Mechanical - General A
Mechanical - General A
MEKANIKAL
Ulasan ini adalah tertakluk kepada lukisan mekanikal yang dikemukakan. Bahagian ini tidak akan
bertanggungjawab atas percanggahan/ketidakseragaman lukisan premis pemohon.
Perlu pastikan tiada percanggahan lukisan antara arkitek/awam, mekanikal dan elektrikal. Jika
berlaku percanggahan, premis perlu mengemukakan semula untuk semakan.
Kepatuhan:
Perkara Ya (√ ) / Tidak Ulasan/Saranan
(X)
1. Penyaman udara dan pengalihudaraan
(Bahagian X, Bab 7, Peraturan 89)
(Bahagian X, Bab 3, Peraturan 75)
ASHRAE 170-2021, ASHRAE 62.1-2019
Guideline On Conceptual Design And Engineering Requirements For Isolation Room, KKM, 2017
Standards for Assisted Reproductive Technology – Facility Embryology Laboratory and Operation Theatre, KKM
Operating Theatre Complex Guidelines For Private Healthcare, KKM
a. Setiap bilik dan kawasan dalam - - Lukisan menunjukkan pemasangan sistem
kemudahan atau perkhidmatan jagaan AHU, FCU dan SUAC bagi keseluruhan
kesihatan swasta hendaklah premis. Ditunjukkan FCU menerima bekalan
dialihudarakan dengan secukupnya. udara terawat (precool) dari AHU / PAHU.
Namun demikian, tidak ditunjukkan dengan
jelas lokasi Fresh Air Intake dalam lukisan.
Premis diminta memastikan setiap kawasan
dalam kemudahan dialihudarakan dengan
secukupunya.
Page 1 of 8
GENERAL COMMENT – M
Page 2 of 8
GENERAL COMMENT – M
*ASHRAE 170-2021
6.3.2 Exhaust Discharges
6.3.2.1 General.
Exhaust discharge outlets that discharge air from AII
rooms, bronchoscopy and sputum collection and
pentamidine administration rooms, emergency
department public waiting areas, nuclear medicine hot
labs, radiology waiting rooms programmed to hold
patients who are waiting for chest x-rays for diagnosis
of respiratory dis- ease, pharmacy hazardous-drug
exhausted enclosures, and laboratory work area
chemical fume hoods shall
(a) be designed so that all ductwork within the building
is under negative pressure;
Page 3 of 8
GENERAL COMMENT – M
b. Bahagian bawah outdoor air intake √ - Premis hendaklah memastikan perkara ini
hendaklah tidak kurang daripada 0.9m dipatuhi.
dari aras tanah / bumbung.
Page 4 of 8
GENERAL COMMENT – M
GUIDELINE ON CONCEPTUAL
DESIGN AND ENGINEERING
REQUIREMENTS FOR CENTRAL
STERILE SUPPLY UNIT (CSSU)
7) Sterilized products storage area
located within the operating theatre
shall be provided with HEPA filter.
Separated sterilized products storage
area shall be equipped with secondary
filter.
Page 5 of 8
GENERAL COMMENT – M
diluluskan.
5. Bekalan Air
(Bahagian XIX, Peraturan 289)
Page 6 of 8
GENERAL COMMENT – M
Page 7 of 8
GENERAL COMMENT – M
Disediakan oleh:
Tandatangan :
Page 8 of 8