GENERAL NOTES
1867-T-0001C 1867-P-0001E 1867-P-0002A/B
DIESEL FUEL DAILY TANK MAIN FIRE WATER PUMPS (DIESEL ENGINE) JOCKEY PUMPS (MOTOR)
SIZE, ID x HEIGHT (mm) 1300 x 2000 RATED FLOWRATE (m³/hr) 1136.0 RATED FLOWRATE (m³/hr) 60 PSL PSH
A NOMINAL CAPACITY (m³) 2 RATED DIFF. HEAD (m) 119.0 RATED DIFF, HEAD (m) 123.3 00002 00002 A
NOTE 2 NOTE 1
DESIGN PRESSURE (kg/cm²g) 0 RATED DRIVER POWER (kw) 541.0 RATED DRIVER POWER (kw) 48.5
DESIGN TEMPERATURE (°c) 32 INSULATION / TRACING NI INSULATION / TRACING NI
TEMPERATURE / TRACING NI MIN MIN PT
MOC CS 1.5 M 1.5 M 00001
2"-P-760301-01LC2B01-NI
439 1867-3E10-7602 B.L
FROM DIESEL TRUCK TANK 2"-P-760308-01LC2BO1-NI
UG NOTES
3/4" 3/4" 3/4"
HOLD 2 1. JOCKEY PUMP 1867-P-02 A/B OPERATION PHILOSOPHY IS TO MAINTAIN THE
20"-FW-760305-01LC2B01-NI PRESSURE OF FIRE WATER MAIN :
1867 1867-3E10-7602 453 - AUTOMATIC RUN IF PRESSURE AT DISCHARGE FIRE WATER HEADER
B TO MAIN FIRE WATER RING B
DROPPED TO 10.8kg/cm²g.
- AUTOMATIC STOP AT 12.5 kg/cm²g.
H - AND ALSO THE PRESSURE SUFFICIENT FOR FIGHTING BY OPERATOR DURING
LS INITIAL FIRE.
00001C 14" LO 2. LOCAL CONTROL PANEL BY VENDOR.
LI L 4"
4" 3. PG-00001/00002, PSV-00001/00002 BY VENDOR.
00001C
4. A/G : ABOVE GROUND.
5. DETAIL ENGINE FUEL TANKS (LOCATED HIGHER THAN THE DIESEL ENGINE
FUEL PUMP INLET) BY VENDOR.
400 2"2"
1" 2"
MM 2" 6. ANTI SURGE VALVE
C C
1867-T-0001C
- NOTE 6
4"-FW-760331-01LC2B01-NI
4"-FW-760332-01LC2B01-NI
CI CURRENT CI CURRENT
14"-FW-760337-01LC2B01-NI
CI INDICATION INDICATION
0002A 0002B
COOLING WATER 0001E CURRENT INDICATION
TAHH START
TEMPERATURE XA XA
D 0001E HIGH-HIGH HS XA D
0002A FAULT 0002B FAULT
1"-P-760309-01LC2B01-NI
COOLING HOLDS
WATER
VALVE ASSY SET @ 16.00 kg/cm^2g SET @ 16.00 kg/cm^2g 1. CAPACITY AND NUMBER OF MAIN FIRE WATER PUMPS NOT YET FIXED DUE TO
SET @ 16.00 kg/cm^2g PSV FIRE WATER DEMAND CALCULATION NOT YET ISSUED.
8"x6" PSV +
PSV
2. P&ID MAIN FIRE WATER RING NOT YET ISSUED.
+
0002A
+
00001E 0002A
D
3-1/2"x2-1/2"
2" PG PG
3-1/2"x2-1/2"
14" 1" 1"
0001A 4" 00001B 4"
PG
14"x8"
00001D
E
NOTE 2
1"-FW-760324-01LR2B01-NI
2"-FW-760334-01LR2B01-NI
3-1/2"-FW-760330-01LR2B01-NI
REV DATE DESCRIPTION DRAWN CHK'D APP'D
1"-FW-760328-01LC2B01-NI
I I
THIS DRAWING EMBODIES PROPRIETARY INFORMATION OF PT. KILANG PERTAMINA INTERNASIONAL THIS DRAWING OR THE
MATERIAL DESCRIBED THEREON MAY NOT BE COPIED OR DISCLOSED IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED
FOR OTHER THAN THE PURPOSE FOR IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED FOR OTHER THAN THE
PURPOSE FOR WHICH IT HAS BEEN PROVIDED, IN WHOLE OR IN PART IN ANY MANNER EXCEPT AS EXPRESSLY PERMITTED
BY PT. KILANG PERTAMINA INTERNASIONAL.
PROJECT
TPPI OLEFIN COMPLEX DEVELOPMENT PROJECT
OWNER
J PT KILANG PERTAMINA J
INTERNASIONAL
CONTRACTOR
TITLE :
PIPING & INSTRUMENTATION DIAGRAM
FOR FIRE SYSTEM
K K
(UNIT 1867)
FILE NAME :