Phase L1-E:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L2-E:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L3-E:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L1-L2:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L2-L3:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L3-L1:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L1-L2-L3:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Tested By Checked By
Actual Dir
Characterstic Polarizing Pick up Drop off Current Calculated
Phase Duty Is (A) T.M.S RCA Time % Error Signal Operating Remarks
Curve Phase (A) (A) Injected Time (sec)
(sec) Area
12.00 4.012 4.053 1.02
R
51 6.00 0.40 IEC SI - - 15.00 3.028 3.072 1.44 Okay -
Element
18.00 2.521 2.549 1.11
12.00 4.012 4.053 1.02
Y
51 6.00 0.40 IEC SI - - 15.00 3.028 3.072 1.44 Okay -
Element
18.00 2.521 2.549 1.11
12.00 4.012 4.053 1.02
B
51 6.00 0.40 IEC SI - - 15.00 3.028 3.072 1.44 Okay -
Element
18.00 2.521 2.549 1.11
2.00 6.519 6.551 0.49
N
51N 1.00 0.65 IEC SI - - 3.00 4.096 4.139 1.03 Okay -
Element
5.00 2.782 2.818 1.28
Tested By Checked By
Actual Dir
Characterstic Polarizing Pick up Drop off Current Calculated
Phase Duty Is (A) T.M.S RCA Time % Error Signal Operating Remarks
Curve Phase (A) (A) Injected Time (sec)
(sec) Area
12.00 3.510 3.613 2.85
R -145°
67 6.00 0.35 IEC SI YB 15.00 2.649 2.763 4.11 Okay
Element ~+25°
18.00 2.206 2.325 5.13
12.00 3.510 3.613 2.85
Y -145°
67 6.00 0.35 IEC SI BR 15.00 2.649 2.763 4.11 Okay
Element ~+25°
18.00 2.206 2.325 5.13
12.00 3.510 3.613 2.85
B -145°
67 6.00 0.35 IEC SI RY 15.00 2.649 2.763 4.11 Okay
Element ~+25°
18.00 2.206 2.325 5.13
2.00 6.017 6.046 0.47
N -145°
67N 1.00 0.60 IEC SI -3V0 3.00 3.781 3.816 0.91 Okay
Element ~+25°
5.00 2.568 2.618 1.92
Tested By Checked By