SALISH SEA HOUSING

CENTRAL SAANICH RD, EAST SAANICH RESERVE NO. 2


ARCHITECTURAL STRUCTURAL MECHANICAL ELECTRICAL CIVIL

FINLAYSON BONET ARCHITECTURE LTD. READ JONES CHRISTOFFERSEN LTD. AVALON MECHANICAL CONSULTANTS LTD. E2 ENGINEERING MCELHANNEY
#4 - 7855 EAST SAANICH ROAD, 645 TYEE ROAD, SUITE 220 300 - 1245 ESQUIMALT ROAD 549 HERALD ST SUITE 500, 3960 QUADRA STREET
SAANICHTON, BC V8M 2B4 VICTORIA, BC V9A 6X5 VICTORIA, BC V9A 3P2 VICTORIA, BC V8W 1S5 VICTORIA BC V8X 4A3
PHONE: 250-656-7794 PHONE: 250-384-4128 PHONE: 778-433-9391 PHONE: 250 370 9221
PHONE: 250-656-2224
ENGINEER OF RECORD: CLINT PLETT, P. ENG ENGINEER OF RECORD: JON EDGELL, P.ENG. ENGINEER OF RECORD: PATRICK LOURDU, P.ENG. ENGINEER OF RECORD: IAN MCCALL, P.ENG.
ARCHITECT OF RECORD: SILVIA BONET, ARCHITECT AIBC MRAIC
CONTACT: KYLE SHICK

ISSUED FOR CONSTRUCTION


OCT 05, 2021
PROJECT DATA GENERAL NOTES
LEGAL: LOT 43, PLAN 63839 CLSR 1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.
CIVIC ADDRESS: 7611 CENTRAL SAANICH RD, EAST SAANICH RESERVE NO. 2 2. ALL ELEVATIONS ARE IN GEODETIC
METERS UNLESS NOTES OTHERWISE.
LOT AREA: 1,423.75 M2 / 15,323.16 FT2
3. ALL DIMENSIONS ARE TO FACE OF
BUILDING AREA: 687.4 M2 / 7,399.15 FT2 CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
CENTRELINE OF DOORS AND
SITE COVERAGE: 687.4 M2 / 1,423.75M2 48.2% WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
FLOOR AREA: NOT LISTED.
LEVEL 1: 281.5 M2 / 3,030FT2
LEVEL 2: 623.6 M2 / 6,712 FT2 4. CONTRACTOR TO VERIFY ALL
DIMENSIONS ON SITE AND INFORM
LEVEL 3: 623.6 M2 / 6,712 FT2 COORDINATING REGISTERED
LEVEL 4: 623.6 M2 / 6,712 FT2 PROFESSIONAL OF ANY
LEVEL 5: 623.6 M2 / 6,712 FT2 DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
TOTAL FLOOR AREA: 2,775.9 M2 / 29,878 FT2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.
BUILDING HEIGHT: 16.77M 5. DO NOT SCALE THESE DRAWINGS.
FINLAYSON BONET ARCHITECTURE
SETBACK: LTD. IS NOT RESPONSIBLE FOR
EXISTING GRADE FRONT SETBACK = 6.0 m (20 FT.) ISSUES THAT ARISE FROM A
19.55m INTERIOR SIDE SETBACK = 0.0 m (0 FT.) FAILURE TO COMPLY.
REAR SETBACK = 0.0 m (0 FT.) 6. THESE DRAWINGS ARE TO BE READ
IN CONJUNCTION WITH ALL
UNITS TYPES: ARCHITECTURAL SPECIFICATIONS,
EXISTING ELEV.
2 BEDROOM 'A' (768 FT2) 4 UNITS STRUCTURAL DRAWINGS AND
19.03m 2 BEDROOM 'B' (772 FT2) 4 UNITS SPECIFICATIONS, MECHANICAL
A LL 28'-5 1/4" A LL DRAWINGS AND SPECIFICATIONS,
LINE OF 6'-0" HIGH WOOD FENCE ON 8" 2 BEDROOM 'C' (752 FT2) 12 UNITS
FW FW ELECTRICAL DRAWINGS AND
P O [8.67m] CONCRETE CURB P O 2 BEDROOM 'D' (782 FT2) 4 UNITS SPECIFICATIONS, CIVIL DRAWINGS
TO 80m TO 80m 3 BEDROOM (1,046 FT2) 4 UNITS AND SPECIFICATIONS, LANDSCAPE
9 . 9 .
1 [41.27 M] 1 DRAWINGS AND SPECIFICATIONS,
TOP O TOTAL NO. OF UNITS: 28 INTERIOR DESIGN DRAWINGS AND
FP NT
19.20m AVEMENT E ME 0m SPECIFICATIONS AND ANY OTHER
V 5 CONSULTANT DEEMED PERTINENT
F PA 19. PARKING: 29 STALLS TO THE CONSTRUCTION OF THIS
EXISTING GRADE PO PROJECT.
TO BICYCLES: CLASS 1 = 3 BIKES (SECURED COVERED AREA)

[4.85m]
15'-11"
19.74m 7. CONTRACTOR TO OBTAIN ALL
NECESSARY PERMITS, BYLAW
12 11 4 3 2 CODE ANALYSIS APPROVALS, AND OBSERVE ALL
15 14 13 SMALL CAR SMALL CAR 10 9 8 7 6 5 SMALL CAR SMALL CAR 1 LINE OF 6'-0" HIGH WOOD REQUIRED SAFETY REGULATIONS
SMALL CAR
FENCE ON 8" CONCRETE THROUGHOUT THE COURSE OF
LINE OF EDGE OF SLAB ABOVE CURB REFERENCE : BRITISH COLUMBIA BUILDING CODE 2018 CONSTRUCTION
SYMBOL LEGEND
T

T
EXISTING GRADE BUILDING CLASSIFICATION:
EN

EN
M

M
19.09m FLOOR DRAIN
VE

VE
3.2.2.50 GROUP C, UP TO 6 STOREYS, SPRINKLERED FD
PA

PA
P 6m

P 0m
F

F
1 a) SPRINKLERED THROUGHOUT
TO 9.4

TO 9.1
O

O
ROOF / DECK DRAIN
b) NOT MORE THEN 6 STORIES
1

c) BUILDING HEIGHT NOT MORE THEN 18M


EXISTING GRADE d) BUILDING AREA NOT MORE THEN 1 800m2 IF 5 STORIES IN XX ASSEMBLY MARKER
LINE OF EXTERIOR WALL ABOVE 19.26m HEIGHT

2 a) FLOOR ASSEMBLIES OF COMBUSTIBLE CONSTRUCTION GLAZING TYPE (REFER TO


TOP OF WALL WITH A FIRE RESISTANCE RATING OF 1.0 HR
GX WINDOW SCHEDULE)
EXISTING GRADE 19.80m b) ROOF ASSEMBLIES SHALL HAVE A FIRE RESISTANCE
DRIVEWAY RATING NOT LESS THAN 1HOUR DOOR TYPE (REFER TO DOOR

60'-5 1/4"
19.64m

[18.42m]
e) LOAD BEARING WALLS, COLUMNS, AND ARCHES DXXX SCHEDULE)
SUPPORTING AN ASSEMBLY SHALL BE NOT LESS THEN
1.0HR FIRE RESISTANCE RATING
5 % SLOPE CATCH BASIN PARKING TOP OF PAVEMENT X
SECTION MARKER
18.90m M.F.E. 18.90M 19.50m NO. OF STOREYS: 5 STOREYS AXXX

BUILDING AREA: 687.4 M2 / 7,399.15 FT2 X DETAIL MARKER


AXXX
STREETS FACING: 1 INTERIOR ELEVATION MARKER
X
T

T
EN

EN

NT CONSTRUCTION TYPE: COMBUSTIBLE CONSTRUCTION


ME
M

XX

PROPERTY LINE
EXISTING ELEVATION MARKER
VE

VE

VE

[33.83 M]
PA X .X
PA

PA

LINE OF EXTERIOR WALL ABOVE


P 9m

P 0m

F
PO
F

F
TO 9.3

TO 9.1
O

O
T 00m NEW ELEVATION MARKER
TOP OF PAVEMENT X.XXXm
1

.
19 19.04m
H2O VAULT
GRADE
19.30m HATCHED WALL INDICATED
SHEAR WALL (REFER TO STRUCT.)
EXISTING GRADE
SMALL CAR SMALL CAR SMALL CAR 19.04m TOP OF WALL HATCHED WALL INDICATED LOAD
ENTRY BEARING WALL (REFER TO
SMALL CAR 26 27 28 19.80m STRUCT.)
16 17 18 19 20 21 22 23 24 25 29
EXISTING GRADE EXISTING GRADE
[33.57 M]

19.35m 19.35m TOP OF PAVEMENT TO


20'-0 1/8" P
[6.1m] 19.00m OF
FRONT YARD SETBACK EXISTING GRADE PA
VE
19.66m ME
19 N
.5 0 T
T

TOP OF PAVEMENT TOP OF PAVEMENT


EN

m
M

19.20m 19.14m
VE
PA
P 0m
F
TO 9.3
O

°
1

EN

.6
86
M
VE
PA
P m 8
F
TO 9.2
O
1

#4 - 7855 East Saanich Rd.


PROPOSED BUILDING Saanichton V8M 2B4
MAIN MAIN FLOOR ELEV. - 19.00m (GEODETIC)
TOP OF PAVEMENT
ENTRY Phone: 250-656-2224
18.98m Fax. 250-656-2279
email:
EXISTING GRADE info@finlaysonbonet.ca

[11.53m]
37'-10"
19.57m
GRADE
SWALE TO CULVERT

18.90m 3'-0"
(REFER TO CIVIL)

[0.91m]

TOP OF PAVEMENT

[15.32m]
18.98m

50'-3"
SEWER

LINE OF EDGE OF SLAB ABOVE


EXISTING GRADE
GRADE 18.77m
18.90m
WATER SERVICE COORDINATE FOOTING
TOP OF PAVEMENT EXCAVATION AND FENECE
TOP OF PAVEMENT
GATE (REFER TO LANDSCAPING) 18.98m POST INSTALLATION WITH
18.90m
EXISTING SANITARY MAIN
LOCATION. REFER TO CIVIL
T
EN

OUTDOOR AMENITY SPACE FOR MORE INFORMATION 21.10.05 ISSUED FOR


M

4'-0" (REFER TO LANDSCAPING) CONSTRUCTION


VE
PA

21.05.25 ISSUED FOR TENDER


P 8m

EXISTING GRADE
F
TO 9.1
O

19.14m GRADE 21.04.23 ISSUED FOR B.P.


1

EXISTING GRADE 1
A1.01 18.90m Rev Date Description

12'-8 1/4"
19.17m

[3.87m]
T

12'-5 3/4"
GARBAGE
EN

EN

EXISTING LID ELEVATION

[3.81m]
AREA BASKET BALL COURT Checked SMB/KDS
M

8'-0"

18.41m
VE

VE

(REFER TO LANDSCAPE)
Drawn AV
PA

PA
P 5m

P 2m
F

F
TO 9.1

TO 9.1
O

Scale 1/8"=1'-0"
1

Date
1'-6"

OCT 05, 2021


[43.31 M]
3'-8 3/4" Project Name
[1.14m] SALISH SEA
LINE OF 6'-0" HIGH WOOD FENCE COORDINATE FINISHED GRADING WITH HOUSING
ADJACENT PROPERTY
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
Drawing Title

SITE PLAN

1 SITE PLAN J N
su une

is 1
Scale: 1/8" = 1'-0"

nr 2
A1.00 ns 2

e
su une
et 1 Drawing No.

J
March 21 W March 21
A1.00
E sunrise Project No.
sunset
19323
D © Copyright reserved. These plans and
su ec designs are and at all times remain the

et 1
ns . 2
nr . 2 property of Finlayson Bonet Architecture to be

su ec
S is 1
e used for the project shown and may not be

D
reproduced without written consent.
GENERAL NOTES
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

2. ALL ELEVATIONS ARE IN GEODETIC


METERS UNLESS NOTES OTHERWISE.

3. ALL DIMENSIONS ARE TO FACE OF


CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
CENTRELINE OF DOORS AND
WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
COORDINATING REGISTERED
PROFESSIONAL OF ANY
DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.

5. DO NOT SCALE THESE DRAWINGS.


FINLAYSON BONET ARCHITECTURE
LTD. IS NOT RESPONSIBLE FOR
ISSUES THAT ARISE FROM A
FAILURE TO COMPLY.

6. THESE DRAWINGS ARE TO BE READ


IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
DRAWINGS AND SPECIFICATIONS,
ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
DRAWINGS AND SPECIFICATIONS,
INTERIOR DESIGN DRAWINGS AND
SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
TO THE CONSTRUCTION OF THIS
PROJECT.

7. CONTRACTOR TO OBTAIN ALL


NECESSARY PERMITS, BYLAW
APPROVALS, AND OBSERVE ALL
REQUIRED SAFETY REGULATIONS
THROUGHOUT THE COURSE OF
CONSTRUCTION
SYMBOL LEGEND
FD FLOOR DRAIN

ROOF / DECK DRAIN

XX ASSEMBLY MARKER

GLAZING TYPE (REFER TO


GX WINDOW SCHEDULE)

DOOR TYPE (REFER TO DOOR


DXXX SCHEDULE)

2'-0" 24'-0" 2'-0" X


SECTION MARKER
AXXX

X DETAIL MARKER
2'-0" 10'-6" 2'-0" EQ. EQ. EQ. AXXX
2 x 10 CEDAR RAFTER WITH
2 x 10 CEDAR RAFTER WITH PREFINISHED METAL 2 x 10 CEDAR RAFTER WITH
INTERIOR ELEVATION MARKER
PREFINISHED METAL FLASHING (TYPICAL) X
PREFINISHED METAL
FLASHING FLASHING
X
X.XX EXISTING ELEVATION MARKER

3 - 2 x 12 CEDAR BEAM 3 - 2 x 12 CEDAR BEAM 3 - 2 x 12 CEDARNEW


BEAM
ELEVATION MARKER
WITH PREFINISHED METAL WITH PREFINISHED METAL WITH PREFINISHED
X.XXXm METAL
FLASHING FLASHING FLASHING
H2O VAULT
6 x 6 CEDAR POST CEDAR FENCE WITH
(TYPICAL) DECORATIVE CAP AND
1 x 6 PICKETS HATCHED WALL INDICATED
CEDAR FENCE WITH SHEAR WALL (REFER TO STRUCT.)
DECORATIVE CAP AND

4'-8"

4'-8"
6 x 6 CEDAR POST ON HATCHED WALL INDICATED LOAD
1 x 6 PICKETS CONCRETE BEARING WALL (REFER TO
PEDESTAL STRUCT.)

CONCRETE BOLLARD

10"

10"
LIGHTING

DUMPSTER
CONCRETE BOLLARD DUMPSTER
RECYCLING AND LIGHTING RECYCLING AND
COMPOST BINS RECYCLING AND COMPOST BINS
COMPOST BINS

43 43
2 SECTION 1
3 SECTION 2 Scale: 1/4" = 1'-0"
Scale: 1/4" = 1'-0" A1.01
A1.01 #4 - 7855 East Saanich Rd.
Saanichton V8M 2B4

Phone: 250-656-2224
3 Fax. 250-656-2279
email:
A1.01 info@finlaysonbonet.ca

24'-0"

7'-10 1/8" 7'-10 1/8" 7'-10 1/8"

CONCRETE BOLLARD
LIGHTING

96 GAL.
64 GAL.

GARBAGE

96 GAL.
2
AREA 21.10.05 ISSUED FOR
A1.01

10'-6"
CONSTRUCTION
21.05.25 ISSUED FOR TENDER

96 GAL.
21.04.23 ISSUED FOR B.P.
Rev Date Description

96 GAL.
Checked SMB/KDS

64 GAL. Drawn AV
Scale 1/4"=1'-0"
CONCRETE BOLLARD Date
LIGHTING OCT 05, 2021
Project Name
SALISH SEA
HOUSING
1 GARBAGE ENCLOSURE PLAN 7583 CENTRAL SAANICH RD.,
A1.01 Scale: 1/4" = 1'-0" TSAWOUT FIRST NATION
Drawing Title

GARBAGE
ENCLOSURE

Drawing No.

A1.01
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
INTERIOR • D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10
• 2 x 6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55

FOUNDATION WALL ASSEMBLIES BC ENERGY STEP CODE 4 WALL ASSEMBLIES • 6MIL POLYETHYLENE VAPOUR BARRIER - BC ENERGY STEP CODE 4
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079 EFFECTIVE
ASSEMBLY ILLUSTRATION IN PLAN DESCRIPTION FIRE TESTING RSI-VALUE STC
EFFECTIVE *REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12 RATING AGENCY RATING
ASSEMBLY ILLUSTRATION IN PLAN DESCRIPTION FIRE TESTING RSI-VALUE STC NUMBER
NUMBER RATING AGENCY RATING WALL SCHEDULE* 3.98 RSI REQUIRED 3.89 (m2•K)/W
REQUIRED 2.78 (m2•K)/W
CORRUGATED METAL SIDING ON WOOD STUD WALL RSI VALUE
EXTERIOR RSI VALUE • XYPEX CRYSTALLINE WATERPROOFING ADMIXTURE
AIR FILM 0.03
AIR FILM 0.0 • 8" REINFORCED CONCRETE - ARCHITECTURAL FINISH
• CORRUGATED METAL SIDING -
• GRANULAR FILL - • PAINT FINISH
- - 3.58 RSI - • THERMALLY BROKEN Z-GIRTS @ 16" O.C 0.16
• POLYETHYLENE DRAINAGE MAT - 3.05 RSI
R20.32 • 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943
FDN1 • SELF ADHERED SBS WATERPROOFING MEMBRANE - - - R17.3 -
0.27 U (METRIC) W9 • VP SELF ADHERED SHEATHING MEMBRANE -
• 4", RSI 3.5 (R19.8) RIGID INSULATION, GLUED 3.5 0.33 U (METRIC)
• D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10
• 8" REINFORCED CONCRETE 0.08
INTERIOR • 2x4 SPF WOOD STUDS @ 16" O.C W/ R14 BATT 1.62
3.58 RSI
• 6MIL POLYETHYLENE VAPOUR BARRIER -
EXTERIOR
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079
FDN2 • GRANULAR FILL
*REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12
• POLYETHYLENE DRAINAGE MAT - - - - -
WALL SCHEDULE*
• SELF ADHERED SBS WATERPROOFING MEMBRANE
3.05RSI
• 8" REINFORCED CONCRETE CORRUGATED METAL SIDING ON STEEL STUD WALL
INTERIOR • CORRUGATED METAL SIDING
• THERMALLY BROKEN Z-GIRTS @ 16" O.C
• VP SELF ADHERED SHEATHING MEMBRANE
WALL ASSEMBLIES BC ENERGY STEP CODE 4 W10 • 5/8" TYPE 'X' DENSGLASS EXTERIOR SHEATHING
• 6" 25ga. STEEL STUDS @ 16" O.C - 1.0 HR U419 - -
EFFECTIVE • 5/8" TYPE 'X' GYPSUM WALLBOARD
ASSEMBLY ILLUSTRATION IN PLAN DESCRIPTION FIRE TESTING RSI-VALUE STC TENANT STORGE
NUMBER RATING AGENCY RATING • 1/2" GOOD-ONE-SIDE PLYWOOD SHEATHING - 4' TALL
REQUIRED 3.89 (m2•K)/W HORIZONTAL CORRUGATED METAL SIDING ON RSI VALUE
WOOD STUD WALL
AIR FILM 0.03
• XYPEX CRYSTALLINE WATERPROOFING ADMIXTURE
- 1.0 HR ULC J900 - - • HORIZONTAL CORRUGATED METAL SIDING -
• 8" REINFORCED CONCRETE - ARCHITECTURAL FINISH 3.98 RSI
W1 • THERMALLY BROKEN Z-GIRTS @ 16" O.C 0.16
• PAINT FINISH 1.0 HR - R22.6 -
W11 • 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943
0.25 U (METRIC)
• VP SELF ADHERED SHEATHING MEMBRANE -
CONCRETE WALL AND WOOD STUD FURRING WALL RSI VALUE • D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10
AIR FILM 0.03 • 2x6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55
• XYPEX CRYSTALLINE WATERPROOFING ADMIXTURE - • 6MIL POLYETHYLENE VAPOUR BARRIER -
3.02 RSI
• 8" REINFORCED CONCRETE 0.08 1.0 HR - - • 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079
R17.14
W2 • 1/2" AIR GAP 0.16 *REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12
0.33 U (METRIC)
• 2x6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55 WALL SCHEDULE* 3.98 RSI
• 6MIL POLYETHYLENE VAPOUR BARRIER - INSULATED 2x6 PARTITION ASSEMBLY RSI VALUE
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079
AIR FILM 0.12 TENANT STORGE
AIR FILM 0.12
3.02 RSI • 1/2" GOOD-ONE-SIDE PLYWOOD SHEATHING - 4' TALL 0.139
3.89
W12 • 2x8 SPF WOOD STUDS @ 16" O.C W/ R28 3.35
CORRUGATED METAL SIDING ON CONCRETE WALL 1.0 HR - R22 -
RSI VALUE • 6MIL POLYETHYLENE VAPOUR BARRIER -
0.25 U (METRIC)
AIR FILM 0.03 • 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079
• CORRUGATED METAL SIDING - *REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12
1.33 RSI
• THERMALLY BROKEN Z-GIRTS @ 16" O.C 0.16 WALL SCHEDULE*
1.0 HR - R7.57 -
W3 • 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943 3.89 RSI
0.75 U (METRIC)
• VP SELF ADHERED SHEATHING MEMBRANE -
ROOF ASSEMBLIES BC ENERGY STEP CODE 4
• 8" REINFORCED CONCRETE 0.08
EFFECTIVE
AIR FILM 0.12 ASSEMBLY ILLUSTRATION IN SECTION DESCRIPTION FIRE TESTING RSI-VALUE STC
NUMBER RATING AGENCY RATING
1.33 RSI REQUIRED 6.53 (m2•K)/W
CEDAR SIDING WITH V-GROOVE ON CONCRETE WALL ROOF - ABOVE DECK INSULATION RSI VALUE
RSI VALUE
AIR FILM 0.03
AIR FILM 0.03
• 2 PLY SBS MODIFIED BITUMEN ROOFING MEMBRANE 0.03
• CEDAR SIDING WITH T+G V-GROOVE -
1.33 RSI • PROTECTION BOARD 0.05
• THERMALLY BROKEN Z-GIRTS @ 16" O.C 0.16 - BCBC 2018 6.93 RSI
1.0 HR - R7.57 R1 -
W4 • 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION • TAPERED RIGID INSULATION, LOW POINT MIN. 6" 1.0 HR APPENDIX R39.36
0.943
0.75 U (METRIC) • 7", 6.223 RSI RIGID INSULATION CONTINUOUS 6.223 D-2.3.4
• VP SELF ADHERED SHEATHING MEMBRANE - 0.14 U (METRIC)
• SELF ADHERED VAPOUR RETARDER MEMBRANE -
• 8" REINFORCED CONCRETE 0.08
• 5/8" D.FIR PLYWOOD SHEATHING 0.172
AIR FILM 0.12
• WOOD ROOF JOISTS (REFER TO STRUCTURAL) 0.16
1.33 RSI
• 2 LAYER 5/8" TYPE 'X' GYPSUM CEILING BOARD 0.079
CEDAR SIDING WITH V-GROOVE AND WOOD STUDS RSI VALUE AIR FILM 0.11

AIR FILM 0.03 6.93 RSI

• CEDAR SIDING WITH T+G V-GROOVE - SUSPENDED CONCRETE SLAB RSI VALUE
3.98 RSI
• 3/4 P.T PLYWOOD STRAPPING @ 16" O.C 0.16
1.0 HR - R22.6 - AIR FILM 0.03
W5 • 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943
0.25 U (METRIC) • 2 PLY SBS MODIFIED BITUMEN ROOFING MEMBRANE -
• VP SELF ADHERED SHEATHING MEMBRANE - BCBC 2018 6.87 RSI
-
1.0 HR -
• PROTECTION BOARD APPENDIX R39
• D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10
• MIN. 2" SLOPED RIGID INSULATION 1.8 D-2.1.1 0.14 U (METRIC)
• 2x6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55 #4 - 7855 East Saanich Rd.
• VAPOUR RETARDER MEMBRANE Saanichton V8M 2B4
• 6MIL POLYETHYLENE VAPOUR BARRIER -
R2 • REINFORCED SUSPENDED CONCRETE SLAB 0.08
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079 Phone: 250-656-2224
(REFER TO STRUCTURAL) Fax. 250-656-2279
*REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12
• 11" RIGID MINERAL WOOL INSULATION (R38) 4.93 email:
WALL SCHEDULE* 3.98 RSI
info@finlaysonbonet.ca
VERTICAL CORRUGATED METAL SIDING ON WOOD (ONLY REQUIRED TO EXTEND INSULATION
STUD WALL RSI VALUE
4x THE THICKNESS OF THE SLAB BEYOND WALLFACE)
AIR FILM 0.03 • GALVANIZED HAT TRACK EACH WAY FOR SUSPENDED -
• CORRUGATED METAL SIDING - SOFFIT AND SUPPORT INSULATION -
3.98 RSI
• THERMALLY BROKEN Z-GIRTS @ 16" O.C 0.16 -
R22.6 - • AIRCRAFT SUSPENSION CABLES @ 16" O.C.
W6 1.0 HR -
• 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943
0.25 U (METRIC) • PREFINISHED METAL SOFFIT WITH VENT STRIP -
• VP SELF ADHERED SHEATHING MEMBRANE - AIR FILM 0.03
• D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10 6.87 RSI
• 2x6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55 CORRIDOR FLOOR ASSEMBLY
2% 5TH FLOOR BALCONY ROOF
• 6MIL POLYETHYLENE VAPOUR BARRIER - • FLOOR FINISH / UNDERLAYMENT AS SPECIFIED
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079 • 1PREFINISHED
1/2" LIGHTWEIGHT
METALCONCRETE
FLASHING TOPPING
(REFER TO STRUCTURAL)
• 2 PLY SBS MODIFIED BITUMEN ROOFING MEMBRANE
*REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12 R3 • 5/8" PLYWOOD
TONGUE AND SHEATHING
GROOVE (REFER
PLYWOOD TO SHEATHING
STRUCTURAL) BCBC 2018
WALL SCHEDULE* 3.98 RSI • 2X8
WOOD FLOOR JOISTS
DECK JOISTS (REFER TO STRUCTURAL) - 1.0 HR APPENDIX - - 21.10.05 ISSUED FOR
• ACOUSTIC
STRAPPINGBATT INSULATION
@ 24" O.C. TO FILL CAVITY D-2.3.4 CONSTRUCTION
FIBRE CEMENT PANEL SIDING ON WOOD STUD WALL RSI VALUE • RESILIENT
1 LAYER 5/8"CHANNELS @ 24" O.C. EXTERIOR
TYPE 'X' DENSGLASS
•SHEATHING
1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD 21.05.25 ISSUED FOR TENDER
AIR FILM 0.03 • PREFINISHED METAL SOFFIT WITH VENT STRIP 21.04.23 ISSUED FOR BP
• FIBRE CEMENT PANEL SIDING -
3.98 RSI Rev Date Description
• 3/4" P.T PLYWOOD STRAPPING 16"O.C 0.16
W7
- - R22.6 - DECK ASSEMBLIES BC ENERGY STEP CODE 4 Checked SMB/KDS
• 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943 0.25 U (METRIC)
• VP SELF ADHERED SHEATHING MEMBRANE -
Drawn AV
EFFECTIVE
ASSEMBLY ILLUSTRATION IN SECTION DESCRIPTION FIRE TESTING RSI-VALUE STC
• D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10 NUMBER RATING AGENCY RATING Scale 1/4"=1'-0"
• 2x6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55 REQUIRED 6.53 (m2•K)/W Date
• 6MIL POLYETHYLENE VAPOUR BARRIER - RSI VALUE SEPT 05, 2021
CONCRETE DECK ASSEMBLY - 2ND LEVEL
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079
AIR FILM 0.03 Project Name
*REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12
WALL SCHEDULE* 3.98 RSI 2%
• CONCRETE PAVERS ON ADJUSTABLE PEDESTALS - SALISH SEA
• 2 PLY SBS MODIFIED BITUMEN ROOFING MEMBRANE - HOUSING
FIBRE CEMENT LAPPED SIDING ON WOOD STUD WALL RSI VALUE • PROTECTION BOARD -
6.87 RSI CENTRAL SAANICH RD.,
D1 • MIN. 2" SLOPED RIGID INSULATION 1.8 BCBC 2018 TSAWOUT FIRST NATION
AIR FILM 0.03
1.0 HR APPENDIX R39 -
• FIBRE CEMENT LAPPED SIDING - • VAPOUR RETARDER MEMBRANE Drawing Title
3.98 RSI D-2.1.1 0.14 U (METRIC)
• 3/4" P.T PLYWOOD STRAPPING @ 16" O.C 0.16 • REINFORCED CONCRETE SLAB (REFER TO 0.08
- - R22.6 -
W8 • 1 1/2" CAVITY ROCK MINERAL WOOL INSULATION 0.943 STRUCTURAL)
0.25 U (METRIC)
• VP SELF ADHERED SHEATHING MEMBRANE - • 8" MINERAL WOOL BATT INSULATION (R28) 4.93 CONSTRUCTION
• D.FIR PLYWOOD SHEATHING (REFER TO STRUCT.) 0.10 • GALVANIZED HAT TRACK EACH WAY FOR SUSPENDED ASSEMBLIES
• 2 x 6 SPF WOOD STUDS @ 16" O.C W/ R22 BATT 2.55 SOFFIT AND SUPPORT INSULATION -
• 6MIL POLYETHYLENE VAPOUR BARRIER - • AIRCRAFT SUSPENSION CABLES @ 16" O.C. -
• 5/8" TYPE 'X' GYPSUM WALLBOARD 0.079 • PREFINISHED METAL SOFFIT WITH VENT STRIP -
Drawing No.

A1.02
*REFER TO STRUCTURAL FOR SHEAR AIR FILM 0.12 AIR FILM 0.03
WALL SCHEDULE* 3.98 RSI
6.87 RSI
CORRUGATED METAL SIDING ON WOOD STUD WALL RSI VALUE Project No.
2% WOOD DECK ASSEMBLY - 3RD AND 4TH LEVEL
• VINYL DECKING WITH SMOOTH BACKING
19323
• 5/8" TONGUE AND GROOVE PLYWOOD SHEATHING BCBC 2018 © Copyright reserved. These plans and
APPENDIX designs are and at all times remain the
• WOOD DECK JOISTS (REFER TO STRUCTURAL) - 1.0 HR - - property of Finlayson Bonet Architecture to be
• STRAPPING @ 24" O.C. D-2.3.4 used for the project shown and may not be
D2 reproduced without written consent.
• 1 LAYER 5/8" TYPE 'X' DENSGLASS EXTERIOR
SHEATHING
• PREFINISHED METAL SOFFIT WITH VENT STRIP
2x6 ELEVATOR SHAFT ASSEMBLY

• 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD


• PLYWOOD SHEATHING (REFER TO STRUCTURAL)
• 2x6 WOOD STUDS @ 16" O.C. BC ENERGY STEP CODE 4
FLOOR ASSEMBLIES BC ENERGY STEP CODE 4 PARTITION ASSEMBLIES (REFER TO STRUCTURAL)
• ACOUSTICAL BATT INSULATION
EFFECTIVE • PLYWOOD SHEATHING (REFER TO STRUCTURAL) EFFECTIVE
ASSEMBLY FIRE TESTING STC ASSEMBLY ILLUSTRATION IN PLAN •DESCRIPTION
RESILIENT METAL CHANNELS @ 24" O.C. FIRE TESTING RSI-VALUE
STC
ILLUSTRATION IN SECTION DESCRIPTION RSI-VALUE
NUMBER RATING AGENCY RATING NUMBER • 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD RATING AGENCY RATING
REQUIRED 6.53 (m2•K)/W REQUIRED 3.89 (m2•K)/W
2x6 PARTITION SEPARATING GARDEN SHED
SLAB ON GRADE - PARKING AREA
INTERIOR
• 1 LAYER 5/8" CORRIDOR
TYPE 'X'PARTITION
GYPSUM WALLBOARD BCBC
F1 • BROOM AND EPOXY FINISH • 2x6 WOOD STUDS @ 16" O.C. 2018
- - - - - •(REFER
1 LAYER TYPE 'X' GYPSUM WALLBOARD 1.0 HR - -
• 4" REINFORCED CONCRETE SLAB ON GRADE P4 TO5/8"
STRUCTURAL) APPENDIX
(REFER TO STRUCTURAL) •• ACOUSTICAL
PLYWOOD SHEATHING (REFER TO STRUCTURAL)
BATT INSULATION D-2.3.4
• 10 MIL VAPOUR BARRIER MEMBRANE GARDEN SHED •• 2x4 STAGGERED WOOD STUDS ON
1 LAYER 5/8" TYPE 'X' GYPSUM 2 x 6 BASE AND TOP PLATES
WALLBOARD
• COMPACTED INORGANIC FILL (REFER TO STRUCTURAL FOR SPACING)
• BEARING SOIL • 1/2" PLYWOOD SHEATHING
• PLYWOOD SHEATHING (REFER TO STRUCTURAL)
• ACOUSTIC INSULATION TO FILL CAVITY
CONCRETE WALL WITH
SUSPENDED CONCRETE SLAB RSI VALUE • PLYWOOD SHEATHING (REFER TO STRUCTURAL)
INSULATED 2x4 FURRING ASSEMBLY
• SELF ADHERED VAPOUR PERMEABLE MEMBRANE
• FLOOR FINISH / UNDERLAYMENT AS SPECIFIED AIR FILM 0.16 • •RESILIENT METAL
5/8" TYPE 'X' CHANNELS
GYPSUM @ 24" O.C.
WALLBOARD
• REINFORCED SUSPENDED CONCRETE SLAB
• •21/2"
LAYERS 5/8" TYPE
GALVANIZED 'X' CHANNELS
HAT GYPSUM WALLBOARD
@ 16" O/C
0.10 6.93 RSI
1.0 HR BCBC 2018 • 8" CONCRETE WALL
(REFER TO STRUCTURAL) - NOTE:
• 1/2" AIR GAP
F2 APPENDIX R39.34 P5 1.0 HR - - -
• 11" RIGID MINERAL WOOL INSULATION (R38) D-2.1.1 *•REFER
2x4 WOODTO STRUCTURAL
STUDS @ 16" FOR
O.C SHEAR WALL SCHEDULE*
6.68 0.14 U (METRIC)
• GALVANIZED HAT TRACK EACH WAY FOR SUSPENDED • 5/8" TYPE 'X' GYPSUM WALLBOARD
-
SOFFIT AND SUPPORT INSULATION -
• AIRCRAFT SUSPENSION CABLES @ 16" O.C. -
• PREFINISHED METAL SOFFIT WITH VENT STRIP -
57 STC
AIR FILM 0.03 PARTY WALL PARTITION WITH 2x6 FURRING WALL
(BCBC
• 1 LAYER 1/2" GYPSUM WALLBOARD BCBC 2018
6.93 RSI P6 1.0 HR 2018 -
• 2 x 6 WOOD STUDS @ 16" O.C TABLE
2ND FLOOR UNIT APPENDIX A.9.10.3.1.
• P2 - PARTY WALL ASSEMBLY D-2.3.4 A
2ND FLOOR ASSEMBLY
W13A)
• FLOOR FINISH / UNDERLAYMENT AS SPECIFIED
• SUSPENDED REINFORCED CONCRETE SLAB 1.0 HR BCBC 2018 -
F3 (REFER TO STRUCTURAL) - APPENDIX - 57 STC
• DROPPED T-BAR CEILING D-2.1.1
PARTY WALL PARTITION WITH 2x4 FURRING WALL (BCBC
BCBC 2018
P7 • 1 LAYER 1/2" GYPSUM WALLBOARD 1.0 HR 2018 - TABLE
LOBBY APPENDIX
• 2x4 WOOD STUDS @ 16" O.C A.9.10.3.1.
FLOOR ASSEMBLY 68 STC D-2.3.4 A
• P2 - PARTY WALL ASSEMBLY W13A)
• FLOOR FINISH / UNDERLAYMENT AS SPECIFIED (BCBC
• 1 1/2" LIGHTWEIGHT CONCRETE TOPPING 2018
(REFER TO STRUCTURAL)
F4 • 5/8" PLYWOOD SHEATHING (REFER TO STRUCTURAL) - 1.0 HR UL L589 - TABLE PARTY WALL PARTITION WITH 2x4 FURRING WALL EACH SIDE 57 STC
• 2X10 FLOOR JOISTS A-9.10.3.1.
• ACOUSTIC BATT INSULATION TO FILL CAVITY B- • 1 LAYER 1/2" GYPSUM WALLBOARD BCBC
(BCBC
• RESILIENT CHANNELS @ 24" O.C. F21f) • 2x4 WOOD STUDS @ 16" O.C 1.0 HR 2018 -
2018
• 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD P8 APPENDIX
TABLE
• P2 - PARTY WALL ASSEMBLY D-2.3.4
A.9.10.3.1.
CANTILEVERED TJI FLOOR ASSEMBLY RSI VALUE A
• 2x4 WOOD STUDS @ 16" O.C W13A)
• FLOOR FINISH / UNDERLAYMENT AS SPECIFIED AIR FILM 0.16 • 1 LAYER 1/2" GYPSUM WALLBOARD
• 1 1/2" LIGHTWEIGHT CONCRETE TOPPING 0.015
(REFER TO STRUCTURAL) SUITE 56 STC
INTERIOR
• 5/8" PLYWOOD SHEATHING (REFER TO STRUCTURAL) 0.172 INTERIOR CORRIDOR PARTITION WITH 2x4 FURRING WALL
(BCBC
6.89 RSI BCBC
• 2X10 FLOOR JOISTS 2018
• 1 LAYER 1/2" GYPSUM WALLBOARD 2018
• 6" (R30) SPRAY APPLIED POLYURETHANE FOAM 6.26 1.0 HR UL L589 R39.1 - P9
• 2x4 WOOD STUDS @ 16" O.C
1.0 HR APPENDIX
- TABLE
F5 A-9.10.3.1.
• 1 LAYER 5/8" TYPE 'X' DENSGLASS GYPSUM SHEATHING 0.145 U (METRIC) D-2.3.4
0.10 A
• P1 - CORRIDOR WALL
• GALVANIZED FURRING CHANNELS @ 16" O.C. 0.15 W11a)
• FIBRE CEMENT PANEL SOFFIT WITH VENT STRIP - CORRIDOR
AIR FILM 0.03
SUITE
56 STC
INTERIOR CORRIDOR PARTITION WITH 2x6 FURRING WALL
6.89 RSI (BCBC
BCBC
2018
P10 • 1 LAYER 1/2" GYPSUM WALLBOARD 2018
SLAB ON GRADE - INSULATED RSI VALUE
• 2x6 WOOD STUDS @ 16" O.C
1.0 HR APPENDIX
- TABLE
A-9.10.3.1.
AIR FILM 0.16 D-2.3.4
A
• P1 - CORRIDOR WALL
• FLOOR FINISH / UNDERLAYMENT AS SPECIFIED 2.625 W11a)
2.76 RSI
• 4" REINFORCED CONCRETE SLAB ON GRADE 0.08 - - -
R15.7 CORRIDOR
F6 (REFER TO STRUCTURAL) - 0.36 U (METRIC)
• 3" RSI 2.625 (R15) RIGID INSULATION -
2x4 RATED PARTITION ASSEMBLY
• 6 MIL VAPOUR BARRIER MEMBRANE
• COMPACTED INORGANIC FILL • 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD
P11 • 2x4 WOOD STUDS @ 16" O.C. 1.0 HR UL 305 - -
• BEARING SOIL • MINERAL WOOL BATT INSULATION TO FILL CAVITY
2.76 RSI
• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD
CORRIDOR FLOOR ASSEMBLY
• FLOOR FINISH / UNDERLAYMENT AS SPECIFIED 2x6 RATED PARTITION ASSEMBLY
• 1 1/2" LIGHTWEIGHT CONCRETE TOPPING #4 - 7855 East Saanich Rd.
(REFER TO STRUCTURAL) • 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD Saanichton V8M 2B4
F7 • 5/8" PLYWOOD SHEATHING (REFER TO STRUCTURAL) - 1.0 HR UL L589 - -
• 2x6 WOOD STUDS @ 16" O.C.
• 2X8 FLOOR JOISTS P12 • MINERAL WOOL BATT INSULATION TO FILL CAVITY 1.0 HR UL 305 - - Phone: 250-656-2224
• ACOUSTIC BATT INSULATION TO FILL CAVITY • 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD Fax. 250-656-2279
• RESILIENT CHANNELS @ 24" O.C. email:
• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD **REFER TO STRUCTURAL FOR SHEER WALL LOCATIONS** info@finlaysonbonet.ca

MECHANICAL SHAFT WALL


SHAFT UL 415
BC ENERGY STEP CODE 4 1.0 HR - -
PARTITION ASSEMBLIES P13
• 1" SHAFTLINER SYSTEM
• CT STUDS "A"
ASSEMBLY FIRE TESTING EFFECTIVE STC • 2 LAYERS OF 5/8" TYPE 'X' GYPSUM WALLBOARD
NUMBER ILLUSTRATION IN PLAN DESCRIPTION RATING AGENCY
RSI-VALUE
RATING
REQUIRED 3.89 (m2•K)/W INTERIOR 2x6 LOAD-BEARING PARTITION ASSEMBLY

INTERIOR CORRIDOR PARTITION • 5/8" TYPE 'X' GYPSUM WALLBOARD


• 2x6 WOOD STUDS @ 16" O.C.
P14 • PIPE INSULATION @ PLUMBING STACK + RAIN WATER LEADERS - - - -
• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD
• PLYWOOD SHEATHING (REFER TO STRUCTURAL) 56 STC • ACOUSTIC INSULATION TO FILL CAVITY @ BEDROOM AND
• 2x4 STAGGERED WOOD STUDS ON 2 x 6 BASE AND TOP PLATES WASHROOM SEPARATIONS
SUITE • 5/8" TYPE 'X' GYPSUM WALLBOARD
(REFER TO STRUCTURAL FOR SPACING) (BCBC
• PLYWOOD SHEATHING (REFER TO STRUCTURAL) BCBC 2018 2018 21.10.05 ISSUED FOR
P1 • ACOUSTIC INSULATION TO FILL CAVITY 1.0 HR APPENDIX - TABLE CONSTRUCTION
• PLYWOOD SHEATHING (REFER TO STRUCTURAL) D-2.3.4 A-9.10.3.1. INTERIOR 2x4 LOAD-BEARING PARTITION ASSEMBLY 21.05.25 ISSUED FOR TENDER
• SELF ADHERED VAPOUR PERMEABLE MEMBRANE A
• RESILIENT METAL CHANNELS @ 24" O.C. W11a) • 5/8" TYPE 'X' GYPSUM WALLBOARD 21.04.23 ISSUED FOR BP
• 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD P15 • 2x4 WOOD STUDS @ 16" O.C. - - - -
• ACOUSTIC INSULATION TO FILL CAVITY @ BEDROOM AND Rev Date Description
CORRIDOR WASHROOM SEPARATIONS
NOTE: Checked SMB/KDS
* REFER TO STRUCTURAL FOR SHEAR WALL SCHEDULE* • 5/8" TYPE 'X' GYPSUM WALLBOARD
Drawn AV
INTERIOR 2x6 PARTITION ASSEMBLY Scale 1/4"=1'-0"
PARTY WALL PARTITION
• 1/2" GYPSUM WALLBOARD Date
• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD
• SELF ADHERED VAPOUR PERMEABLE MEMBRANE P16
• 2x6 WOOD STUDS @ 16" O.C.
- - - - SEPT 05, 2021
• PIPE INSULATION @ PLUMBING STACK + RAIN WATER LEADERS
• PLYWOOD SHEATHING (REFER TO STRUCTURAL) • ACOUSTIC INSULATION TO FILL CAVITY @ BEDROOM AND
57 STC
• WOOD STUDS @ 16" O.C. (REFER TO STRUCTURAL) WASHROOM SEPARATIONS Project Name
• ACOUSTIC BATT INSULATION BCBC • 1/2" GYPSUM WALLBOARD SALISH SEA
(BCBC
P2 • 1" AIR SPACE 1.0 HR 2018 -
2018
• ACOUSTIC BATT INSULATION APPENDIX
TABLE
HOUSING
• WOOD STUDS @ 16" O.C. (REFER TO STRUCTURAL) D-2.3.4 INTERIOR 2x4 PARTITION
A.9.10.3.1. CENTRAL SAANICH RD.,
• PLYWOOD SHEATHING (REFER TO STRUCTURAL)
A • 1/2" GYPSUM WALLBOARD TSAWOUT FIRST NATION
• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD
W13A) • 2x4 WOOD STUDS @ 16" O.C.
P17 - - - - Drawing Title
NOTE: • ACOUSTIC INSULATION TO FILL CAVITY @ BEDROOM AND
* REFER TO STRUCTURAL FOR SHEAR WALL SCHEDULE* WASHROOM SEPARATIONS
• 1/2" GYPSUM WALLBOARD
2x6 ELEVATOR SHAFT ASSEMBLY CONSTRUCTION
ELEVATOR SHAFT 58 STC ASSEMBLIES
• 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD
• PLYWOOD SHEATHING (REFER TO STRUCTURAL) BCBC (BCBC
• 2x6 WOOD STUDS @ 16" O.C. 2018 2018
P3 (REFER TO STRUCTURAL)
1.0 HR APPENDIX
-
TABLE
• ACOUSTICAL BATT INSULATION D-2.3.4 A.9.10.3.1.
• PLYWOOD SHEATHING (REFER TO STRUCTURAL) A Drawing No.
CORRIDOR • RESILIENT METAL CHANNELS @ 24" O.C.
• 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD
W6b)
A1.03
2x6 PARTITION SEPARATING GARDEN SHED Project No.

• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD 19323


• 2x6 WOOD STUDS @ 16" O.C. © Copyright reserved. These plans and
(REFER TO STRUCTURAL) designs are and at all times remain the
property of Finlayson Bonet Architecture to be
• ACOUSTICAL BATT INSULATION used for the project shown and may not be
• 1 LAYER 5/8" TYPE 'X' GYPSUM WALLBOARD reproduced without written consent.
• 1/2" PLYWOOD SHEATHING
A B C D 1 E F 2 G
A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.
1'-0" 23'-0" 2'-4" 1'-0" 16'-8" 6"6" 19'-6" 6'-0" 1'-0" 25'-0" 1'-0" 2. ALL ELEVATIONS ARE IN GEODETIC
METERS UNLESS NOTES OTHERWISE.
1 3. ALL DIMENSIONS ARE TO FACE OF
CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
4'-0"

4'-0"
CENTRELINE OF DOORS AND
WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT

7'-0"
NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
COORDINATING REGISTERED
3'-0"

3'-0"
U/S OF FOOTING U/S OF FOOTING U/S OF FOOTING U/S OF FOOTING
PROFESSIONAL OF ANY
18.54m 18.54m 18.54m 18.54m DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
U/S OF FOOTING
2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.
18.54m
5. DO NOT SCALE THESE DRAWINGS.
FINLAYSON BONET ARCHITECTURE
LTD. IS NOT RESPONSIBLE FOR
5'-9"

5'-9"

5'-9"
ISSUES THAT ARISE FROM A
FAILURE TO COMPLY.

6. THESE DRAWINGS ARE TO BE READ


IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
DRAWINGS AND SPECIFICATIONS,
ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
DRAWINGS AND SPECIFICATIONS,
INTERIOR DESIGN DRAWINGS AND
SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
TO THE CONSTRUCTION OF THIS
PROJECT.

7. CONTRACTOR TO OBTAIN ALL


NECESSARY PERMITS, BYLAW
APPROVALS, AND OBSERVE ALL
16'-4"

16'-4"
REQUIRED SAFETY REGULATIONS
THROUGHOUT THE COURSE OF
CONSTRUCTION
SYMBOL LEGEND
FD FLOOR DRAIN
8'-3" 1'-0" 23'-0" 2'-4" 1'-0" 16'-8" 6"6" 19'-6" 6'-0" 1'-0" 25'-0" 1'-0" 9'-9"
ROOF / DECK DRAIN

XX ASSEMBLY MARKER

PROPERTY LINE
[33.83 M]
GLAZING TYPE (REFER TO
GX WINDOW SCHEDULE)

4 DOOR TYPE (REFER TO DOOR


DXXX
1'-11"

1'-11"
SCHEDULE)

X
SECTION MARKER
AXXX
3'-0"

3'-0"
X DETAIL MARKER

7'-8"
U/S OF FOOTING U/S OF FOOTING U/S OF FOOTING U/S OF FOOTING U/S OF FOOTING AXXX
18.54m 18.54m 18.54m 18.54m 18.54m INTERIOR ELEVATION MARKER
X
XX EXISTING ELEVATION MARKER
2'-9"

2'-9"
X .X
NEW ELEVATION MARKER
5 X.XXXm

H2O VAULT
5'-0"

5'-0"
HATCHED WALL INDICATED
8'-3" 8'-11" 5'-9" 9'-4" 1" 20'-5" SHEAR WALL (REFER TO STRUCT.)
HATCHED WALL INDICATED LOAD
BEARING WALL (REFER TO

82'-11"
STRUCT.)
6

26" DEEP RAFT FOOTING, REFER TO


STRUCTURAL 26" DEEP RAFT FOOTING, REFER TO STRUCTURAL
7'-3"

7'-3"

7'-3"
7'-3"
U/S OF FOOTING U/S OF FOOTING U/S OF FOOTING
17.58m 17.58m 17.58m

7
8"

8"
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4

°
.6
5'-9" 3

86
5'-0"
A4.00 Phone: 250-656-2224
PIT ELEVATION Fax. 250-656-2279
17.78m email:
9'-5"

info@finlaysonbonet.ca
8'-9"

9'-5"

11'-5"

11'-10"
14'-1"

16'-8" 10" 9'-6" 3'-4" 1'-8" 4'-9"

16'-9"
32" DEEP RAFT FOOTING,
REFER TO STRUCTURAL
U/S OF FOOTING U/S OF FOOTING
17.43m U/S OF FOOTING
18.54m 18.54m

11'-1"

1'-8"

10"
5'-10"
7'-4"

U/S OF FOOTING
18.54m 21.10.05 ISSUED FOR
U/S OF FOOTING

4'-1"
3'-8"
CONSTRUCTION
18.54m
2'-0"

21.05.25 ISSUED FOR TENDER


10"

21.04.23 ISSUED FOR B.P.


9
Rev Date Description
Checked SMB/KDS
Drawn AV
21'-6" 2'-0" 6" 14'-2" 10" 5'-6" 11'-0" 10" 8'-2" 10" 5'-2" 16'-8" 10" 9'-6" 4'-2" 1'-8" 3'-11"
Scale 1/4"=1'-0"

8'-3"

8'-3"
Date
9'-5"

9'-5"

9'-5"
OCT 05, 2021
10" 4'-2" 5'-9" 10"
Project Name
MAIN FLOOR CONCRETE SLAB ON GRADE, REFER TO U/S OF FOOTING U/S OF FOOTING
STRUCTURAL 18.54m 18.54m SALISH SEA
HOUSING

4" 10"
1'-2"
7583 CENTRAL SAANICH RD.,
10 TSAWOUT FIRST NATION

6"
8"

Drawing Title
MAIN FLOOR CONCRETE SLAB, 2'-3"
REFER TO STRUCTURAL

FOUNDATION
6'-5"

7'-9"
PLAN

7'-3"
U/S OF FOOTING
4'-10"

17.58m

U/S OF FOOTING MAIN FLOOR CONCRETE SLAB, REFER TO STRUCTURAL


17.58m U/S OF FOOTING
18.54m Drawing No.

A2.00
8"

8"

11

10" 2'-2 1/4"


1'-7"
26" DEEP RAFT FOOTING,
REFER TO STRUCTURAL 26" DEEP RAFT FOOTING, REFER TO U/S OF FOOTING U/S OF FOOTING J
su u n e N
Project No.

is 1
nr 2
ns 2
STRUCTURAL

e
su u n e
18.54m et 1
18.54m
19323

J
2'-0"
2'-4" 2'-8" 1'-8" 4'-4" March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
3'-3" 5'-0" 6'-7" 3'-4" 12'-7" 1'-6" 20'-6" 20'-0" 10" 5'-2" 16'-9" 10" 9'-5" 4'-2" 1'-8" 3'-11" D
su e c
reproduced without written consent.

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C 3 D 1 E F 2 G
A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
12 11 4 3 2 1. ALL DIMENSIONS ARE IN FEET AND
14 13 SMALL CAR SMALL CAR 10 9 8 7 6 5 SMALL CAR SMALL CAR 1 INCHES UNLESS NOTED OTHERWISE.
SMALL CAR 2. ALL ELEVATIONS ARE IN GEODETIC
METERS UNLESS NOTES OTHERWISE.
LINE OF BALCONY ABOVE 1 3. ALL DIMENSIONS ARE TO FACE OF
CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
4'-0"

LINE OF BUILDING ABOVE CENTRELINE OF DOORS AND


WINDOWS, AND TO FACE OF ANY
LINE OF SLAB ABOVE OTHER STRUCTURAL ELEMENT

7'-0"
NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
COORDINATING REGISTERED
3'-0"

PROFESSIONAL OF ANY
DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.

5. DO NOT SCALE THESE DRAWINGS.


FINLAYSON BONET ARCHITECTURE
LTD. IS NOT RESPONSIBLE FOR

5'-9"
ISSUES THAT ARISE FROM A
FAILURE TO COMPLY.

6. THESE DRAWINGS ARE TO BE READ


LINE OF BUILDING ABOVE IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
DRAWINGS AND SPECIFICATIONS,
LINE OF WALL ABOVE ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
DRAWINGS AND SPECIFICATIONS,
INTERIOR DESIGN DRAWINGS AND
SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
22'-1"

TO THE CONSTRUCTION OF THIS


LINE OF SLAB ABOVE PROJECT.

PARKING 7. CONTRACTOR TO OBTAIN ALL


NECESSARY PERMITS, BYLAW
APPROVALS, AND OBSERVE ALL

16'-4"
REQUIRED SAFETY REGULATIONS
THROUGHOUT THE COURSE OF
CONSTRUCTION
SYMBOL LEGEND
FD FLOOR DRAIN
8'-3" 1'-0" 7'-11" 5'-9" 9'-5" 2'-4" 1'-0" 16'-8" 6"6" 19'-6" 6'-0" 1'-0" 25'-0" 1'-0" 9'-9" 2'-2 3/4"
ROOF / DECK DRAIN

XX ASSEMBLY MARKER

PROPERTY LINE
[33.83 M]
GLAZING TYPE (REFER TO
GX WINDOW SCHEDULE)

4 DOOR TYPE (REFER TO DOOR


DXXX
1'-11"

SCHEDULE)

X
SECTION MARKER
AXXX
3'-0"

X DETAIL MARKER

7'-8"
AXXX

X INTERIOR ELEVATION MARKER

LINE OF EXTERIOR WALL ABOVE XX EXISTING ELEVATION MARKER


2'-9"

X .X
NEW ELEVATION MARKER
5 X.XXXm

H2O VAULT
LINE OF WALL ABOVE
SMALL CAR SMALL CAR SMALL CAR
SMALL CAR
5'-0"

5'-0"
HATCHED WALL INDICATED
26 27 28 SHEAR WALL (REFER TO STRUCT.)
17 18 19 20 21 22 23 24 25 29 HATCHED WALL INDICATED LOAD
8'-3" 8'-11" 5'-9" 9'-4" 1" 20'-5" 20'-0" 10" BEARING WALL (REFER TO

82'-11"
STRUCT.)
6
2'-8" 5'-7" 2'-1" 3'-8"
2'-6"

W9
LINE OF SLAB ABOVE
D102
7'-6 1/4" 7'-1" 17'-5 3/4" 4'-4 3/4" 4'-0 1/2"

7'-3"
2 EXIT
A5.00
4'-9"

VESTIBULE 6
W3 W9 102 W9 A6.03
G5 W2 W2 W2 W1

7
8"

D103b #4 - 7855 East Saanich Rd.


3'-5"

°
.6
Saanichton V8M 2B4

86
GROUND FLOOR AREA
BABY CHANGE

EXIT 2370 SQ. FT. 1 2 3 4 5 6 3


TABLE

4'-8 1/4"

D100 P12 1HR F.R.R CORRIDOR M.F.E. 19.0M D112b A4.00 Phone: 250-656-2224
ST-1 108 Fax. 250-656-2279
100 P5 ELEVATOR P16 email:
9'-5"

8'-1"

ACCESSIBLE info@finlaysonbonet.ca
8'-5 1/4"
8'-9"

P17 P17 P11 P12


P5
P5 WASHROOM P11
W12
5'-9" 107
UP D110b D111 21'-4 1/8"
1HR F.R.R
JANITOR

16'-9"
W3
111 2
1HR F.R.R A5.01
8"

MOP
D107 P12 SINK
10'-3 3/4"

W5 P5 P17
3'-10"

P5 D109b P12
1HR F.R.R 11 10 9 8 7
EXIT EXIT 1HR F.R.R
D103a 1HR F.R.R
VESTIBULE LOBBY CORRIDOR
7'-4"

D101 P17 CLIENT


101 103 108 SERVICES AREA 3'-11 1/4" P5
AMENITY AREA
3'-0" 2'-0" 6'-3" 2'-8" TOP OF MAIN FLOOR
109 [1.2m] 112 21.10.05 ISSUED FOR

27'-2"
19.00m 1HR F.R.R CONSTRUCTION
3'-6"

12 13 14 15 16
5
P15 21.05.25 ISSUED FOR TENDER
P11 MAILBOX P11 0HR F.R.R A6.03 D109a
21.04.23 ISSUED FOR B.P.
9
8"

D108 Rev Date Description


G1 G1 G1
D105 D106 W6 W3 W6 Checked SMB/KDS
W4 1HR F.R.R
LINE OF WALL ABOVE W12 BIKE STORAGE W10
5'-0"

1HR F.R.R Drawn AV


114
6'-7"

ELECTRICAL MECHANICAL COMMON W6


Scale 1/4"=1'-0"
LINE OF SLAB ABOVE
104 105 LAUNDRY Date
9'-5"

9'-5"
106 OCT 05, 2021
8'-9"

P4 P11 UP
ST-2
D110a EXIT 110 1HR F.R.R
Project Name

P4 21 20 19 18 17 SALISH SEA
2'-10"

RD HOUSING
D104 3
10"

W5 7583 CENTRAL SAANICH RD.,


A6.03
10 TSAWOUT FIRST NATION
8"

8"

W6 GARDEN STORAGE Drawing Title


22 23 24 25 26
2'-9"

OUTDOOR AMENITY SPACE 113 2


W5 (REFER TO LANDSCAPING) A6.03 W12
W4 4 D113 D112a
5'-3"
A6.03
G1 G1
MAIN FLOOR
VICE
6'-5"

6'-5"

7'-9"
2'-5"
W6 LINE OF WALL ABOVE PLAN
3'-10" 7'-7" 6'-5" 2'-8" 3'-4" 5'-3" 2'-9" 4'-0" 6'-0" 8" 6'-3" 6'-3" 3'-7"
5'-0"

D114
3'-3" 5'-0" LINE6'-7"
OF WALL ABOVE 6'-3" 11'-2" 14'-7" 5'-11" 11'-4" 8'-8"

LINE OF WALL ABOVE OUTDOOR COVERED PATIO Drawing No.

A2.01
8"

8"

11

6'-2"
W10
J N
LINE OF SLAB ABOVE LINE OF WALL ABOVE su u n e Project No.

is 1
28 27

nr 2
ns 2

e
su u n e
et 1
4'-4"

19323

J
LINE OF SLAB ABOVE LINE OF SLAB ABOVE
March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
property of Finlayson Bonet Architecture to be
W10 used for the project shown and may not be
1
3'-3" 2'-4" 2'-8" 6'-7" 3'-4" 12'-7" 1'-6" 20'-6" 20'-0" 10" 10" 4'-4" 16'-9" 10" 9'-5" 4'-2" 1'-8" 3'-11" 2'-2 3/4" D reproduced without written consent.
A6.03 su e c

et 1
EMENT

ns . 2
nr . 2

su e c
S is 1
e

D
11'-11 1/2"
A B C 3 D 1 E F 2 G
TYPICAL 7
A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0" 9'-7"
A6.02
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.
8x8 CONCRETE PILASTER
8x8 CONCRETE PILASTER 2. ALL ELEVATIONS ARE IN GEODETIC

7" 8"
METERS UNLESS NOTES OTHERWISE.
11'-6 1/2" 8" 11'-1 1/2" 8" 10'-2" 8" 9'-8" 13'-6" 8" 5'-10" 1 3. ALL DIMENSIONS ARE TO FACE OF
OVERFLOW SCUPPER OVERFLOW SCUPPER CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,

3'-9"

3'-9"

3'-9"
CENTRELINE OF DOORS AND
T.O. DRAIN T.O. CONC. CURB 6" CONCRETE CURB EDGE OF CONCRETE SLAB WINDOWS, AND TO FACE OF ANY
EDGE OF EDGE OF CONCRETE SLAB
T.O. CONC. 22.45m 22.65m OTHER STRUCTURAL ELEMENT
CONCRETE SLAB
7'-0"

7'-0"
7'-0"
22.51m NOT LISTED.

6"
4. CONTRACTOR TO VERIFY ALL
DIMENSIONS ON SITE AND INFORM

3'-3"

3'-3"
CONCRETE COORDINATING REGISTERED

2'-9"
T.O. CONC. CURB
COLUMN BELOW PROFESSIONAL OF ANY
22.65m 8x8 CONCRETE PILASTER DISCREPANCIES PRIOR TO
T.O. DRAIN
UNDERTAKING THE PORTION OF
2

2% SLOPE

2% SLOPE
22.45m WORK WHICH IS IN REFERENCE TO
T.O. DRAIN

8" 9"
ANY DISCREPANCY.
22.45m
CONCRETE CONCRETE

3'-9"
5. DO NOT SCALE THESE DRAWINGS.
COLUMN BELOW COLUMN BELOW T.O. CONC. CURB FINLAYSON BONET ARCHITECTURE
8x8 CONCRETE PILASTER LTD. IS NOT RESPONSIBLE FOR
5'-9"

5'-9"

5'-9"
5'-9"
T.O. CONC. 22.65m
W ISSUES THAT ARISE FROM A

4'-5"
22.51m FAILURE TO COMPLY.

6" 1'-6" 6"


6. THESE DRAWINGS ARE TO BE READ
T.O. CONC. IN CONJUNCTION WITH ALL
22.51m ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND

6"
SPECIFICATIONS, MECHANICAL
EDGE OF DRAWINGS AND SPECIFICATIONS,
T.O. CONC. CURB CONCRETE SLAB ELECTRICAL DRAWINGS AND
22.65m SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
DRAWINGS AND SPECIFICATIONS,
6" 10'-2" 8" 23'-2" 8" 11'-11" 6" 26'-6" INTERIOR DESIGN DRAWINGS AND
W SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
RD TO THE CONSTRUCTION OF THIS
PROJECT.

11'-10"
SINK
7. CONTRACTOR TO OBTAIN ALL
NECESSARY PERMITS, BYLAW
EDGE OF 6 SIMILAR APPROVALS, AND OBSERVE ALL
16'-4"

DW SINK

16'-4"
16'-4"
15'-10"

CONCRETE SLAB REQUIRED SAFETY REGULATIONS


DW SINK FD A6.02 THROUGHOUT THE COURSE OF
CONSTRUCTION
SAN

SHWR
TUB

LINE OF WOOD FRAMED SYMBOL LEGEND


SINK

WALL ABOVE SAN FD FLOOR DRAIN


RD LINE OF WOOD FRAMED
WALL ABOVE
ROOF / DECK DRAIN

6"
XX ASSEMBLY MARKER

PROPERTY LINE
[33.83 M]
LINE OF WOOD FRAMED

3'-6"
TUB GLAZING TYPE (REFER TO
WALL ABOVE
SINK DW W GX WINDOW SCHEDULE)
W
4 DOOR TYPE (REFER TO DOOR
DXXX SCHEDULE)
SAN
CONCRETE COLUMN BELOW CONCRETE COLUMN BELOW RD CONCRETE COLUMN BELOW 2% SLOPE
X
SECTION MARKER
AXXX
CONCRETE COLUMN BELOW
X DETAIL MARKER
7'-8"

7'-8"

7'-8"
7'-8"
AXXX
SINK
X INTERIOR ELEVATION MARKER

SAN

TUB
T.O. CONC. CURB

SINK
LINE OF WOOD FRAMED 22.65m 1 XX EXISTING ELEVATION MARKER
WALL ABOVE X .X
LINE OF WOOD FRAMED A6.04

21'-4"
WALL ABOVE NEW ELEVATION MARKER
5 X.XXXm

H2O VAULT
5'-0"

5'-0"

5'-0"
5'-0"
EDGE OF HATCHED WALL INDICATED
8'-3" CONCRETE SLAB SHEAR WALL (REFER TO STRUCT.)
9'-0" RD
LINE OF WALL ABOVE EDGE OF CONCRETE SLAB
8'-11" HATCHED WALL INDICATED LOAD
4 1/2"

BEARING WALL (REFER TO


STRUCT.)
6
1'-2"

7 TYPICAL
SINK

LINE OF WALL BELOW


2% SLOPE A6.02
LINE OF WOOD FRAMED
TUB

2'-2" 5'-1 1/2"

5'-2"

5'-2"
SAN

WALL ABOVE 11'-8" 3'-10" 4'-6" 5'-4" 8" 1'-4" 23'-8" 6" 1'-6" 2'-10" 8" 6'-1"
7'-3"

7'-3"

7'-3"
7'-3"
MOP 8x8 CONCRETE
24'-0" SINK PILASTER
LINE OF WOOD FRAMED

1'-7" 6"

1'-5" 8"
1'-3" 2'-8" 5'-0" 15'-0" RD WALL ABOVE
OVERFLOW SCUPPER
7

1'-2"
8"

8"

CONCRETE W DW SINK #4 - 7855 East Saanich Rd.


WALL BELOW
Saanichton V8M 2B4

2'-4"
CONCRETE 3
4'-5"

8" 5'-9" 8" WALL BELOW


A4.00 Phone: 250-656-2224

11'-0"
Fax. 250-656-2279

1'-5"
T.O. DRAIN

8'-4"
8'-6"
8'-11"

EDGE OF CONCRETE SLAB email:


22.45m info@finlaysonbonet.ca
8'-9"

EDGE OF
CONCRETE SLAB
3'-10"

EDGE OF CONCRETE SLAB SINK DW LINE OF WOOD FRAMED 8x8 CONCRETE


WALL ABOVE T.O. CONC.
PILASTER

16'-9"
16'-9"
22.51m

8"
6"
2'-10" 8"

13'-3"
8"

T.O. CONC. CURB

12'-2"
TUB T.O. CONC.
TUB 22.65m
22.51m
T.O. CONC. CURB
22.65m
7'-11"

7'-11"

7'-9"

7'-9"
6'-2"

SAN CONCRETE SAN


CONCRETE WALL BELOW
CONCRETE COLUMN BELOW
21.10.05 ISSUED FOR
COLUMN BELOW T.O. CONC. CURB CONSTRUCTION
22.65m 21.05.25 ISSUED FOR TENDER
SINK SINK 21.04.23 ISSUED FOR B.P.
6"

9
2% SLOPE

2% SLOPE

T.O. CONC.
RD Rev Date Description
22.51m
2'-6"

DW SINK DW SINK
Checked SMB/KDS
EDGE OF
4'-4"

CONCRETE CONCRETE T.O. CONC. CURB Drawn AV


SLAB WALL BELOW T.O. DRAIN RD 22.65m
22.45m Scale 1/4"=1'-0"
W EDGE OF CONCRETE SLAB
W Date
9'-5"

9'-5"

9'-5"
9'-5"
2% SLOPE
8"

OVERFLOW SCUPPER
OCT 05, 2021
4" CONCRETE CURB EDGE OF
6'-11"

T.O. CONC. CURB CONCRETE SLAB T.O. DRAIN


TYPICAL 7 Project Name
22.65m 22.40m
A6.02 SALISH SEA
4'-5"

1'-0" 8" 9'-3" 8" 8'-5" CONCRETE COLUMN BELOW


8x8 CONCRETE PILASTER HOUSING
7583 CENTRAL SAANICH RD.,
T.O. DRAIN 10 TSAWOUT FIRST NATION
22.90m Drawing Title
LINE OF WALL BELOW CONCRETE
2'-8"

COLUMN BELOW
6" CONCRETE CURB

8'-3" 10'-4" 13'-8" 1'-0" LEVEL 2 SLAB

7'-3"
7'-9"

7'-9"

7'-9"
7'-9"
PLAN
CONCRETE
5'-1"

EDGE OF CONCRETE STAB CONCRETE


COLUMN BELOW T.O. CONC. CURB T.O. CONC. CURB LINE OF WALL BELOW
2% SLOPE COLUMN BELOW
22.65m 22.65m
Drawing No.

A2.02

6"
11
1'-0"

T.O. CONC. 8" T.O. CONC. 12'-0" 8" 18'-2" 1'-6" 12'-0"
22.51m OVERFLOW SCUPPER
22.51m J N

3'-1"
su u n e Project No.
8" 12'-4" 8" 1'-0"

is 1
3'-7"

nr 2
ns 2
T.O. CONC. CURB T.O. DRAIN CONCRETE

e
su u n e
et 1
4'-4"

4'-4"

OVERFLOW SCUPPER T.O. CONC.


19323

J
EDGE OF 22.65m 22.45m COLUMN BELOW
T.O. CONC. CURB T.O. DRAIN T.O. DRAIN 22.51m
CONCRETE SLAB © Copyright reserved. These plans and
8x8 CONCRETE PILASTER 22.45m

6"
22.65m 22.60m 8x8 CONCRETE PILASTER
March 21 W
sunset
March 21
E sunrise designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
8x8 CONCRETE PILASTER 8x8 CONCRETE PILASTER CONCRETE
8"

8"

D reproduced without written consent.


su e c
EDGE OF CONCRETE SLAB

et 1
COLUMN BELOW

ns . 2
nr . 2

su e c
S is 1
e

D
A B C D E F G
3 1 2
A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
11'-10" 11'-10 1/2" 3 1/2" 10'-6" 4" 9'-8" 13'-6" 4" 6'-2" 8'-0" 19'-0" INCHES UNLESS NOTED OTHERWISE.
W6
G3a 2. ALL ELEVATIONS ARE IN GEODETIC
8"

BALCONY METERS UNLESS NOTES OTHERWISE.


8"

6'-0" 8'-0" 5'-2" 4'-10"


1 3. ALL DIMENSIONS ARE TO FACE OF
8 TYPICAL CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
A6.02
3'-9"

3'-9"
CENTRELINE OF DOORS AND
W5 OVERFLOW SCUPPER W6 WINDOWS, AND TO FACE OF ANY
G3a G4 OVERFLOW SCUPPER OTHER STRUCTURAL ELEMENT

6'-9"

7'-0"
NOT LISTED.
D201b

2'-3 1/2"
4. CONTRACTOR TO VERIFY ALL
BALCONY DIMENSIONS ON SITE AND INFORM
3'-3"

3'-3"
G3a COORDINATING REGISTERED
PROFESSIONAL OF ANY

11 1/2"
P15 P17 DISCREPANCIES PRIOR TO
W5 P17
UNDERTAKING THE PORTION OF
2

3"
2% SLOPE

2% SLOPE
WORK WHICH IS IN REFERENCE TO

1'-1"
3'-6" D205-4 ANY DISCREPANCY.
P16
ROOF

3'-9"
5. DO NOT SCALE THESE DRAWINGS.
BALCONY AREA W7 FINLAYSON BONET ARCHITECTURE
3'-6" 4'-8" 8'-0" 10'-7" 5'-8" 5'-6" 6'-2" 2'-5" LTD. IS NOT RESPONSIBLE FOR
5'-9"

5'-9"
4'-8 1/2"
G7 D205-3
STORAGE P17 ISSUES THAT ARISE FROM A
LAUNDRY FAILURE TO COMPLY.
5 adjustable

3'-0"
D205b wire shelves P12 W6
W8 W D

2'-0"
medicine 6. THESE DRAWINGS ARE TO BE READ
G6 G3a G3 IN CONJUNCTION WITH ALL
cabinet P15 ARCHITECTURAL SPECIFICATIONS,
D203b 3 STRUCTURAL DRAWINGS AND
D201-3 P15 D205-2 SPECIFICATIONS, MECHANICAL
D205-5 DRAWINGS AND SPECIFICATIONS,

5'-0"
P17 ELECTRICAL DRAWINGS AND
fold down SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE

6'-0"
swivel
ironing board DRAWINGS AND SPECIFICATIONS,

1'-0"
W5 D P15 INTERIOR DESIGN DRAWINGS AND
D205-1
BR. CL. UNIT 205 SPECIFICATIONS AND ANY OTHER
P17 1 shelf 3 BEDROOM CONSULTANT DEEMED PERTINENT
W ACCESSIBLE 1'-0" LINEN TO THE CONSTRUCTION OF THIS
P17 CHAIR RAIL RD P17 P17 P17 G3
1,046 SQ.FT 5 shelves PROJECT.

3'-0"
TV.
open 7. CONTRACTOR TO OBTAIN ALL
NECESSARY PERMITS, BYLAW
D201-2 below

10"
APPROVALS, AND OBSERVE ALL
16'-4"

16'-4"
P17 P17 CHAIR RAIL REQUIRED SAFETY REGULATIONS
P16
4'-0" THROUGHOUT THE COURSE OF
FD

2'-0"
P6 CONSTRUCTION

6'-10"
1HR F.R.R 1HR F.R.R
LN P15 DW
mountable
SYMBOL LEGEND
P17 FD
5 shelves 2'-9" curb FLOOR DRAIN
P15 P15 P2 FD
RD P2

10"
W6
UNIT 201 WAINSCOTING D203-4 D203-3 PTRY ROOF / DECK DRAIN
30" RANGE
2 BEDROOM

2'-0"
P12 HOOD VENT
P15 1HR F.R.R

3"
768 SQ.FT / MICRO. UNIT 203 fold down ASSEMBLY MARKER

3 '-
D201-1 XX
swivel DW

PROPERTY LINE
2 BEDROOM P6 P2
ironing board

[33.83 M]
1HR F.R.R

3'-6"
752 SQ.FT 2'-9"

10"
GLAZING TYPE (REFER TO
P6 GX
30" REF. D WINDOW SCHEDULE)
W open

2'-0"
P17 P6 below
W 4

5'-0"
fold down LN 30" RANGE DOOR TYPE (REFER TO DOOR
4"

DW 5 shelves D HOOD VENT G3a


PTRY ironing board P17 P17
DXXX SCHEDULE)
G3 P15 P17 / MICRO.
1'-0" 2'-9" RD STORAGE D203-1 2% SLOPE
STORAGE 5 adjustable
X
SECTION MARKER
5 adjustable wire shelves
AXXX
wire shelves P17 P17 P2 30" REF. P17
X DETAIL MARKER
7'-8"

7'-8"
P17
7'-4"

AXXX
P15 P7 D206-3 fold down
30" REF. P15 swivel X INTERIOR ELEVATION MARKER
P6 ironing board 1

PANTRY
30" RANGE D206-2
D201a D203a 1HR F.R.R A6.04
P11 HOOD VENT P11 P11 XX EXISTING ELEVATION MARKER
MECH. / MICRO. MECH. MECH. D205a X .X
3" 1'-0"

3" 1'-0"
W8
D201c D203c D205c NEW ELEVATION MARKER
P1 P11 STORAGE 5 X.XXXm
P1 1HR F.R.R 1HR F.R.R P10 1'-8" 5 adjustable
2'-6"

W5 P9 1HR F.R.R P1 wire shelves P12 H2O VAULT


2'-11" 6'-4" 5'-9" 1" 11'-7" CORRIDOR 6'-0" 2'-11" 12'-0" 8'-0" 6'-0" 1'-2"
G2 D206-1
P17

4'-8"
208 P16

5'-0"
5'-0"

5'-0"

5'-0"
HATCHED WALL INDICATED
8'-3" 7'-6" 22'-4" TOP OF 2nd FLOOR 5'-8" 11'-4" 3'-1" 5'-6" 5'-1" 11" MECH. P17 G3 SHEAR WALL (REFER TO STRUCT.)
9'-0" RD
22.51m
2'-6"

P12 D206c HATCHED WALL INDICATED LOAD


1HR F.R.R P10 1HR F.R.R P9 P12 BEARING WALL (REFER TO

82'-11"
LINEN
STRUCT.)

1'-0" 3"
5 shelves

4"
P1 6
D209 D204c P1
1HR F.R.R 1HR F.R.R 1'-6" 3'-2 1/2" 6'-5"
30" RANGE

PANTRY
MECH. HOOD VENT P17
W8 P11 D204a 2% SLOPE 8 TYPICAL

5'-6 1/2"
JAN.

4'-9"
P13 / MICRO.
D206a UNIT 206
30" REF. P9 1'-9" 1'-0" 2 BEDROOM A6.02
3'-1" D208
7'-3"

6'-7"
D202c 5'-6" 3" 752 SQ.FT
7'-3"

7'-3"
3 ELEC.

8'-0"
P2
2'-8" 5'-7" A5.00 MECH. 209

SINK
MOP
P12
P17 P17 2'-9" 1'-0"
RD P9

1'-8 1/2"
2'-6"
W6 P12 1HR F.R.R P15
G5 D204-1 STORAGE P12
5 adjustable P17 OVERFLOW SCUPPER

11" 8"
D210 30" REF.
wire shelves LN DW P12 7
4"

D 5 shelves

2'-0"
P1 1HR F.R.R D206b
P3 P6 W #4 - 7855 East Saanich Rd.
30" RANGE
P1 ST-2 Saanichton V8M 2B4

10"
P16 HOOD VENT
UP D200 UNIT 204 210 DN / MICRO. 3
fold down

4'-8"
1HR F.R.R A4.00 Phone: 250-656-2224

0"
1HR F.R.R swivel 2 BEDROOM

3 '-
ironing board 746 SQ.FT BALCONY Fax. 250-656-2279
8'-10" 6'-7 1/4" P17 UP G4
ELEVATOR

8'-8"
email:
9'-5"

ST-1 CHAIR RAIL 2'-9" info@finlaysonbonet.ca

8'-3"
9'-6"

D204-3 D204-4 P13


200 P2
P12 MECH.
P15 P15 1HR F.R.R
W6 DW
DN P9

2'-0"
1HR F.R.R D207c CHAIR RAIL
P1

16'-9"
P17 P1
W8
P1 P3 P17
W5
D207a
2"

10'-0"
P2

PANTRY
D202a 1HR F.R.R
P8
1HR F.R.R 30" REF.

8'-1 1/2"
6'-0"

P17 30" REF. P2


7'-4"

30" RANGE
P17 HOOD VENT
30" RANGE 1HR F.R.R
G3 HOOD VENT 1HR F.R.R / MICRO. 21.10.05 ISSUED FOR
P15 P14 PTRY P15 CONSTRUCTION
/ MICRO. 2'-9"
3
2'-9" P14 21.05.25 ISSUED FOR TENDER

1'-4"
A5.01
1'-4"

D204b 21.04.23 ISSUED FOR B.P.


9
2% SLOPE

2% SLOPE

LN DW
RD5 shelves Rev Date Description

2'-0"
DW G3 G3a G4 G5
2'-6"

4'-0" P15
2'-0"

W8 W8 W6 LINEN G3a Checked SMB/KDS


4'-8 1/2"

D202-1 5 shelves

10"
W7
D207-3 Drawn AV
RD
10"

1'-0"
D BALCONY P14 Scale 1/4"=1'-0"
OVERFLOW SCUPPER
CHAIR RAIL D
D202-2 P14 UNIT 207 D207-2 Date
9'-5"

9'-5"

9'-5"

9'-5"
3 1/2"

P17 W 2% SLOPE W5
2 BEDROOM W OCT 05, 2021
W7 782 SQ.FT CHAIR RAIL
UNIT 202 TYPICAL 8 ROOF Project Name
2 BEDROOM G3a
P12 P17 772 SQ.FT A6.02
1'-4" 10'-0"
AREA 8'-8"
P12 W5 SALISH SEA
D202-3 fold down
G3
D207-1 HOUSING
swivel P17
ironing board P17 fold down 7583 CENTRAL SAANICH RD.,
ironing board 10 TSAWOUT FIRST NATION
6"

1'-3"
P17 Drawing Title
10'-7" 4'-6" 3'-4" 4'-8" 7'-9" 4'-2"
ROOF
P15
STORAGE
AREA
5 adjustable P15 P15 LEVEL 2 FLOOR
wire shelves
7'-9"

7'-9"

7'-9"
G3
STORAGE PLAN
7'-3"

6'-6"
5 adjustable
wire shelves
P15 2% SLOPE

Drawing No.
D202b D207b 11 A2.03
1'-0"

1'-0"

G3 G7 OVERFLOW SCUPPER G6
W7 OVERFLOW SCUPPER J
su u n e N
Project No.
W5

is 1
nr 2
ns 2
4'-8 1/2"

4'-8 1/2"

e
su u n e
4'-10" 5'-2" et 1
19323

J
5'-11" 2'-4" 13'-0" 5'-8" 5'-4"
BALCONY BALCONY © Copyright reserved. These plans and
March 21 W March 21
10'-4" 3 1/2" 13'-1" 3 1/2" 3 1/2" 12'-9 1/2" 3 1/2" 18'-2" 1'-6" 12'-0" sunset
E sunrise designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
3 1/2"

3 1/2"

D reproduced without written consent.


su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C 3 D 1 E F 2 G
A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
8'-0" 19'-0" 1. ALL DIMENSIONS ARE IN FEET AND
11'-10" 11'-10 1/2" 3 1/2" 10'-6" 4" 9'-8" 13'-6" 4" 6'-2" INCHES UNLESS NOTED OTHERWISE.
1'-2" 12'-0" 1'-2"
W6
7 1/2"

2. ALL ELEVATIONS ARE IN GEODETIC

11 1/2"
G3a W7
BALCONY

1'-0"

1'-0"
7 1/2"

METERS UNLESS NOTES OTHERWISE.


6'-0" 8'-0" 5'-2" 4'-10"
1 3. ALL DIMENSIONS ARE TO FACE OF
8 TYPICAL CONCRETE, FACE OF SHEATHING,

SLOPE
CENTRELINE OF STUD,

2%
A6.02
3'-9"

3'-9"
CENTRELINE OF DOORS AND
W7 W6 W7 WINDOWS, AND TO FACE OF ANY

5'-9"
G3a G4 OTHER STRUCTURAL ELEMENT
D301b

6'-9"

7'-0"
NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


P17 DIMENSIONS ON SITE AND INFORM
3'-3"

3'-3"
G3a COORDINATING REGISTERED
PROFESSIONAL OF ANY

12'-4"
4"
11 1/2"
P15 DISCREPANCIES PRIOR TO
W7 UNDERTAKING THE PORTION OF
D305-5
2

3"
WORK WHICH IS IN REFERENCE TO

1'-1"

SLOPE
BALCONY ANY DISCREPANCY.

2%
9'-0"
P17

3'-9"
5. DO NOT SCALE THESE DRAWINGS.
W7 FINLAYSON BONET ARCHITECTURE
3'-6" 4'-8" 8'-0" 10'-7" 5'-8" 5'-6" 6'-2" 2'-5"

SLOPE
LTD. IS NOT RESPONSIBLE FOR
5'-9"

5'-9"
4'-8 1/2"
G7 D305-4
D305b

2%
BALCONY ISSUES THAT ARISE FROM A
D P17 FAILURE TO COMPLY.
STORAGE
5 adjustable P12 1'-0" 2 TYPICAL
W11 W

2'-0"
wire shelves P15 A6.04 6. THESE DRAWINGS ARE TO BE READ
G6 G3a G3
D303b IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3

1'-2"
STRUCTURAL DRAWINGS AND
D301-3 SPECIFICATIONS, MECHANICAL
P15 DRAWINGS AND SPECIFICATIONS,
P17 D305-3 ELECTRICAL DRAWINGS AND
W6
SPECIFICATIONS, CIVIL DRAWINGS
P17 AND SPECIFICATIONS, LANDSCAPE

6'-0"
W7 UNIT 305 DRAWINGS AND SPECIFICATIONS,
D P15 CHAIR RAIL 3 BEDROOM D305-1 D305-2 INTERIOR DESIGN DRAWINGS AND
BR. CL. BR SPECIFICATIONS AND ANY OTHER
1,046 SQ.FT 1 shelf LN
P17 1 shelf 5 shelves CONSULTANT DEEMED PERTINENT
W RD TO THE CONSTRUCTION OF THIS
P17 P17 G3
PROJECT.

7. CONTRACTOR TO OBTAIN ALL


NECESSARY PERMITS, BYLAW
D301-2

10"
APPROVALS, AND OBSERVE ALL
CHAIR RAIL
16'-4"

16'-4"
P17 P17 P16 REQUIRED SAFETY REGULATIONS
4'-0" P16 THROUGHOUT THE COURSE OF

2'-0"
P2 CONSTRUCTION

6'-10"
P16
1HR F.R.R 1HR F.R.R
LN P15 DW SYMBOL LEGEND
5 shelves P17
2'-9" P15 FD FLOOR DRAIN
P2 P15 P2
RD

10"
W6
UNIT 301 D303-3 D303-2 ROOF / DECK DRAIN
30" RANGE CHAIR RAIL
2 BEDROOM

2'-0"
P12 HOOD VENT
P15 1HR F.R.R

3"
768 SQ.FT / MICRO. UNIT 303 fold down ASSEMBLY MARKER

3 '-
D301-1 XX
swivel DW

PROPERTY LINE
2 BEDROOM P6 P2
ironing board

[33.83 M]
1HR F.R.R

3'-6"
752 SQ.FT

10"
2'-9" GLAZING TYPE (REFER TO
30" REF. P6 D GX WINDOW SCHEDULE)
W

2'-0"
P17 P6 fold down
LN W 4
fold down DOOR TYPE (REFER TO DOOR
4"

D 30" RANGE
ironing board
PTRY DW 5 shelves G3a DXXX SCHEDULE)
G3 ironing board P17 HOOD VENT P17
P15 1'-0" 2'-9" P17 / MICRO.
RD STORAGE D303-1
STORAGE 5 adjustable
X
SECTION MARKER
5 adjustable wire shelves
AXXX
wire shelves P17 P17 P2 30" REF. PTRY P17
D306-3 X DETAIL MARKER
7'-8"

7'-8"
P17
7'-4"

AXXX
P15 P7 fold down
P17
30" REF. P15 swivel X INTERIOR ELEVATION MARKER
P6 ironing board

PANTRY
30" RANGE D306-2
D301a P11 D303a
1HR F.R.R P11
HOOD VENT P11 XX EXISTING ELEVATION MARKER
MECH. / MICRO. MECH. MECH. X .X
3" 1'-0"

3" 1'-0"
D305a W11

21'-4"
D301c D303c D305c NEW ELEVATION MARKER
P1
P11 STORAGE 5 X.XXXm
P1 1HR F.R.R 1HR F.R.R P10 1'-8" 5 adjustable
2'-6"

W7 P9 1HR F.R.R P1 wire shelves P12 H2O VAULT


2'-11" 6'-4" 5'-9" 1" 11'-7" CORRIDOR 6'-0" 2'-11" 12'-0" 8'-0" 6'-0" 1'-2"
G2 D306-1
P17

4'-8"
308

5'-0"
5'-0"

5'-0"

5'-0"
HATCHED WALL INDICATED
7'-6" 22'-4" T.O. CONC. TOPPING 5'-8" 11'-4" 3'-1" 5'-6" 5'-1" 11" MECH. P17 SHEAR WALL (REFER TO STRUCT.)
8'-3" 9'-0" RD
25.71m
2'-6"

P12 D306c HATCHED WALL INDICATED LOAD


1HR F.R.R P10 1HR F.R.R P9 P12 5'-0" BEARING WALL (REFER TO

82'-11"
P16 LINEN
STRUCT.)

1'-0" 3"
5 shelves

4"
D304c P1 6
D309 P1
1HR F.R.R 1HR F.R.R 1'-6" 3'-2 1/2"
MECH. 30" RANGE P17

PANTRY
P11 D304a HOOD VENT D306a
W11 G3

5'-5 1/2"
JAN.

4'-9"
P13
/ MICRO. UNIT 306 8 TYPICAL
30" REF. P9 D308 1'-9" 1'-0" 2 BEDROOM
7'-3"

6'-7"
D302c 3'-1" 5'-6" 3" 752 SQ.FT A6.02
7'-3"

7'-3"
4

8'-0"
ELEC. P2
2'-8" 5'-7" A5.00 MECH. 309

SINK
MOP
P17 P17 P12
P17 P17 2'-9" 1'-0"
RD P9

1'-9 1/2"
2'-6"
W6 P12 1HR F.R.R P15
G5 D304-1 STORAGE P12
5 adjustable D310

11" 8"
30" REF.
wire shelves LN DW P12 7
4"

D 5 shelves

2'-0"
P1 1HR F.R.R D306b
P3 P6 W #4 - 7855 East Saanich Rd.
30" RANGE
P16 P1 Saanichton V8M 2B4

10"
HOOD VENT
UP D300
ST-2 / MICRO. 3
fold down UNIT 304 310

4'-8"
1HR F.R.R A4.00 Phone: 250-656-2224

0"

11'-0"
1HR F.R.R swivel 2 BEDROOM

3 '-
ironing board 746 SQ.FT Fax. 250-656-2279
ST-1 8'-10" 6'-7 1/4" P17 UP DN G4

8'-8"
email:
9'-5"

300 P13 2'-9" info@finlaysonbonet.ca

8'-3"
9'-6"

ELEVATOR D304-2 D304-3 BALCONY


CHAIR RAIL
W6 P2
P12 MECH. 2%
P15 P15 1HR F.R.R
DW SLOPE
DN D307c

2'-0"
1HR F.R.R CHAIR RAIL W11
P9
P1

16'-9"
P17 P1
P1 P3 P17
D307a
2"

10'-0"
P2

PANTRY
P8 1HR F.R.R W7
D302a
1HR F.R.R 30" REF.

8'-1 1/2"
P2
6'-0"

30" REF.
P17
7'-4"

30" RANGE
30" RANGE HOOD VENT
1HR F.R.R P17 / MICRO. 21.10.05 ISSUED FOR
G3 HOOD VENT 1HR F.R.R P15
P15 P14 PTRY / MICRO. CONSTRUCTION
4 2'-9"
2'-9" P14 21.05.25 ISSUED FOR TENDER

1'-4"
A5.01
1'-4"

D304b 21.04.23 ISSUED FOR B.P.


LN DW
9
RD5 shelves Rev Date Description

2'-0"
DW G3 G3a G4 G5
4'-0" P15
2'-0"

W11 W11 W6 LINEN G3a Checked SMB/KDS


4'-8 1/2"

D302-1 5 shelves
4'-9"

10"
D307-3 Drawn AV
SLOPE

W7 2 TYPICAL RD
10"

2%

A6.04 D BALCONY Scale 1/4"=1'-0"


CHAIR RAIL P14 D
D303-2 P14 UNIT 307 D307-2 Date
9'-5"

9'-5"

9'-5"

9'-5"
3 1/2"

P17 W W6
2 BEDROOM W OCT 05, 2021
1'-2"

W7 782 SQ.FT
UNIT 302 TYPICAL 8 Project Name
2 BEDROOM G3a
P12 P17 772 SQ.FT A6.02
1'-4" 10'-0" 8'-8"
CHAIR RAIL P12 W7 SALISH SEA
1'-0"
D302-3 fold down
G3
P17
D307-1 HOUSING
swivel
ironing board P17 fold down 7583 CENTRAL SAANICH RD.,
ironing board 10 TSAWOUT FIRST NATION
6"

1'-3"
P17 Drawing Title
10'-7" 4'-6" 3'-4" 4'-8" 7'-9" 4'-2"
11'-3"

P15
STORAGE
P15 P15
5 adjustable LEVEL 3 FLOOR
wire shelves
7'-9"

7'-9"

7'-9"
G3
STORAGE PLAN
7'-3"

6'-6"
5 adjustable
wire shelves
P15

Drawing No.
D302b D307b 11 A2.04
1'-0"

1'-0"

G3 G7 G6 J N
W6 W7 W7 su u n e Project No.

is 1
nr 2
ns 2
4'-8 1/2"

4'-8 1/2"

e
su u n e
6" 5'-11" 2'-4" 13'-0" 5'-8" 5'-4" 4'-10" 5'-2" et 1
19323

J
SLOPE

5'-0"

5'-0"

SLOPE
2%

11'-9" 1'-2" BALCONY


2%

BALCONY March 21 W March 21


© Copyright reserved. These plans and
10'-4" 3 1/2" 13'-1" 3 1/2" 3 1/2" 12'-9 1/2" 3 1/2" 18'-2" 1'-6" sunset
E sunrise designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
3 1/2"

3 1/2"

D reproduced without written consent.


su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C 3 D 1 E F 2 G
A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
11'-10" 11'-10 1/2" 3 1/2" 10'-6" 4" 9'-8" 13'-6" 4" 6'-2" 1'-2" 12'-0" INCHES UNLESS NOTED OTHERWISE.
8'-0" 19'-0"
3 1/2"

W6
2. ALL ELEVATIONS ARE IN GEODETIC
11 1/2"

11 1/2"
BALCONY G3a W7

1'-0"
METERS UNLESS NOTES OTHERWISE.
6'-0" 8'-0" 5'-2" 4'-10"
1 3. ALL DIMENSIONS ARE TO FACE OF

SLOPE
CONCRETE, FACE OF SHEATHING,

2%
CENTRELINE OF STUD,
3'-9"

3'-9"
CENTRELINE OF DOORS AND
W7 W6 W7 WINDOWS, AND TO FACE OF ANY

5'-9"
G3a G4 OTHER STRUCTURAL ELEMENT

6'-9"

7'-0"
NOT LISTED.
401
4. CONTRACTOR TO VERIFY ALL
P17 DIMENSIONS ON SITE AND INFORM
3'-3"

3'-3"
G3a COORDINATING REGISTERED
PROFESSIONAL OF ANY

12'-4"
4"
11 1/2"
P15 DISCREPANCIES PRIOR TO
W7 UNDERTAKING THE PORTION OF
2

3"
WORK WHICH IS IN REFERENCE TO

1'-1"
BALCONY D405-5 ANY DISCREPANCY.

SLOPE
9'-0"
BALCONY

2%
P17

3'-9"
5. DO NOT SCALE THESE DRAWINGS.
3'-6" 4'-8" 8'-0" 10'-7" 5'-8" 5'-6" 6'-2" 2'-5" FINLAYSON BONET ARCHITECTURE
W7

SLOPE
LTD. IS NOT RESPONSIBLE FOR
5'-9"

5'-9"
4'-8 1/2"
G7 D405-4

2%
ISSUES THAT ARISE FROM A
D P17 FAILURE TO COMPLY.
STORAGE
D405b 5 adjustable P12 1'-0" 2 TYPICAL
W11 W

2'-0"
wire shelves P15 A6.04 6. THESE DRAWINGS ARE TO BE READ
G6 G3a G3 IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3

1'-2"
D402b STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
P15 DRAWINGS AND SPECIFICATIONS,
D401-3 D405-3
P17 W6 ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
CHAIR RAIL P17 AND SPECIFICATIONS, LANDSCAPE

6'-0"
UNIT 405 DRAWINGS AND SPECIFICATIONS,
W7 D P15 INTERIOR DESIGN DRAWINGS AND
3 BEDROOM D405-1 BR D405-2
BR. CL. 1,046 SQ.FT LN SPECIFICATIONS AND ANY OTHER
P17 1 shelf 1 shelf CONSULTANT DEEMED PERTINENT
W RD 5 shelves
P17 G3 TO THE CONSTRUCTION OF THIS
PROJECT.

7. CONTRACTOR TO OBTAIN ALL


D401-2 NECESSARY PERMITS, BYLAW
33'-0"

P17

10"
APPROVALS, AND OBSERVE ALL
CHAIR RAIL
16'-4"

16'-4"
P17 P17 P16 REQUIRED SAFETY REGULATIONS
4'-0" THROUGHOUT THE COURSE OF

2'-0"
P2 CONSTRUCTION

6'-10"
P17
1HR F.R.R 1HR F.R.R
LN P15 DW SYMBOL LEGEND
5 shelves P17
2'-9" P15 FD FLOOR DRAIN
P2 P15 P2
RD

10"
W6
UNIT 401 D403-3 D403-2 ROOF / DECK DRAIN
30" RANGE CHAIR RAIL
2 BEDROOM

2'-0"
P12 HOOD VENT
P15 1HR F.R.R

3"
768 SQ.FT / MICRO. UNIT 403 fold down ASSEMBLY MARKER

3 '-
D401-1 XX
swivel DW

PROPERTY LINE
2 BEDROOM P6 P2
ironing board

[33.83 M]
1HR F.R.R

3'-6"
752 SQ.FT

10"
2'-9" GLAZING TYPE (REFER TO
30" REF. P6 D GX WINDOW SCHEDULE)
W

2'-0"
P17 P6 fold down
LN W 4
fold down DOOR TYPE (REFER TO DOOR
4"

D 30" RANGE
ironing board
PTRY DW 5 shelves G3a DXXX SCHEDULE)
G3 ironing board P17 HOOD VENT P17
P15 P17
1'-0" 2'-9" RD STORAGE D403-1 / MICRO.
STORAGE 5 adjustable
X
SECTION MARKER
5 adjustable wire shelves
AXXX
wire shelves P17 P17 P2 30" REF. PTRY P17
X DETAIL MARKER
7'-8"

7'-8"
P17
7'-4"

AXXX
P15 P7 D406-3 fold down
P17
30" REF. P15 swivel X INTERIOR ELEVATION MARKER
P6 ironing board

PANTRY
30" RANGE D406-2
P11 1HR F.R.R P11
401a HOOD VENT P11 XX EXISTING ELEVATION MARKER
MECH. / MICRO. D402a MECH. MECH. X .X
3" 1'-0"

3" 1'-0"
W11

21'-4"
D405a
401c D402c D405c NEW ELEVATION MARKER
P1 P11 STORAGE 5 X.XXXm
P1 1HR F.R.R 1HR F.R.R P10 1'-8" 5 adjustable
2'-6"

W7 P9 1HR F.R.R P1 wire shelves P12 H2O VAULT


2'-11" 6'-4" 5'-9" 1" 11'-7" CORRIDOR 6'-0" 2'-11" 12'-0" 8'-0" 6'-0" 1'-2"
G2 D406-1
P17

4'-8"
408

5'-0"
5'-0"

5'-0"

5'-0"
HATCHED WALL INDICATED
7'-6" 22'-4" T.O. CONC. TOPPING 5'-8" 11'-4" 3'-1" 5'-6" 5'-1" 11" MECH. P17 SHEAR WALL (REFER TO STRUCT.)
8'-3" 9'-0" RD
28.91m
2'-6"

P12 D406c HATCHED WALL INDICATED LOAD


1HR F.R.R P10 1HR F.R.R P9 P12 5'-0" BEARING WALL (REFER TO

82'-11"
LINEN
STRUCT.)

1'-0" 3"
D404c 5 shelves

4"
P1 6
D409 P1 3 1/2"
12'-3"

1HR F.R.R 1HR F.R.R 1'-6" 3'-2 1/2"


MECH. 30" RANGE

PANTRY
P11 D404a HOOD VENT P17
W11 G3

5'-5 1/2"
JAN.

4'-9"
/ MICRO.
D408 UNIT 406
P13 P9 2 BEDROOM
30" REF. 1'-9" 1'-0"
7'-3"

6'-7"
3'-1" 5'-6" 3" D406a 752 SQ.FT
7'-3"

7'-3"
5 D402c

8'-0"
ELEC. P2
2'-8" 5'-7" A5.00 MECH. 409

SINK
MOP
P17 P12
P17 P17 2'-9" 1'-0"
RD P9

1'-9 1/2"
2'-6"
W6 P12 1HR F.R.R P15
G5 STORAGE P12
5 adjustable D410

11" 8"
30" REF.
wire shelves LN DW P12 7
4"

D 5 shelves

2'-0"
P1 1HR F.R.R D406c
P3 P6 W #4 - 7855 East Saanich Rd.
D404-1 30" RANGE
P1 Saanichton V8M 2B4

10"
HOOD VENT
UP D400
P16 ST-2 / MICRO. 3
fold down UNIT 404 410

4'-8"
1HR F.R.R A4.00 Phone: 250-656-2224

0"

11'-0"
1HR F.R.R swivel 2 BEDROOM

3 '-
ironing board 746 SQ.FT BALCONY Fax. 250-656-2279
ST-1 8'-10" 6'-7 1/4" P17 UP DN G4

8'-8"
email:
400 CHAIR RAIL P13 2'-9" info@finlaysonbonet.ca

8'-3"
9'-6"

D404-2 D404-3 2%
ELEVATOR
W6 P2 SLOPE
P12 MECH.
P15 P15 1HR F.R.R
DW
DN D407c

2'-0"
1HR F.R.R CHAIR RAIL W11
P9
P1

16'-9"
P17 P1
P1 P3 P17
D407a
2"

10'-0"
PANTRY
D402a 1HR F.R.R P2
P8 W7
1HR F.R.R 30" REF.

8'-1 1/2"
P2
6'-0"

30" REF.
P17

30" RANGE
30" RANGE HOOD VENT
1HR F.R.R P17 / MICRO. 21.10.05 ISSUED FOR
G3 HOOD VENT 1HR F.R.R P15
P15 P14 PTRY / MICRO. CONSTRUCTION
5 2'-9"
2'-9" P14 21.05.25 ISSUED FOR TENDER

1'-4"
A5.01
1'-4"

D404b 21.04.23 ISSUED FOR B.P.


LN DW
9
RD5 shelves Rev Date Description

2'-0"
DW G3 G3a G4 G5
4'-0" P15
2'-0"

W11 W11 W6
4'-8 1/2" LINEN G3a Checked SMB/KDS
4'-8 1/2"

D402-1 5 shelves

10"
D407-3 Drawn AV
SLOPE

W7 2 TYPICAL RD
10"

2%

A6.04 D BALCONY P14 Scale 1/4"=1'-0"

1'-2"
CHAIR RAIL D
D402-2 P14 UNIT 407 D407-2 Date
9'-5"

9'-5"

9'-5"
3 1/2"
3 1/2"

P17 W W6
2 BEDROOM W OCT 05, 2021
1'-2"

W7 782 SQ.FT
UNIT 402 Project Name
G3a CHAIR RAIL
P12 P17
2 BEDROOM
772 SQ.FT 1'-4" 10'-0" 8'-8"
P12 W7 SALISH SEA
D402-3 fold down
G3
D407-1 HOUSING
swivel P17
ironing board
P17 fold down 7583 CENTRAL SAANICH RD.,
ironing board 10 TSAWOUT FIRST NATION
6"

1'-3"
P17 Drawing Title
10'-7" 4'-6" 3'-4" 4'-8" 7'-9" 4'-2" P15

12'-4"
11'-3"

P15
STORAGE
5 adjustable LEVEL 4 FLOOR
wire shelves
7'-9"

7'-9"
G3
P15 STORAGE PLAN
7'-3"

6'-6"
W6 5 adjustable
wire shelves
P15

Drawing No.
D402c D407c 11 A2.05
1'-0"

1'-0"
G3 G7 G6 J N
W6 W7 W7 W6 su u n e Project No.

is 1
nr 2
ns 2
4'-8 1/2"

4'-8 1/2"

e
su u n e
5'-11" 2'-4" 13'-0" 5'-8" 5'-4" 4'-10" 5'-2" et 1
19323

J
SLOPE

SLOPE
2%

6" 11'-9" 1'-2"


2%

BALCONY March 21 W March 21


© Copyright reserved. These plans and
10'-4" 3 1/2" 13'-1" 3 1/2" 3 1/2" 12'-9 1/2" 3 1/2" 18'-2" 1'-6" sunset
E sunrise designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
3 1/2"

3 1/2"

BALCONY
1'-2" 12'-4" 1'-0" 6" D
su e c
reproduced without written consent.

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C 3 D 1 E F 2 G
A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1'-2" 12'-0" 1. ALL DIMENSIONS ARE IN FEET AND
11'-10" 11'-10 1/2" 3 1/2" 10'-6" 4" 9'-8" 13'-6" 4" 6'-2" INCHES UNLESS NOTED OTHERWISE.
W6 8'-0" 19'-0"
3 1/2"

W7 2. ALL ELEVATIONS ARE IN GEODETIC


11 1/2"

11 1/2"
BALCONY G3a

1'-0"
METERS UNLESS NOTES OTHERWISE.
6'-0" 8'-0" 5'-2" 4'-10"
1 3. ALL DIMENSIONS ARE TO FACE OF

SLOPE
CONCRETE, FACE OF SHEATHING,

2%
CENTRELINE OF STUD,
3'-9"

3'-9"
CENTRELINE OF DOORS AND
W7 W6 W7 WINDOWS, AND TO FACE OF ANY

5'-9"
G3a G4 OTHER STRUCTURAL ELEMENT
NOT LISTED.
D501C
4. CONTRACTOR TO VERIFY ALL
P17 DIMENSIONS ON SITE AND INFORM
3'-3"

3'-3"
G3a COORDINATING REGISTERED
PROFESSIONAL OF ANY

12'-4"
4"
11 1/2"
P15 DISCREPANCIES PRIOR TO
W7 BALCONY UNDERTAKING THE PORTION OF
2

SLOPE
WORK WHICH IS IN REFERENCE TO

1'-1"

2%
D505-5 ANY DISCREPANCY.

9'-0"
BALCONY P17

3'-9"
5. DO NOT SCALE THESE DRAWINGS.
3'-6" 4'-8" 8'-0" 10'-7" 5'-8" 5'-6" 6'-2" 2'-5" FINLAYSON BONET ARCHITECTURE
W7

SLOPE
LTD. IS NOT RESPONSIBLE FOR
5'-9"

4'-8 1/2"
G7 D505-4

2%
ISSUES THAT ARISE FROM A
D P17 FAILURE TO COMPLY.
STORAGE
D505b 5 adjustable P12 2 TYPICAL
W11 W 1'-0"

2'-0"
wire shelves P15 A6.04 6. THESE DRAWINGS ARE TO BE READ
G6 G3a G3 IN CONJUNCTION WITH ALL

25'-7"
ARCHITECTURAL SPECIFICATIONS,
3

1'-2"
D503b STRUCTURAL DRAWINGS AND
D501-3 SPECIFICATIONS, MECHANICAL
P15 DRAWINGS AND SPECIFICATIONS,
P17 D505-3 ELECTRICAL DRAWINGS AND
W6
SPECIFICATIONS, CIVIL DRAWINGS
P17 AND SPECIFICATIONS, LANDSCAPE
UNIT 505 DRAWINGS AND SPECIFICATIONS,
W7 D P15 INTERIOR DESIGN DRAWINGS AND
3 BEDROOM D505-1 BR D505-2
BR. CL. 1,046 SQ.FT LN SPECIFICATIONS AND ANY OTHER
1 shelf CHAIR RAIL 1 shelf CONSULTANT DEEMED PERTINENT
P17 5 shelves
W RD TO THE CONSTRUCTION OF THIS
P17 G3
PROJECT.

7. CONTRACTOR TO OBTAIN ALL


NECESSARY PERMITS, BYLAW
33'-0"

D501-2 CHAIR RAIL P17

10"
APPROVALS, AND OBSERVE ALL
16'-4"

P17 P17 P16 REQUIRED SAFETY REGULATIONS


4'-0" THROUGHOUT THE COURSE OF

2'-0"
P2 CONSTRUCTION
P17
1HR F.R.R 1HR F.R.R
LN P15 DW SYMBOL LEGEND
5 shelves P17
2'-9" P15 FD FLOOR DRAIN
P2 P15 P2
RD

10"
W6
UNIT 501 D503-3 D503-2 ROOF / DECK DRAIN
30" RANGE CHAIR RAIL
2 BEDROOM

2'-0"
P12 HOOD VENT
P15 1HR F.R.R

3"
768 SQ.FT / MICRO. UNIT 503 fold down ASSEMBLY MARKER

3 '-
D501-1 XX
swivel DW
2 BEDROOM P6 P2
752 SQ.FT ironing board 1HR F.R.R

10"
2'-9" GLAZING TYPE (REFER TO
30" REF. P6 D GX WINDOW SCHEDULE)
W

2'-0"
P17 P6 fold down
LN W 4
fold down DOOR TYPE (REFER TO DOOR
4"

D 30" RANGE
ironing board
PTRY DW 5 shelves G3a DXXX SCHEDULE)
G3 ironing board P17 HOOD VENT P17
P15 1'-0" 2'-9" P17 / MICRO.
RD STORAGE D503-1
STORAGE 5 adjustable
X
SECTION MARKER
5 adjustable P16 wire shelves
AXXX
wire shelves P17 P2 30" REF. PTRY P17
X DETAIL MARKER
7'-8"

P17 P17
7'-4"

AXXX
P15 P7 D506-3 fold down
P17
30" REF. P15 swivel X INTERIOR ELEVATION MARKER
P6 ironing board

PANTRY
30" RANGE D506-2
D501a P11 D503a 1HR F.R.R
P1 HOOD VENT P11 P11 XX EXISTING ELEVATION MARKER
MECH. / MICRO. MECH. MECH. X .X
3" 1'-0"

3" 1'-0"
W11

21'-4"
D505a
D501c D503c D505c NEW ELEVATION MARKER
P1
P11 STORAGE 5 X.XXXm
1HR F.R.R 1HR F.R.R P10 1'-8" 5 adjustable
2'-6"

W7 P9 1HR F.R.R P1 wire shelves P12 H2O VAULT


2'-11" 6'-4" 5'-9" 1" 11'-7" CORRIDOR 6'-0" 2'-11" 12'-0" 8'-0" 6'-0" 1'-2"
G2 D506-1
P17

4'-8"
508
5'-0"

5'-0"

HATCHED WALL INDICATED


7'-6" 22'-4" T.O. CONC. TOPPING 5'-8" 11'-4" 3'-1" 5'-6" 5'-1" 11" MECH. P17 SHEAR WALL (REFER TO STRUCT.)
8'-3" 9'-0" RD
32.11m D506c
2'-6"

P12 1HR F.R.R 1HR F.R.R HATCHED WALL INDICATED LOAD


P10 P9 P12 P16 LINEN 5'-0" BEARING WALL (REFER TO
STRUCT.)

1'-0" 3"
5 shelves

4"
D504c
P1
P1
6
D509 3 1/2"
12'-3"

1HR F.R.R 1HR F.R.R 1'-6" 3'-2 1/2"


MECH. 30" RANGE P17

PANTRY
W11 P11 D504a HOOD VENT
G3
JAN.

4'-9"
/ MICRO.
D506a UNIT 506
P13 P9 D508 2 BEDROOM
30" REF. 1'-9" 1'-0"
7'-3"

6'-7"
3'-1" 5'-6" 3" 752 SQ.FT
7'-3"

6 D502c
ELEC. P2
2'-8" 5'-7" A5.00 MECH. 509

SINK
MOP
P16 P12
P17 P17 2'-9" 1'-0"
RD P9

2'-6"
W6 P12 1HR F.R.R P15
G5 D504-1 STORAGE P12
5 adjustable D510

11" 8"
P17 30" REF.
wire shelves LN DW P12 7
4"

D 5 shelves

2'-0"
P1 1HR F.R.R D506b
P3 P6 W #4 - 7855 East Saanich Rd.
30" RANGE
P1 Saanichton V8M 2B4

10"
D500 HOOD VENT
P16
UNIT 504
ST-2 / MICRO. 3
fold down
510 1HR F.R.R A4.00 Phone: 250-656-2224

0"

11'-0"
1HR F.R.R swivel 2 BEDROOM

3 '-
ST-1 ironing board 746 SQ.FT BALCONY Fax. 250-656-2279
8'-10" 6'-7 1/4" P17 DN G4
email:
500 2'-9" info@finlaysonbonet.ca

8'-3"
9'-6"

D504-3 D504-3 P13 2%


W6 P2 SLOPE
P12 MECH.
P15 P15 1HR F.R.R
DW
DN

2'-0"
1HR F.R.R CHAIR RAIL D507c CHAIR RAIL W11
ELEVATOR P9
P1 P1
P17
P1 P3 P17
D507a
2"

PANTRY
D502a P8 1HR F.R.R P2 W7
1HR F.R.R 30" REF.
P2
6'-0"

30" REF.
P17

30" RANGE
30" RANGE P17 HOOD VENT
1HR F.R.R / MICRO. 21.10.05 ISSUED FOR
G3 HOOD VENT 1HR F.R.R P15
P15 P14 PTRY / MICRO. CONSTRUCTION
6 2'-9"
2'-9" P14 21.05.25 ISSUED FOR TENDER
A5.01
1'-4"

D504b 21.04.23 ISSUED FOR B.P.


LN DW
9
RD5 shelves Rev Date Description

2'-0"
DW G3 G3a G4 G5
4'-0" P15
2'-0"

W11 W11 W6
4'-8 1/2" LINEN G3a Checked SMB/KDS
4'-8 1/2"

D502-1 5 shelves

10"
D507-3 Drawn AV
SLOPE

W7 W7
RD
10"

2%

D BALCONY P14 Scale 1/4"=1'-0"

1'-2"
D D507-2

25'-0"
D502-2 P14 Date
9'-5"

9'-5"
3 1/2"
3 1/2"

P17 W W6
CHAIR RAIL W OCT 05, 2021
1'-2"

W7
CHAIR RAIL
UNIT 502 UNIT 507 Project Name
2 BEDROOM G3a 2 BEDROOM
P12 P17 772 SQ.FT 10'-0" 8'-8"
8'-5" 782 SQ.FT
P12 W6 SALISH SEA
D502-3 fold down
G3
D507-1 HOUSING
swivel P17
ironing board P17 fold down 7583 CENTRAL SAANICH RD.,
ironing board 10 TSAWOUT FIRST NATION
6"

P17 Drawing Title


10'-7" 4'-6" 3'-4" 4'-8" 7'-9" 4'-2"

12'-4"
11'-3"

P15
STORAGE
P15
5 adjustable P15 LEVEL 5 FLOOR
wire shelves
7'-9"

G3
STORAGE PLAN
7'-3"

W6 5 adjustable
wire shelves
P15

Drawing No.
D502b D507b 11 A2.06
1'-0"

1'-0"
G3 G7 G6 J N
W6 W7 W7 W6 su u n e Project No.

is 1
nr 2
ns 2
4'-8 1/2"

4'-8 1/2"

e
su u n e
5'-11" 2'-4" 13'-0" 5'-8" 5'-4" 4'-10" 5'-2" et 1
19323

J
SLOPE

SLOPE
2%

2%

6" 11'-9" 1'-2"


BALCONY March 21 W March 21
© Copyright reserved. These plans and
10'-4" 3 1/2" 13'-1" 3 1/2" 3 1/2" 12'-9 1/2" 3 1/2" 18'-2" 1'-6" sunset
E sunrise designs are and at all times remain the
property of Finlayson Bonet Architecture to be
BALCONY 1'-2" 12'-4" 1'-0" 6" used for the project shown and may not be
3 1/2"

3 1/2"

D reproduced without written consent.


su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C 3 D 1 E F 2 T.O. PARAPET G
T.O. ROOF A4.01 A4.00 A4.00 GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0" 35.77M
0"
34.70M
0" 1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

1'-8"
2. ALL ELEVATIONS ARE IN GEODETIC
METERS UNLESS NOTES OTHERWISE.
1

SLOPE
3. ALL DIMENSIONS ARE TO FACE OF

2%
CONCRETE, FACE OF SHEATHING,
1'-8" CENTRELINE OF STUD,
CENTRELINE OF DOORS AND
WINDOWS, AND TO FACE OF ANY

1'-8"
T.O. PARAPET OTHER STRUCTURAL ELEMENT

7'-0"
35.77M
0" NOT LISTED.
T.O. PARAPET 4. CONTRACTOR TO VERIFY ALL
35.77M
0" DIMENSIONS ON SITE AND INFORM
COORDINATING REGISTERED
T.O. ROOF PROFESSIONAL OF ANY
34.70M
0" DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
2

SLOPE
T.O. PARAPET WORK WHICH IS IN REFERENCE TO

2%
ANY DISCREPANCY.
35.77M
0"
1'-8" 5. DO NOT SCALE THESE DRAWINGS.

SLOPE
FINLAYSON BONET ARCHITECTURE
T.O. PARAPET

2%
LTD. IS NOT RESPONSIBLE FOR

SLOPE 2%

5'-9"
35.77M
0" T.O. PARAPET ISSUES THAT ARISE FROM A
35.77M
0" FAILURE TO COMPLY.

6. THESE DRAWINGS ARE TO BE READ

1'-8"
IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
DRAWINGS AND SPECIFICATIONS,
7'-2" ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
T.O. PARAPET 1'-8" DRAWINGS AND SPECIFICATIONS,
SLOPE 2%
INTERIOR DESIGN DRAWINGS AND
35.77M
0" SLOPE 2% SLOPE 2% SPECIFICATIONS AND ANY OTHER
RD CONSULTANT DEEMED PERTINENT
TO THE CONSTRUCTION OF THIS
T.O. ROOF DRAIN PROJECT.
34.90M
0" 7. CONTRACTOR TO OBTAIN ALL
NECESSARY PERMITS, BYLAW

SLOPE 2%
APPROVALS, AND OBSERVE ALL
1'-8" 8'-8"

16'-4"
REQUIRED SAFETY REGULATIONS
THROUGHOUT THE COURSE OF
CONSTRUCTION
LINE OF WALL BELOW LINE OF WALL BELOW
SYMBOL LEGEND

11'-10"

SLOPE 2%
SLOPE 2% SLOPE 2% FD FLOOR DRAIN
RD
ROOF / DECK DRAIN
T.O. ROOF DRAIN 3'-2"
34.90M
0" ASSEMBLY MARKER
5'-2"

XX

PROPERTY LINE
[33.83 M]
SLOPE 2% SLOPE 2%
LINE OF WALL BELOW GLAZING TYPE (REFER TO
GX WINDOW SCHEDULE)

4 DOOR TYPE (REFER TO DOOR

1'-6"
DXXX SCHEDULE)
T.O. ROOF DRAIN
SLOPE 2%

RD
34.90M
0" X
SECTION MARKER
AXXX

SLOPE 2%
X DETAIL MARKER

7'-8"

7'-8"
AXXX

SLOPE 2%
X INTERIOR ELEVATION MARKER
LINE OF WALL BELOW
XX EXISTING ELEVATION MARKER
X .X
NEW ELEVATION MARKER
5 X.XXXm

H2O VAULT
T.O. ROOF DRAIN

3'-2"
34.90M
0"

5'-0"
T.O. PARAPET HATCHED WALL INDICATED
SLOPE 2% SLOPE 2% SHEAR WALL (REFER TO STRUCT.)
RD 35.77M
0"
OVERFLOW SCUPPER HATCHED WALL INDICATED LOAD
BEARING WALL (REFER TO

82'-11"
SLOPE 2%
STRUCT.)
6
T.O. PARAPET 8'-7" OVERFLOW SCUPPER
35.77M
0"
LINE OF WALL BELOW

6'-2"

7'-3"
T.O. PARAPET
4'-4"

SLOPE 2%
35.77M
0"

SLOPE 2%
RD SLOPE 2%
1'-1"

T.O. ROOF DRAIN


7
34.90M
0" T.O. ROOF
34.70M
0" #4 - 7855 East Saanich Rd.
ROOF Saanichton V8M 2B4
HATCH ELEVATOR 3
2% A4.00 Phone: 250-656-2224
SLOPE BALCONY Fax. 250-656-2279
ROOF SCUPPER
BELOW email:
C/W R.W.L
info@finlaysonbonet.ca
SLOPE 2%

LINE OF WALL BELOW

16'-9"
SLOPE 2%

SLOPE 2%
LINE OF STAIR BELOW T.O. ELEVATOR
PARAPET LINE OF STAIR BELOW
36.70M
0"

21.10.05 ISSUED FOR


8'-5" 15'-7" LINE OF WALL BELOW CONSTRUCTION
7'-4" 21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.
9
1'-2"

SLOPE 2% SLOPE 2% ROOF BELOW Rev Date Description


RD

3'-4"
T.O. PARAPET
Checked SMB/KDS
T.O. ROOF DRAIN Drawn AV
35.77M
0"
SLOPE

T.O. PARAPET
34.90M
0" SLOPE 2% SLOPE 2%
2%

35.77M
0" RD Scale 1/4"=1'-0"
T.O. ROOF DRAIN Date

9'-5"
OCT 05, 2021
8'-3"

34.90M
0"
T.O. ROOF

6'-1"
Project Name
34.70M
0" SALISH SEA
SLOPE 2%

1'-8" 1'-8" EXIST STAIR 2 1'-8"


HOUSING

SLOPE 2%
ROOF BELOW
7583 CENTRAL SAANICH RD.,
10 TSAWOUT FIRST NATION
Drawing Title
T.O. PARAPET
35.77M
0"
T.O. PARAPET
35.77M
0"

7'-9"
T.O. PARAPET ROOF PLAN
35.77M
0"

LINE OF WALL BELOW

Drawing No.
11 A2.07

1'-8"
J N
su u n e Project No.

is 1
nr 2
ns 2

e
su u n e
et 1
19323

J
SLOPE

SLOPE

T.O. PARAPET T.O. ROOF T.O. ROOF


2%

2%

© Copyright reserved. These plans and


35.77M
0" 34.70M
0" 34.70M
0"
March 21 W
sunset
March 21
E sunrise designs are and at all times remain the
T.O. PARAPET property of Finlayson Bonet Architecture to be
used for the project shown and may not be
35.77M
0" D reproduced without written consent.
su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
1 2
A4.00 A4.00

14 2 1 7 14 8 1 8 3 14 8 5 2 12 9 14 7 5 1 14 2 5

PROPERTY LINE
PROPERTY LINE
T/O ELEVATOR 36.70M
mf MATERIAL LEGEND
mf

3'-1"
88.32 inch 88.32 inch T/O PARAPET 35.77M 1 HARDIE PANEL - PAINTED BENJAMIN MOORE HORIZON
GRAY 1241-50
mf
2 VERTICAL CORRUGATED METAL SIDING - DARK CHARCOAL
88.32 inch
WINDOW HEIGHT 34.24M
3 HARDIE LAP SIDING - PAINTED

12'-0"
4 WOODTONE RUSTIC SERIES LAPPED SIDING - ASPEN RIDGE

7'-0"
5 METAL FASCIA - CHARCOAL
LEVEL 5 32.11M
6 WOOD FASCIA W/ FIRST NATION ART
WINDOW HEIGHT 31.04M

84.00 inch
7 PREFINISHED METAL GUARD RAIL SYSTEM

10'-6"
W/ OPAQUE GLAZING

7'-0"
mf
8 EXTERIOR PREFINISHED ALUMINUM SUNSHADE

9 FIBRE CEMENT PANEL SIDING - PAINTED BENJAMIN MOORE


LEVEL 4 28.91M HONEYMOON AF-345
10 FIBRE CEMENT PANEL SIDING - PAINTED WHITE
WINDOW HEIGHT 27.83M

[16.77mM]
55'-0"
55'-0"
11 FIBRE CEMENT PANEL SIDING - PAINTED BENJAMIN MOORE

10'-6"
MEXICANA 2172-30

7'-0"
12 FIBRE CEMENT PANEL SIDING - PAINTED CHARCOAL

LEVEL 3 25.71M 13 ARCHITECTURAL CONCRETE FINISH

14 FIBRE CEMENT FASCIA


WINDOW HEIGHT 24.63M
15 CEDAR FENCE

10'-6"
7'-0"
LEVEL 2 22.51M

WINDOW HEIGHT 21.44M

11'-6"
8'-0"
MAIN FLOOR 19.00M

15 2 13 14 1 6 4 7
5 2 3 14 2 11 10 13 14 2 7 1 14 4 2 7
5

2 SOUTH ELEVATION
A3.00 Scale: 1/8" = 1'-0"

3
A4.00

7 5 14 1 8 3 14 2 8 14 1 14 2 5
PROPERTY LINE

PROPERTY LINE
T/O ELEVATOR 36.70M

3'-1"
T/O PARAPET 35.77M
mf mf
84.16 inch 84.16 inch
#4 - 7855 East Saanich Rd.
60.10 inch

60.07 inch
WINDOW HEIGHT 34.24M
Saanichton V8M 2B4

12'-0"
Phone: 250-656-2224
mf

mf
Fax. 250-656-2279

7'-0"
email:
info@finlaysonbonet.ca

Salish LEVEL 5 32.11M

Sea
Art Display Salish
Salish WINDOW HEIGHT 31.04M

10'-6"
1 Sea
Sea

7'-0"
LEVEL 4 28.91M

WINDOW HEIGHT 27.83M

[16.77mM]
55'-0"
55'-0"
10'-6"
21.10.05 ISSUED FOR

7'-0"
CONSTRUCTION
21.05.25 ISSUED FOR TENDER

7 LEVEL 3 25.71M 21.04.23 ISSUED FOR B.P.


Rev Date Description
6 WINDOW HEIGHT 24.63M
Checked SMB/KDS

10'-6"
1 Drawn AV

7'-0"
Scale 1/4"=1'-0"
1 LEVEL 2 22.51M
Date
OCT 05, 2021
WINDOW HEIGHT 21.44M Project Name
SALISH SEA

11'-6"
HOUSING

8'-0"
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
MAIN FLOOR 19.00M Drawing Title

4 13 14 14 1 4 13 14 3 14 2 4 6 1 14 13 7
5
ELEVATIONS
1 WEST ELEVATION
Art Display A3.00 Scale: 1/8" = 1'-0"
2&3 Drawing No.

A3.00
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
PROPERTY LINE
2 1

PROPERTY LINE
A4.00 A4.00

G F E D C B A
5 1 14 2 14 7 1 14 3 5 14 1 2
T/O ELEVATOR 36.70M
MATERIAL LEGEND

3'-1"
T/O PARAPET 35.77M 1 HARDIE PANEL - PAINTED BENJAMIN MOORE HORIZON
GRAY 1241-50
2 VERTICAL CORRUGATED METAL SIDING - DARK CHARCOAL

WINDOW HEIGHT 34.24M


3 HARDIE LAP SIDING - PAINTED

12'-0"
12 4 WOODTONE RUSTIC SERIES LAPPED SIDING - ASPEN RIDGE

7'-0"
5 METAL FASCIA - CHARCOAL
LEVEL 5 32.11M
6 WOOD FASCIA W/ FIRST NATION ART
WINDOW HEIGHT 31.04M
7 PREFINISHED METAL GUARD RAIL SYSTEM

10'-6"
W/ OPAQUE GLAZING
9

7'-0"
8 EXTERIOR PREFINISHED ALUMINUM SUNSHADE

9 FIBRE CEMENT PANEL SIDING - PAINTED BENJAMIN MOORE


LEVEL 4 28.91M HONEYMOON AF-345
10 FIBRE CEMENT PANEL SIDING - PAINTED WHITE
WINDOW HEIGHT 27.83M

[16.77mM]
55'-0"
55'-0"
11 FIBRE CEMENT PANEL SIDING - PAINTED BENJAMIN MOORE

10'-6"
MEXICANA 2172-30
10

7'-0"
12 FIBRE CEMENT PANEL SIDING - PAINTED CHARCOAL

LEVEL 3 25.71M 13 ARCHITECTURAL CONCRETE FINISH

14 FIBRE CEMENT FASCIA


WINDOW HEIGHT 24.63M
15 CEDAR FENCE

10'-6"
11

7'-0"
LEVEL 2 22.51M

WINDOW HEIGHT 21.44M

11'-6"
8'-0"
MAIN FLOOR 19.00M

13
7 14
5 2 13 13
7 14
5 7
5 1 13
7 13 13
7 14
5 7
5 4 13
7 2 12

2 NORTH ELEVATION
A3.01 Scale: 1/8" = 1'-0"

3
A4.00

11 10 9 7 6 5 4 3 2 1
5 7 2 14 5 1 5 14 3 2 14 14 1
PROPERTY LINE

PROPERTY LINE
T/O ELEVATOR 36.70M

3'-1"
T/O PARAPET 35.77M

WINDOW HEIGHT 34.24M #4 - 7855 East Saanich Rd.


Saanichton V8M 2B4

12'-0"
Phone: 250-656-2224

7'-0"
Fax. 250-656-2279
email:
info@finlaysonbonet.ca
LEVEL 5 32.11M

WINDOW HEIGHT 31.04M

10'-6"
7'-0"
LEVEL 4 28.91M

WINDOW HEIGHT 27.83M

[16.77mM]
55'-0"
55'-0"
10'-6"
7'-0"
21.10.05 ISSUED FOR
CONSTRUCTION
LEVEL 3 25.71M 21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.

WINDOW HEIGHT 24.63M Rev Date Description

10'-6"
Checked SMB/KDS

7'-0"
Drawn AV
Scale 1/4"=1'-0"
LEVEL 2 22.51M Date
OCT 05, 2021
WINDOW HEIGHT 21.44M
Project Name
SALISH SEA

11'-6"
HOUSING

8'-0"
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
MAIN FLOOR 19.00M
Drawing Title

14 4 2 3 13 2 14 14 13

ELEVATIONS
1 EAST ELEVATION
A3.01 Scale: 1/8" = 1'-0"
Drawing No.

A3.01
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
A B C D E F G
1
A4.02

4
A6.00
R1
T/O ELEVATOR 36.70M

3'-1"
R1 R1 R1
T/O PARAPET 35.77M
R3

P1 WINDOW HEIGHT 34.24M

12'-11"

12'-0"
ST-1 CORR. P6
UNIT 504 P1
ST-2 CORR. P9 UNIT 506 W8
500 508 510 508

7'-0"
W6 1HR F.R.R F4 1HR F.R.R F4 1HR F.R.R F4 1HR F.R.R D2
LEVEL 5 32.11M

1HR F.R.R P1 WINDOW HEIGHT 31.04M


1HR F.R.R

10'-6"
ST-1 CORR. P6
UNIT 404 P1
ST-2 CORR. P9 UNIT 406 W8
400 408 410 408

7'-0"
W6 F4 1HR F.R.R F4 1HR F.R.R F4 1HR F.R.R D2
LEVEL 4 28.91M

ELEVATOR
1HR F.R.R P1 WINDOW HEIGHT 27.84M

[16.77mM]
55'-0"
55'-0"
10'-6"
ST-1 CORR. P6
UNIT 304 P1
ST-2 CORR. P9 UNIT 306 W8
300 308 310 308

7'-0"
W6 F4 1HR F.R.R F4 1HR F.R.R F4 1HR F.R.R D2
LEVEL 3 25.71M

1HR F.R.R P1 WINDOW HEIGHT 24.64M


W8

10'-6"
ST-1 CORR. P6
UNIT 204 P1
ST-2 CORR. P9 UNIT 206
200 208 210 208

7'-0"
W6 F3 F3 F2 D1
1HR F.R.R 1HR F.R.R F3 1HR F.R.R
LEVEL 2 22.51M

W3
ACC. 1HR F.R.R WINDOW HEIGHT 21.44M
WASH
ST-1 LOBBY ROOM CORRIDOR AMENITY AREA BIKE STORAGE

11'-6"
1HR F.R.R
100 103 107 108 112 P12 114 W10

8'-0"
1
A6.01 F6 F6 F6 F6 F6 F1
MAIN FLOOR 19.00M

4'-0"
3 SECTION
A4.00 Scale: 1/8" = 1'-0"

1 2 3 4 5 6 7 9 10 11

2 1 3
A4.01 A4.01 A4.01

11 10 9 7 6 5 4 3 2 1

6 6 T/O ELEVATOR 36.70M T/O ELEVATOR 36.70M


A6.04 A6.04 mf

3'-1"

3'-1"
R1 R1 R1 R1
T/O PARAPET 35.77M 72.00 inch T/O PARAPET 35.77M
R3 #4 - 7855 East Saanich Rd.
R3 Saanichton V8M 2B4
5 5 1HR F.R.R Phone: 250-656-2224
P17 P17 WINDOW HEIGHT 34.24M WINDOW HEIGHT 34.24M
A6.04 A6.04 12'-0" Fax. 250-656-2279

12'-0"

84.00 inch
P1
W6 email:
W7 P8 P17 P6
UNIT 507 UNIT 506 P15
P17
UNIT 505 info@finlaysonbonet.ca
7'-0"

7'-0"
UNIT 505 CORRIDOR ST-2

mf
W6
D2 F4 1HR F.R.R 1HR F.R.R F4 1HR F.R.R F4
D2 F4
1HR F.R.R 508 510
W6
LEVEL 5 32.11M LEVEL 5 32.11M

5 5 1HR F.R.R
P15
P17 P17 WINDOW HEIGHT 31.04M WINDOW HEIGHT 31.04M
A6.04 A6.04 P1
10'-6"

10'-6"
P8 W8
W7 P17 P6
UNIT 407 UNIT 406 P15 UNIT 405
P17 UNIT 405 CORRIDOR ST-2
7'-0"

7'-0"
W6
D2 F4 F4 F4
D2 F4 408 410
1HR F.R.R 1HR F.R.R 1HR F.R.R 1HR F.R.R
W6
LEVEL 4 28.91M LEVEL 4 28.91M

5 5 1HR F.R.R
WINDOW HEIGHT 27.84M WINDOW HEIGHT 27.84M
[16.77mM]

[16.77mM]
A6.04 P15
P17 A6.04 P17
P1 21.10.05 ISSUED FOR
55'-0"

55'-0"
55'-0"

55'-0"
10'-6"

10'-6"
W7 P8 P17 P6 CONSTRUCTION
UNIT 307 UNIT 306 P15
P17 UNIT 305 W8 CORRIDOR ST-2
UNIT 305 21.05.25 ISSUED FOR TENDER
7'-0"

7'-0"
308 310 W6
D2 F4 F4 F4 F4 21.04.23 ISSUED FOR B.P.
1HR F.R.R 1HR F.R.R 1HR F.R.R D2 1HR F.R.R
W6
LEVEL 3 25.71M LEVEL 3 25.71M Rev Date Description
Checked SMB/KDS
4 P17 4 P17 WINDOW HEIGHT 24.64M 1HR F.R.R WINDOW HEIGHT 24.64M
A6.04 A6.04
Drawn AV
P1
10'-6"

10'-6"
W5 P8 P17 P15 P6 W8
UNIT 207 UNIT 206 UNIT 205 Scale 1/4"=1'-0"
P17 UNIT 205 CORRIDOR ST-2 R1
7'-0"

7'-0"
Date
208 210
D1 F2 F3 1HR F.R.R 1HR F.R.R F2 1HR F.R.R F2 D1 F2 1HR F.R.R OCT 05, 2021
W6
LEVEL 2 22.51M LEVEL 2 22.51M
Project Name
1HR F.R.R
W6
SALISH SEA
WINDOW HEIGHT 21.44M WINDOW HEIGHT 21.44M
W6 W2
ST-2 HOUSING
AMENITY AREA CORR.
11'-6"

11'-6"
PARKING PARKING 110 7583 CENTRAL SAANICH RD.,
112 W2 108
1HR F.R.R GARDEN TSAWOUT FIRST NATION
8'-0"

8'-0"
JAN. P4

F1 F6 111 STORAGE Drawing Title


F6 F1
MAIN FLOOR 19.00M
1HR F.R.R 113
MAIN FLOOR 19.00M

SECTIONS

2 SECTION 1 Drawing No.


A4.00 Scale: 1/8" = 1'-0"
A4.00
SECTION
Scale: 1/8" = 1'-0" A4.00
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
2 3 11 10 2 1
R1 R1
R1 T/O PARAPET 35.77M T/O PARAPET 35.77M T/O PARAPET 35.77M

1'-6"

1'-6"

1'-6"
4
1 T/O ROOF SHEATHING 35.30M T/O ROOF SHEATHING 35.30M 2 T/O ROOF SHEATHING 35.30M
4
A6.02 A6.02 A6.00
R3 R3

WINDOW HEIGHT 34.24M WINDOW HEIGHT 34.24M WINDOW HEIGHT 34.24M

TOP OF SHEATHING
W7 W7

10'-6"

10'-6"

10'-6"
8'-6" (34.70M)
UNIT 503 UNIT 507 UNIT 505

7'-0"

7'-0"

7'-0"
3'-6 1/8"
3'-6 1/8"
1HR F.R.R 1HR F.R.R 1HR F.R.R F4 W6
D2 F4 D2 F4
T.O. CONCRETE LEVEL 5 32.11M T.O. CONCRETE LEVEL 5 32.11M T.O. CONCRETE LEVEL 5 32.11M

T.O. SHEATHING 32.07M T.O. SHEATHING 32.07M T.O. SHEATHING 32.07M

WINDOW HEIGHT 31.04M WINDOW HEIGHT 31.04M WINDOW HEIGHT 31.04M

W7
W7 UNIT 403 UNIT 407 UNIT 405

10'-6"

10'-6"

10'-6"
7'-0"

7'-0"

7'-0"
3'-6 1/8"
3'-6 1/8"
1HR F.R.R 1HR F.R.R 1HR F.R.R F4 W6
D2 F4 D2 F4
T.O. CONCRETE LEVEL 4 28.91M T.O. CONCRETE LEVEL 4 28.91M T.O. CONCRETE LEVEL 4 28.91M

T.O. SHEATHING 38.87M T.O. SHEATHING 38.87M T.O. SHEATHING 38.87M

WINDOW HEIGHT 27.84M WINDOW HEIGHT 27.84M WINDOW HEIGHT 27.84M

55'-0" [16.76]

55'-0" [16.76]

55'-0" [16.76]
W7 UNIT 303 W7 UNIT 307 UNIT 305

10'-6"

10'-6"

10'-6"
1 3
A6.00 A6.00

7'-0"

7'-0"

7'-0"
3'-6 1/8"
3'-6 1/8"

1HR F.R.R 1HR F.R.R 1HR F.R.R F4 W6


D2 F4 D2 F4
T.O. CONCRETE LEVEL 3 25.71M T.O. CONCRETE LEVEL 3 25.71M T.O. CONCRETE LEVEL 3 25.71M

T.O. SHEATHING 25.67M T.O. SHEATHING 25.67M T.O. SHEATHING 25.67M


W7

WINDOW HEIGHT 24.64M WINDOW HEIGHT 24.64M WINDOW HEIGHT 24.64M

UNIT 203 W7 UNIT 207 UNIT 205


10'-6"

10'-6"

10'-6"
4 #4 - 7855 East Saanich Rd.
A6.01 Saanichton V8M 2B4
8 TYPICAL
7'-0"

7'-0"

7'-0"
Phone: 250-656-2224
A6.04 Fax. 250-656-2279
3'-6 1/8"

3'-6 1/8"
email:
info@finlaysonbonet.ca
D1 F2 1HR F.R.R D1 F2 1HR F.R.R F3 1HR F.R.R F2 W6

T.O. CONCRETE LEVEL 2 22.51M T.O. CONCRETE LEVEL 2 22.51M T.O. CONCRETE LEVEL 2 22.51M

6
A6.02

WINDOW HEIGHT 21.44M WINDOW HEIGHT 21.44M WINDOW HEIGHT 21.44M

PARKING AMENITY
11'-6"

11'-6"

11'-6"
AREA PARKING
112
8'-0"

8'-0"

8'-0"
21.10.05 ISSUED FOR
CONSTRUCTION
21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.
F6
Rev Date Description
MAIN FLOOR 19.00M MAIN FLOOR 19.00M MAIN FLOOR 19.00M
Checked SMB/KDS
Drawn AV
FND1
Scale 1/4"=1'-0"
Date
OCT 05, 2021
Project Name
SALISH SEA
HOUSING
7583 CENTRAL SAANICH RD.,
3 WALL SECTION 2 WALL SECTION 1 WALL SECTION TSAWOUT FIRST NATION

Scale: 1/4" = 1'-0" Scale: 1/4" = 1'-0" Scale: 1/4" = 1'-0" Drawing Title
A4.01 A4.01 A4.01

WALL
SECTIONS

Drawing No.

A4.01
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
G

1'-6" 3'-6"
2 3
R1
R1 T/O PARAPET 35.77M T/O PARAPET 35.77M

4
TOP OF ROOF SHEATHING 35.10M
A6.02
R3

WINDOW HEIGHT 34.20M WINDOW HEIGHT 34.20M

TOP OF SHEATHING

12'-0"
12'-0"
W7 UNIT 506 W8

8'-6" (34.70M)
UNIT 503

6'-10"
6'-10"

3'-6 1/8"
F4
F4 1HR F.R.R 1HR F.R.R D2
T.O. CONCRETE LEVEL 5 32.11M LEVEL 5 32.11M

T.O. SHEATHING 32.07M

WINDOW HEIGHT 31.00M WINDOW HEIGHT 31.00M

W7 UNIT 403 UNIT 406 W8

10'-6"
10'-6"

6'-10"
6'-10"

3'-6 1/8"
F4
F4 1HR F.R.R 1HR F.R.R D2
T.O. CONCRETE LEVEL 4 28.91M LEVEL 4 28.91M

T.O. SHEATHING 38.87M

WINDOW HEIGHT 27.80M WINDOW HEIGHT 27.70M

[16.76mM]
[16.77mM]
UNIT 303 UNIT 306

55'-0"
55'-0"
W7 W8

10'-6"
10'-6"
3 1
A6.00 A6.00

6'-10"
6'-10"

3'-6 1/8"
F4
F4 1HR F.R.R 1HR F.R.R D2
T.O. CONCRETE LEVEL 3 25.71M LEVEL 3 25.71M

#4 - 7855 East Saanich Rd.


T.O. SHEATHING 25.67M Saanichton V8M 2B4

Phone: 250-656-2224
WINDOW HEIGHT 24.60M WINDOW HEIGHT 24.60M Fax. 250-656-2279
email:
W8 info@finlaysonbonet.ca
W7 UNIT 203 UNIT 206

10'-6"
10'-6"

6'-10"
6'-10"

3'-6"
8
A6.04
R2 F2 1HR F.R.R 1HR F.R.R F2 D1

T.O. CONCRETE LEVEL 2 22.51M LEVEL 2 22.51M


6"

WINDOW HEIGHT 21.30M WINDOW HEIGHT 21.30M 21.10.05 ISSUED FOR


BIKE STORAGE CONSTRUCTION

PARKING 114 21.05.25 ISSUED FOR TENDER

11'-6"
11'-6"

W10 21.04.23 ISSUED FOR B.P.


Rev Date Description

7'-6"
Checked SMB/KDS
Drawn AV
Scale 1/4"=1'-0"
F1 Date
MAIN FLOOR 19.00M MAIN FLOOR 19.00M OCT 05, 2021
Project Name
FND2 SALISH SEA
HOUSING
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
Drawing Title

WALL
2
SECTIONS
WALL SECTION
A4.02 Scale: 1/4" = 1'-0"

Drawing No.
1
A4.02
SECTION
Scale: 1/4" = 1'-0" A4.02
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
A 4'-0" B
7'-8" 4'-2 1/2"

ROOF ACCESS

D500
A B
3'6 1/8" HIGH GUARD RAIL ST-1
500

8'-0"
WITH WOOD CAP

CONTRASTING STAIR T.O. PARAPET 35.77M


NOSING (TYP.) TACTILE WARNING STRIP

3'-8"
DN 1HR F.R.R
STANDPIPE CONNECTION 1'-0" 1HR F.R.R
(REFER TO MECHANICAL)

11 1/2" 2'-0"
1-1/2" Ø HANDRAIL ST-1
500 ST-1

12'-0"
410
FIXED LADDER IN
FRONT (REFER TO

9'-7"
PLAN)

3'6 1/8" HIGH 1HR F.R.R


6 LEVEL 5 FLOOR PLAN GUARDRAIL

3'-6 1/8"
Scale: 1/4" = 1'-0" 1-1/2" Ø
A5.00 HANDRAIL

LEVEL 5 32.11M
11 1/2"

9 EQ. RISERS
7"

5'-3"
3'-6 1/8"
A B
ST-1

3'-0"
A B
7'-3"

2'-8" 4'-0" 5'-7" 7'-8" 4'-2 1/2" 4'-0" 7'-8" 4'-2 1/2" 400
30.51M

10'-6"
LANDING
1'-0" 1'-0"

9 EQ. RISERS
1'-0" 11 1/2" 1'-0" 11 1/2"
1-1/2" Ø HANDRAIL 1-1/2" Ø HANDRAIL
7 7

5'-3"
3'-6 1/8"
9'-2 1/2"

3'-0"
11 1/2" 2'-0" 11 1/2" 11 1/2" 3'6 1/8" HIGH
GUARDRAIL
RUN RUN

3'-8"

3'-8"
UP D400 UP D200 1-1/2" Ø LEVEL 4 28.91M
1-1/2" Ø CONTINUOUS 1-1/2" Ø CONTINUOUS HANDRAIL 11 1/2"
CONTRASTING STAIR CONTRASTING STAIR
HANDRAIL NOSING (TYP.) HANDRAIL NOSING (TYP.)
ST-1

9 EQ. RISERS
8'-0"

8'-0"
400 ST-1

7"

5'-3"
3'6 1/8" HIGH GUARD RAIL 3'6 1/8" HIGH GUARD RAIL 200
TACTILE WARNING STRIP TACTILE WARNING STRIP
WITH WOOD CAP WITH WOOD CAP
ST-1

3'-0"
3'-8"

3'-8"
DN DN
STANDPIPE CONNECTION 1'-0"
1HR F.R.R
1HR F.R.R STANDPIPE CONNECTION 1'-0"
1HR F.R.R
1HR F.R.R
300
27.31M

10'-6"
(REFER TO MECHANICAL) (REFER TO MECHANICAL) LANDING

9 EQ. RISERS
2'-5 7/8" 11 1/2" 2'-0"
1-1/2" Ø HANDRAIL 1-1/2" Ø HANDRAIL

5'-3"
3'-6 1/8"
9'-2 1/2"

3'-0"
3'6 1/8" HIGH
GUARDRAIL
1-1/2" Ø LEVEL 3 25.71M
HANDRAIL 11 1/2"

9 EQ. RISERS
5 LEVEL 4 FLOOR PLAN 3 LEVEL 2 FLOOR PLAN

7"

5'-3"
A5.00 Scale: 1/4" = 1'-0" A5.00 Scale: 1/4" = 1'-0"
ST-1

3'-0"
200
24.11M

10'-6"
LANDING
#4 - 7855 East Saanich Rd.

7'-6 1/4"
Saanichton V8M 2B4

9 EQ. RISERS
3'6 1/8" HIGH Phone: 250-656-2224
GUARDRAIL

5'-3"
Fax. 250-656-2279
1-1/2" Ø email:

3'-0"
HANDRAIL info@finlaysonbonet.ca

LEVEL 2 22.51M
11 1/2"

6 EQ. RISERS
A B

3'-6 1/8"

3'-5 1/2"
4'-0" 7'-8" 4'-2 1/2" 3'-8" 12'-0"

3'-0"
A B
4'-9"

VESTIBULE

6 7/8"
1'-0" 1'-0"
102 21.45M
1'-0" 11 1/2" 11 1/2" LANDING
1-1/2" Ø HANDRAIL

7'-7 1/2"
7 7 1-1/2" Ø

9 EQ. RISERS
8"
HANDRAIL

11'-6"
9'-1 3/4"
11 1/2"

5'-2"
CONTRASTING STAIR
3'-5"

3'-6 1/8"
NOSING (TYP.) ST-1
RUN
3'-8"

3'-8"
D300

3'-0"
UP

7'-6 1/2"
D100 1-1/2" Ø CONTINUOUS 100
CONTRASTING STAIR ST-1

7'-0"
HANDRAIL 21.10.05 ISSUED FOR
ST-1 NOSING (TYP.) 100 11 1/2" LANDING 19.88M CONSTRUCTION

5 EQ. RISERS
9'-5"
8'-0"

9'-5"

8'-1"
300

6 7/8"
21.05.25 ISSUED FOR TENDER

2'-10 1/2"
3'6 1/8" HIGH GUARD RAIL

3'-0"
3'6 1/8" HIGH GUARD RAIL WITH WOOD CAP 21.04.23 ISSUED FOR B.P.
TACTILE WARNING STRIP TACTILE WARNING STRIP
WITH WOOD CAP
1-1/2" Ø HANDRAIL
3'-8"

3'-8"
19.00M Rev Date Description
DN 1HR F.R.R UP MAIN FLOOR
STANDPIPE CONNECTION 1'-0" 1HR F.R.R STANDPIPE CONNECTION 1'-0" 1HR F.R.R Checked SMB/KDS
1HR F.R.R
(REFER TO MECHANICAL) (REFER TO MECHANICAL)
Drawn AV
8"

Scale 1/4"=1'-0"
1-1/2" Ø HANDRAIL 2'-5 7/8"
11 1/2" Date
OCT 05, 2021
3'-10"

1'-0"

7'-10" 3'-10" 4'-0" Project Name


SALISH SEA
HOUSING
7583 CENTRAL SAANICH RD.,
4 LEVEL 3 FLOOR PLAN 2 MAIN FLOOR PLAN 1 STAIR 1 SECTION TSAWOUT FIRST NATION
A5.00 Scale: 1/4" = 1'-0" A5.00 Scale: 1/4" = 1'-0" A5.00 Scale: 1/4" = 1'-0" Drawing Title

STAR 1
SECTION +
PLANS

Drawing No.

A5.00
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
5'-1" 5'-1" 5'-1"

E E E

6'-7"

6'-7"

6'-7"
8'-0" 3" 8'-0" 3" 8'-0" 3"

4'-4" 3'-8" 3'-8" 3'-8" 3'-8" 3'-8"

SINK
SINK

SINK
MOP

MOP

MOP
TACTILE TACTILE
1HR F.R.R TACTILE 1HR F.R.R WARNING 1HR F.R.R WARNING
WARNING STRIP STRIP
STRIP
D510 D410 D310

8"

8"

8"
7 7 7
CONTRASTING CONTRASTING
STAIR NOSING STAIR NOSING
(TYP.) (TYP.)

5'-2"

5'-2"

5'-2"

5'-2"

5'-2"
ST-2 ST-2 ST-2
410 310

1'-0"

1'-0"
510 1HR F.R.R 1HR F.R.R 1HR F.R.R
7 9 10

11 1/2"

11 1/2"
1'-0"

1'-0"

1'-0"
DN UP DN UP DN
CHAIR RAIL
CHAIR RAIL

11 1/2"

11 1/2"
1HR
1HR F.R.R
F.R.R 1HR F.R.R 1HR F.R.R 1HR F.R.R 1HR F.R.R

RUN

RUN
11 1/2"

RUN

1-1/2" Ø HANDRAIL 1-1/2" Ø HANDRAIL 1-1/2" Ø HANDRAIL


CHAIR RAIL T.O. PARAPET 35.77M

16'-10"
7'-8"

7'-8"

7'-8"
7'-8"

7'-8"
11 1/2"

11 1/2"
RUN

RUN
1-1/2" Ø 1-1/2" Ø 1-1/2" Ø CONTINUOUS
CONTINUOUS CONTINUOUS HANDRAIL
HANDRAIL HANDRAIL

1-1/2" Ø HANDRAIL 1-1/2" Ø HANDRAIL


CONTRASTING CONTRASTING CONTRASTING
STAIR NOSING STAIR NOSING STAIR NOSING 1HR F.R.R
(TYP.) (TYP.) (TYP.)

1'-0"

1'-0"

12'-0"

12'-0"
4'-0"

4'-0"
1HR F.R.R 1HR F.R.R 1HR F.R.R
TACTILE
STANDPIPE CONNECTION WARNING STRIP STANDPIPE CONNECTION STANDPIPE CONNECTION
TACTILE
(REFER TO MECHANICAL) (REFER TO MECHANICAL) WARNING STRIP (REFER TO MECHANICAL) ST-2
510
9 9 9

3'-0"
LEVEL 5 32.11M

11 1/2"

9 EQ. RISERS
STAIR 2 STAIR 2 STAIR 2

5'-3"
6 LEVEL 5 PLAN 5 LEVEL 4 PLAN 4 LEVEL 3 PLAN 1HR F.R.R

7"
Scale: 1/4" = 1'-0" Scale: 1/4" = 1'-0" Scale: 1/4" = 1'-0"

3'-0"
A5.01 A5.01 A5.01
30.51M

10'-6"
LANDING

ST-2

9 EQ. RISERS
410

9'-1 7/8"

5'-3"
3'-0"
LEVEL 4 28.91M

E 11 1/2"

9 EQ. RISERS
5'-3"
8'-0" 1HR F.R.R

7"
3'-8" 3'-8"

3'-0"
E
SINK
MOP

1HR F.R.R TACTILE WARNING STRIP


27.31M

10'-6"
LANDING
ST-2
D210
7 7 310

9 EQ. RISERS
CONTRASTING

9'-1 7/8"
3'-10"

STAIR NOSING

5'-3"
(TYP.)
ST-2
5'-2"

GROUND FLOOR AREA


210

3'-0"
1'-0"

2370 SQ. FT.


DN
1'-0"

1HR F.R.R M.F.E. 19.0M D112b


11 1/2"

UP LEVEL 3 25.71M
1-1/2" Ø CONTINUOUS #4 - 7855 East Saanich Rd.
HANDRAIL Saanichton V8M 2B4
11 1/2"

9 EQ. RISERS
11 1/2"

1HR 1HR
F.R.RF.R.R Phone: 250-656-2224
RUN

5'-3"
1-1/2" Ø HANDRAIL D111 1HR F.R.R Fax. 250-656-2279
D110b email:

7"

3'-0"
JANITOR info@finlaysonbonet.ca
7'-8"

11 1/2"

111
RUN

24.11M

10'-6"
1HR F.R.R MOP LANDING
SINK ST-2
CONTRASTING 210

9 EQ. RISERS
1-1/2" Ø HANDRAIL STAIR NOSING
(TYP.)

5'-3"
1HR F.R.R 1HR F.R.R
1'-0"

3'-0"
CLIENT
SERVICES AREA 3'-11 1/4"
4'-0"

4'-0"

1HR F.R.R [1.2m] 22.51M


109 LEVEL 2
STANDPIPE CONNECTION

9'-6"
TACTILE
WARNING STRIP (REFER TO MECHANICAL)
D109a
1HR F.R.R
9 9
21.10.05 ISSUED FOR

7'-5 1/4"
CONSTRUCTION
11 1/2"

21.05.25 ISSUED FOR TENDER


RUN

CORR.

20 EQ. RISERS
3'-0"
PARKING 108
21.04.23 ISSUED FOR B.P.
6'-7"

ST-2

11'-6"

11'-6"
Rev Date Description
110 GARDEN
Checked SMB/KDS
UP
1HR F.R.R JAN. STORAGE
11 1/2"
ST-2 111 113 Drawn AV
EXIT 110
3'-8"

ROOF D110a 1HR F.R.R Scale 1/4"=1'-0"


AREA

6 7/8"
3'-8" Date
2'-10"

3'-0"
RD 1HR F.R.R OCT 05, 2021
10"

MAIN FLOOR 19.00M


10 10 Project Name
GARDEN STORAGE SALISH SEA
2'-9"

113 HOUSING
D113 7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
Drawing Title

5'-3" 2'-9" 4'-0" 6'-0"


5'-0"

STAR 2
SECTION +
STAIR 2 STAIR 2 PLANS
3 LEVEL 2 PLAN 2 MAIN FLOOR PLAN 1 STAIR 2 SECTION
A5.01 Scale: 1/4" = 1'-0" A5.01 Scale: 1/4" = 1'-0" A5.01 Scale: 1/4" = 1'-0"
Drawing No.

A5.01
Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
22ga PREFINISHED METAL CAP FLASHING
6% SLOPE WITH S LOCK JOINTS AND DRIP EDGE
BOTH SIDES.

SEAL VAPOUR RETARDER TO SHEATHING PERFORATED J-MOLD


MEMBRANE AT INTERSECTION
INSULATED HATCH COVER 2 PLY SBS MODIFIED BITUMEN MEMBRANE
R1
ROOFING

6"
PROTECTION BOARD
CONTINUOUS METAL CLEAT
TAPERED RIGID INSULATION

2" PUCK VENT - TIE IN WITH MOISTURE BARRIER AND


SEALANT

70
SELF ADHERED VAPOUR PERMEABLE SHEATHING

°
MIN. 6" CONTINUOUS RIGID MEMBRANE
INSULATION

FIBRE CEMENT PANEL FASCIA


SELF ADHERED VAPOUR
RETARDER (A.B. / V.B.)
ROOF HATCH FRAME
WITH INTEGRAL DRIP
EDGE FLASHING PROVIDE 3/4" HOLE IN BOTTOM PLATE AND
SHEATHING TO VENT PARAPET THROUGH SOFFIT

APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR


6% SLOPE MINIMUM PROVIDE POSITIVE LAP SEQUENCING
6% SLOPE MINIMUM PRESTRIP SHEATHING
MEMBRANE PRIOR TO FRAMING
PREFIN. METAL CAP ROOF OVERHANG
R1
FLASHING OVER CAP SHEET
SHEATHING MEMBRANE (A.B.)
SEAL VAPOUR BARRIER AT

8" MIN.
TOP
SLOPE MIN. 2% PLATE WITH ACOUSTICAL
SEALANT SLOPE MIN. 2%

SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL

1/2"
FLANGE OF FLASHING. EXTEND ON TO SHEATHING

6"
SPRAY FOAM AT RIM JOIST, MIN. MEMBRANE A MINIMUM OF 3" BEYOND FLASHING
6" THICK
PERFORATED J-MOLD
3" x 1/4" THICK SEAL VAPOUR BARRIER TO 1'-4"
STEEL LADDER SPRAY FOAM PREFINISHED METAL FLASHING
BOLTED TO CURB WITH DRIP EDGE

8"
PREFINISHED METAL SOFFIT
T.O. ROOF SHEATHING 35.10M WITH VENT STRIP
1" Ø METAL RUNG
PERFORATED J-MOLD
7"

1'-0"

APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR


W7 PROVIDE POSITIVE LAP SEQUENCING

SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL


FLANGE OF FLASHING. EXTEND ON TO SHEATHING
MEMBRANE A MINIMUM OF 3" BEYOND FLASHING
4 ROOF HATCH SECTION DETAIL
6 MIL POLYETHYLENE VAPOUR FIBRE CEMENT PANEL SIDING
A6.00 1 1/2" = 1'-0" SCALE BARRIER

PAINTED WOOD CASING PERFORATED J-MOLD

1/2"
WINDOW FLANGE PRE-STRIPPED WITH SELF
ADHERED SHEATHING MAMBRANE

22ga. PREFINISHED METAL HEAD


POLYURETHANE CAULKING AND FLASHING WITH DRIP EDGE
CLOSED CELL FOAM BACKER ROD
ROOF PARAPET AND EYEBROW
2 SECTION DETAIL
A6.00 2" = 1'0" SCALE
W7

APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR


PROVIDE POSITIVE LAP SEQUENCING WHERE POSSIBLE
#4 - 7855 East Saanich Rd.
SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL Saanichton V8M 2B4
FLANGE OF FLASHING. EXTEND ON TO SHEATHING
MEMBRANE A MINIMUM OF 3" BEYOND FLASHING Phone: 250-656-2224
Fax. 250-656-2279
PERFORATED J-MOLD
email:
info@finlaysonbonet.ca
1/2"

SELF ADHERED WATERPROOF MEMBRANE OVER VENTING CHANNEL


5/8" TYPE 'X' DENSGLASS GYPSUM
SHEATHING
22 ga. PREFINISHED METAL FLASHING WITH DRIP EDGE. 6% MIN. PREFINISHED ALUMINUM AND GLAZED
POSITIVE SLOPE GUARD
SEAL VAPOUR BARRIER SEALED TO
FRAMING WITH ACOUSTIC SEALANT PRESSURE TREATED PLYWOOD STRAPPING
PERFORATED ALUMINUM FLATSTOCK TO FACE OF FURRING, PRIOR TO
2"

PAINTED COMB FACED SPRUCE WOOD TRIM. MITRE


F4 VERTICAL PLYWOOD INSTALLATION TRIM JOINTS ON ALL SIDES
SHEATHING MEMBRANE
5 1/2" MAINTAIN 3/4" AIR GAP - PERFORATED ALUMINUM J-MOLD PERFORATED J MOLD
COUNTERSUNK FASTENERS. FILL HOLE WITH
D2 OVERLAP SHEATHING MEMBRANE 2" ON TO VINYL DECK MEMBRANE PAINTABLE POLYURETHANE CAULKING. TYPICAL
2X6 FURRING
1/2" PLYWOOD VINYL DECK MEMBRANE. EXTEND MEMBRANE 8" ON TO
WOOD POST. REFER TO STRUCTURAL FOR MORE
8"

WOOD POST ABOVE


D2 INFORMATION
VINYL DECK MEMBRANE, RETURN UP 2%
MIN. 8" 21.10.05 ISSUED FOR
STRUCTURAL PLATE CONNECTION. REFER TO CONSTRUCTION

6"
STRUCTURAL DRAWINGS FOR MORE INFORMATION. PREFINISHED METAL FLASHING FOR 21.05.25 ISSUED FOR TENDER

2 1/2"
VINYL MEMBRANE TERMINATION WITH 21.04.23 ISSUED FOR BP
DRIP EDGE
SPRAY FOAM INSULATION AT RIM JOIST Rev Date Description

SLOPED DECK JOISTS


Checked SMB/KDS
WOOD BEAM. REFER TO STRUCTURAL FOR MORE
APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR INFORMATION Drawn AV
1'-0" POLYURETHANE CAULKING
PROVIDE POSITIVE LAP SEQUENCING WHERE POSSIBLE
Scale AS NOTED
5/8" TYPE ‘X DENSGLASS SHEATHING
Date
SEAL VAPOUR BARRIER TO SELF ADHERED SHEATHING MEMBRANE 2X4 BLOCKING SEPT 05, 2021
SPRAY INSULATION FLASHING OVER STEEL ANGLE
Project Name
SALISH SEA
22 ga. PREFINISHED METAL FLASHING WITH DRIP EDGE
PREFINISHED METAL SOFFIT WITH VENT STRIP HOUSING
1/2"

5/8" TYPE 'X' EXTERIOR GYPSUM PERFORATED J-MOLD CENTRAL SAANICH RD.,
PERFORATED J-MOLD TSAWOUT FIRST NATION
PREFINISHED METAL SOFFIT COUNTERSUNK FASTENERS. FILL HOLE WITH
WITH VENT STRIP PAINTABLE POLYURETHANE CAULKING. TYPICAL Drawing Title
W7
STRUCTURAL STEEL METAL ANGLE
(REFER TO STRUCTURAL) PAINTED COMB FACED SPRUCE WOOD TRIM.
MITRE TRIM JOINTS ON ALL SIDES
APPLY BEAD OF MASTIC TO TOP OF FLASHING OR
PROVIDE A POSITIVE LAP SEQUENCING 5/8" TYPE 'X' DENSGLASS GYPSUM SECTION DETAILS
PAINTED WOOD CASING SHEATHING
1/2"

SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL


FLANGE OF FLASHING. EXTEND ON TO SHEATHING
MEMBRANE A MINIMUM OF 3" BEYOND FLASHING SHEATHING MEMBRANE
PERFORATED J-MOLD PRESSURE TREATED PLYWOOD
Drawing No.

A6.00
STRAPPING
POLYURETHANE CAULKING AND 22ga. PREFINISHED METAL HEAD
CLOSED CELL FOAM BACKER ROD FLASHING WITH DRIP EDGE WOOD POST. REFER TO
STRUCTURAL
Project No.

BALCONY AT EXTERIOR BASE OF WALL WOOD POST CAP & BASE AT BALCONY EDGE
19323
3 SECTION DETAIL 1 - 1 HR RATED SECTION DETAIL © Copyright reserved. These plans and
designs are and at all times remain the
A6.00 2" = 1'0" SCALE A6.00 2" = 1'0" SCALE property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
MASTIC SEALANT
SAW CUT REGLET W2 CORRIDOR
TERMINATE TOP OF SELF ADHERED MEMBRANE IN
108
COMPATIBLE MASTIC SEALANT

(1070mm)
3'-6 1/8"
CONCRETE FACED XPS TO EXTEND 2" ABOVE MAIN PRE STRIP 6 MIL POLYETHYLENE VAPOUR BARRIER
FLOOR SLAB. CONTINUE BELOW GRADE TO TOP OF UNDER INTERIOR FRAMING ABOVE SLAB. SEAL TO
COLUMN BEYOND FOOTING RIGID INSULATION AND TO CONCRETE WITH ACOUSTIC
SEALANT
PREFINISHED ALUMINUM AND GLASS SELF ADHERED MODIFIED WATERPROOF

2"
GUARD SYSTEM SBS MEMBRANE F6
W7 POLYETHYLENE DRAINAGE MAT

D1 APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR F2 PREFINISHED METAL FLASHING WITH HEMMED EDGE
PROVIDE NEGATIVE LAP SEQUENCING
VAPOUR IMPERMEABLE SELF ADHERED SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL
MEMBRANE ONTOP OF PARAPET, LAP MIN. 2" PARKING SURFACE
FLANGE OF FLASHING. EXTEND ON TO SHEATHING SLOPE 2% AWAY FROM BUILDING
DOWN BOTH SIDES. POSITIVE LAP ONTO MEMBRANE A MINIMUM OF 3" BEYOND FLASHING
ROOFING MEMBRANE AND WALL MEMBRANE
PERFORATED J-MOLD

1/2"
REFER TO ENGINEERED DESIGN OF CONCRETE CURB (REFER
GUARD SYSTEM FOR ANCHOR SIZE & TYPE 22 ga. PREFINISHED METAL FLASHING WITH HEMMED EDGE TO STRUCTURAL)
6% SLOPE 2 PLY SBS MODIFIED ROOFING MEMBRANE RETURN TO WALL FACE
R12 RIGID INSULATION SEAL VAPOUR BARRIER
SEALED TO CONC. CURB
22ga PREFINISHED METAL CAP FLASHING 2 PLY SBS TORCH ON WATERPROOF WITH ACOUSTIC SEALANT DRAIN ROCK AGAINST POLYETHYLENE
WITH S LOCK JOINTS AND DRIP EDGE MEMBRANE DRAINAGE MAT
BOTH SIDES.

CURB
MIN.
MIN. 2" SLOPED RIGID INSULATION BENTONITE WATERSTOP SELF ADHERED WATERPROOF MEMBRANE

6"

6"
(OR SIMILAR) AT COLD
JOINT
22.51M 2ND LEVEL POLYETHYLENE DRAINAGE MAT

CONTINUOUS METAL CLEAT FDN1


SEALANT ON TOP SIDE OF PLATE
EPOXY EMBEDED FASTENERS

SELF ADHERED VAPOUR PERMEABLE


SHEATHING MEMBRANE SLOPE FOOTING 2% AWAY FROM
BUILDING
FILTER FABRIC OVER
FIBRE CEMENT PANEL FASCIA DRAIN ROCK
BENTONITE WATERSTOP
(OR SIMILAR) AT COLD
JOINT
PERIMETER STORM
EXTERIOR GYPSUM SHEATHING DRAIN (REFER TO MECH.)

PERFORATED FOOTING
PERFORATED J-MOLD DRAIN (REFER TO
MECH.)
AIRCRAFT WIRE SUSPENSION
GALVANIZED HAT TRACK EACH WAY
FOR SUSPENDED SOFFIT AND SUPPORT CONCRETE COLUMN BEYOND
INSULATION

PREFINISHED METAL SOFFIT WITH VENT STRIP

4 SECOND LEVEL BALCONY PARAPET DETAIL 2 FOOTING DETAIL


A6.01 1 1/2" = 1'-0" SCALE A6.01 1 1/2" = 1'-0" SCALE

SELF ADHERED VAPOUR PERMEABLE SHEATHING MEMBRANE

W3

5/8" TYPE 'X' DENSGLASS GYPSUM


EXTEND SELF ADHERED VAPOUR PERMEABLE SHEATHING ST-1 #4 - 7855 East Saanich Rd.
MEMBRANE ON TO VERTICAL LEG OF FLASHING Saanichton V8M 2B4
SHEATHING ON ALL FOUR SIDES OF 100
COLUMN
Phone: 250-656-2224
SELF ADHERED VAPOUR PERMEABLE SELF ADHERED MODIFIED SBS WATERPROOF MEMBRANE Fax. 250-656-2279
SHEATHING MEMBRANE EXTEND MEMBRANE UP WALL 8" BEYOND CONCRETE CLOROPLAST BOND email:
BREAKER info@finlaysonbonet.ca
SELF ADHERED VAPOUR PERMEABLE SHEATHING CONCRETE FACED XPS TO EXTEND 2" ABOVE MAIN FLOOR
MEMBRANE PAINTED COMB FACED SPRUCE WOOD SLAB. CONTINUE BELOW GRADE TO TOP OF FOOTING
TRIM. MITRE TRIM JOINTS ON ALL SIDES
F6
PREFINISHED METAL FLASHING WITH HEMMED EDGE
WOOD POST. (REFER TO
PAINTED COMB FACED SPRUCE WOOD TRIM. STRUCTURAL)
POLYETHYLENE DRAINAGE MAT
COUNTERSUNK FASTENERS. FILL HOLE WITH
PRESSURE TREATED PLYWOOD PAINTABLE POLYURETHANE CAULKING. TYPICAL
STRAPPING SIDEWALK SURFACE
PERFORATED J-MOLD SLOPE 2% AWAY FROM BUILDING
STRUCTURAL KNIFE PLATE CONNECTION C/W THRU
BOLT. REFER TO STRUCTURAL DRAWINGS FOR MORE
INFORMATION. WOOD COLUMN TO BE MIN. 1"
ABOVE CONCRETE PEDESTAL
2 PLY SBS TORCH ON
1"

WATERPROOF MEMBRANE
22ga PREFINISHED METAL FLASHING WITH 21.10.05 ISSUED FOR
CURB
MIN.

CONSTRUCTION
6"

6"

DRIP EDGE
21.05.25 ISSUED FOR TENDER
22.51M 2ND LEVEL 21.04.23 ISSUED FOR BP
SELF ADHERED MODIFIED SBS
WATERPROOF MEMBRANE Rev Date Description
CONTINUOUS METAL CLEAT
SEALANT ON TOP SIDE OF PLATE Checked SMB/KDS
POLYETHYLENE DRAINAGE MAT
EPOXY EMBEDED FASTENERS Drawn AV
SELF ADHERED VAPOUR PERMEABLE SHEATHING FDN1 Scale AS NOTED
MEMBRANE. CONTINUE ONTO FACE OF COLUMN AND SLOPE FOOTING 2% AWAY FROM
OVER LAP WITH SHEATHING MEMBRANE FROM ABOVE Date
BUILDING
SEPT 05, 2021
FILTER FABRIC OVER
FIBRE CEMENT PANEL FASCIA, SMOOTH FINISH DRAIN ROCK
Project Name
- REFER TO ELEVATIONS FOR COLOUR
BENTONITE WATERSTOP SALISH SEA
(OR SIMILAR) AT COLD
JOINT HOUSING
EXTERIOR GYPSUM SHEATHING PERIMETER STORM DRAIN CENTRAL SAANICH RD.,
(REFER TO MECH.) TSAWOUT FIRST NATION
PERFORATED J-MOLD Drawing Title
PERFORATED FOOTING
DRAIN (REFER TO MECH.)
AIRCRAFT WIRE SUSPENSION
GALVANIZED HAT TRACK EACH WAY
FOR SUSPENDED SOFFIT AND SUPPORT CONCRETE COLUMN BEYOND
INSULATION SECTION DETAILS
PREFINISHED METAL SOFFIT WITH VENT STRIP

Drawing No.

A6.01
Project No.
SECOND LEVEL BALCONY PARAPET DETAIL @ WOOD POST FOOTING DETAIL
3 1 19323
A6.01 1 1/2" = 1'-0" SCALE A6.01 1 1/2" = 1'-0" SCALE © Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
1

COUNTERSUNK FASTENERS. FILL HOLE


WITH PAINTABLE POLYURETHANE
CAULKING. TYPICAL W6
PRESSURE TREATED PLYWOOD CONCRETE PAVERS ON ADJUSTABLE
STRAPPING PEDESTALS
PAINTED COMB FACED SPRUCE WOOD
TRIM. MITRE TRIM JOINTS ON ALL SIDES
WRAP COLUMN WITH SELF SELF ADHERED VAPOUR PERMEABLE SHEATING MEMBRANE
ADHERED VAPOUR WOOD POST REFER TO STRUCTURAL FOR 2 PLY SBS MODIFIED ROOFING
PERMEABLE SHEATHING MORE INFORMATION
F2 2% MEMBRANE
MEMBRANE

PROTECTION BOARD

MIN. 2" SLOPED RIGID INSULATION

5/8" DENSGLASS EXTERIOR SHEATHING

8 WOOD POST PLAN DETAIL - TYPICAL


A6.02 SCALE: 2" = 1'-0"
EPOXY EMBEDDED FASTENERS
APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR
PROVIDE POSITIVE LAP SEQUENCING

SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL


FLANGE OF FLASHING. EXTEND ON TO SHEATHING
MEMBRANE A MINIMUM OF 3" BEYOND FLASHING
AIRCRAFT WIRE SUSPENSION CABLING

AIRCRAFT WIRE SUSPENSION 8" MINERAL WOOL BATT INSULATION (R28)


8 X 8 CONCRETE PEDESTAL
PERFORATED J-MOLD
AIRCRAFT WIRE SUSPENDED CEILING

1/2"
WOOD POST REFER TO STRUCUTRAL
22 ga. PREFINISHED METAL FLASHING WITH DRIP EDGE
CHAMFER TOP OF CONCRETE GALVANIZED HAT TRACK FOR
PEDESTAL, SLOPE TO DRAIN GALVANIZED HAT TRACK EACH WAY SUSPENDED SOFFIT
FOR SUSPENDED SOFFIT AND SUPPORT
INSULATION
PREFINISHED METAL SOFFIT WITH VENT
PREFINISHED METAL SOFFIT WITH VENT STRIP STRIP

7 CONCRETE PEDESTAL PLAN DETAIL - TYPICAL 6 SECOND FLOOR SOFFIT DETAIL - TYPICAL 5 SECOND FLOOR SOFFIT DETAIL
A6.02 SCALE: 2" = 1'-0" A6.02 SCALE: 2" = 1'-0" A6.02 SCALE: 2" = 1'-0"

APPLY 1 LAYER OF SHEATHING MEMBRANE ON HEAD


OF ROUGH OPENING PRIOR TO WINDOW INSTALLATION

CAVITY ROCK EXTERIOR INSULATION

FIBRE CEMENT PANEL SIDING


PRESSURE TREATED PLYWOOD STRAPPING

GYPSUM WALLBOARD APPLY BEAD OF MASTIC TO TOP OF VP FLASHING OR


PROVIDE POSITIVE LAP SEQUENCING
6 MIL POLY VAPOUR BARRIER
SELF ADHERED WATERPROOF MEMBRANE ON VERTICAL
R22 ROXUL MINERAL WOOL BATT INSULATION FLANGE OF FLASHING. EXTEND ON TO SHEATHING
MEMBRANE A MINIMUM OF 3" BEYOND FLASHING
SELF ADHERED WATERPROOF MEMBRANE TO WRAP AROUND
PAINT GRADE TRIM BLOCKING AND RETURN MEMBRANE ONTO WINDOW HEAD

PERFORATED J-MOULD
22ga. PREFINISHED METAL HEAD
22ga PREFINISHED METAL CAP FLASHING
6% SLOPE WITH S LOCK JOINTS AND DRIP EDGE SEAL VAPOUR BARRIER TO ROUGH OPENING FLASHING WITH DRIP EDGE
BOTH SIDES. WITH ACOUSTICAL CAULKING
POLYURETHANE CAULKING AT INSIDE OF WINDOW FRAME
SEAL VAPOUR RETARDER TO SHEATHING PERFORATED J-MOLD POLYURETHANE CAULKING AND CLOSED CELL
FOAM BACKER ROD VINYL WINDOWS. REFER TO WINDOW
MEMBRANE AT INTERSECTION SCHEDULE
R1 2 PLY SBS MODIFIED BITUMEN MEMBRANE
ROOFING
3 WINDOW @ HEAD DETAIL - FIBRE CEMENT SIDING
6"

PROTECTION BOARD A6.02


CONTINUOUS METAL CLEAT SCALE: 2" = 1'-0"
TAPERED RIGID INSULATION

2" PUCK VENT - TIE IN WITH MOISTURE BARRIER AND


SEALANT
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
SELF ADHERED VAPOUR PERMEABLE SHEATHING
MIN. 6" CONTINUOUS RIGID MEMBRANE POLYURETHANE CAULKING AND CLOSED
INSULATION CELL FOAM BACKER ROD
Phone: 250-656-2224
Fax. 250-656-2279
VINYL OR FIBRE GLASS FRAME WINDOWS. email:
FIBRE CEMENT PANEL FASCIA 3/4" ALUMINUM ANGLE REFER TO WINDOW SCHEDULE
SELF ADHERED VAPOUR info@finlaysonbonet.ca
RETARDER (A.B. / V.B.) FOIL FACED PLYWOOD SILL
3/8" SHIMS BEHIND NAILING FLANGE
PROVIDE 3/4" HOLE IN BOTTOM PLATE AND
SHEATHING TO VENT PARAPET THROUGH SOFFIT PAINT GRADE TRIM
SEAL VAPOUR BARRIER TO ROUGH OPENING 22 ga. PREFINISHED METAL SILL FLASHING FASTENED WITH
WITH ACOUSTICAL CAULKING UPTURN AT SILL. 1" END DAMS
PRESTRIP SHEATHING SELF ADHERED WATERPROOF MEMBRANE TO WRAP AROUND
MEMBRANE PRIOR TO FRAMING BLOCKING AND ON TO SILL. RETURN MEMBRANE UP BACK DAM
ROOF OVERHANG ANGLE
6 MIL POLY VAPOUR BARRIER
PRESSURE TREATED WOOD / PLYWOOD STRAPPING
SHEATHING MEMBRANE (A.B.) R22 ROXUL MINERAL WOOL BATT INSULATION
GYPSUM WALLBOARD
SELF ADHERED WATERPROOF R3
MEMBRANE OVER VERTICAL FIBRE CEMENT PANEL SIDING
FLANGE OF FLASHING
CAVITY ROCK EXTERIOR INSULATION
21.10.05 ISSUED FOR
CONSTRUCTION
PERFORATED J-MOLD 2 WINDOW @ SILL DETAIL - FIBRE CEMENT SIDING
2 PLY SBS MODIFIED BITUMEN MEMBRANE 21.05.25 ISSUED FOR TENDER
SPRAY FOAM AT RIM JOIST, MIN. PREFINISHED METAL FLASHING 2% ROOFING, LAP ON TO FACE OF ROOF A6.02 SCALE: 2" = 1'-0"
6" THICK 1'-4" FASCIA MIN. 6" 21.04.23 ISSUED FOR BP
WITH DRIP EDGE
Rev Date Description
SEAL VAPOUR BARRIER TO PREFINISHED METAL FLASHING OVER
SPRAY FOAM BALCONY ROOF WITH DRIP EDGE C/W Checked SMB/KDS
CONTINUOUS METAL CLEAT
SLOPED 2x BALCONY ROOF JOISTS Drawn AV
Scale AS NOTED
PROVIDE BLOCKING TO IN-FILL PREFINISHED METAL FASCIA FLASHING PRESSURE TREATED PLYWOOD STRAPPING PREFINISHED METAL J-MOLD ATTACHED TO
SPACE STRAPPING Date
WITH DRIP EDGE C/W CONTINUOUS
METAL CLEAT SEPT 05, 2021
FIBRE CEMENT PANEL SIDING SELF ADHERED WATERPROOF MEMBRANE TO WRAP AROUND POLYURETHANE CAULKING WITH CLOSED
SELF ADHERED VAPOUR PERMEABLE
SHEATHING MEMBRANE BLOCKING AND RETURN ON TO JAMB OPENING CELL FOAM BACKER ROD Project Name
FIBRE CEMENT PANEL SIDING SALISH SEA
HOUSING
1/2"

VINYL WINDOWS. REFER TO WINDOW SCHEDULE


PREFINISHED METAL SOFFIT
5'-0" WITH VENT STRIP SELF ADHERED WATERPROOF MEMBRANE / BUILDING PAPER
JAMB LINER. APPLY WATERPROOF MEMBRANE UP TO 8" ABOVE CENTRAL SAANICH RD.,
PREFINISHED METAL SOFFIT SILL LEVEL, APPLY BUILDING PAPER ABOVE TO U/S OF WINDOW TSAWOUT FIRST NATION
5/8" TYPE ‘X DENSGLASS HEAD
WITH VENT STRIP SHEATHING Drawing Title
POLYURETHANE CAULKING AT INSIDE OF WINDOW
CAVITY ROCK EXTERIOR INSULATION FRAME
POLYURETHANE CAULKING AND CLOSED
CELL FOAM BACKER ROD
PERFORATED J-MOLD

FIBRE CEMENT PANEL SIDING


SEAL VAPOUR BARRIER TO ROUGH OPENING WITH
POLYURETHANE CAULKING
DETAILS
6 MIL POLYETHYLENE VAPOUR
BARRIER

Drawing No.

A6.02
GYPSUM WALLBOARD
PAINTED WOOD CASING PERFORATED J-MOLD R22 ROXUL MINERAL WOOL BATT INSULATION
1/2"

22ga. PREFINISHED METAL HEAD 6 MIL POLY VAPOUR BARRIER Project No.
FLASHING WITH DRIP EDGE
4
ROOF PARAPET / EYEBROW
SECTION DETAIL AND BALCONY OVERHANG
PAINT GRADE TRIM
1 WINDOW @ JAMB DETAIL - FIBRE CEMENT SIDING 19323
SEAL VAPOUR BARRIER TO
A6.02 © Copyright reserved. These plans and
FRAMING 2" = 1'0" SCALE A6.02 SCALE: 2" = 1'-0" designs are and at all times remain the
property of Finlayson Bonet Architecture to be
POLYURETHANE CAULKING AND used for the project shown and may not be
reproduced without written consent.
CLOSED CELL FOAM BACKER ROD
W12

W2 W1

2x8 SPF WOOD STUDS @ 16" O.C W/ R28

6MIL POLYETHYLENE VAPOUR BARRIER

1"
5/8" TYPE 'X' GYPSUM WALLBOARD

STEEL ANGLE SET IN CONINUOUS


BEAD OF POLYURETHANE CAULKING

1/2" PLYWOOD SHEATHING TO


PROTECT DRYWALL HOLLOW STEEL METAL DOOR

ANCHOR BOLT
5/8" TYPE 'X' GYPSUM WALLBOARD

5/8" TYPE 'X' GYPSUM WALLBOARD

6MIL POLYETHYLENE VAPOUR BARRIER

SET DOOR FRAME INTO CONTINUOUS BEAD OF


POLYURETHANE CAULKING

W12 POLYURETHANE CAULKING


PREFINISHED METAL HAIRPIN FLAHSING WITH
HEMMED EDGE
Z-GIRTS @ 16" O.C
SELF ADHERED WATERPROOF MEMBRANE TO
WRAP AROUND AND RETURN ON TO JAMB W4 W5
VAPOUR PERMEABLE SELF ADHERED
OPENING SHEATHING MEMBRANE
POLYURETHANE CAULKING
CEDAR SIDING WITH T+G V-GROOVE
VAPOUR PERMEABLE SELF ADHERED
SHEATHING MEMBRANE 1 1/2" CAVITY ROCK INSULATION 5/8" TYPE 'X' GYPSUM WALLBOARD
W12
CEDAR SIDING WITH T+G V-GROOVE 2x6 SPF WOOD STUDS @ 16" O.C W/ R22
3/4 P.T PLYWOOD STRAPPING @ 16" O.C

6MIL POLYETHYLENE VAPOUR BARRIER

6 4 1/2" PLYWOOD SHEATHING TO


PLAN DETAIL INSIDE CORNER PLAN DETAIL AT METAL DOOR JAM - CEDAR SIDING PROTECT DRYWALL
A6.03 SCALE: 2" = 1'-0" A6.03 SCALE: 2" = 1'-0"
5/8" TYPE 'X' GYPSUM WALLBOARD

PRESTRIP OF 5/8" DENSGLASS


EXTERIOR SHEATHING TO SEPARATE
WOOD FRAMING FROM STEEL
STUDS

PRESTRIP OF VAPOUR
PERMEABLE SHEATHING
MEMBRANE PRIOR TO
1.0 HOUR INSTALLING STEEL STUD
WALL
SELF ADHERED VAPOUR PERMEABLE
W6 SHEATHING MEMBRANE
5/8" TYPE 'X' DENSGLASS
EXTERIOR SHEATHING
5/8" TYPE 'X' DENSGLASS EXTERIOR SHEATHING

PREFINISHED METAL J-MOLD FLASHING

POLYURETHANE CAULKING & BACKER ROD

OUTSIDE CORNER METAL FLASHING.


COLOUR TO MATCH CORRUGATED METAL
P4 ADDITIONAL LAYER OF SHEATHING
MEMBRANE AT ALL CORNERS W10
5/8" TYPE 'X' GYPSUM WALLBOARD 5/8" TYPE 'X' GYPSUM WALLBOARD
#4 - 7855 East Saanich Rd.
1/2" PLYWOOD SHEATHING Saanichton V8M 2B4
P15
SEAL VAPOUR BARRIER TO 2 PLAN DETAIL INSIDE CORNER - CORRUGATED SIDING
CONCRETE WITH Phone: 250-656-2224
POLYURETHANE CAULKING A6.03 SCALE: 2" = 1'-0" Fax. 250-656-2279
REINFORCED CONCRETE WALL (REFER TO
STRUCTURAL) email:
info@finlaysonbonet.ca

1/2" GALVANIZED HAT CHANNELS @ 16" O/C


P5
W10
6 MIL POLY VAPOUR BARRIER
5/8" TYPE 'X' DENSGLASS EXTERIOR SHEATHING
5/8" TYPE 'X' GYPSUM WALLBOARD 5/8" TYPE 'X' GYPSUM WALLBOARD
1/2" GALVANIZED HAT CHANNELS @ 16" O/C
6" 25ga. STEEL STUDS @ 16" O.C
1 1/2" CAVITY ROCK INSULATION
1/2" PLYWOOD SHEATHING

5/8" TYPE 'X' GYPSUM WALLBOARD

5/8" TYPE 'X' GYPSUM WALLBOARD 21.10.05 ISSUED FOR


CORRUGATED METAL SIDING C/W COLOUR MATCHED CONSTRUCTION
PAINTED WOOD CASING 6MIL POLYETHYLENE VAPOUR BARRIER FASTENERS (SEE ELEVATIONS FOR COLOUR)
21.05.25 ISSUED FOR TENDER
6 MIL POLY VAPOUR BARRIER 21.04.23 ISSUED FOR BP
5/8" TYPE 'X' GYPSUM WALLBOARD
EXTEND PAST FURRING CHANNELS TO CONCRETE 5/8" TYPE 'X' GYPSUM WALLBOARD REINFORCED CONCRETE Rev Date Description
6MIL POLYETHYLENE VAPOUR BARRIER, SEAL TO COLUMN
SEAL VAPOUR BARRIER TO ROUGH OPENING 2x6 SPF WOOD STUDS @ 16" O.C W/ R22 Checked SMB/KDS
CONCRETE
WITH POLYURETHANE CAULKING
Drawn AV
POLYURETHANE CAULKING WITH
CLOSED CELL FOAM BACKER ROD Scale AS NOTED
SELF ADHERED VAPOUR PERMEABLE 5/8" TYPE 'X' GYPSUM WALLBOARD
Date
SHEATHING MEMBRANE
SEPT 05, 2021
Project Name
ADDITIONAL LAYER OF SHEATHING MEMBRANE
POLYURETHANE CAULKING AT CORNER SALISH SEA
SELF ADHERED WATERPROOF MEMBRANE HOUSING
PREFINISHED METAL HAIRPIN FLAHSING WITH TO WRAP AROUND BLOCKING AND RETURN GALVANIZED Z-GIRTS @ 16" O.C
HEMMED EDGE W3 ON TO JAMB OPENING CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
POLYURETHANE CAULKING 5/8" TYPE 'X' DENSGLASS EXTERIOR PREFINISHED METAL J-MOLD FLASHING
SHEATHING Drawing Title
GALVANIZED Z-GIRTS @ 16" O.C OUTSIDE CORNER METAL FLASHING. COLOUR TO
PREFINISHED METAL J-MOLD FLASHING GALVANIZED Z-GIRTS @ 16" O.C MATCH CORRUGATED METAL
CORRUGATED METAL SIDING C/W CORRUGATED METAL SIDING C/W COLOUR MATCHED
COLOUR MATCHED FASTENERS (SEE W6 PREFINISHED METAL J-MOLD FLASHING GALVANIZED Z-GIRTS @ 16" O.C
FASTENERS (SEE ELEVATIONS FOR COLOUR)
ELEVATIONS FOR COLOUR)
CORRUGATED METAL SIDING C/W COLOUR MATCHED
PLAN DETAILS
5/8" TYPE 'X' DENSGLASS EXTERIOR 5/8" TYPE 'X' DENSGLASS EXTERIOR W10
SHEATHING FASTENERS (SEE ELEVATIONS FOR COLOUR) SHEATHING

SELF ADHERED VAPOUR PERMEABLE


SHEATHING MEMBRANE 6" 25ga. STEEL STUDS @ 16" O.C
Drawing No.

A6.03
Project No.
5
A6.03
PLAN DETAIL AT WINDOW AND CONCRETE COLUMN - CORRUGATED SIDING
SCALE: 2" = 1'-0"
3
A6.03
PLAN DETAIL AT CONCRETE WALL - CORRUGATED SIDING
SCALE: 2" = 1'-0"
1 1
A6.03
PLAN DETAIL OUTSIDE CORNER - CORRUGATED SIDING
SCALE: 2" = 1'-0"
19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
R1 GL

FIBRE CEMENT PANEL SIDING - SMOOTH FINISH WITH


COLOUR MATCHED FASTENERS
P.T TREATED
PLYWOOD STRAPPING
@ MIN.16" O.C
OUTSIDE MITERED CORNER

8"
1/
THIN GAUGE METAL FLASHING ANGLE ONTO
STRAPPING AT CORNER PRIOR TO CLADDING
INSTALL.

1'-2"
LINE OF FIRE SEPARATION BETWEEN SUITES. REFER TO ADDITIONAL LAYER OF
ASSEMBLIES FOR RATING INFORMATION SHEATHING MEMBRANE AT
ALL CORNERS
5/8" TYPE X DENSGLASS GYPSUM SHEATHING. USE IN
ROOF CAVITY ONLY. SHEATHING MEMBRANE

FILL BOTH STUD CAVITIES WITH


ACOUSTICAL BATT INSULATION
EXTEND VAPOUR BARRIER ACROSS TOP PLATES. AFTER FIRE
SEPARATION WORK IS COMPLETE SEAL VAPOUR BARRIER TO
ADJACENT INSTALLATION

SEAL VAPOUR BARRIER IN ACOUSTICAL


SEALANT
INTUMESCENT FIRE CAULKING. HILTI
FS-ONE OR APPROVED EQUIVALENT 1'-0"
THIN GAUGE METAL FLASHING ANGLE ONTO STRAPPING AT
CORNER PRIOR TO CLADDING INSTALL.

SELF ADHERED VAPOUR PERMEABLE 5/8" TYPE 'X' DENSGLASS GYPSUM


SHEATHING MEMBRANE 5 1/2" SHEATHING ON ALL FOUR SIDES OF
COLUMN
P2

PAINTED COMB FACED SPRUCE WOOD


PAINTED COMB FACED SPRUCE WOOD TRIM TRIM. MITRE TRIM JOINTS ON ALL SIDES
WOOD 6" x 6" POST. (REFER TO
STRUCTURAL) 6 SUITE SEPARATION AT ROOF CAVITY SECTION DETAIL
PRESSURE TREATED PLYWOOD
STRAPPING COUNTERSUNK FASTENERS. FILL HOLE WITH A6.04 SCALE: 2" = 1'-0"
PAINTABLE POLYURETHANE CAULKING.
STRUCTURAL KNIFE PLATE CONNECTION C/W TYPICAL 2 EYEBROW PLAN DETAIL
THRU BOLT. REFER TO STRUCTURAL DRAWINGS
FOR MORE INFORMATION. A6.04 SCALE: 2" = 1'-0"
PERFORATED J-MOLD
1"

1" GAP P2
2 PLY SBS TORCH ON
WATERPROOF MEMBRANE ACOUSTICAL SEALANT
8"

INTUMESCENT FIRE CAULKING.


CONCRETE PEDESTAL 8" x 8" x 8" HIGH HILTI FS-ONE OR APPROVED EXTEND ACOUSTICAL UNDERLAY UP ON TO
8" (REFER TO STRUCTURAL) CHAMFER CORNERS OF EQUIVALENT BASE PLATES. SEAL WITH ACOUSTICAL
UPSTAND CAULKING.
RIGID INSULATION G
CONCRETE TOPPING
ACOUSTICAL UNDERLAY

INTUMESCENT FIRE CAULKING. HILTI


FS-ONE OR APPROVED EQUIVALENT
CONTINUOUS BEADS OF ACOUSTICAL
SEALANT
LINE OF FIRE SEPARATION BETWEEN
SUITES. REFER TO ASSEMBLIES FOR
RATING INFORMATION
FILL BOTH JOIST CAVITIES ON EITHER SIDE OF
SUITE SEPARATION WITH ACOUSTICAL BATT W8
INSULATION

WOOD BLOCKING

P2
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
2" XPS SLOPED RIGID
INSULATION Phone: 250-656-2224
Fax. 250-656-2279
2 PLY SBS MODIFIED ROOFING email:
2% MEMBRANE

CURB
info@finlaysonbonet.ca

6"
8 WOOD POST ON CONC. PEDESTAL SECTION DETAIL 5 BASE OF WALL AT SUITE SEPARATION SECTION DETAIL
A6.04 SCALE: 2" = 1'-0" A6.04 SCALE: 2"=1'-0" 2ND LEVEL 22.51M

FILL CAVITIES WITH ACOUSTICAL


BATT INSULATION
LINE OF FIRE SEPARATION
BETWEEN SUITES. REFER TO
ASSEMBLIES FOR RATING SELF ADHERED VAPOUR PERMEABLE
INFORMATION SHEATHING MEMBRANE.
P2

21.10.05 ISSUED FOR


ACOUSTICAL SEALANT ACOUSTICAL SEALANT CONSTRUCTION
21.05.25 ISSUED FOR TENDER
INTUMESCENT FIRE CAULKING. INTUMESCENT FIRE CAULKING.
HILTI FS-ONE OR APPROVED HILTI FS-ONE OR APPROVED 21.04.23 ISSUED FOR BP
EQUIVALENT EQUIVALENT 2" XPS RIGID INSULATION
Rev Date Description
LINE OF FIRE SEPARATION
BETWEEN SUITES. REFER TO CONCRETE SLAB Checked SMB/KDS
ASSEMBLIES FOR RATING EXTERIOR GYPSUM SHEATHING Drawn AV
INFORMATION
Scale 1 1/2"=1'-0"
Date
SEPT 05, 2021
Project Name
APPLY BEAD OF INTUMESCENT FIRE GALVANIZED HAT TRACK EACH WAY SALISH SEA
CAULKING (HILTI FS-ONE OR APPROVED LINE OF FIRE SEPARATION BETWEEN AIRCRAFT WIRE SUSPENSION
EQUIVALENT) PRIOR TO INSTALLING SUITES. REFER TO ASSEMBLIES FOR
FOR SUSPENDED SOFFIT AND SUPPORT
INSULATION
HOUSING
BULKHEAD FRAMING CONTINUOUS BEADS OF ACOUSTICAL RATING INFORMATION CONCRETE COLUMN BEYOND
CENTRAL SAANICH RD.,
SEALANT TSAWOUT FIRST NATION
PREFINISHED METAL SOFFIT WITH Drawing Title
INSULATED MECHANICAL DUCTING. REFER VENT STRIP
TO MECHANICAL DRAWINGS FOR MORE
INFORMATION

DETAILS
STANDARD DROPED CEILING WITH 1/2" GYPSUM
APPLY BEAD OF WALLBOARD
INTUMESCENT FIRE CAULKING
(HILTI FS-ONE OR APPROVED 2 LAYERS 5/8" TYPE 'X' GYPSUM WALLBOARD
EQUIVALENT) PRIOR TO
INSTALLING BULKHEAD Drawing No.
FRAMING
A6.04
Project No.

7 RATED BULKHEAD FRAMING SECTION DETAIL 4 BASE OF WALL TO SLAB AT SUITE SEPARATION SECTION DETAIL 1 SECOND FLOOR SLAB PROJECTION 19323
A6.04 A6.04 © Copyright reserved. These plans and
SCALE: 2" = 1-'0" SCALE: 2"=1'-0" A6.04 SCALE: 2" = 1'-0" designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
A B C D E F G
GENERAL NOTES
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

2. ALL ELEVATIONS ARE IN GEODETIC


1 METERS UNLESS NOTES OTHERWISE.

3. ALL DIMENSIONS ARE TO FACE OF


CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
CENTRELINE OF DOORS AND
WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
COORDINATING REGISTERED
PROFESSIONAL OF ANY
2 DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.

5. DO NOT SCALE THESE DRAWINGS.


FINLAYSON BONET ARCHITECTURE
LTD. IS NOT RESPONSIBLE FOR
ISSUES THAT ARISE FROM A
FAILURE TO COMPLY.

6. THESE DRAWINGS ARE TO BE READ


3 IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
DRAWINGS AND SPECIFICATIONS,
ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
DRAWINGS AND SPECIFICATIONS,
INTERIOR DESIGN DRAWINGS AND
SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
TO THE CONSTRUCTION OF THIS
PARKING PROJECT.
SOFFIT SOFFIT 7. CONTRACTOR TO OBTAIN ALL
9'-6" AFF 9'-6" AFF NECESSARY PERMITS, BYLAW
APPROVALS, AND OBSERVE ALL
REQUIRED SAFETY REGULATIONS
THROUGHOUT THE COURSE OF
CONSTRUCTION
SYMBOL LEGEND
FD FLOOR DRAIN

ROOF / DECK DRAIN

XX ASSEMBLY MARKER

GLAZING TYPE (REFER TO


GX WINDOW SCHEDULE)
4
DOOR TYPE (REFER TO DOOR
DXXX SCHEDULE)

X
SECTION MARKER
AXXX

X DETAIL MARKER
AXXX

X INTERIOR ELEVATION MARKER

XX EXISTING ELEVATION MARKER


X .X
5
NEW ELEVATION MARKER
X.XXXm

H2O VAULT

HATCHED WALL INDICATED


SHEAR WALL (REFER TO STRUCT.)
HATCHED WALL INDICATED LOAD
6 BEARING WALL (REFER TO
STRUCT.)

VESTIBULE
102

GWB 7
9'-6" AFF

GROUND FLOOR AREA


GWB 2370 SQ. FT. #4 - 7855 East Saanich Rd.
7'-6" AFF Saanichton V8M 2B4
CORRIDOR M.F.E. 19.0M
ST-1 108
100 ELEVATOR Phone: 250-656-2224
Fax. 250-656-2279
ACCESSIBLE email:
WASHROOM info@finlaysonbonet.ca
107
GWB
9'-6" AFF JANITOR
111

GWB
9'-6" AFF GWB
9'-6" AFF
GWB
VESTIBULE LOBBY
9'-6" AFF CORRIDORGWB CLIENT
101 103 108 9'-6" AFF SERVICES AREA AMENITY AREA
109 112
21.10.05 ISSUED FOR
GWB CONSTRUCTION
9'-6" AFF
21.05.25 ISSUED FOR TENDER
9
21.04.23 ISSUED FOR B.P.
Rev Date Description
SOFFIT BIKE STORAGE Checked SMB/KDS
9'-6" AFF 114
ELECTRICAL MECHANICAL COMMON GWB Drawn AV
104 LAUNDRY 11'-10" AFF
105 Scale 1/4"=1'-0"
106
UP Date
ST-2 OCT 05, 2021
110
GWB
9'-6" AFF Project Name
RD SALISH SEA
HOUSING
10 7583 CENTRAL SAANICH RD.,
GARDEN STORAGE TSAWOUT FIRST NATION
113
Drawing Title

SOFFIT
9'-6" AFF MAIN FLOOR
REFLECTED
CEILING PLAN

OUTDOOR COVERED PATIO


11 Drawing No.

A7.00
4'-4"

SOFFIT J
su u n e N
Project No.

is 1
nr 2
9'-6" AFF ns 2

e
su u n e
et 1
19323

J
March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
D reproduced without written consent.
su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C D E F G
GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

2. ALL ELEVATIONS ARE IN GEODETIC


METERS UNLESS NOTES OTHERWISE.

BALCONY
1 3. ALL DIMENSIONS ARE TO FACE OF
CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
U/S SOFFIT CENTRELINE OF DOORS AND
7'-6" AFF BULK-HEAD WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
GWB +/-8-2" AFF NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
BEDROOM 3 BEDROOM 2 COORDINATING REGISTERED
GWB 9'-5" AFF GWB 9'-5" AFF PROFESSIONAL OF ANY
DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
BALCONY
2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.
1'-0"
MASTER BEDROOM U/S SOFFIT 5. DO NOT SCALE THESE DRAWINGS.
DINING/LIVING 7'-6" AFF FINLAYSON BONET ARCHITECTURE
GWB 9'-5" AFF GWB 9'-5" AFF BALCONY LTD. IS NOT RESPONSIBLE FOR
STORAGE ISSUES THAT ARISE FROM A
LAUNDRY FAILURE TO COMPLY.
U/S SOFFIT GWB
BULK-HEAD 7'-6" AFF GWB
9'-5" AFF 8'-2" AFF GWB 6. THESE DRAWINGS ARE TO BE READ
GWB +/-8-2" AFF +/-8'-2" AFF IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
BULK-HEAD DRAWINGS AND SPECIFICATIONS,
GWB +/-8-2" AFF ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
UNIT 205 DRAWINGS AND SPECIFICATIONS,
2'-0" 2'-0" 2'-0" 2'-0" 3 BEDROOM 2'-0" INTERIOR DESIGN DRAWINGS AND
1,046 SQ.FT SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
BEDROOM 2 MASTER BEDROOM TO THE CONSTRUCTION OF THIS
GWB 9'-5" AFF GWB 9'-5" AFF PROJECT.
MASTER BEDROOM
DINING/LIVING DINING/LIVING GWB 9'-5" AFF 7. CONTRACTOR TO OBTAIN ALL
GWB 9'-5" AFF GWB 9'-5" AFF NECESSARY PERMITS, BYLAW
BATHROOM GWB APPROVALS, AND OBSERVE ALL
GWB +/-8'-2" AFF REQUIRED SAFETY REGULATIONS
BATHROOM
+/-8'-2" AFF THROUGHOUT THE COURSE OF
GWB CONSTRUCTION
+/-8'-2" AFF
SYMBOL LEGEND
BULK-HEAD FD FLOOR DRAIN
GWB +/-8-2" AFF GWB +/-8-2" AFF
GWB +/-8-2" AFF
KITCHEN ROOF / DECK DRAIN
UNIT 201 GWB
2 BEDROOM +/-8'-2" AFF
768 SQ.FT GWB +/-8-2" AFF
UNIT 203 ASSEMBLY MARKER

1'-0"
GWB XX
2 BEDROOM +/-8'-2" AFF
752 SQ.FT
LAUNDRY GLAZING TYPE (REFER TO
BULK-HEAD GX WINDOW SCHEDULE)
LAUNDRY GWB GWB +/-8-2" AFF
GWB 9'-5" AFF BATHROOM 9'-5" AFF
KITCHEN
GWB
4 DOOR TYPE (REFER TO DOOR
GWB DXXX SCHEDULE)
+/-8'-2" AFF
+/-8'-2" AFF
BEDROOM 2 MASTER BEDROOM
KITCHEN STORAGE X
SECTION MARKER
GWB GWB 9'-5" AFF
+/-8'-2" AFF STORAGE GWB +/-8'-2" AFF GWB AXXX

GWB ENTRY +/-8'-2" AFF


ENTRY +/-7'-2" AFF BATHROOM X DETAIL MARKER
GWB AXXX
GWB 9'-5" AFF GWB
+/-8'-2" AFF +/-8'-2" AFF ENTRY INTERIOR ELEVATION MARKER
GWB
X
MECHANICAL MECHANICAL MECHANICAL +/-8'-2" AFF
XX EXISTING ELEVATION MARKER
GWB
9'-5" AFF
GWB
9'-5" AFF
GWB
9'-5" AFF
X .X
NEW ELEVATION MARKER
5 X.XXXm
STORAGE GWB H2O VAULT

2'-0"
GWB +/-8'-2" AFF
MECHANICAL +/-8'-2" AFF GWB
CORRIDOR GWB +/-8'-2" AFF
HATCHED WALL INDICATED
SD SD
GWB
208 9'-5" AFF SHEAR WALL (REFER TO STRUCT.)
MECHANICAL ELECTRICAL 2'-0"
GWB GWB 9'-7" AFF HATCHED WALL INDICATED LOAD
9'-5" AFF 9'-5" AFF BEARING WALL (REFER TO
1'-0" STRUCT.)
BEDROOM 2 6
FD ENTRY
MECHANICAL GWB 9'-5" AFF
1.0 HR F.R.R. JANITOR
GWB GWB
RATED BULKHEAD FD 9'-5" AFF UNIT 206
9'-5" GWB AFF +/-8'-2" AFF
2 BEDROOM
GWB 752 SQ.FT
ELEC. ENTRY 9'-7" AFF
BATHROOM

2'-0"
7 209 GWB
GWB GWB
A6.04 9'-5" AFF KITCHEN +/-8'-2" AFF
+/-8'-2" AFF STORAGE
GWB EXIT
GWB +/-8'-2" AFF
+/-8'-2" AFF

LAUNDRY GWB
SD 7
GWB 9'-5" AFF 9'-5" AFF
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
EXIT

GWB ST-2 KITCHEN DINING/LIVING


+7'-6" AFF GWB UNIT 204 GWB BALCONY Phone: 250-656-2224
+/-8'-2" AFF 2 BEDROOM 210 +/-8'-2" AFF
GWB 9'-5" AFF
746 SQ.FT Fax. 250-656-2279
2'-0"

SD
U/S SOFFIT email:
ST-1 7'-6" AFF info@finlaysonbonet.ca
ELEVATOR
200

2'-0"
MECHANICAL
GWB
GWB BULK-HEAD BULK-HEAD 9'-5" AFF
9'-3" AFF GWB +/-8-2" AFF
GWB +/-8-2" AFF DINING/LIVING
GWB 9'-5" AFF
FD FD 2'-0" 2'-0" 2'-0"

2'-0"
MASTER BEDROOM BEDROOM 2 ENTRY
ENTRY GWB 9'-5" AFF GWB 9'-5" AFF GWB
GWB 9'-5" AFF BATHROOM
BULK-HEAD
+/-8'-2" AFF GWB
+/-8'-2" AFF GWB +/-8-2" AFF
BATHROOM
GWB KITCHEN BULK-HEAD KITCHEN
MASTER BEDROOM MASTER BEDROOM 21.10.05 ISSUED FOR
+/-8'-2" AFF GWB GWB +/-8-2" AFF GWB
GWB 9'-5" AFF GWB 9'-5" AFF CONSTRUCTION
+/-8'-2" AFF +/-8'-2" AFF
1'-0" 21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.
9
Rev Date Description
Checked SMB/KDS
BALCONY BULK-HEAD
GWB +/-8-2" AFF Drawn AV
LAUNDRY U/S SOFFIT Scale 1/4"=1'-0"
7'-6" AFF LAUNDRY
GWB

2'-9"
9'-5" AFF UNIT 202 UNIT 207 GWB Date
2 BEDROOM 2 BEDROOM 9'-5" AFF OCT 05, 2021
772 SQ.FT 782 SQ.FT
GWB Project Name
+/-8'-2" AFF
SALISH SEA
GWB HOUSING
+/-8'-2" AFF
DINING/LIVING DINING/LIVING 7583 CENTRAL SAANICH RD.,
GWB 9'-5" AFF GWB 9'-5" AFF 10 TSAWOUT FIRST NATION
Drawing Title

BEDROOM 2 BEDROOM 2
GWB 9'-5" AFF GWB 9'-5" AFF
LEVEL 2
REFLECTED
STORAGE STORAGE CEILING PLAN
GWB GWB 9'-5" AFF
+/- 8'-2" AFF

Drawing No.

J
11
N
A7.01
su u n e Project No.

is 1
nr 2
ns 2

e
su u n e
et 1
BALCONY BALCONY
19323

J
U/S SOFFIT U/S SOFFIT March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
7'-6" AFF 7'-6" AFF property of Finlayson Bonet Architecture to be
used for the project shown and may not be
D reproduced without written consent.
su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C D E F G
GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

2. ALL ELEVATIONS ARE IN GEODETIC


METERS UNLESS NOTES OTHERWISE.

BALCONY
1 3. ALL DIMENSIONS ARE TO FACE OF
CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
U/S SOFFIT CENTRELINE OF DOORS AND
7'-6" AFF BULK-HEAD WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
GWB +/-8-2" AFF NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
BEDROOM 3 BEDROOM 2 COORDINATING REGISTERED
GWB 9'-5" AFF GWB 9'-5" AFF PROFESSIONAL OF ANY
DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
BALCONY
2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.
1'-0"
MASTER BEDROOM U/S SOFFIT 5. DO NOT SCALE THESE DRAWINGS.
DINING/LIVING 7'-6" AFF FINLAYSON BONET ARCHITECTURE
GWB 9'-5" AFF GWB 9'-5" AFF BALCONY LTD. IS NOT RESPONSIBLE FOR
STORAGE ISSUES THAT ARISE FROM A
LAUNDRY FAILURE TO COMPLY.
U/S SOFFIT GWB
BULK-HEAD 7'-6" AFF GWB
9'-5" AFF 8'-2" AFF GWB 6. THESE DRAWINGS ARE TO BE READ
GWB +/-8-2" AFF +/-8'-2" AFF IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
BULK-HEAD DRAWINGS AND SPECIFICATIONS,
GWB +/-8-2" AFF ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
UNIT 305 DRAWINGS AND SPECIFICATIONS,
2'-0" 2'-0" 2'-0" 2'-0" 3 BEDROOM 2'-0" INTERIOR DESIGN DRAWINGS AND
1,046 SQ.FT SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
BEDROOM 2 MASTER BEDROOM TO THE CONSTRUCTION OF THIS
GWB 9'-5" AFF GWB 9'-5" AFF PROJECT.
MASTER BEDROOM
DINING/LIVING DINING/LIVING GWB 9'-5" AFF 7. CONTRACTOR TO OBTAIN ALL
GWB 9'-5" AFF GWB 9'-5" AFF NECESSARY PERMITS, BYLAW
BATHROOM GWB APPROVALS, AND OBSERVE ALL
GWB +/-8'-2" AFF REQUIRED SAFETY REGULATIONS
BATHROOM
+/-8'-2" AFF THROUGHOUT THE COURSE OF
GWB CONSTRUCTION
+/-8'-2" AFF
SYMBOL LEGEND
BULK-HEAD FD FLOOR DRAIN
GWB +/-8-2" AFF GWB +/-8-2" AFF
GWB +/-8-2" AFF
KITCHEN ROOF / DECK DRAIN
UNIT 301 GWB
2 BEDROOM +/-8'-2" AFF
768 SQ.FT GWB +/-8-2" AFF
UNIT 303 ASSEMBLY MARKER

1'-0"
GWB XX
2 BEDROOM +/-8'-2" AFF
752 SQ.FT
LAUNDRY GLAZING TYPE (REFER TO
BULK-HEAD GX WINDOW SCHEDULE)
LAUNDRY GWB GWB +/-8-2" AFF
GWB 9'-5" AFF BATHROOM 9'-5" AFF
KITCHEN
GWB
4 DOOR TYPE (REFER TO DOOR
GWB DXXX SCHEDULE)
+/-8'-2" AFF
+/-8'-2" AFF
BEDROOM 2 MASTER BEDROOM
KITCHEN STORAGE X
SECTION MARKER
GWB GWB 9'-5" AFF
+/-8'-2" AFF STORAGE GWB +/-8'-2" AFF GWB AXXX

GWB ENTRY +/-8'-2" AFF


ENTRY +/-7'-2" AFF BATHROOM X DETAIL MARKER
GWB AXXX
GWB 9'-5" AFF GWB
+/-8'-2" AFF +/-8'-2" AFF ENTRY INTERIOR ELEVATION MARKER
GWB
X
MECHANICAL MECHANICAL MECHANICAL +/-8'-2" AFF
XX EXISTING ELEVATION MARKER
GWB
9'-5" AFF
GWB
9'-5" AFF
GWB
9'-5" AFF
X .X
NEW ELEVATION MARKER
5 X.XXXm
STORAGE GWB H2O VAULT

2'-0"
GWB +/-8'-2" AFF
MECHANICAL +/-8'-2" AFF GWB
CORRIDOR GWB +/-8'-2" AFF
HATCHED WALL INDICATED
SD SD
GWB
308 9'-5" AFF SHEAR WALL (REFER TO STRUCT.)
MECHANICAL ELECTRICAL 2'-0"
GWB GWB 9'-7" AFF HATCHED WALL INDICATED LOAD
9'-5" AFF 9'-5" AFF BEARING WALL (REFER TO
1'-0" STRUCT.)
BEDROOM 2 6
FD ENTRY
MECHANICAL GWB 9'-5" AFF
1.0 HR F.R.R. JANITOR
GWB GWB
RATED BULKHEAD FD 9'-5" AFF UNIT 306
9'-5" GWB AFF +/-8'-2" AFF
2 BEDROOM
GWB 752 SQ.FT
ENTRY 9'-7" AFF
ELEC. BATHROOM

2'-0"
7 GWB
309 GWB GWB
A6.04 9'-5" AFF KITCHEN +/-8'-2" AFF
+/-8'-2" AFF STORAGE
GWB EXIT
GWB +/-8'-2" AFF
+/-8'-2" AFF

LAUNDRY GWB
SD 7
GWB 9'-5" AFF 9'-5" AFF
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
EXIT

GWB
ST-2 KITCHEN DINING/LIVING
+7'-6" AFF GWB UNIT 304 310 GWB BALCONY Phone: 250-656-2224
2 BEDROOM GWB 9'-5" AFF
+/-8'-2" AFF +/-8'-2" AFF Fax. 250-656-2279
746 SQ.FT
2'-0"

ST-1 SD
U/S SOFFIT email:
300 7'-6" AFF info@finlaysonbonet.ca
ELEVATOR

2'-0"
MECHANICAL
GWB
GWB BULK-HEAD BULK-HEAD 9'-5" AFF
9'-3" AFF GWB +/-8-2" AFF
GWB +/-8-2" AFF DINING/LIVING
GWB 9'-5" AFF
FD FD 2'-0" 2'-0" 2'-0"

2'-0"
MASTER BEDROOM BEDROOM 2 ENTRY
ENTRY GWB 9'-5" AFF GWB 9'-5" AFF GWB
GWB 9'-5" AFF BATHROOM
BULK-HEAD
+/-8'-2" AFF GWB
+/-8'-2" AFF GWB +/-8-2" AFF
BATHROOM
GWB KITCHEN BULK-HEAD KITCHEN
MASTER BEDROOM MASTER BEDROOM 21.10.05 ISSUED FOR
+/-8'-2" AFF GWB GWB +/-8-2" AFF GWB
GWB 9'-5" AFF GWB 9'-5" AFF CONSTRUCTION
+/-8'-2" AFF +/-8'-2" AFF
1'-0" 21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.
9
Rev Date Description
Checked SMB/KDS
BALCONY BULK-HEAD
GWB +/-8-2" AFF Drawn AV
LAUNDRY U/S SOFFIT Scale 1/4"=1'-0"
7'-6" AFF LAUNDRY
GWB

2'-9"
9'-5" AFF UNIT 302 UNIT 307 GWB Date
2 BEDROOM 2 BEDROOM 9'-5" AFF OCT 05, 2021
772 SQ.FT 782 SQ.FT
GWB Project Name
+/-8'-2" AFF
SALISH SEA
GWB HOUSING
+/-8'-2" AFF
DINING/LIVING DINING/LIVING 7583 CENTRAL SAANICH RD.,
GWB 9'-5" AFF GWB 9'-5" AFF 10 TSAWOUT FIRST NATION
Drawing Title

BEDROOM 2 BEDROOM 2
GWB 9'-5" AFF GWB 9'-5" AFF
LEVEL 3
REFLECTED
STORAGE STORAGE CEILING PLAN
GWB GWB 9'-5" AFF
+/- 8'-2" AFF

Drawing No.

J
11
N
A7.02
su u n e Project No.

is 1
nr 2
ns 2

e
su u n e
et 1
BALCONY BALCONY
19323

J
U/S SOFFIT U/S SOFFIT March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
7'-6" AFF 7'-6" AFF property of Finlayson Bonet Architecture to be
used for the project shown and may not be
D reproduced without written consent.
su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C D E F G
GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

2. ALL ELEVATIONS ARE IN GEODETIC


METERS UNLESS NOTES OTHERWISE.

BALCONY
1 3. ALL DIMENSIONS ARE TO FACE OF
CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
U/S SOFFIT CENTRELINE OF DOORS AND
7'-6" AFF BULK-HEAD WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
GWB +/-8-2" AFF NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
BEDROOM 3 BEDROOM 2 COORDINATING REGISTERED
GWB 9'-5" AFF GWB 9'-5" AFF PROFESSIONAL OF ANY
DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
BALCONY
2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.
1'-0"
MASTER BEDROOM U/S SOFFIT 5. DO NOT SCALE THESE DRAWINGS.
DINING/LIVING 7'-6" AFF FINLAYSON BONET ARCHITECTURE
GWB 9'-5" AFF GWB 9'-5" AFF BALCONY LTD. IS NOT RESPONSIBLE FOR
STORAGE ISSUES THAT ARISE FROM A
LAUNDRY FAILURE TO COMPLY.
U/S SOFFIT GWB
BULK-HEAD 7'-6" AFF GWB
9'-5" AFF 8'-2" AFF GWB 6. THESE DRAWINGS ARE TO BE READ
GWB +/-8-2" AFF +/-8'-2" AFF IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
BULK-HEAD DRAWINGS AND SPECIFICATIONS,
GWB +/-8-2" AFF ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
UNIT 405 DRAWINGS AND SPECIFICATIONS,
2'-0" 2'-0" 2'-0" 2'-0" 3 BEDROOM 2'-0" INTERIOR DESIGN DRAWINGS AND
1,046 SQ.FT SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
BEDROOM 2 MASTER BEDROOM TO THE CONSTRUCTION OF THIS
GWB 9'-5" AFF GWB 9'-5" AFF PROJECT.
MASTER BEDROOM
DINING/LIVING DINING/LIVING GWB 9'-5" AFF 7. CONTRACTOR TO OBTAIN ALL
GWB 9'-5" AFF GWB 9'-5" AFF NECESSARY PERMITS, BYLAW
BATHROOM GWB APPROVALS, AND OBSERVE ALL
GWB +/-8'-2" AFF REQUIRED SAFETY REGULATIONS
BATHROOM
+/-8'-2" AFF THROUGHOUT THE COURSE OF
GWB CONSTRUCTION
+/-8'-2" AFF
SYMBOL LEGEND
BULK-HEAD FD FLOOR DRAIN
GWB +/-8-2" AFF GWB +/-8-2" AFF
GWB +/-8-2" AFF
KITCHEN ROOF / DECK DRAIN
UNIT 401 GWB
2 BEDROOM +/-8'-2" AFF
768 SQ.FT GWB +/-8-2" AFF
UNIT 403 ASSEMBLY MARKER

1'-0"
GWB XX
2 BEDROOM +/-8'-2" AFF
752 SQ.FT
LAUNDRY GLAZING TYPE (REFER TO
BULK-HEAD GX WINDOW SCHEDULE)
LAUNDRY GWB GWB +/-8-2" AFF
GWB 9'-5" AFF BATHROOM 9'-5" AFF
KITCHEN
GWB
4 DOOR TYPE (REFER TO DOOR
GWB DXXX SCHEDULE)
+/-8'-2" AFF
+/-8'-2" AFF
BEDROOM 2 MASTER BEDROOM
KITCHEN STORAGE X
SECTION MARKER
GWB GWB 9'-5" AFF
+/-8'-2" AFF STORAGE GWB +/-8'-2" AFF GWB AXXX

GWB ENTRY +/-8'-2" AFF


ENTRY +/-7'-2" AFF BATHROOM X DETAIL MARKER
GWB AXXX
GWB 9'-5" AFF GWB
+/-8'-2" AFF +/-8'-2" AFF ENTRY INTERIOR ELEVATION MARKER
GWB
X
MECHANICAL MECHANICAL MECHANICAL +/-8'-2" AFF
XX EXISTING ELEVATION MARKER
GWB
9'-5" AFF
GWB
9'-5" AFF
GWB
9'-5" AFF
X .X
NEW ELEVATION MARKER
5 X.XXXm
STORAGE GWB H2O VAULT

2'-0"
GWB +/-8'-2" AFF
MECHANICAL +/-8'-2" AFF GWB
CORRIDOR GWB +/-8'-2" AFF
HATCHED WALL INDICATED
SD SD
GWB
408 9'-5" AFF SHEAR WALL (REFER TO STRUCT.)
MECHANICAL ELECTRICAL 2'-0"
GWB GWB 9'-7" AFF HATCHED WALL INDICATED LOAD
9'-5" AFF 9'-5" AFF BEARING WALL (REFER TO
1'-0" STRUCT.)
BEDROOM 2 6
FD ENTRY
MECHANICAL GWB 9'-5" AFF
1.0 HR F.R.R. JANITOR
GWB GWB
RATED BULKHEAD FD 9'-5" AFF UNIT 406
9'-5" GWB AFF +/-8'-2" AFF
2 BEDROOM
GWB 752 SQ.FT
ENTRY 9'-7" AFF
ELEC. BATHROOM

2'-0"
7 GWB
409 GWB GWB
A6.04 9'-5" AFF KITCHEN +/-8'-2" AFF
+/-8'-2" AFF STORAGE
GWB EXIT
GWB +/-8'-2" AFF
+/-8'-2" AFF

LAUNDRY GWB
SD 7
GWB 9'-5" AFF 9'-5" AFF
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
EXIT

GWB
ST-2 KITCHEN DINING/LIVING
+7'-6" AFF GWB UNIT 404 410 GWB BALCONY Phone: 250-656-2224
2 BEDROOM GWB 9'-5" AFF
+/-8'-2" AFF +/-8'-2" AFF Fax. 250-656-2279
746 SQ.FT
2'-0"

ST-1 SD
U/S SOFFIT email:
400 7'-6" AFF info@finlaysonbonet.ca
ELEVATOR

2'-0"
MECHANICAL
GWB
GWB BULK-HEAD BULK-HEAD 9'-5" AFF
9'-3" AFF GWB +/-8-2" AFF
GWB +/-8-2" AFF DINING/LIVING
GWB 9'-5" AFF
FD FD 2'-0" 2'-0" 2'-0"

2'-0"
MASTER BEDROOM BEDROOM 2 ENTRY
ENTRY GWB 9'-5" AFF GWB 9'-5" AFF GWB
GWB 9'-5" AFF BATHROOM
BULK-HEAD
+/-8'-2" AFF GWB
+/-8'-2" AFF GWB +/-8-2" AFF
BATHROOM
GWB KITCHEN BULK-HEAD KITCHEN
MASTER BEDROOM MASTER BEDROOM 21.10.05 ISSUED FOR
+/-8'-2" AFF GWB GWB +/-8-2" AFF GWB
GWB 9'-5" AFF GWB 9'-5" AFF CONSTRUCTION
+/-8'-2" AFF +/-8'-2" AFF
1'-0" 21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.
9
Rev Date Description
Checked SMB/KDS
BALCONY BULK-HEAD
GWB +/-8-2" AFF Drawn AV
LAUNDRY U/S SOFFIT Scale 1/4"=1'-0"
7'-6" AFF LAUNDRY
GWB

2'-9"
9'-5" AFF UNIT 402 UNIT 407 GWB Date
2 BEDROOM 2 BEDROOM 9'-5" AFF OCT 05, 2021
772 SQ.FT 782 SQ.FT
GWB Project Name
+/-8'-2" AFF
SALISH SEA
GWB HOUSING
+/-8'-2" AFF
DINING/LIVING DINING/LIVING 7583 CENTRAL SAANICH RD.,
GWB 9'-5" AFF GWB 9'-5" AFF 10 TSAWOUT FIRST NATION
Drawing Title

BEDROOM 2 BEDROOM 2
GWB 9'-5" AFF GWB 9'-5" AFF
LEVEL 4
REFLECTED
STORAGE STORAGE CEILING PLAN
GWB GWB 9'-5" AFF
+/- 8'-2" AFF

Drawing No.

J
11
N
A7.03
su u n e Project No.

is 1
nr 2
ns 2

e
su u n e
et 1
BALCONY BALCONY
19323

J
U/S SOFFIT U/S SOFFIT March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
7'-6" AFF 7'-6" AFF property of Finlayson Bonet Architecture to be
used for the project shown and may not be
D reproduced without written consent.
su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
A B C D E F G
GENERAL NOTES
8'-3" 24'-0" 20'-6" 20'-0" 6'-0" 27'-0"
1. ALL DIMENSIONS ARE IN FEET AND
INCHES UNLESS NOTED OTHERWISE.

2. ALL ELEVATIONS ARE IN GEODETIC


METERS UNLESS NOTES OTHERWISE.

BALCONY
1 3. ALL DIMENSIONS ARE TO FACE OF
CONCRETE, FACE OF SHEATHING,
CENTRELINE OF STUD,
U/S SOFFIT CENTRELINE OF DOORS AND
7'-6" AFF BULK-HEAD WINDOWS, AND TO FACE OF ANY
OTHER STRUCTURAL ELEMENT
GWB +/-8-4" AFF NOT LISTED.

4. CONTRACTOR TO VERIFY ALL


DIMENSIONS ON SITE AND INFORM
BEDROOM 3 BEDROOM 2 COORDINATING REGISTERED
GWB 9'-7" AFF GWB 9'-7" AFF PROFESSIONAL OF ANY
DISCREPANCIES PRIOR TO
UNDERTAKING THE PORTION OF
BALCONY
2 WORK WHICH IS IN REFERENCE TO
ANY DISCREPANCY.
1'-0"
MASTER BEDROOM U/S SOFFIT 5. DO NOT SCALE THESE DRAWINGS.
DINING/LIVING 7'-6" AFF FINLAYSON BONET ARCHITECTURE
GWB 9'-7" AFF GWB 9'-7" AFF BALCONY LTD. IS NOT RESPONSIBLE FOR
ISSUES THAT ARISE FROM A
U/S SOFFIT STORAGE LAUNDRY FAILURE TO COMPLY.
BULK-HEAD 7'-6" AFF GWB GWB GWB
GWB +/-8-4" AFF 9'-7" AFF 9'-7" AFF 6. THESE DRAWINGS ARE TO BE READ
+/-8'-4" AFF IN CONJUNCTION WITH ALL
ARCHITECTURAL SPECIFICATIONS,
3 STRUCTURAL DRAWINGS AND
SPECIFICATIONS, MECHANICAL
BULK-HEAD DRAWINGS AND SPECIFICATIONS,
GWB +/-8-4" AFF ELECTRICAL DRAWINGS AND
SPECIFICATIONS, CIVIL DRAWINGS
AND SPECIFICATIONS, LANDSCAPE
UNIT 505 DRAWINGS AND SPECIFICATIONS,
2'-0" 2'-0" 2'-0" 2'-0" 3 BEDROOM 2'-0" INTERIOR DESIGN DRAWINGS AND
1,046 SQ.FT SPECIFICATIONS AND ANY OTHER
CONSULTANT DEEMED PERTINENT
BEDROOM 2 MASTER BEDROOM TO THE CONSTRUCTION OF THIS
GWB 9'-7" AFF GWB 9'-7" AFF PROJECT.
MASTER BEDROOM
DINING/LIVING DINING/LIVING GWB 9'-7" AFF 7. CONTRACTOR TO OBTAIN ALL
GWB 9'-7" AFF GWB 9'-7" AFF BATHROOM NECESSARY PERMITS, BYLAW
BATHROOM GWB GWB APPROVALS, AND OBSERVE ALL
GWB +/-8'-4" AFF +/-8'-4" AFF REQUIRED SAFETY REGULATIONS
+/-8'-4" AFF THROUGHOUT THE COURSE OF
BATHROOM CONSTRUCTION
GWB
+/-8'-4" AFF SYMBOL LEGEND
BULK-HEAD FD FLOOR DRAIN
GWB +/-8-4" AFF GWB +/-8-4" AFF
GWB +/-8-4" AFF
KITCHEN ROOF / DECK DRAIN
UNIT 501 GWB
2 BEDROOM +/-8'-4" AFF
768 SQ.FT GWB +/-8-4" AFF
UNIT 503 ASSEMBLY MARKER

1'-0"
GWB XX
2 BEDROOM +/-8'-4" AFF
752 SQ.FT
LAUNDRY GLAZING TYPE (REFER TO
BULK-HEAD GX WINDOW SCHEDULE)
LAUNDRY GWB GWB +/-8-4" AFF
GWB 9'-7" AFF BATHROOM 9'-7" AFF
KITCHEN
GWB
4 DOOR TYPE (REFER TO DOOR
GWB DXXX SCHEDULE)
+/-8'-4" AFF
+/-8'-4" AFF
BEDROOM 2 MASTER BEDROOM
KITCHEN STORAGE X
SECTION MARKER
GWB GWB 9'-7" AFF
+/-8'-4" AFF STORAGE GWB +/-8'-4" AFF GWB AXXX

GWB ENTRY +/-8'-4" AFF


ENTRY +/-7'-2" AFF BATHROOM X DETAIL MARKER
GWB AXXX
GWB 9'-7" AFF GWB
+/-8'-4" AFF +/-8'-4" AFF ENTRY INTERIOR ELEVATION MARKER
GWB
X
MECHANICAL MECHANICAL MECHANICAL +/-8'-4" AFF
XX EXISTING ELEVATION MARKER
GWB
9'-7" AFF
GWB
9'-7" AFF
GWB
9'-7" AFF
X .X
NEW ELEVATION MARKER
5 X.XXXm
STORAGE GWB H2O VAULT

2'-0"
GWB +/-8'-4" AFF
MECHANICAL +/-8'-4" AFF GWB
CORRIDOR GWB +/-8'-4" AFF
HATCHED WALL INDICATED
SD SD
GWB
508 9'-7" AFF SHEAR WALL (REFER TO STRUCT.)
MECHANICAL ELECTRICAL 2'-0 1/8"
GWB GWB 9'-7" AFF HATCHED WALL INDICATED LOAD
9'-7" AFF 9'-7" AFF BEARING WALL (REFER TO
1'-0" STRUCT.)
BEDROOM 2 6
FD ENTRY
MECHANICAL GWB 9'-7" AFF
1.0 HR F.R.R. JANITOR
GWB GWB
RATED BULKHEAD FD 9'-7" AFF UNIT 506
9'-7" GWB AFF +/-8'-4" AFF
2 BEDROOM
GWB 752 SQ.FT
ENTRY 9'-7" AFF
ELEC. BATHROOM

2'-0"
7 GWB
509 GWB GWB
A6.04 9'-7" AFF KITCHEN +/-8'-4" AFF
+/-8'-4" AFF STORAGE
GWB EXIT
GWB +/-8'-4" AFF
+/-8'-4" AFF

LAUNDRY GWB SD 7
9'-7" AFF
GWB 9'-7" AFF
#4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
EXIT

GWB GWB
UNIT 504 ST-2 KITCHEN DINING/LIVING
9'-7" AFF +7'-6" AFF GWB BALCONY
2 BEDROOM 510 GWB GWB 9'-7" AFF Phone: 250-656-2224
+/-8'-4" AFF +/-8'-4" AFF Fax. 250-656-2279
ST-1 SD 746 SQ.FT
U/S SOFFIT email:
500 7'-6" AFF info@finlaysonbonet.ca
ELEVATOR

2'-0"
ROOF
HATCH MECHANICAL
GWB
BULK-HEAD BULK-HEAD 9'-7" AFF
GWB +/-8-4" AFF
GWB +/-8-4" AFF DINING/LIVING
GWB 9'-7" AFF
FD FD 2'-0" 2'-0" 2'-0"

2'-0"
ENTRY MASTER BEDROOM BEDROOM 2 ENTRY
GWB GWB 9'-7" AFF GWB 9'-7" AFF GWB
+/-8'-4" AFF 9'-7" AFF BATHROOM
BULK-HEAD
GWB
+/-8'-4" AFF GWB +/-8-4" AFF
BATHROOM
GWB KITCHEN BULK-HEAD KITCHEN
MASTER BEDROOM MASTER BEDROOM 21.10.05 ISSUED FOR
+/-8'-4" AFF GWB GWB +/-8-4" AFF GWB
GWB 9'-7" AFF GWB 9'-7" AFF CONSTRUCTION
+/-8'-4" AFF +/-8'-4" AFF
1'-0" 21.05.25 ISSUED FOR TENDER
21.04.23 ISSUED FOR B.P.
9
Rev Date Description
Checked SMB/KDS
BALCONY BULK-HEAD
GWB +/-8-4" AFF Drawn AV
LAUNDRY U/S SOFFIT Scale 1/4"=1'-0"
7'-6" AFF LAUNDRY
GWB
UNIT 502 UNIT 507 GWB Date

2'-0"
9'-7" AFF
2 BEDROOM 2 BEDROOM 9'-7" AFF OCT 05, 2021
772 SQ.FT 782 SQ.FT
GWB Project Name
+/-8'-4" AFF
SALISH SEA
GWB HOUSING
+/-8'-4" AFF
DINING/LIVING DINING/LIVING 7583 CENTRAL SAANICH RD.,
GWB 9'-7" AFF GWB 9'-7" AFF 10 TSAWOUT FIRST NATION
Drawing Title

BEDROOM 2 BEDROOM 2
GWB 9'-7" AFF GWB 9'-7" AFF
LEVEL 5
REFLECTED
STORAGE STORAGE CEILING PLAN
GWB GWB 9'-7" AFF
+/- 8'-4" AFF

Drawing No.

J
11
N
A7.04
su u n e Project No.

is 1
nr 2
ns 2

e
su u n e
et 1
BALCONY BALCONY
19323

J
U/S SOFFIT U/S SOFFIT March 21 W March 21
© Copyright reserved. These plans and
E sunrise designs are and at all times remain the
sunset
7'-6" AFF 7'-6" AFF property of Finlayson Bonet Architecture to be
used for the project shown and may not be
D reproduced without written consent.
su e c

et 1
ns . 2
nr . 2

su e c
S is 1
e

D
D210
D310 208 TO ST-2 310
CORRIDOR 308 210 3 3'0" x 7'0" LH HM PT 45 min. WIRED PANIC PS PT CL, GA, WS

DOOR SCHEDULE
Location Info Door Frame Notes Location Info Door Frame Notes
Door # Door Name Style Size Swing Material Finish Label Glazing Hdwe Material Finish Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
MAIN FLOOR LEVEL 4
2
D100 EXTERIOR TO ST-1 100 3 3'0" x 7'0" LHR HM PT - - PANIC PS PT CL, GA D200
D400 CORRIDOR 408
208 TO ST-1 400
200 3 3'0" x 7'0" RH HM PT 45 min. WIRED PANIC PS PT CL, WS
D101 EXTERIOR TO VESTIBULE 101 2 3'0" x 8'0" LHR AL/GL FACTORY - - ENTRY AL FACTORY CL, GA, MC D201a
D401a CORRIDOR 408
208 TO UNIT 401
201 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D102 EXTERIOR TO VESTIBULE 102 3 3'0" x 7'0" LHR HM PT - - ENTRY PS FACTORY CL, GA, MC D201b
D401b UNIT 401
201 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D103a VESTIBULE 101 TO LOBBY 103 3 3'0" x 7'0" LHR HM PT - - P/PULL PS PT CL, WS D201c
D401c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D103b VESTIBULE 102 TO LOBBY 103 3 3'0" x 7'0" LHR HM PT 45 min. WIRED PANIC PS PT CL, WS, GA D202a
D402a CORRIDOR 408
208 TO UNIT 402
202 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D104 EXTERIOR TO ELECTRICAL 104 1 3'0" x 7'0" RHR HM PT - - ENTRY PS PT CL, GA D202b
D402b UNIT 402
202 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D105 LOBBY 103 TO MECHANICAL ROOM 105 1 3'0" x 7'0" LH HM PT 45 min. - ENTRY PS PT CL, GA D202c
D402c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D106 LOBBY 103 TO LAUNDRY ROOM 106 3 3'0" x 7'0" LH HM PT 0.0 HR TEMP'D PANIC PS PT CL, WS, GA D203a
D403a CORRIDOR 408
208 TO UNIT 403
203 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D107 CORRIDOR 108 TO ACC W/C 107 1 3'0" x 7'0" LH SCW PT 45 min. - PRIVACY WD PT CL, WS D203b
D403b UNIT 403
203 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D108 CORRIDOR 108 TO EXTERIOR 2 3'0" x 8'0" RH AL/GL FACTORY - - ENTRY AL FACTORY CL, GA, MC D203c
D403c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D109a EXTERIOR TO CLIENT SERVICES AREA 109 2 3'0" x 8'0" RHR AL/GL FACTORY - - ENTRY AL FACTORY CL, GA, MC D204a
D404a CORRIDOR 408
208 TO UNIT 404
204 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D109b CLIENT SERVICES AREA 109 TO CORRIDOR 108 2 3'0" x 7'0" RHR SCW PT - TEMP'D PRIVACY WD PT CL, WS D204b
D404b UNIT 404
204 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D110a EXTERIOR TO ST-2 110 1 3'0" x 7'0" LHR HM PT - - PANIC PS PT CL, GA D204c
D404c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D110b ST-2 110 TO CORRIDOR 108 3 3'0" x 7'0" RHR HM PT 45 min. WIRED PANIC PS PT CL, WS, GA D205a
D405a CORRIDOR 408
208 TO UNIT 405
205 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D111 CORRIDOR 108 TO JANITOR CLOSET 1 3'0" x 7'0" LHR HM PT 45 min. - ENTRY PS PT CL, GA D205b
D405b UNIT 405
205 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D112a EXTERIOR TO AMENITY 112 4 2 - 3'0" x 8'0" RHR / LHR AL/GL FACTORY - - ENTRY AL FACTORY CL, GA, MC D205c
D405c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D112b AMENITY 112 TO CORRIDOR 108 2 3'0" x 7'0" RHR SCW PT - TEMP'D PRIVACY WD PT CL, WS D206a
D406a CORRIDOR 408
208 TO UNIT 406
206 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D113 EXTERIOR TO GARDEN STORAGE 113 1 2 - 3'0" x 7'0" RHR / LHR HM PT - - ENTRY WD PT CL, GA D206b
D406b UNIT 406
206 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D114 EXTERIOR TO BIKE STORAGE 114 3 3'0" x 7'0" LHR HM PT - - ENTRY PS PT CL, GA D206c
D406c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D207a
D407a 208 TO UNIT 407
CORRIDOR 408 207 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D207b
D407b 207 - BALCONY
UNIT 407 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D207c
D407c 208 TO MECH. CLOSET
CORRIDOR 408 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
Location Info Door Frame Notes
D208
D408 208 TO JANITOR CLOSET
CORRIDOR 408 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
D209
D409 208 TO ELECT. ROOM 409
CORRIDOR 408 209 1 3'0" x 7'0" LH HM PT 45 min. - ENTRY PS PT CL,GA,WS,MC,THROWS
LEVEL 2
D210
D410 208 TO ST-2 410
CORRIDOR 408 210 3 3'0" x 7'0" LH HM PT 45 min. WIRED PANIC PS PT CL, GA, WS
D200 CORRIDOR 208 TO ST-1 200 3 3'0" x 7'0" RH HM PT 45 min. WIRED PANIC PS PT CL, WS
D201a CORRIDOR 208 TO UNIT 201 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D201b UNIT 201 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
Location Info Door Frame Notes
D201c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
D202a CORRIDOR 208 TO UNIT 202 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS LEVEL 5
2
D202b UNIT 202 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D500
D200 CORRIDOR 508
208 TO ST-1 500
200 3 3'0" x 7'0" RH HM PT 45 min. WIRED PANIC PS PT CL, WS
D202c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D501a
D201a CORRIDOR 508
208 TO UNIT 501
201 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D203a CORRIDOR 208 TO UNIT 203 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS D501b
D201b UNIT 201
501 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D203b UNIT 203 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D501c
D201c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D203c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D502a
D202a CORRIDOR 508
208 TO UNIT 502
202 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D204a CORRIDOR 208 TO UNIT 204 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS D502b
D202b UNIT 202
502 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D204b UNIT 204 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D502c
D202c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D204c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D503a
D203a 508 TO UNIT 503
CORRIDOR 208 203 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D205a CORRIDOR 208 TO UNIT 205 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS D503b
D203b UNIT 203
503 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D205b UNIT 205 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D503c
D203c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D205c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D504a
D204a CORRIDOR 508
208 TO UNIT 504
204 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D206a CORRIDOR 208 TO UNIT 206 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS D504b
D204b UNIT 204
504 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D206b UNIT 206 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D504c
D204c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D206c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D505a
D205a 508 TO UNIT 505
CORRIDOR 208 205 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D207a CORRIDOR 208 TO UNIT 207 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS D505b
D205b UNIT 205
505 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D207b UNIT 207 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D505c
D205c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D207c CORRIDOR 208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D506a
D206a CORRIDOR 508
208 TO UNIT 506
206 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D208 CORRIDOR 208 TO JANITOR CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D506b
D206b UNIT 206
506 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D209 CORRIDOR 208 TO ELECT. ROOM 209 1 3'0" x 7'0" LH HM PT 45 min. - ENTRY PS PT CL,GA,WS,MC,THROWS
D506c
D206c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D210 CORRIDOR 208 TO ST-2 210 3 3'0" x 7'0" LH HM PT 45 min. WIRED PANIC PS PT CL, GA, WS
D507a
D207a 508 TO UNIT 507
CORRIDOR 208 207 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D207b
D507b UNIT 507
207 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D207c
D507c CORRIDOR 508
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
Location Info Door Frame Notes
D208
D508 CORRIDOR 508
208 TO JANITOR CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
D209
D509 CORRIDOR 508
208 TO ELECT. ROOM 509
209 1 3'0" x 7'0" LH HM PT 45 min. - ENTRY PS PT CL,GA,WS,MC,THROWS
LEVEL 3
2
D210
D510 CORRIDOR 508
208 TO ST-2 510
210 3 3'0" x 7'0" LH HM PT 45 min. WIRED PANIC PS PT CL, GA, WS
D200
D300 CORRIDOR 308
208 TO ST-1 300
200 3 3'0" x 7'0" RH HM PT 45 min. WIRED PANIC PS PT CL, WS
D201a
D301a CORRIDOR 308
208 TO UNIT 301
201 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D201b
D301b UNIT 301
201 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D201c
D301c CORRIDOR 308
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D202a
D302a CORRIDOR 308
208 TO UNIT 302
202 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D202b
D302b UNIT 203
202 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D202c
D302c CORRIDOR 308
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D203a
D303a CORRIDOR 308
208 TO UNIT 303
203 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D203b
D303b UNIT 303
203 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D203c
D303c CORRIDOR 308
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D204a
D304a CORRIDOR 308
208 TO UNIT 304
204 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D204b
D304b UNIT 304
204 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY -
D204c
D304c CORRIDOR 308
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS #4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
D205a
D305a CORRIDOR 308
208 TO UNIT 305
205 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D205b
D305b UNIT 305
205 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY - Phone: 250-656-2224
Fax. 250-656-2279
D205c
D305c CORRIDOR 308
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
email:
D206a
D306a CORRIDOR 308
208 TO UNIT 306
206 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS info@finlaysonbonet.ca
D206b
D306b UNIT 306
206 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D206c
D306c CORRIDOR 308
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D207a
D307a 208 TO UNIT 307
CORRIDOR 308 207 1 3'0" x 7'0" RH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS
D207b
D307b UNIT 207
307 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - FACTORY VINYL FACTORY -
D207c
D307c 208 TO MECH. CLOSET
CORRIDOR 308 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D208
D308 CORRIDOR 208
308 TO JANITOR CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - - PS PT CL,GA,WS,MC,THROWS
D209
D309 208 TO ELECT. ROOM 309
CORRIDOR 308 209 1 3'0" x 7'0" LH HM PT 45 min. - ENTRY PS PT CL,GA,WS,MC,THROWS RIGHT HAND SWING
LEFT HAND SWING
D210
D310 CORRIDOR 208
308 TO ST-2 210
310 3 3'0" x 7'0" LH HM PT 45 min. WIRED PANIC PS PT CL, GA, WS RIGHT HAND REVERSE SWING
LEFT HAND REVERSE SWING
RIGHT HAND REVERSE ACTIVE LEAF

Door Frame Notes HOLLOW METAL


Location Info SOLID CORE WOOD
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish HOLLOW CORE WOOD 21.10.05 ISSUED FOR
ALUMINUM CONSTRUCTION
LEVEL 4
2 PRESSED STEEL
D200
D400 CORRIDOR 408
208 TO ST-1 400
200 3 3'0" x 7'0" RH HM PT 45 min. WIRED PANIC PS PT CL, WS SOLID WOOD 21.05.25 ISSUED FOR TENDER
GLAZING
D201a
D401a CORRIDOR 408
208 TO UNIT 401
201 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, WS 21.04.23 ISSUED FOR B.P.
D201b
D401b UNIT 401
201 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY - FACTORY FINISH
FACTORY PRIMED - SITE PAINTED Rev Date Description
D201c
D401c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. -
DOOR- SCHEDULE
PS
GENERAL NOTES
PT CL,GA,WS,MC,THROWS CLEAR LACQUER
1. ALL DOORS INDICATED TO HAVE A FIRE RESISTANCE RATING IN SCHEDULE TO HAVE A MAXIMUM CLEAR ANODIZED Checked SMB/KDS
D202a
D402a CORRIDOR 408
208 TO UNIT 402
202 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW
OF A 16mm UNDERCUT BETWEENPT FINISHED FLOORCL,AND
GA, UNDERSIDE
WS OF RATED DOOR. REFER TO NFPA 80 FOR MORE
INFORMATION Drawn AV
D202b
D402b UNIT 402
202 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY - STANDARD FLOAT GLASS
GEORGIAN WIRED GLASS Scale N.T.S.
D202c
D402c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - 2. -ALL DOORS INDICATED
PS TO HAVEPTA FIRE RESISTANCE
CL,GA,WS,MC,THROWS
RATING IN SCHEDULE TO BE PROVIDED WITH TEMPERED GLASS
D203a
D403a CORRIDOR 408
208 TO UNIT 403
203 1 3'0" x 7'0" LH SCW PT 20 min. - POSITIVE
ENTRY LATCHING
SCW HARDWARE PTDESIGNED TO HOLD THE
CL, GA, WSDOOR IN A CLOSED POSITION TO CLEAR CERAMIC FIRE RATED GLAZING Date
ENSURE CONTINUITY OF THE FIRE RESISTANCE RATING OF THE CLOSURE.
D203b
D403b UNIT 403
203 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - FACTORY VINYL FACTORY - OCT 05, 2021
D203c
D403c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - -
ABBREVIATIONS PSUSED IN DOOR PT SCHEDULECL,GA,WS,MC,THROWS
ENTRY KEYED LOCKSET Project Name
D204a
D404a CORRIDOR 408
208 TO UNIT 404
204 1 3'0" x 7'0" LH SCW PT 20 min. - RH ENTRY RIGHT HAND SCWSWING PT CL, GA, P/PULL
WS PUSH - PULL HARDWARE
D204b
D404b UNIT 404
204 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - LH FACTORYLEFT HAND SWING
VINYL FACTORY
OFFICE
- PRIVACY
KEYED LOCKSET WITH INTERIOR BUTTON DOOR SCHEDULE GENERAL NOTES SALISH SEA
LOCKSET WITH INTERIOR BUTTON
D204c
D404c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. -
RHR
-
RIGHT HAND REVERSE SWING
PSREVERSE SWING PT PANIC
CL,GA,WS,MC,THROWS PUSHBAR EXIT DEVICE EQ EQ HOUSING
LHR LEFT HAND
RHRA RIGHT HAND REVERSE ACTIVE LEAF PASSAGE LOCKSET W/O ANY LOCK
D205a
D405a CORRIDOR 408
208 TO UNIT 405
205 1 3'0" x 7'0" LH SCW PT 20 min. - ENTRY SCW PT CL, GA, ROLL/CATCH
WS ROLLER CATCH HARDWARE 7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
D205b
D405b UNIT 405
205 - BALCONY 2 3'0" x 6'6" RH VINYL FACTORY - - HMFACTORYHOLLOWVINYL METAL FACTORY -
SCW SOLID CORE WOOD Drawing Title
D205c
D405c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - HCW - PS
HOLLOW CORE WOOD PT CL,GA,WS,MC,THROWS
D206a
D406a CORRIDOR 408
208 TO UNIT 406
206 1 3'0" x 7'0" RH SCW PT 20 min. - AL ENTRY ALUMINUM SCW PT CL, GA, CL
WS DOOR CLOSER
PS PRESSED STEEL WS WALL STOP
D206b
D406b UNIT 406
206 - BALCONY 2 3'0" x 6'6" LH VINYL FACTORY - - WD FACTORY VINYL
SOLID WOOD FACTORY -
FS FLOOR STOP
D206c
D406c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - GL - GLAZING PS PT CL,GA,WS,MC,THROWS
ELEC
PR
ELECTRIC STRIKE
PROXIMITY READER
DOOR
D207a
D407a
D207b UNIT 207
208 TO UNIT 407
CORRIDOR 408
- BALCONY
207 1
2
3'0" x 7'0"
3'0" x 6'6"
RH
LH
SCW
VINYL
PT
FACTORY
20 min.
-
-
-
ENTRY FACTORYSCW
FACTORY
PT FACTORYFACTORY
FINISH PT
PRIMED - SITEFACTORY
VINYL PAINTED
CL, GA, GA
WS
- KP
WEATHERSTRIPPING GASKETS SCHEDULE
D407b 407 KICKPLATE
CLEAR CLEAR LACQUER THROWS FLUSH BOLTS TOP AND BOTTOM
D207c
D407c CORRIDOR 408
208 TO MECH. CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - ANOD - PS
CLEAR ANODIZED PT CL,GA,WS,MC,THROWS
HC HANDICAP ACTUATOR
D208
D408 CORRIDOR 208
408 TO JANITOR CLOSET 1 2 - 2'0" x 7'0" RHR/LHR HM PT 45 min. - FLOAT - PS
STANDARD FLOAT GLASS PT MC
CL,GA,WS,MC,THROWS MORTISE CYLINDER
PKT POCKET DOOR & DOOR HARDWARE Drawing No.
D209
D409
D210
D410
208 TO ELECT. ROOM 409
CORRIDOR 408
CORRIDOR 208
408 TO ST-2 210
410
209 1
3
3'0" x 7'0"
3'0" x 7'0"
LH
LH
HM
HM
PT
PT
45 min.
45 min.
-
WIRED
ENTRY GEORGIANPS
WIRED
TEMP'D
PANIC PS
WIRED GLASS PT
TEMPERED GLASS
PT
CERAMIC CLEAR CERAMIC FIRE RATED GLAZING
CL,GA,WS,MC,THROWS
CL, GA,
BARN
SRC
WS
BARN STYLE (FACE MOUNT) SLIDING DOOR
SINGLE ROLLER CATCH W/ PASSAGE SET HANDLE TOP OF FLOOR A8.00
1 2 3 4 Project No.

NOTE: 19323
6" x 24" WIRED GLASS © Copyright reserved. These plans and
DOOR SCHEDULE GENERAL NOTES DOOR LITE designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
WDT - FINGER JOINED PAINTED WINDOW TRIM (1 x 3)

CHR - CHAIR RAIL - INSTALL 32" ABOVE FINISHED FLOOR

Location Info Door Frame Notes Location Info Door Frame Notes
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
UNIT 201 401
UNIT 301
D201-1 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D401-1
D301-1 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D201-2 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D401-2
D301-2 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D201-3 LIVING/DINING TO MASTE RBEDROOM 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS D401-3
D301-3 LIVING/DINING TO
LIVING/DINING TO MASTER
MASTERBEDROOM
BEDROOM 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS

UNIT 202 UNIT 402


302
D202-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS D402-1
D302-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS
D202-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS D402-2
D302-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS
D202-3 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D402-3
D302-3 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D202-4 HALL TO LAUNDRY 1 3'0" x 6'9" LHR HCW PT - - PASSAGE WD PT FS D402-4
D302-4 HALL TO LAUNDRY 1 3'0" x 6'9" LHR HCW PT - - PASSAGE WD PT FS

UNIT 203 UNIT 403


303
D203-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS D403-1
D303-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS
D203-2 HALL TO LAUNDRY 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS D403-2
D303-2 HALL TO LAUNDRY 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS
D203-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS D403-3
D303-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS
D203-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D403-4
D303-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS

UNIT 204 UNIT 404


304
D204-1 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D404-1
D304-1 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D204-2 HALL TO LAUNDRY 1 3'0" X 6'8" RHR HCW PT - - PASSAGE WD PT FS D404-2
D304-2 HALL TO LAUNDRY 1 3'0" X 6'8" RHR HCW PT - - PASSAGE WD PT FS
D204-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS D404-3
D304-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS
D204-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D404-4
D304-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS

UNIT 205 UNIT 405


305
D205-1 HALL TO BATHROOM 1 3'0" X 6'8" RHR SCW PT - - PRIVACY WD PT FS D305-1
D405-1 HALL TO BATHROOM 1 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS
D205-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS D305-2
D405-2 HALL TO BATHROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS
D205-3 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D305-3
D405-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS
D205-4 HALL TO DEN 1 2'8" x 6'8" RH SCW PT - - PASSAGE WD PT WS D305-4
D405-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS
D205-5 HALL TO POWDER ROOM 1 2'4" X 6'8" POCKET HCW PT - - PRIVACY WD PT FS D305-5
D405-5 HALL TO BEDROOM 3 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS
D205-6 HALL TO LAUNDRY 1 4'0" X 6'8" RHR/LHR HCW PT - - PASSAGE WD PT FS D305-6
D405-6 HALL TO LAUNDRY CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS

UNIT 206 306


UNIT 406
D206-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D306-1
D406-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS
D206-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS D306-2
D406-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS
D206-3 HALL TO LAUNDRY CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT WS D306-3
D406-3 HALL TO LAUNDRY CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT WS
D206-4 HALL TO BATHROOM 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D306-4
D406-4 HALL TO BATHROOM 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS

UNIT 207 307


UNIT 407
D207-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D307-1
D407-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS
D207-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS D307-2
D407-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS
D207-3 HALL TO BATHROOM 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D307-3
D407-3 HALL TO BATHROOM 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS
D207-4 HALL TO LAUNDRY CLOSET 1 4'0" X 6'8" RHR/LHR HCW PT - - PASSAGE WD PT WS D307-4
D407-4 HALL TO LAUNDRY CLOSET 1 4'0" X 6'8" RHR/LHR HCW PT - - PASSAGE WD PT WS

Location Info Door Frame Notes Location


Location Info
Info Door Frame Notes
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish Door # Door
Door Name
Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
UNIT 301 UNIT 501
301
D301-1 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D301-1
D501-1 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D301-2 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D301-2
D501-2 HALL
HALL TO
TO BATHROOM
BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D301-3 LIVING/DINING TO MASTER BEDROOM 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS D301-3
D501-3 LIVING/DINING
LIVING/DININGTO
TO MASTER
MASTERBEDROOM
BEDROOM 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS

UNIT 302 UNIT 502


302
D302-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS D302-1
D502-1 HALL
HALL TO
TO BATHROOM
BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS
D302-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS D302-2
D502-2 HALL
HALL TO
TO MASTER
MASTER BEDROOM
BEDROOM 11 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT FS
D302-3 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D302-3
D502-3 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D302-4 HALL TO LAUNDRY 1 3'0" x 6'9" LHR HCW PT - - PASSAGE WD PT FS D302-4
D502-4 HALL
HALL TO
TO LAUNDRY
LAUNDRY 1 3'0" x 6'9" LHR HCW PT - - PASSAGE WD PT FS

UNIT 303 UNIT 503


303
D303-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS D303-1
D503-1 HALL
HALL TO
TO BATHROOM
BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT FS
D303-2 HALL TO LAUNDRY 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS D303-2
D503-2 HALL
HALL TO
TO LAUNDRY
LAUNDRY 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS
D303-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS D303-3
D503-3 HALL
HALL TO
TO MASTER
MASTER BEDROOM
BEDROOM 11 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS
D303-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D303-4
D503-4 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS

UNIT 304 UNIT 504


304
D304-1 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS D304-1
D504-1 HALL
HALL TO
TO BATHROOM
BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT FS
D304-2 HALL TO LAUNDRY 1 3'0" X 6'8" RHR HCW PT - - PASSAGE WD PT FS D304-2
D504-2 HALL
HALL TO
TO LAUNDRY
LAUNDRY 1 3'0" X 6'8" RHR HCW PT - - PASSAGE WD PT FS
D304-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS D304-3
D504-3 HALL
HALL TO
TO MASTER
MASTER BEDROOM
BEDROOM 11 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS
D304-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D304-4
D504-4 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS #4 - 7855 East Saanich Rd.
Saanichton V8M 2B4
UNIT 305 305
UNIT 505 Phone: 250-656-2224
D305-1 HALL TO BATHROOM 1 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D305-1
D505-1 HALL
HALL TO
TO BATHROOM
BATHROOM 11 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS Fax. 250-656-2279
email:
D305-2 HALL TO BATHROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D305-2
D505-2 HALL
HALL TO
TO BATHROOM
BATHROOM 22 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS info@finlaysonbonet.ca
D305-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS D305-3
D505-3 HALL
HALL TO
TO MASTER
MASTER BEDROOM
BEDROOM 11 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT WS
D305-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D305-4
D505-4 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS
D305-5 HALL TO BEDROOM 3 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D305-5
D505-5 HALL
HALL TO
TO BEDROOM
BEDROOM 33 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS
D305-6 HALL TO LAUNDRY CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS D305-6
D505-6 HALL
HALL TO
TO LAUNDRY
LAUNDRY CLOSET
CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT FS

UNIT 306 306


UNIT 506
D306-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D306-1
D506-1 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS
D306-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS D306-2
D506-2 HALL
HALL TO
TO MASTER
MASTER BEDROOM
BEDROOM 11 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS
D306-3 HALL TO LAUNDRY CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT WS D306-3
D506-3 HALL
HALL TO
TO LAUNDRY
LAUNDRY CLOSET
CLOSET 1 3'0" X 6'8" LHR
RIGHT HAND SWINGHCW PT - - PASSAGE WD PT WS
D306-4 HALL TO BATHROOM 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D306-4
D506-4 HALL
HALL TO
TO BATHROOM
BATHROOM 1 2'8" x 6'8" LEFTLH
HAND SWING SCW PT - - PRIVACY WD PT WS
RIGHT HAND REVERSE SWING
LEFT HAND REVERSE SWING
UNIT 307 307
UNIT 507 RIGHT HAND REVERSE ACTIVE LEAF
21.10.05 ISSUED FOR
D307-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY WD PT WS D307-1
D507-1 HALL
HALL TO
TO BEDROOM
BEDROOM 22 1 2'8" x 6'8" LH METAL
HOLLOW SCW PT - - PRIVACY WD PT WS CONSTRUCTION
D307-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT WS SOLID CORE WOOD
D307-2
D507-2 HALL
HALL TO
TO MASTER
MASTER BEDROOM
BEDROOM 11 1 3'0" X 6'8" RH CORE WOOD
HOLLOW SCW PT - - PRIVACY WD PT WS 21.05.25 ISSUED FOR TENDER
D307-3 HALL TO BATHROOM 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT WS D307-3
D507-3 HALL
HALL TO
TO BATHROOM
BATHROOM 1 2'8" x 6'8" RH
ALUMINUM SCW PT - - PRIVACY WD PT WS 21.04.23 ISSUED FOR B.P.
PRESSED STEEL
D307-4 HALL TO LAUNDRY CLOSET 1 4'0" X 6'8" RHR/LHR HCW PT - - PASSAGE WD PT WS D307-4
D507-4 HALL
HALL TO
TO LAUNDRY
LAUNDRY CLOSET
CLOSET 1 4'0" X 6'8" RHR/LHR
SOLID WOOD HCW PT - - PASSAGE WD PT WS
Rev Date Description
GLAZING
Checked SMB/KDS
FACTORY FINISH
DOOR SCHEDULE GENERAL NOTES FACTORY PRIMED - SITE PAINTED Drawn AV
CLEAR LACQUER
1. ALL DOORS INDICATED TO HAVE A FIRE RESISTANCE RATING IN SCHEDULE TO HAVE A MAXIMUM CLEAR ANODIZED Scale N.T.S.
OF A 16mm UNDERCUT BETWEEN FINISHED FLOOR AND UNDERSIDE OF RATED DOOR. REFER TO NFPA 80 FOR MORE
INFORMATION STANDARD FLOAT GLASS Date
GEORGIAN WIRED GLASS OCT 05, 2021
2. ALL DOORS INDICATED TO HAVE A FIRE RESISTANCE RATING IN SCHEDULE TO BE PROVIDED WITH TEMPERED GLASS
POSITIVE LATCHING HARDWARE DESIGNED TO HOLD THE DOOR IN A CLOSED POSITION TO CLEAR CERAMIC FIRE RATED GLAZING
ENSURE CONTINUITY OF THE FIRE RESISTANCE RATING OF THE CLOSURE. Project Name
SALISH SEA
ABBREVIATIONS USED IN DOOR SCHEDULE ENTRY KEYED LOCKSET HOUSING
RH RIGHT HAND SWING P/PULL PUSH - PULL HARDWARE
LH LEFT HAND SWING OFFICE KEYED LOCKSET WITH INTERIOR BUTTON DOOR SCHEDULE GENERAL NOTES 7583 CENTRAL SAANICH RD.,
RHR RIGHT HAND REVERSE SWING PRIVACY LOCKSET WITH INTERIOR BUTTON TSAWOUT FIRST NATION
PANIC PUSHBAR EXIT DEVICE EQ EQ
LHR LEFT HAND REVERSE SWING
RHRA RIGHT HAND REVERSE ACTIVE LEAF PASSAGE LOCKSET W/O ANY LOCK Drawing Title
ROLL/CATCH ROLLER CATCH HARDWARE
HM HOLLOW METAL
SCW SOLID CORE WOOD
HCW HOLLOW CORE WOOD
AL ALUMINUM CL DOOR CLOSER DOOR
PS PRESSED STEEL
WD SOLID WOOD
WS
FS
WALL STOP
FLOOR STOP SCHEDULE
GL GLAZING ELEC ELECTRIC STRIKE
PR PROXIMITY READER
FACTORY FACTORY FINISH GA WEATHERSTRIPPING GASKETS
PT FACTORY PRIMED - SITE PAINTED KP KICKPLATE
CLEAR CLEAR LACQUER Drawing No.

A8.01
THROWS FLUSH BOLTS TOP AND BOTTOM
ANOD CLEAR ANODIZED HC HANDICAP ACTUATOR
MC MORTISE CYLINDER
FLOAT STANDARD FLOAT GLASS PKT POCKET DOOR & DOOR HARDWARE
WIRED GEORGIAN WIRED GLASS BARN BARN STYLE (FACE MOUNT) SLIDING DOOR Project No.
TEMP'D TEMPERED GLASS SRC SINGLE ROLLER CATCH W/ PASSAGE SET HANDLE
CERAMIC CLEAR CERAMIC FIRE RATED GLAZING TOP OF FLOOR 19323
1 2 3 4 © Copyright reserved. These plans and
designs are and at all times remain the
NOTE: property of Finlayson Bonet Architecture to be
used for the project shown and may not be
6" x 24" WIRED GLASS reproduced without written consent.
DOOR SCHEDULE GENERAL NOTES DOOR LITE
2'-6" 2'-6"

2'-0"

2'-0"
5TH FLOOR LEVEL 5TH FLOOR LEVEL

5'-0"

5'-0"
3'-0"

3'-0"
G5 G5

2'-6" 2'-6"

2'-0"

2'-0"
4TH FLOOR LEVEL 4TH FLOOR LEVEL

5'-0"

5'-0"
3'-0"

3'-0"
G5 G5

2'-6" 2'-6"

2'-0"

2'-0"
3RD FLOOR LEVEL 3RD FLOOR LEVEL

5'-0"

5'-0"
3'-0"

3'-0"
G5 G5
STAIRWELL 2

2'-6"

2'-0"
2ND FLOOR LEVEL 2ND FLOOR LEVEL #4 - 7855 East Saanich Rd.

5'-0"
Saanichton V8M 2B4

3'-0"
Phone: 250-656-2224
Fax. 250-656-2279
email:
info@finlaysonbonet.ca
G5
ST-2 ST-1

6'-0" 5'-0" 4'-0" 6'-0" 6'-0" 4'-0"

3'-0" 3'-0"
3'-0" 3'-0" 3'-0" 3'-0"
TOP OF WINDOW HEAD HEIGHT
1'-10"

1'-10"
1'-10"

21.10.05 ISSUED FOR

3'-4"

3'-4"
CONSTRUCTION
5'-0"

5'-0"

5'-0"

5'-0"
5'-0"

5'-0"
21.05.25 ISSUED FOR TENDER
3'-2"

3'-2"
3'-2"

7'-0"
21.04.23 ISSUED FOR B.P.

1'-8"

1'-8"
Rev Date Description

3'-8"

3'-8"
Checked SMB/KDS
2'-0"

2'-0"

2'-0"

2'-0"
2'-0"

2'-0"
Drawn AV
2ND, 3RD, 4TH, + 5TH FLOOR
Scale N.T.S.
Date
G7 G6 G4 G3a G3 G2
OCT 05, 2021
Project Name
5'-0" SALISH SEA
PERFORMANCE REQUIREMENTS VALUE REFERENCE HOUSING
TOP OF WINDOW HEAD HEIGHT 7583 CENTRAL SAANICH RD.,
Energy Performance TSAWOUT FIRST NATION
USI 1.4W/m2•k BC Housing Design Guidelines Drawing Title
SHGC 0.3 Maximum BC Housing Design Guidelines

4'-6"
VLT 0.6 or greater Step Code Energy Model

WINDOW

8'-0"
NAFS/BC Housing Window Requirements
Performance Class: CW BC Housing Design Guidelines SCHEDULE

2'-0"
PG Rating: 35 BC Housing Design Guidelines
Min. Positive design pressure: 1440 Pa NAFS Calculator (Sidney BC)
Min. Negative design pressure: 1440 Pa NAFS Calculator (Sidney BC)

1'-6"
Drawing No.
Min. Water penetration resistance test pressure: 510 Pa BC Housing Design Guidelines
Min. Canadian air infiltration/exfiltration: A-3 BC Housing Design Guidelines
MAIN FLOOR
A8.02
G1 Project No.

19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
LEVEL 2 ROOM NAME FLOOR CEILINGS WALLS TRIM NOTES COMMON AREAS ROOM NAME FLOOR CEILINGS WALLS TRIM NOTES
COMMON AREAS ST-1 200 RUBBER ST CONCRETE / G.W.B PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS LEVEL 1

ST-1 210 RUBBER ST G.W.B. PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS ST-1 100 RUBBER ST CONCRETE 2 / G.W.B. PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS

CORRIDOR CPT 1 T-BAR / G.W.B. PAINT G.W.B. PAINT 1 / WSC RCB VESTIBULE 101 CPT 1 T-BAR G.W.B. PAINT 1 / WSC RCB

ELECTRICAL CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB VESTIBULE 102 CPT 1 T-BAR G.W.B. PAINT 1 / WSC RCB

JANITOR CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB LOBBY 103 CPT 1 T-BAR G.W.B. PAINT 1 / WSC RCB

MECHANICAL CLOSETS CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB ELECTRICAL 104 CONCRETE 1 CONCRETE 2 G.W.B. PAINT 1 RCB
MECHANICAL 105 CONCRETE 1 CONCRETE 2 G.W.B. PAINT 1 RCB

UNIT 201 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT COMMON LAUNDRY 106 R.S.F. 1 T-BAR G.W.B. PAINT 1 / WSC RCB

STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ACCESSIBLE WASHROOM 107 R.S.F. 1 G.W.B. PAINT G.W.B. PAINT 1 RCB

ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT CORRIDOR 108 CPT 1 T-BAR G.W.B. PAINT 1 / WSC RCB

PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT CLIENT SERVICES 109 CPT 1 T-BAR G.W.B. PAINT 1 / WSC RCB

KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ST-2 110 CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 1 RCB TACTILE WARNING & CONTRASTING NOSINGS

LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT JANITOR 111 CONCRETE 1 T-BAR - RCB

HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT AMENITY 112 LVP 1 T-BAR G.W.B. PAINT 1 / WSC RCB

MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT GARDEN STORAGE 113 CONCRETE 1 - G.W.B. PAINT 1 RCB

MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE 114 CONCRETE 1 - G.W.B. PAINT 1 RCB

BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT


LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 202 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT


ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LIST OF FINISHES
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT CPT 1 - TARKETT MODULAR CARPET TILE OR SIMILAR
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT CONCRETE 1 - TROWEL FINISH WITH SEALER
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
CONCRETE 2 - PAINTED CONCRETE STRUCTURE
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT FRP - PANOLAM FIBREGLASS REINFORCED PANEL
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT G.W.B PAINT 1 (WALLS) - 3 COATS LATEX, EGGSHELL FINISH
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
G.W.B PAINT 2 (WALLS) - 3 COATS LATEX, FLAT FINISH
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
G.W.B PAINT (CEILINGS) - 3 COATS LATEX, FLAT FINISH
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LVP 1 - TARKETT ADORE NATURELL LUXURY VINYL PLANK

LVP 2 - POLYFLOOR COLONIA PUR LUXURY VINYL PLANK


UNIT 203 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
RCB - 100mm RUBBER COVE BASE
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT RUBBER ST - TARKETT RUBBER STRINGERS AND TREAD /
RISER SYSTEM WITH CONTRASTING NOSINGS
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
R.S.F 1 - POLYSAFE VERONA PUR RESILIENT SHEET FLOORING
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT T-BAR - ACOUSTICAL CEILING TILE IN METAL TRACK
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BBT - FINGER JOINED PAINTED WOOD BASEBOARD (1 x 6)
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
WSC - WAINSCOTING PAINTED HARDBOARD PANEL
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT WDT - FINGER JOINED PAINTED WINDOW TRIM (1 x 3)

MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT CHR - CHAIR RAIL - INSTALL 32" ABOVE FINISHED FLOOR
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Door Frame
Location Info
Door # Door Name Style Leaf Size Swing Material Finish Label Glazing Hdwe Material Finish
UNIT 204 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 201
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D201-1 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D201-2 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT D201-3 LIVING/DINING TO MASTE RBEDROOM 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 202
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D202-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT D202-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT D202-3 HALL TO BEDROOM 2 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT D202-4 HALL TO LAUNDRY 1 3'0" x 6'9" LHR HCW PT - - PASSAGE WD PT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT UNIT 203
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D203-1 HALL TO BATHROOM 1 2'8" X 6'8" LH SCW PT - - PRIVACY WD PT
D203-2 HALL TO LAUNDRY 1 3'0" X 6'8" LHR HCW PT - - PASSAGE #4 - 7855
WD PT
East Saanich Rd.
UNIT 205 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D203-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY Saanichton
WD V8M 2B4 PT
ENTRY - CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D203-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD250-656-2224 PT
Phone:
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Fax. 250-656-2279
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT email:
UNIT 204
info@finlaysonbonet.ca
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT D204-1 HALL TO BATHROOM 1 2'8" X 6'8" RH SCW PT - - PRIVACY WD PT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D204-2 HALL TO LAUNDRY 1 3'0" X 6'8" RHR HCW PT - - PASSAGE WD PT
POWDER ROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT D204-3 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT
BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D204-4 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 205
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT D205-1 HALL TO BATHROOM 1 3'0" X 6'8" RHR SCW PT - - PRIVACY WD PT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D205-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" LH SCW PT - - PRIVACY WD PT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT D205-3 HALL TO BEDROOM 2 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D205-4 HALL TO DEN 1 2'8" x 6'8" RH SCW PT - - PASSAGE WD PT
DEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT D205-5 HALL TO POWDER ROOM 1 2'4" X 6'8" POCKET HCW PT - - PRIVACY WD PT
LAUNDRY CLOSET LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT D205-6 HALL TO LAUNDRY 1 4'0" X 6'8" RHR/LHR HCW PT - - PASSAGE WD PT
STORAGE LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT 21.10.05 ISSUED FOR
CONSTRUCTION
UNIT 206 21.05.25 ISSUED FOR TENDER
UNIT 206 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACY21.04.23 ISSUED
WD FOR B.P. PT
D206-1
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D206-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD PT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Rev Date Description
D206-3 HALL TO LAUNDRY CLOSET 1 3'0" X 6'8" LHR HCW PT - - PASSAGE WD PT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT D206-4 HALL TO BATHROOM 1 2'8" x 6'8" LH SCW PT - - PRIVACYChecked WDSMB/KDS PT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Drawn AV
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 207 Scale N.T.S.
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT D207-1 HALL TO BEDROOM 2 1 2'8" x 6'8" LH SCW PT - - PRIVACYDate WD PT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT D207-2 HALL TO MASTER BEDROOM 1 1 3'0" X 6'8" RH SCW PT - - PRIVACY WD05, PT
OCT 2021
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT D207-3 HALL TO BATHROOM 1 2'8" x 6'8" RH SCW PT - - PRIVACY WD PT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT D207-4 HALL TO LAUNDRY CLOSET 1 4'0" X 6'8" RHR/LHR HCW PT - - PASSAGE WD
Project Name PT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT SALISH SEA
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT HOUSING
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
UNIT 207 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Drawing Title
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
FINISH
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT SCHEDULE
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT Drawing No.
MASTER BEDROOM CLOSET
BEDROOM 2
LVP 1
LVP 1
G.W.B. PAINT
G.W.B. PAINT
G.W.B. PAINT 1
G.W.B. PAINT 1
BBT
BBT / WDT
A8.03
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Project No.

STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT 19323


© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
LIST OF FINISHES

CPT 1 - TARKETT MODULAR CARPET TILE OR SIMILAR

CONCRETE 1 - TROWEL FINISH WITH SEALER


LEVEL 4 ROOM NAME FLOOR CEILINGS WALLS TRIM NOTES LEVEL 3 ROOM NAME FLOOR CEILINGS WALLS TRIM NOTES
CONCRETE 2 - PAINTED CONCRETE STRUCTURE
COMMON AREAS ST-1 400 RUBBER ST CONCRETE / G.W.B PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS COMMON AREAS ST-1 300 RUBBER ST CONCRETE / G.W.B PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS
ST-1 410 RUBBER ST G.W.B. PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS ST-1 310 RUBBER ST G.W.B. PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS FRP - PANOLAM FIBREGLASS REINFORCED PANEL
CORRIDOR CPT 1 T-BAR / G.W.B. PAINT G.W.B. PAINT 1 / WSC RCB CORRIDOR CPT 1 T-BAR / G.W.B. PAINT G.W.B. PAINT 1 / WSC RCB G.W.B PAINT 1 (WALLS) - 3 COATS LATEX, EGGSHELL FINISH
ELECTRICAL CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB ELECTRICAL CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB
G.W.B PAINT 2 (WALLS) - 3 COATS LATEX, FLAT FINISH
JANITOR CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB JANITOR CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB
MECHANICAL CLOSETS CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB MECHANICAL CLOSETS CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB G.W.B PAINT (CEILINGS) - 3 COATS LATEX, FLAT FINISH

LVP 1 - TARKETT ADORE NATURELL LUXURY VINYL PLANK


UNIT 401 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 301 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LVP 2 - POLYFLOOR COLONIA PUR LUXURY VINYL PLANK
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
RCB - 100mm RUBBER COVE BASE
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT RUBBER ST - TARKETT RUBBER STRINGERS AND TREAD /
RISER SYSTEM WITH CONTRASTING NOSINGS
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT R.S.F 1 - POLYSAFE VERONA PUR RESILIENT SHEET FLOORING

HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT T-BAR - ACOUSTICAL CEILING TILE IN METAL TRACK
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BBT - FINGER JOINED PAINTED WOOD BASEBOARD (1 x 6)
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
WSC - WAINSCOTING PAINTED HARDBOARD PANEL
BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT WDT - FINGER JOINED PAINTED WINDOW TRIM (1 x 3)
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT CHR - CHAIR RAIL - INSTALL 32" ABOVE FINISHED FLOOR
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 402 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 302 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 403 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 303 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 404 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 304 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
#4 - 7855 East Saanich Rd.
UNIT 405 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 305 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Saanichton V8M 2B4
ENTRY - CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY - CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
Phone: 250-656-2224
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Fax. 250-656-2279
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT email:
info@finlaysonbonet.ca
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
POWDER ROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT POWDER ROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
DEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT DEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
LAUNDRY CLOSET LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY CLOSET LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT 21.10.05 ISSUED FOR
CONSTRUCTION
21.05.25 ISSUED FOR TENDER
UNIT 406 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 306 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
21.04.23 ISSUED FOR B.P.
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Rev Date Description

LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT Checked SMB/KDS
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Drawn AV
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
Scale N.T.S.
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
Date
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
OCT 05, 2021
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT Project Name
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT SALISH SEA
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT HOUSING
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
UNIT 407 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT UNIT 307 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Drawing Title
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
FINISH
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT SCHEDULE
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT Drawing No.
MASTER BEDROOM CLOSET
BEDROOM 2
LVP 1
LVP 1
G.W.B. PAINT
G.W.B. PAINT
G.W.B. PAINT 1
G.W.B. PAINT 1
BBT
BBT / WDT
MASTER BEDROOM CLOSET
BEDROOM 2
LVP 1
LVP 1
G.W.B. PAINT
G.W.B. PAINT
G.W.B. PAINT 1
G.W.B. PAINT 1
BBT
BBT / WDT
A8.04
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Project No.

STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT 19323
© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.
LIST OF FINISHES

CPT 1 - TARKETT MODULAR CARPET TILE OR SIMILAR

CONCRETE 1 - TROWEL FINISH WITH SEALER


LEVEL 5 ROOM NAME FLOOR CEILINGS WALLS TRIM NOTES
CONCRETE 2 - PAINTED CONCRETE STRUCTURE
COMMON AREAS ST-1 500 RUBBER ST CONCRETE / G.W.B PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS
ST-1 510 RUBBER ST G.W.B. PAINT G.W.B. PAINT 1 RUBBER ST / RCB TACTILE WARNING & CONTRASTING NOSINGS FRP - PANOLAM FIBREGLASS REINFORCED PANEL
CORRIDOR CPT 1 T-BAR / G.W.B. PAINT G.W.B. PAINT 1 / WSC RCB G.W.B PAINT 1 (WALLS) - 3 COATS LATEX, EGGSHELL FINISH
ELECTRICAL CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB
G.W.B PAINT 2 (WALLS) - 3 COATS LATEX, FLAT FINISH
JANITOR CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB
MECHANICAL CLOSETS CONCRETE 1 G.W.B. PAINT G.W.B. PAINT 2 RCB G.W.B PAINT (CEILINGS) - 3 COATS LATEX, FLAT FINISH

LVP 1 - TARKETT ADORE NATURELL LUXURY VINYL PLANK


UNIT 501 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT LVP 2 - POLYFLOOR COLONIA PUR LUXURY VINYL PLANK
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
RCB - 100mm RUBBER COVE BASE
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT RUBBER ST - TARKETT RUBBER STRINGERS AND TREAD /
RISER SYSTEM WITH CONTRASTING NOSINGS
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT R.S.F 1 - POLYSAFE VERONA PUR RESILIENT SHEET FLOORING

HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT T-BAR - ACOUSTICAL CEILING TILE IN METAL TRACK
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT BBT - FINGER JOINED PAINTED WOOD BASEBOARD (1 x 6)
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
WSC - WAINSCOTING PAINTED HARDBOARD PANEL
BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT WDT - FINGER JOINED PAINTED WINDOW TRIM (1 x 3)
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT CHR - CHAIR RAIL - INSTALL 32" ABOVE FINISHED FLOOR
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 502 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT


ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 503 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT


ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT

UNIT 504 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT


ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
#4 - 7855 East Saanich Rd.
UNIT 505 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Saanichton V8M 2B4
ENTRY - CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
Phone: 250-656-2224
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Fax. 250-656-2279
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT email:
info@finlaysonbonet.ca
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
POWDER ROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
DEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT
LAUNDRY CLOSET LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
STORAGE LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT 21.10.05 ISSUED FOR
CONSTRUCTION
21.05.25 ISSUED FOR TENDER
UNIT 506 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
21.04.23 ISSUED FOR B.P.
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Rev Date Description

LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT Checked SMB/KDS
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Drawn AV
LINEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
Scale N.T.S.
STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
Date
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
OCT 05, 2021
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT Project Name
MASTER BEDROOM CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT SALISH SEA
BEDROOM 2 LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT HOUSING
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
7583 CENTRAL SAANICH RD.,
TSAWOUT FIRST NATION
UNIT 507 ENTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Drawing Title
ENTRY CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
PANTRY LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
KITCHEN LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT
LIVING / DINING LVP 1 G.W.B. PAINT G.W.B. PAINT 1 / CHR BBT / WDT
FINISH
HALL LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT SCHEDULE
LAUNDRY LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
BATHROOM LVP 2 G.W.B. PAINT G.W.B. PAINT 1 BBT
MASTER BEDROOM LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT / WDT Drawing No.
MASTER BEDROOM CLOSET
BEDROOM 2
LVP 1
LVP 1
G.W.B. PAINT
G.W.B. PAINT
G.W.B. PAINT 1
G.W.B. PAINT 1
BBT
BBT / WDT
A8.05
BEDROOM 2 CLOSET LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT Project No.

STORAGE LVP 1 G.W.B. PAINT G.W.B. PAINT 1 BBT 19323


© Copyright reserved. These plans and
designs are and at all times remain the
property of Finlayson Bonet Architecture to be
used for the project shown and may not be
reproduced without written consent.