CL-NG-6460-002-060 Check list of Timers (62) Commissioning Page Number: 1 of 3
1.0 Equipment General Data and Information
Substation Bay/Panel Equipment Serial No 2.0 Mechanical checks& visual inspection
Item Description Done Remarks
General Visual Inspection. (check list CL- NG-6460-002-056 1. should be attached ) On Units fitted with hand reset flag indicators, check that the flag is free to fall before, or just, any contacts closes. Make 2. sure that the reset mechanism in the cover is correctly located with respect to the relay element and the flag (or mechanism) can be reset. Check condition of any connectors, contacts alignment and 3. travel.
3.0 Electrical tests
Item Description Done Remarks
General Electrical Tests. (check list CL- NG-6460-002-057 1. should be attached ) Ensure correct values of external resistors (where applicable) 2. and check these are wired to the correct relay terminals. 3. Check Pick-up and Drop-off Voltage. 4. Check current at Pick-up\ drop-off voltage. 5. Check the contact operating time pickup\ drop-off Test. 6. Check the burden at rated voltage. 7. Check Timing at different points setting. Check that trip indicator operates correctly and can be reset 8. using reset mechanism. For versions fitted with LEDs trip indicator check proper operation of LEDs. 9. Check that contact operate by doing continuity check. Check that necessary trip and alarm circuits are energized 10. according to relevant Schematic diagram by operating the relay with trip and alarm links restored. Archiving System Website: http://AMAS NATIONAL GRID
Title: Index Number:
CL-NG-6460-002-060 Check list of Timers (62) Commissioning Page Number: 2 of 3
11. Check Timer range is matched with drawing.
4.0 Related Tests
Item Description Done Remarks
1. Final Setting as per approved setting. 2. Function Test & Scheme Check.
CSD Contractor T&C Contractor
Name Sign.