Professional Documents
Culture Documents
N6166 - E05 - F510 - TV - EF - Relay - 7SJ61 Site Test Report
N6166 - E05 - F510 - TV - EF - Relay - 7SJ61 Site Test Report
Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 - Transformer T202
Functions
Enabled Disabled
IEC No. Description
Description
50N/51N Earth fault Protection Enabled
F - LED function
Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X510
CT RATIO: 600/1 A
2.3 Earth Fault function (IDMT- Normal inverse curve ): 51N 0.14
T= .TP [s]
0.02
[(I/IP) - 1]
Instruments Used
Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Characteristics
Company: Siemens
Test Person: Josip Spolador
Testmodules Checked: 9
Testmodules Passed: 9
Substation/Bay:
Substation: 132/11 kV SS ADNEC Substation address:
Bay: 40MVA Transformer 2 Bay address: =E05 -T202
Device:
Name/description: TV_EF 7SJ61 Manufacturer: SIEMENS
Device type: 7SJ6111-5EB90-1FA0 Device address: =E05+R1-F510
Serial/model number: BF1108116132
Additional info 1: TertiaryWinding Earthfault Relay
Additional info 2:
Hardware Configuration
Test Equipment
Type Serial Number
CMC256-6 JG655S
Hardware Check
Performed At Result Details
23/08/2012 09:29:20 Passed
IE:
Current output 1 ---> -X510: 26,28
Tertiary_EF
Mode selection:
Information or instruction
Instruction Text:
Settings: IEp>=0.2A; T-IEp=0.5; IEC Normal Inverse
IE>=0.5A; T-IE>=1.0; DT
IE>>=1A; T-IE>>=0.5; DT
Instruction Text:
Disable IDMT , and enable 50N-1 DMT
Instruction Text:
Disable DMT , and enable 51N IDMT
10000.0
1000.0
100.0
t/s
10.0
1.0
End of Test