1.0 INTRODUCTION
This calculation provides the detail of type of load on cable brackets, plates & bolts,
and their withstand capacity with the installed weight. The analysis is done using STAAD
Pro software.
2.0 TOOLS
i) STAAD Pro
3.0 SUMMARY
The calculations are done using STAAD Pro software to analyse the bracket size, load
on bracket, load on insert plates & bolts.
Typical calculations are done using lowest angle size of 40X40X5 with longer length of 600mm
having weight of the maximum size cable in the substation to analyse the impact & withstand
capacity of angle, insert plate & bolts. Results are done considering the point load of 41kg
which includes weight of cable & cable tray on angle support with 6 tiers in a single trench.
Based on the following results bracket support of higher side is considered in cable trench
design which will be sufficient to withstand the loads.