QF-SPM-02

POWER GRID COMPANY OF BANGLADESH LTD.


Distance Relay Test Report

Name Of The Substation: TONGI CTR: 1600/1 A


Name Of The Line Feeder: Kaliakoir FP1 PTR: 230/0.110 kV
Relay Type: 7SA522 Date 15.12.2021
Relay Serial No: BF0410077488 Manufacturer: Siemens
Testing Instrument: CMC 256 Line Angle 82
Testing Type: Annual Maintenance

Reverse Starter Resistive


Z1 Z1E Z2 Z2E Z3 Z3E
Zone Zone Reach
Impedance 9.63 Ω 9.63 Ω 14.45 Ω 14.45 Ω 18.47 Ω 18.47 Ω 3.01 Ω - -
Relay Setting
Time 0 ms 0 ms 400 ms 400 ms 800 ms 800 ms 1200 ms - -

Test Result: Machine Generated Results Can be added.

Phase L1-E:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 26 ms -13% Passed

2 13.25 Ω 82° Z2 430 ms 440 ms 2% Passed

3 17.47 Ω 82° Z3 830 ms 837 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1230 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L2-E:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 40 ms 33% Passed

2 13.25 Ω 82° Z2 430 ms 436 ms 1% Passed

3 17.47 Ω 82° Z3 830 ms 838 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1236 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L3-E:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 32 ms 7% Passed

2 13.25 Ω 82° Z2 430 ms 439 ms 2% Passed

3 17.47 Ω 82° Z3 830 ms 831 ms 0% Passed

4 1.51 Ω -98° Reverse 1230 ms 1238 ms 1% Passed

5 23.09 Ω 82° Out - no trip - Passed


QF-SPM-02

Phase L1-L2:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 34 ms 13% Passed

2 13.25 Ω 82° Z2 430 ms 430 ms 0% Passed

3 17.47 Ω 82° Z3 830 ms 836 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1231 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L2-L3:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 29 ms -3% Passed

2 13.25 Ω 82° Z2 430 ms 426 ms -1% Passed

3 17.47 Ω 82° Z3 830 ms 836 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1226 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L3-L1:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 27 ms -10% Passed

2 13.25 Ω 82° Z2 430 ms 437 ms 2% Passed

3 17.47 Ω 82° Z3 830 ms 827 ms 0% Passed

4 1.51 Ω -98° Reverse 1230 ms 1236 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L1-L2-L3:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 37 ms 23% Passed

2 13.25 Ω 82° Z2 430 ms 425 ms -1% Passed

3 17.47 Ω 82° Z3 830 ms 837 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1226 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Tested By Checked By

Sub Divisional Engineer Executive Engineer


SPMD, Dhaka - 2, PGCB SPMD, Dhaka - 2, PGCB
QF-SPM-02
POWER GRID COMPANY OF BANGLADESH LTD.
Distance Relay Test Report

Name Of The Substation: TONGI CTR: 1600/1 A


Name Of The Line Feeder: Kaliakoir FP2 PTR: 230/0.110 kV
Relay Type: 7SA61 Date 15.12.2021
Relay Serial No: BF0410077477 Manufacturer: Siemens
Testing Instrument: CMC 256 Line Angle 82
Testing Type: Annual Maintenance

Reverse Starter Resistive


Z1 Z1E Z2 Z2E Z3 Z3E
Zone Zone Reach
Impedance 9.63 Ω 9.63 Ω 14.45 Ω 14.45 Ω 18.47 Ω 18.47 Ω 3.01 Ω - -
Relay Setting
Time 0 ms 0 ms 400 ms 400 ms 800 ms 800 ms 1200 ms - -

Test Result: Machine Generated Results Can be added.

Phase L1-E:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 39 ms 30% Passed

2 13.25 Ω 82° Z2 430 ms 425 ms -1% Passed

3 17.47 Ω 82° Z3 830 ms 825 ms -1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1233 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L2-E:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 27 ms -10% Passed

2 13.25 Ω 82° Z2 430 ms 433 ms 1% Passed

3 17.47 Ω 82° Z3 830 ms 827 ms 0% Passed

4 1.51 Ω -98° Reverse 1230 ms 1235 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L3-E:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 33 ms 10% Passed

2 13.25 Ω 82° Z2 430 ms 436 ms 1% Passed

3 17.47 Ω 82° Z3 830 ms 825 ms -1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1238 ms 1% Passed

5 23.09 Ω 82° Out - no trip - Passed


QF-SPM-02

Phase L1-L2:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 35 ms 17% Passed

2 13.25 Ω 82° Z2 430 ms 428 ms 0% Passed

3 17.47 Ω 82° Z3 830 ms 825 ms -1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1232 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L2-L3:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 37 ms 23% Passed

2 13.25 Ω 82° Z2 430 ms 435 ms 1% Passed

3 17.47 Ω 82° Z3 830 ms 838 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1230 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L3-L1:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 35 ms 17% Passed

2 13.25 Ω 82° Z2 430 ms 438 ms 2% Passed

3 17.47 Ω 82° Z3 830 ms 840 ms 1% Passed

4 1.51 Ω -98° Reverse 1230 ms 1238 ms 1% Passed

5 23.09 Ω 82° Out - no trip - Passed

Phase L1-L2-L3:

Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed

1 7.22 Ω 82° Z1 30 ms 31 ms 3% Passed

2 13.25 Ω 82° Z2 430 ms 425 ms -1% Passed

3 17.47 Ω 82° Z3 830 ms 829 ms 0% Passed

4 1.51 Ω -98° Reverse 1230 ms 1226 ms 0% Passed

5 23.09 Ω 82° Out - no trip - Passed

Tested By Checked By

Sub Divisional Engineer Executive Engineer


SPMD, Dhaka - 2, PGCB SPMD, Dhaka - 2, PGCB
QF-SPM-03

POWER GRID COMPANY OF BANGLADESH LTD.


Over Current Relay Test Report

Name Of The Substation: TONGI CTR: 1600/1 A


Name Of The Feeder: Kaliakoir Date: 15.12.2021
Relay Type: 7SJ62 Manufacturer: SIEMENS
Relay Amps: 1A Relay Serial No: BF1707262

Actual Dir
Characterstic Polarizing Pick up Drop off Current Calculated
Phase Duty Is (A) T.M.S RCA Time % Error Signal Operating Remarks
Curve Phase (A) (A) Injected Time (sec)
(sec) Area
2.00 4.012 4.022 0.26
R
51 1.00 0.40 IEC SI - - 3.00 2.521 2.533 0.48 Okay -
Element
5.00 1.712 1.721 0.53
2.00 4.012 4.022 0.26
Y
51 1.00 0.40 IEC SI - - 3.00 2.521 2.533 0.48 Okay -
Element
5.00 1.712 1.721 0.53
2.00 4.012 4.022 0.26
B
51 1.00 0.40 IEC SI - - 3.00 2.521 2.533 0.48 Okay -
Element
5.00 1.712 1.721 0.53
0.40 3.009 3.028 0.64
N
51N 0.20 0.30 IEC SI - - 0.60 1.891 1.902 0.60 Okay -
Element
1.00 1.284 1.294 0.78

Tested By Checked By

Sub Divisional Engineer Executive Engineer


SPMD, Dhaka - 2, PGCB SPMD, Dhaka - 2, PGCB
QF-SPM-03

POWER GRID COMPANY OF BANGLADESH LTD.


Over Current Relay Test Report

Name Of The Substation: TONGI CTR: 1600/1 A


Name Of The Feeder: Kaliakoir Date: 15.12.2021
Relay Type: 7SJ62 Manufacturer: SIEMENS
Relay Amps: 1A Relay Serial No: BF1707262

Actual Dir
Characterstic Polarizing Pick up Drop off Current Calculated
Phase Duty Is (A) T.M.S RCA Time % Error Signal Operating Remarks
Curve Phase (A) (A) Injected Time (sec)
(sec) Area
2.00 3.009 3.032 0.77
R -145°
67 1.00 0.30 IEC SI YB 3.00 1.891 1.911 1.07 Okay
Element ~+25°
5.00 1.284 1.300 1.24
2.00 3.009 3.032 0.77
Y -145°
67 1.00 0.30 IEC SI BR 3.00 1.891 1.911 1.07 Okay
Element ~+25°
5.00 1.284 1.300 1.24
2.00 3.009 3.032 0.77
B -145°
67 1.00 0.30 IEC SI RY 3.00 1.891 1.911 1.07 Okay
Element ~+25°
5.00 1.284 1.300 1.24
0.40 2.507 2.540 1.29
N -145°
67N 0.20 0.25 IEC SI -3V0 0.60 1.575 1.592 1.04 Okay
Element ~+25°
1.00 1.070 1.085 1.39

Tested By Checked By

Sub Divisional Engineer Executive Engineer


SPMD, Dhaka - 2, PGCB SPMD, Dhaka - 2, PGCB