You are on page 1of 6

DESIGN OF EP PLATES

I). INPUT

Ep NO = 12543
Length of the plate = 700 mm

Width of the plate = 700 mm

Center to center of anchor bolt/rod in X direction = 275 mm

Center to center of anchor bolt/rod in Y direction = 275 mm


Distance between outer bolts/rods in X direction a = 550 mm

Distance between outer bolts/rods in Y direction b = 550 mm

a' = 2342 mm (a+2Leff.)

b' = 2342 mm (b+2Leff.)


Effective stress area a' x b' = 5484964 mm²

Thickness of the plate = 30 mm

Dia of Anchor rod D = 48 mm

Area of Anchor rod Avt = 1810 mm²


Length of the rod Leff. = 896 mm

Size of the stud = 90x90x48 thk 700

No of rods = 9 Nos
No of rods per row = 3 Nos

Grade of concrete fck = 35 N/mm²

Yield strength of Bolt fy = 250 N/mm² 700

Co-efficient of friction µ = 0.9


a = 0.45 for bolt/bars

Ø = 0.65 for pull-out strength

= 0.85 for bearing

II). CALCULATION FOR STRENGTH OF ANCHHOR BOLTS/BARS


i). In tension

Required area of anchor bolts/bars for tension Avt = Vt / a fy (Refer section 7.3.1 of DBR of KAPP-3&4)

Design load in tension Vt = Avt x a x fy

= 203.58 kN for Single anchor bolt/rod


= 610.73 kN for 3 edge anchor bolts/rods

ii). In Shear

Required area of anchor bolts/bars for shear Avs = V s / a fy µ (Refer section 7.3.2 of DBR of KAPP-3&4)
Design load in shear Vs = Avs x a x fy x µ
= 183.22 kN for Single anchor bolt/rod

= 1649.0 kN for 9 anchor bolts/rods

II). CALCULATION FOR CONCRETE STRENGTH

i). Pull-out Strength

Leff

a'
Pull-out strength of concrete Pu = 0.33.Ø.Ö fck..Aeff. (Refer section 7.4 of DBR of KAPP-3&4)

= 6960 kN

ii). Concrete capacity in bearing

Leff

a'

Bearing strength of concrete Pb = 0.33.Ø.Ö fck..Aeff.


Aeff. = 1783408.75 mm²

= 2959 kN
DBR of KAPP-3&4)