Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of
1 βdns =
columns due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in mm
4 ∑Pu = Total factored vertical load in kN. (Clause 10.10.5.2)
5 δu = Design displacement in mm
Modification factor reflecting the reduced
6 λ =
mechanical properties of concrete
Coefficient defining the relative contribution of
7 ac =
concrete strength to nominal wall shear strength
Cross-sectional area of a structural member
8 Ach = measured to the outside edges of transverse
reinforcement in sqmm
Gross area of concrete section bounded by web
9 Acv = thickness and length of section in the direction of
shear force considered in sqmm
Effective cross-sectional area within a joint in a
10 Aj = plane parallel to plane of reinforcement generating
shear in the joint in sqmm
Area of non-prestressed longitudinal tension
11 As =
reinforcement in sqmm
Minimum area of shear reinforcement within
12 Avmin =
spacing 's' in sqmm
13 B = Width of column/ wall in mm
Cross-sectional dimension of member core
14 bc = measured to the outside edges of the transverse
reinforcement composing area Ash in mm
Distance from extreme compression fiber to neutral
15 c =
axis in mm
16 Cc = Clear cover to longitudinal reinforcement in mm
Factor relating actual moment diagram to an
17 Cm =
equivalent uniform moment diagram
18 D = Depth / diameter of column in mm
Distance from extreme compression fiber to
19 d = centroid of longitudinal tension reinforcement in
mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 2 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 3 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 4 of 86
Code References:
ACI 318M - 2014
Sr.No Element Clause / table
Minimum area of longitudinal
1 : 18.7.4
reinforcement for column
Maximum area of longitudinal
2 : 18.7.4
reinforcement for column
Minimum longitudinal and transverse
3 : 18.10.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 25.7.2
5 Minimum spacing of transverse ties : 25.7.2
Maximum spacing of longitudinal and
6 : 18.10.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 18.10.6
Area and spacing of special confining
8 : 18.7.5
reinforcement
9 Slenderness Moments : 6.2.5
Shear Strength provided by concrete for
10 : 22.5.5
column
11 Design of shear for non-ductile wall : 11.5.4
12 Design of shear for ductile wall : 18.10.4.1
13 Minimum Flexural Strength of Columns : 18.7.3
14 Shear Check at Column Joint : 18.8.4.1
15 Shear Strength of Column : 18.3.3, 18.4 & 18.6.5
16 fs,perm : 10.6.4
17 fc,perm : 10.2.7.1
18 Wcr : Eq 4.2(a)
General Data
Column No. : C1
Level : 0m To 1.8m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 5 of 86
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 8
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 242.93 kN
Muxt = 5.12 kNm
Muyt = 3.68 kNm
Vuxt = 2.05 kN
Vuyt = -2.85 kN
Pub = 250.35 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = 2.05 kN
Vuyb = -2.85 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 14.85
M1 = 0 kNm
M2 = 5.12 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 14.85
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 6 of 86
M1 = 0 kNm
M2 = 3.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 7 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 1500 mm
Pu Top = 250.35 kN
Mnty = 110.02 kNm
Pu Bottom = 242.93 kN
Mnby = 109.32 kNm
Vuy1 = 146.22 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 242.93 kN
Muy = 5.12 kNm
Vuy3 = -2.8468 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 146.22 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -28.52 kNm
φVcy = 139.49 kN
Vuy > φVcy Hence, Shear links required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 8 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 9 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C1
Level : 1.8m To 4.6m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 10 of 86
Load Data
Analysis Reference No. = 21
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Bottom Joint
Put = 187.92 kN
Muxt = -0.01 kNm
Muyt = 8.18 kNm
Vuxt = 3.56 kN
Vuyt = -3.83 kN
Pub = 199.45 kN
Muxb = -10.73 kNm
Muyb = -1.78 kNm
Vuxb = 3.56 kN
Vuyb = -3.83 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.25
M1 = -0.01 kNm
M2 = -10.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.99
24.25 < 33.99, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 11 of 86
r = 101.04 mm
Klux /r = 24.25
M1 = -1.78 kNm
M2 = 8.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.61
24.25 < 36.61, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 12 of 86
Final Pt = 1 %
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2450 mm
Pu Top = 199.45 kN
Mnty = 104.93 kNm
Pu Bottom = 187.92 kN
Mnby = 103.65 kNm
Vuy1 = 85.13 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 187.92 kN
Muy = 0.01 kNm
Vuy3 = -3.8323 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 85.13 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -26.02 kNm
φVcy = 133.6 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 13 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 14 of 86
Column No. : C1
Level : 4.6m To 7.4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 57
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 77.71 kN
Muxt = -6.53 kNm
Muyt = 3.23 kNm
Vuxt = 0.5 kN
Vuyt = 0.34 kN
Pub = 89.24 kN
Muxb = -5.58 kNm
Muyb = 1.83 kNm
Vuxb = 0.5 kN
Vuyb = 0.34 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 15 of 86
Where
A = Moments from analysis
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 16 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 17 of 86
Luy = 2500 mm
Pu Top = 89.24 kN
Mnty = 92.67 kNm
Pu Bottom = 77.71 kN
Mnby = 91.39 kNm
Vuy1 = 73.63 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 77.71 kN
Muy = 6.53 kNm
Vuy3 = 0.3384 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 73.63 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -4.23 kNm
φVcy = 120.93 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 18 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C2
Level : 0m To 1.8m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 19 of 86
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 14.85
M1 = 0 kNm
M2 = -4.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 14.85
M1 = 0 kNm
M2 = 4.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along B
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 20 of 86
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 21 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 1500 mm
Pu Top = 124.49 kN
Mnty = 96.59 kNm
Pu Bottom = 117.08 kN
Mnby = 95.77 kNm
Vuy1 = 128.24 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 117.08 kN
Muy = 4.67 kNm
Vuy3 = 2.5933 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 128.24 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -11.55 kNm
φVcy = 125.6 kN
Vuy > φVcy Hence, Shear links required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 22 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 23 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C2
Level : 1.8m To 4.6m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 24 of 86
Load Data
Analysis Reference No. = 22
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 69.21 kN
Muxt = -8.19 kNm
Muyt = 6.09 kNm
Vuxt = 2.45 kN
Vuyt = 2.79 kN
Pub = 80.74 kN
Muxb = -0.37 kNm
Muyb = -0.78 kNm
Vuxb = 2.45 kN
Vuyb = 2.79 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.25
M1 = -0.37 kNm
M2 = -8.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.45
24.25 < 33.45, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.25
M1 = -0.78 kNm
M2 = 6.09 kNm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 25 of 86
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 26 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2450 mm
Pu Top = 80.74 kN
Mnty = 91.73 kNm
Pu Bottom = 69.21 kN
Mnby = 90.45 kNm
Vuy1 = 74.36 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 69.21 kN
Muy = 8.19 kNm
Vuy3 = 2.7921 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 74.36 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -1.4 kNm
φVcy = 119.9 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 27 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C2
Level : 4.6m To 7.4m
Design Code = ACI 318M - 2014
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 28 of 86
Load Data
Analysis Reference No. = 58
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Bottom Joint
Put = 22.72 kN
Muxt = 4.64 kNm
Muyt = -0.46 kNm
Vuxt = -2.57 kN
Vuyt = -4.49 kN
Pub = 34.25 kN
Muxb = -7.93 kNm
Muyb = 6.72 kNm
Vuxb = -2.57 kN
Vuyb = -4.49 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 29 of 86
Kluy /r = 24.74
M1 = 4.64 kNm
M2 = -7.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
24.74 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.74
M1 = -0.46 kNm
M2 = 6.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.83
24.74 < 34.83, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 30 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2500 mm
Pu Top = 34.25 kN
Mnty = 86.3 kNm
Pu Bottom = 22.72 kN
Mnby = 84.91 kNm
Vuy1 = 68.49 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 22.72 kN
Muy = 4.64 kNm
Vuy3 = -4.4904 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 68.49 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = 1.49 kNm
φVcy = 114.09 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 31 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 32 of 86
General Data
Column No. : C3
Level : 0m To 1.8m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 10
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 381.26 kN
Muxt = 5.78 kNm
Muyt = 1.06 kNm
Vuxt = 0.59 kN
Vuyt = -3.21 kN
Pub = 388.68 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = 0.59 kN
Vuyb = -3.21 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 33 of 86
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 14.85
M1 = 0 kNm
M2 = 5.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 14.85
M1 = 0 kNm
M2 = 1.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 34 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 1500 mm
Pu Top = 388.68 kN
Mnty = 120.38 kNm
Pu Bottom = 381.26 kN
Mnby = 120.36 kNm
Vuy1 = 160.49 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 381.26 kN
Muy = 5.78 kNm
Vuy3 = -3.21 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 35 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 36 of 86
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -51.75 kNm
φVcx = 153.3 kN
Vux > φVcx Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 37 of 86
General Data
Column No. : C3
Level : 1.8m To 4.6m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 23
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Bottom Joint
Put = 300.63 kN
Muxt = 2.93 kNm
Muyt = -5.11 kNm
Vuxt = -4.12 kN
Vuyt = -5.71 kN
Pub = 312.16 kN
Muxb = -13.05 kNm
Muyb = 6.42 kNm
Vuxb = -4.12 kN
Vuyb = -5.71 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 38 of 86
Q = -0.001
-0.001< 0.05, Column shall be designed as non-sway frame
(Braced)
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.25
M1 = 2.93 kNm
M2 = -13.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.69
24.25 < 36.69, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.25
M1 = -5.11 kNm
M2 = 6.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
24.25 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 39 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2450 mm
Pu Top = 312.16 kN
Mnty = 115.86 kNm
Pu Bottom = 300.63 kN
Mnby = 114.77 kNm
Vuy1 = 94.13 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 300.63 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 40 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 41 of 86
General Data
Column No. : C3
Level : 4.6m To 7.4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 59
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 114.54 kN
Muxt = -12.43 kNm
Muyt = -20.79 kNm
Vuxt = -15.59 kN
Vuyt = 2.36 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 42 of 86
Pub = 126.07 kN
Muxb = -5.82 kNm
Muyb = 22.85 kNm
Vuxb = -15.59 kN
Vuyb = 2.36 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.74
M1 = -5.82 kNm
M2 = -12.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.38
24.74 < 28.38, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.74
M1 = -20.79 kNm
M2 = 22.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
24.74 < 40, Column not slender along B
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 43 of 86
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 44 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 45 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C4
Level : 0m To 1.8m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 46 of 86
Load Data
Analysis Reference No. = 12
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 220.1 kN
Muxt = -4.98 kNm
Muyt = 0.87 kNm
Vuxt = 0.49 kN
Vuyt = 2.77 kN
Pub = 227.51 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = 0.49 kN
Vuyb = 2.77 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 14.85
M1 = 0 kNm
M2 = -4.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 14.85
M1 = 0 kNm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 47 of 86
M2 = 0.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 48 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 1500 mm
Pu Top = 227.51 kN
Mnty = 107.86 kNm
Pu Bottom = 220.1 kN
Mnby = 107.16 kNm
Vuy1 = 143.35 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 220.1 kN
Muy = 4.98 kNm
Vuy3 = 2.7666 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 143.35 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -25.51 kNm
φVcy = 137.07 kN
Vuy > φVcy Hence, Shear links required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 49 of 86
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 50 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C4
Level : 1.8m To 4.6m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 51 of 86
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 25
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 145.31 kN
Muxt = -17.36 kNm
Muyt = -2.16 kNm
Vuxt = -2.8 kN
Vuyt = 7.58 kN
Pub = 156.84 kN
Muxb = 3.86 kNm
Muyb = 5.68 kNm
Vuxb = -2.8 kN
Vuyb = 7.58 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.25
M1 = 3.86 kNm
M2 = -17.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.67
24.25 < 36.67, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 52 of 86
Klux /r = 24.25
M1 = -2.16 kNm
M2 = 5.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.56
24.25 < 38.56, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 53 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2450 mm
Pu Top = 156.84 kN
Mnty = 100.19 kNm
Pu Bottom = 145.31 kN
Mnby = 98.91 kNm
Vuy1 = 81.27 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 145.31 kN
Muy = 17.36 kNm
Vuy3 = 7.5811 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 81.27 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -2.76 kNm
φVcy = 128.85 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 54 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 55 of 86
Column No. : C4
Level : 4.6m To 7.4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 61
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Bottom Joint
Put = 48.93 kN
Muxt = -0.91 kNm
Muyt = -16.65 kNm
Vuxt = -13.06 kN
Vuyt = 0.53 kN
Pub = 60.46 kN
Muxb = 0.57 kNm
Muyb = 19.92 kNm
Vuxb = -13.06 kN
Vuyb = 0.53 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 56 of 86
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 57 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2500 mm
Pu Top = 60.46 kN
Mnty = 89.45 kNm
Pu Bottom = 48.93 kN
Mnby = 88.07 kNm
Vuy1 = 71.01 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 48.93 kN
Muy = 0.91 kNm
Vuy3 = 0.5288 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 71.01 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -5.87 kNm
φVcy = 117.4 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 58 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 59 of 86
General Data
Column No. : C5
Level : 0m To 1.8m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 11
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 459.85 kN
Muxt = 5.66 kNm
Muyt = -4.57 kNm
Vuxt = -2.54 kN
Vuyt = -3.15 kN
Pub = 467.26 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = -2.54 kN
Vuyb = -3.15 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 60 of 86
Along D
Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame
(Braced)
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 14.85
M1 = 0 kNm
M2 = 5.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 14.85
M1 = 0 kNm
M2 = -4.57 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 61 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 1500 mm
Pu Top = 467.26 kN
Mnty = 120.68 kNm
Pu Bottom = 459.85 kN
Mnby = 120.65 kNm
Vuy1 = 160.88 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 62 of 86
Nu = 459.85 kN
Muy = 5.66 kNm
Vuy3 = -3.1461 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 160.88 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -58.03 kNm
φVcy = 160.62 kN
Vuy > φVcy Hence, Shear links required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 63 of 86
= 160.88 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -59.12 kNm
φVcx = 160.62 kN
Vux > φVcx Hence, Shear links required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 64 of 86
General Data
Column No. : C5
Level : 1.8m To 4.6m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 24
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Bottom Joint
Put = 395.59 kN
Muxt = 10.35 kNm
Muyt = 3.8 kNm
Vuxt = -0.69 kN
Vuyt = -9.79 kN
Pub = 407.12 kN
Muxb = -17.06 kNm
Muyb = 5.72 kNm
Vuxb = -0.69 kN
Vuyb = -9.79 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 65 of 86
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.25
M1 = 10.35 kNm
M2 = -17.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
24.25 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.25
M1 = 3.8 kNm
M2 = 5.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.03
24.25 < 26.03, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 66 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2450 mm
Pu Top = 407.12 kN
Mnty = 120.45 kNm
Pu Bottom = 395.59 kN
Mnby = 120.41 kNm
Vuy1 = 98.31 kN
Critical Analysis Load Combination : 201
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 67 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 68 of 86
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
General Data
Column No. : C5
Level : 4.6m To 7.4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 60
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 190.51 kN
Muxt = -10.47 kNm
Muyt = 38.15 kNm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 69 of 86
Vuxt = 18.82 kN
Vuyt = -1.1 kN
Pub = 202.04 kN
Muxb = -13.56 kNm
Muyb = -14.53 kNm
Vuxb = 18.82 kN
Vuyb = -1.1 kN
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.74
M1 = -10.47 kNm
M2 = -13.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 24.74
24.74 > 24.74,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.74
M1 = -14.53 kNm
M2 = 38.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.57
24.74 < 38.57, Column not slender along B
Moment Magnification:
For Non-sway frame:
Along D
βdns = 0.6
Ec = 23500 N/sqmm
Ig ( x 10 9) = 1.251 mm^4
EI ( x 10 6) = 8483361.387 N-sqmm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 70 of 86
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 71 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2500 mm
Pu Top = 202.04 kN
Mnty = 105.22 kNm
Pu Bottom = 190.51 kN
Mnby = 103.94 kNm
Vuy1 = 83.66 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 190.51 kN
Muy = 10.47 kNm
Vuy3 = -1.1045 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 83.66 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -15.91 kNm
φVcy = 133.88 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 72 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 73 of 86
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 175 --- 125 175 125
General Data
Column No. : C6
Level : 0m To 1.8m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 13
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 270.17 kN
Muxt = -6.92 kNm
Muyt = -5.55 kNm
Vuxt = -3.08 kN
Vuyt = 3.84 kN
Pub = 277.59 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = -3.08 kN
Vuyb = 3.84 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 74 of 86
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 14.85
M1 = 0 kNm
M2 = -6.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 14.85
M1 = 0 kNm
M2 = -5.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 34
14.85 < 34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 75 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 1500 mm
Pu Top = 277.59 kN
Mnty = 112.59 kNm
Pu Bottom = 270.17 kN
Mnby = 111.89 kNm
Vuy1 = 149.65 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 270.17 kN
Muy = 6.92 kNm
Vuy3 = 3.8429 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 76 of 86
= 149.65 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -30.5 kNm
φVcy = 142.31 kN
Vuy > φVcy Hence, Shear links required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 77 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 78 of 86
General Data
Column No. : C6
Level : 1.8m To 4.6m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 26
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 212.19 kN
Muxt = -19.41 kNm
Muyt = 8.96 kNm
Vuxt = 1.6 kN
Vuyt = 8.96 kN
Pub = 223.72 kN
Muxb = 5.66 kNm
Muyb = 4.49 kNm
Vuxb = 1.6 kN
Vuyb = 8.96 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 79 of 86
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.25
M1 = 5.66 kNm
M2 = -19.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.5
24.25 < 37.5, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.25
M1 = 4.49 kNm
M2 = 8.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.99
24.25 < 27.99, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 80 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2450 mm
Pu Top = 223.72 kN
Mnty = 107.5 kNm
Pu Bottom = 212.19 kN
Mnby = 106.35 kNm
Vuy1 = 87.29 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 212.19 kN
Muy = 19.41 kNm
Vuy3 = 8.9558 kN
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 81 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 82 of 86
General Data
Column No. : C6
Level : 4.6m To 7.4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 62
Critical Analysis Load Combination : 201
Load Combination = [1] : 1.4 (LOAD 9: DL)
Critical Location = Top Joint
Put = 86.51 kN
Muxt = -4.47 kNm
Muyt = 23.35 kNm
Vuxt = 11.9 kN
Vuyt = 2.37 kN
Pub = 98.04 kN
Muxb = 2.15 kNm
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 83 of 86
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 101.04 mm
Kluy /r = 24.74
M1 = 2.15 kNm
M2 = -4.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.78
24.74 < 39.78, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 101.04 mm
Klux /r = 24.74
M1 = -9.97 kNm
M2 = 23.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.12
24.74 < 39.12, Column not slender along B
Where
A = Moments from analysis
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 84 of 86
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 85 of 86
Luy = 2500 mm
Pu Top = 98.04 kN
Mnty = 93.65 kNm
Pu Bottom = 86.51 kN
Mnby = 92.37 kNm
Vuy1 = 74.41 kN
Critical Analysis Load Combination : 201
Critical Load Combination = [1] : 1.4 (LOAD 9: DL) kN
Nu = 86.51 kN
Muy = 4.47 kNm
Vuy3 = 2.3665 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 74.41 kN
λ = 1
φ = 0.75
deff = 292 mm
ρw (50% of As provided) = 0.016
Mm = -7.51 kNm
φVcy = 121.99 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/GL702VM-EV032T/AppData/Local/Temp/tmp1B94.tmp 20/01/2023
Column Design: Design Calculations Page 86 of 86
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 175 mm