MuyT = 339.63 kNm
M1sldr = Min (255.93, 339.63) kNm
= 255.93 kNm
M2sldr = -235.61 kNm
1.4 MuyB = -312.5 kNm
M2sldr = Min (-235.61, -312.5) kNm
= -235.61 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.72 378.26 2101.25 2148.9 385.72 134.18 1050.63 1131 215.93 0 385.72 0 215.93
400 x 600 0 0.75 369.6 2046.25 2148.9 385.72 82.12 1023.13 1131 215.93 385.72 0 215.93 0
400 x 600 180 0.96 344.58 1889.79 1922.7 349.89 97.94 944.9 1017.9 195.58 349.89 0 195.58 0
400 x 600 270 0.52 373.78 2072.76 2148.9 385.72 136.09 1036.38 1131 215.93 0 385.72 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
General Data
Column No. : C18
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = 17.53 kNm
M2 = -19.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 227.78 kNm
δns x M2s = -210.2 kNm
M1ns = 7.96 kNm
M2ns = -5.51 kNm
δns = 1.05
M1sldr = 235.74 kNm
1.4 MuyT = 313.84 kNm
M1sldr = Min (235.74, 313.84) kNm
= 235.74 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Rebar Number of bundled bar, D1 = 20
Diameter of bundled bar, D1 = 20 mm
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 19.06 kNm
M2 = -21.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -182.91 kNm
M2 = 206.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -21.19 - -21.19
Major Axis Mux (bottom) 19.06 - 19.06
Minor Axis Muy (top) 206.29 - 206.29
Minor Axis Muy (bottom) -182.91 - -182.91
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Rebar Number of bundled bar, D1 = 20
Diameter of bundled bar, D1 = 20 mm
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 19.75 kNm
M2 = -21.51 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -147.73 kNm
M2 = 177.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -21.51 - -21.51
Major Axis Mux (bottom) 19.75 - 19.75
Minor Axis Muy (top) 177.8 - 177.8
Minor Axis Muy (bottom) -147.73 - -147.73
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Maximum Longitudinal Diameter = Dia Of Rebar
Rebar Number of bundled bar, D1 = 20
Diameter of bundled bar, D1 = 20 mm
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 109.64 kNm
M2 = -141.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -21.66 kNm
M2 = 22.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C18
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 84.82 kNm
M2 = -122.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -24.48 kNm
M2 = 32.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Bundled Rebar = No
Minimum diameter of link >= 9.5 mm
Provided Link Rebar Number = 10
Provided Diameter of link = 10 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 223.72 mm
Kluy /r = 15.2
M1 = 213.82 kNm
M2 = -374.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.2 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -12.26 kNm
M2 = 29.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.04
15.38 < 39.04, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.94
r = 223.72 mm
Kluy /r = 14.29
M1 = 326 kNm
M2 = -342.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.29 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 19.85 kNm
δns x M2s = -19.07 kNm
M1ns = 19.52 kNm
M2ns = -16.47 kNm
δns = 1.06
M1sldr = 39.37 kNm
1.4 MuyT = 53.63 kNm
M1sldr = Min (39.37, 53.63) kNm
= 39.37 kNm
M2sldr = -35.54 kNm
1.4 MuyB = -48.33 kNm
M2sldr = Min (-35.54, -48.33) kNm
= -35.54 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.88
r = 173.2 mm
Kluy /r = 17.27
M1 = 260.59 kNm
M2 = -278.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.27 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 21.23 kNm
δns x M2s = -20.88 kNm
M1ns = 15.1 kNm
M2ns = -11.63 kNm
δns = 1.05
M1sldr = 36.34 kNm
1.4 MuyT = 49.36 kNm
M1sldr = Min (36.34, 49.36) kNm
= 36.34 kNm
M2sldr = -32.51 kNm
1.4 MuyB = -44.04 kNm
M2sldr = Min (-32.51, -44.04) kNm
= -32.51 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.1 347.81 1909.78 1922.7 349.89 135.65 954.89 1017.9 195.58 0 349.89 0 195.58
400 x 600 0 0.2 288.58 1551.06 1583.4 294.03 281.83 1511.26 1583.4 294.62 294.03 0 294.62 0
400 x 600 180 0.42 367.9 2035.54 2035.8 367.94 79.09 1017.77 1017.9 195.58 367.94 0 195.58 0
400 x 600 270 0.47 372.72 2066.03 2148.9 385.72 113.42 1033.02 1131 215.93 0 385.72 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 251.18 kNm
M2 = -266.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -35.72 kNm
M2 = 37.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Beam Beam Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
Size angle moment
w.r.t.
column
Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.14 326.11 1776.39 1809.6 331.55 116.26 888.2 904.8 174.94 0 331.55 0 174.94
400 x 600 0 0.09 247.25 1310.32 1357.2 255.4 238.27 1258.98 1357.2 255.82 255.4 0 255.82 0
400 x 600 180 0.31 359.4 1982.05 2035.8 367.94 72.17 991.03 1017.9 195.58 367.94 0 195.58 0
400 x 600 270 0.54 348.72 1915.44 1922.7 349.89 92.84 957.72 1017.9 195.58 0 349.89 0 195.58
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Vuyt = 112.93 kN
Pub = 1089.33 kN
Muxb = 214.3 kNm
Muyb = -35.09 kNm
Vuxb = 18.32 kN
Vuyb = 112.93 kN
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-m x 10^6 mm mm N-m x 10^6 N-m x 10^6
Bottom 401.45 No Beam No Beam - - 2.609
Top 401.45 3000 x 400 x 600 6000 x 400 x 600 205.18 102.59 2.609
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.86
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 214.3 kNm
M2 = -237.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -35.09 kNm
M2 = 38.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
400 x 600 90 0.18 285.41 1532.32 1583.4 294.03 87.74 766.16 791.7 154.04 0 294.03 0 154.04
400 x 600 0 0.14 186.23 967.68 1017.9 195.34 196.56 1024.7 1131 215.93 195.34 0 215.93 0
400 x 600 180 0.27 346.21 1899.87 1922.7 349.89 49.67 949.93 1017.9 195.58 349.89 0 195.58 0
400 x 600 270 0.54 320.18 1740.32 1809.6 331.55 63.72 870.16 904.8 174.94 0 331.55 0 174.94
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 22.3 m To 24.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.013
0.013< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 167.16 kNm
M2 = -189.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -32.06 kNm
M2 = 32.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.26 241.67 1278.39 1357.2 255.4 49.39 639.19 791.7 154.04 0 255.4 0 154.04
400 x 600 0 0.24 123.01 737.2 791.7 153.89 141.15 737.2 791.7 154.04 153.89 0 154.04 0
400 x 600 180 0.18 321.25 1746.82 1809.6 331.55 18.91 873.41 904.8 174.94 331.55 0 174.94 0
400 x 600 270 0.53 282.72 1516.5 1583.4 294.03 26.35 758.25 791.7 154.04 0 294.03 0 154.04
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C19
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Vuyb = 45.65 kN
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.83
r = 173.2 mm
Kluy /r = 16.29
M1 = 86.96 kNm
M2 = -95.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.29 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -67.54 kNm
M2 = 103.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C20
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = 27.94 kNm
M2 = -29.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = 226.23 kNm
M2 = -337.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C20
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Along B
δns x M1s = 240.3 kNm
δns x M2s = -223.97 kNm
M1ns = 1.99 kNm
M2ns = 0.36 kNm
δns = 1.06
M1sldr = 242.29 kNm
1.4 MuyT = 321.26 kNm
M1sldr = Min (242.29, 321.26) kNm
= 242.29 kNm
M2sldr = -223.61 kNm
1.4 MuyB = -296.33 kNm
M2sldr = Min (-223.61, -296.33) kNm
= -223.61 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C20
Level : 10.3 m To 12.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.051
0.051 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.92
r = 173.2 mm
Kluy /r = 18.06
M1 = 31.66 kNm
M2 = -37.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.06 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.32
r = 173.2 mm
Klux /r = 45.54
Permissible slenderness ratio = 22
45.54 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = 217.83 kNm
δns x M2s = -200.54 kNm
M1ns = 5.08 kNm
M2ns = -3.31 kNm
δns = 1.05
M1sldr = 222.9 kNm
1.4 MuyT = 296.58 kNm
M1sldr = Min (222.9, 296.58) kNm
= 222.9 kNm
M2sldr = -203.85 kNm
1.4 MuyB = -271.14 kNm
M2sldr = Min (-203.85, -271.14) kNm
= -203.85 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C20
Level : 14.3 m To 16.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.036
0.036< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 40.8 kNm
M2 = -43.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -170.72 kNm
M2 = 193.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <= 0.33*Sqrt
Check
(f'c)*B*d
d/2 = 270 mm
600 = 600 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Criterion for spacing of Ductile links / Links at Beam
column Joint:
fyt = 414 N/sqmm
Along D
Av/s min-1 = 0.062 x Sqrt(f'c) x B x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Rebar Number 10 --- 10 10 10
Spacing 300 --- 100 300 100
General Data
Column No. : C20
Level : 18.3 m To 20.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 600 mm
Column D = 600 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.026
0.026< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 42.69 kNm
M2 = -45.57 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -136.05 kNm
M2 = 165.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.89
r = 173.2 mm
Kluy /r = 17.47
M1 = 41.92 kNm
M2 = -41.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.89
r = 173.2 mm
Klux /r = 17.47
M1 = -92.87 kNm
M2 = 122.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.47 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
S1 = 100 mm
Ag = 360000 sqmm
bc1 = 520 mm
Ach = 270400 sqmm
AshD1 = 258.21 sqmm
AshD2 = 233.77 sqmm
AshD (Max (AshD1, AshD2)) = 258.21 sqmm
AshD Provided = 549.78 sqmm
Along B
No of bars along B = 7
S1 = 100 mm
Ag = 360000 sqmm
dc1 = 520 mm
Ach = 270400 sqmm
AshB1 = 258.21 sqmm
AshB2 = 233.77 sqmm
AshB (Max (AshB1, AshB2)) = 258.21 sqmm
AshB Provided = 549.78 sqmm
General Data
Column No. : C20
Level : 26.3 m To 28.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Along B
Q = 0.001
0.001< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 173.2 mm
Kluy /r = 16.88
M1 = 47.83 kNm
M2 = -60.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 173.2 mm
Klux /r = 16.88
M1 = -56.08 kNm
M2 = 94.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.88 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 486.22 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 270 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 408.62 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 507.25 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 507.25 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 150 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
General Data
Column No. : C21
Level : 2.3 m To 4.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 4000 mm
Clear Floor Height @ luy = 4000 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.045
0.045< 0.05, Column shall be designed as non-sway frame (Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.86
r = 223.72 mm
Kluy /r = 15.38
M1 = -23.37 kNm
M2 = 23.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.86
r = 223.72 mm
Klux /r = 15.38
M1 = -267.99 kNm
M2 = 388.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.38 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 527.8 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 655.19 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 655.19 sqmm/m
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 120 mm
B/4 = 193.8 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 100 mm
Hence, OK
General Data
Column No. : C21
Level : 6.3 m To 8.6 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C21 N/sqmm
Grade Of Steel (Main) = Fy414 N/sqmm
Grade Of Steel (Shear) = Fy414 N/sqmm
Grade Of Steel - Flexural Design = Fy414 N/sqmm
Grade Of Steel - Shear Design = Fy414 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 775 mm
Column D = 775 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3400 mm
Clear Floor Height @ luy = 3400 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.053
0.053 > 0.05, Column shall be designed as sway frame (Un-Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.96
r = 223.72 mm
Kluy /r = 14.59
M1 = -39.58 kNm
M2 = 44.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.59 < 40, Column not slender along D
Column Is Un-Braced Along B
Slenderness Check along B
k = 2.87
r = 223.72 mm
Klux /r = 43.62
Permissible slenderness ratio = 22
43.62 > 22, Column slender along B
Moment Magnification:
For Sway Frame:
Along B
δns x M1s = -284.09 kNm
δns x M2s = 263.53 kNm
M1ns = -2.91 kNm
M2ns = 3.08 kNm
δns = 1.06
M1sldr = -287 kNm
1.4 MuyT = -380.6 kNm
M1sldr = Min (-287, -380.6) kNm
= -287 kNm
M2sldr = 266.62 kNm
1.4 MuyB = 353.59 kNm
M2sldr = Min (266.62, 353.59) kNm
= 266.62 kNm
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
400 x 600 90 0.55 405.19 2274.89 2375.1 420.42 139.35 1137.45 1244.1 236.02 0 420.42 0 236.02
400 x 600 0 0.58 350.69 1927.71 2035.8 367.94 279.42 1497.04 1583.4 294.62 367.94 0 294.62 0
400 x 600 270 0.48 400.22 2242.53 2262 403.21 142.09 1121.26 1131 215.93 0 403.21 0 215.93
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 831.57 kN
Vs <=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 357.5 mm
600 = 600 mm
Provided spacing = 300 mm