TMG 

MEP requirements  for Commercial spaces  REV:00
Mechanical
HVAC Light Current 
Water supply  Drainage  Fire Fighting  ELECTRIC ELECTRIC
Kitchen to  No Gas With Gas Fire Alarm 
Waste  Soil Exhaust  Fresh air  Telephone
main grease interface 
10 KVA / 100 sqm. 
Retail R R R R R
(Minimum 10 KVA)
Retail Kiosk R R R * 10KVA 
40 KVA / 100 sqm 25 KVA / 100 sqm 2 lines / direct 
F&B, café R R R R R 3000 CFM 2400 CFM R
(Minimum 40 KVA) (Minimum 40 KVA) fiber optics
F&B, café Kiosk R R R * 25KVA 
50 KVA / 100 sqm 25 KVA / 100 sqm 2 lines / direct 
Restaurant R R R R R 5000 CFM 4000 CFM  R
(Minimum 40 KVA) (Minimum 40 KVA) fiber optics
Office & Clinics  R R R R R R
Supper market less 
R R R 30 KVA / 100 sqm R R
than 500 sqm
Supper market more  4 lines / direct 
R R R R R 5000 CFM 4000 CFM  25 KVA / 100 sqm R
than 500 sqm fiber optics
2 lines / direct 
Pharmacy R R ** R R 15 KVA / 100 sqm R
fiber optics
Bakery R R R 3000 CFM 2400 CFM 25 KVA / 100 sqm 15 KVA / 100 sqm R R
Laundry  R R R R 40 KVA / 100 sqm R R
Cinemas  R R R R 15 KVA / 100 sqm R R
6 lines / direct 
Banks R R R R 20 KVA / 100 sqm R
fiber optics
Car showroom R R R R 10 KVA / 100 sqm. R R
2 lines / direct 
Gym  R R R R R 20 KVA / 100 sqm R
fiber optics
Beauty Salon R R R R R 21 KVA / 100 sqm R R
2 lines / direct 
Theme Park R R R R R R R 30 KVA / 100 sqm R
fiber optics

R: Required
* Extinguisher
* * Individual Gulitrap 
All utility rooms doors to be equipped with access card device
All meters shall be prepaid and will be installed by tenants inside his unit, TMG will provide only  e in with disconnected switch inside each unit boundaries.