KO-C1-CST-CSH-RP-011

Geo-Materiaux Engineering Limited,


Off Villagio Road West Airport,
Patrice Lumumba Road,
P.o Box MP 2357, Mamprobi, Accra Ghana,
Tel 0302550888, 0541240899,0559611620, e-mail: GeoMEngLtd@gmail.com

PROCTOR COMPACTION OF COHESIONLESS SANDS AND FINE GRAVELS


REFERENCE STANDARD BS 1377

CONSTRUCTION OF EASTERN
PROJECT: SAMPLE No: SOIL-MPT
REGIONAL HOSPITAL
CHIANA STATE HAULONG
CLIENT: TESTED BY: WIREDU ERIC
CONSTRUCTION GHANA
CONTRACTOR:

SAMPLE ID: CSO2 DEPTH: N/A

DATE TESTED: 20/11/2021 SAMPLE DESCRIPTION: Clayey sandy SILT with some gravels

TEST No. 1 2 3 4 5

MOISTURE CONTENT % 2.58 3.69 6.34 7.85 9.65


3
DRY DENSITY IN g/Cm 1.851 1.908 2.007 1.895 1.780

2.050

2.000

1.950

1.900

1.850

1.800

1.750
1.00 3.00 7.00 11.00

Maximum dry density kg/m3 2.007

Optimum moisture content % 6.34

Approved by: