Considered as 4900 mm in TG Layout

drawing. If 4800 mm is correct then


amend TG layout drawing.

If any part of the DMCW piping is


supplied with these coolers then the
MOC of the pipes/nozzles and Fittings
will be as per Annexure-I of V-II/J1/S-
VI, i.e. "Stainless Steel as per ASTM
A-312 Gr. 304. Thickness- as per
schedule 10S, as per ANSI B36.19"
for pipes and "ASTM-A-351-CF8 or
ASTM-A-403 WP304" for fittings. The
end Details should be "Bevel ended
as per ANSIB- 16.25". Please confirm
the same.

Like other heat exchangers, It should be same as the


consider corrosion allowance design pressure of DMCW
What it is the basis? Is it
on shell side as 3.2 mm (TG) pumps. Please confirm.
relief valve set pressure?
What is the Tube plug Please confirm.
margin considered?