Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump

No type reel riser comer hydrant sprinkler detection tank tank


system system
lodging and height electric 450 LPM
1
rooming upto 7 R R NR NR NR NR NR R NR NR 5000 and 180 LPM
House mtrs
7to 12 R R NR R NR NR R R NR NR 10000 electric 450 LPM
mtrs and 180 LPM
12 to 18 R R R NR NR R R R NR NR 20000 electric 900,450
mtrs LPM and 180 LPM
More 50000 two Electric 1620
than 18 R R R NR R R R R litres LPM, and one jockey 10000 electric 450 LPM
mtrs 180 LPM
height electric 450 LPM
upto 7 R R NR R NR R R R NR NR 10000 and 180 LPM
Dormitories mtrs
2 A 3 and 7to 12 R R NR R NR R R R NR NR 15000 electric 450 LPM
Apartment mtrs and 180 LPM
House A4 12 to 18 R R NR R NR R R R NR NR 20000 two pumps 450
mtrs LPM and 180 LPM
18 mtrs two pumps 900
to 35 R R NR R NR R R R NR NR 20000 LPM and 180 LPM
mtrs
Elec 2280, Diesel
35 to 45 R R R NR NR R R R 75000 2280 and Joc 180 5000 NR
mtrs LPM
Elec 2280, Diesel
45 to 60 R R R NR R R R R 150000 2280 and Joc 180 10000 NR
mtrs LPM
above 60
mtrs R R R NR R R R R NR twoElec 2850, Diesel 10000 NR
2850 and 02 no
Jockey 180 LPM
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
3 A-5 Hotels upto 7 R R NR R NR R NR R NR NR 5000 Electric 450 LPM
mtrs & Jockey 180 LPM
7 to 12 R R NR R NR R NR R NR NR 20000 Electric 900 LPM
mtrs & Jockey 180 LPM
two Electric 900
12 to 15 R R NR R NR R R R NR NR 25000 LPM & Jockey 180
mtrs LPM
15 to 18 two Electric 900
mtrs R R NR R NR R R R NR NR 30000 LPM & Jockey 180
LPM
two Electric 2280
18 to 30 150000 LPM, one diesel 2280
mtrs R R R NR R R R R litres LPM and two jockey 20000 NR
180 LPM

two Electric 2280


above 30 200000 LPM, one diesel 2280 20000 NR
mtrs R R R NR R R R R lires LPM and two jockey litres
180 LPM
4 A-6 Hotels two Electric 2850
Star 250000 LPM, one diesel 2850 20000
hotels R R R NR R R R R litres LPM and two jockey lires NR
180 LPM
up to 7
5 Educational mtrs R NR NR NR NR NR NR NR NR NR NR NR
7 to 12 450 LPM and
mtrs R R NR R NR NR R NR NR NR 10000 Jockey 180 LPM
12 to 18 900 LPM and
mtrs R R NR R R NR R NR NR NR 20000 jockey 180 LPM
18 to 24 900 LPM and
mtrs R R NR R NR NR R NR NR NR 25000 jockey 180 LPM
One electric 1620 lpm
24 to 30 50000 , one diesel 1620 lpm
mtrs R R R NR R NR R NR litres and one jockey 180 5000 NR
lpm
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
upto 4 R R NR R NR NR NR R NR NR 5000 Electric 450 LPM
6 Institutional mtrs & Jockey 180 LPM
4 to 7 Electric 450 LPM
mtrs R R NR R NR NR NR R NR NR 10000 & Jockey 180 LPM
7 to 12 two Electric 450
mtrs R R NR R NR R R R NR NR 20000 LPM & Jockey 180
LPM
two Electric 900
12to 15
R R NR R NR R R R NR NR 25000 LPM & Jockey 180
mtrs
LPM
one Electric 1620
LPM, one diesel 1620
15 to 18
R R R NR R R R R 50000 LPM and one jockey 10000 450 LPM
mtrs
180 LPM
18 to 24 150000 one electric 2280 , NR
mtrs R R R NR R R R R litres one diesel 2280 and 20000
one jockey 180 LPM litres
24 to 45
mtrs but 200000 two Electric 2280
not R R R NR R R R R lires LPM, one diesel 2280
above 45 LPM and two jockey 20000 NR
mtrs 180 LPM litres

7 Custodial c- up to 9 10000 450 lPM and one


R R NR NR NR NR NR NR NR NR
2 & C-3 mtrs litres jockey 180 LPM
Penal and one Electric 1620
Mental 9 to 18 100000 LPM, one diesel 1620
mtrs R R R NR R R R R litres LPM and one jockey 10000
NR
180 LPM litres
18 to 30
mtrs but 200000 two Electric 2280
not R R R NR R R R R litres LPM, one diesel 2280
above 30 LPM and two jockey 20000 NR
mtrs 180 LPM lires
Sr Building Height
Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
8 Assembly up to 4 NR NR
R NR NR NR NR NR NR NR NR NR
mtrs
4 to 8 5000 450 lpm
D1-D4 R R NR NR NR NR NR NR NR NR
mtrs litres
8 to 12 NR 20000 02 electric 900
mtrs R R NR R NR R NR R NR litres LPM and 180 LPM
jockey
one Electric 2280
12 to 15 100000 LPM, one diesel 2280
mtrs 450 LPM
R R R NR R R R R Litres LPM and one jockey 5000
180 LPM litres
one Electric 2280
15 to 24 150000 LPM, one diesel 2280
mtrs R R R NR R R R R lires LPM and one jockey 10000 NR
180 LPM litres

above
24m but
not two Electric 2280
exceding 200000 LPM, one diesel 2280
30 m in R R R NR R R R R lires LPM and two jockey 20000 NR
height 180 LPM litres
9 D-6
two Electric 2850
Mall 200000 LPM, one diesel 2850
R R R NR R R R R Litres LPM and two jockey 20000 NR
180 LPM litres
D-7
10
As NBC per annexure J and K of NBC -2016
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
up to 4 m R NR NR NR NR NR NR NR NR NR NR NR
4 to 7 m 5000 450 lpm and one
R R NR R NR NR R R NR NR
jockey 180 lpm
11 Business
7 to 12 m 15000 450lpm and one
building
R R NR R NR NR R R NR NR
litres jockey 180 lpm

one lectric 900


25000 LPM , one elctric
12 to 15 R R NR R NR R R R NR NR litres 450 LPM and one
m jockey 180 LPM

one Electric 2280


50000 LPM, one diesel 2280
15 to 18 R R R NR NR R R R litres LPM and one jockey 10000 450 LPM
mtrs
180 LPM litres
one Electric 2280
100000 LPM, one diesel 2280
18 to 24 R R R NR R R R R litres LPM and one jockey 10000 NR
m
180 LPM litres
two Electric 2280
150000 LPM, one diesel 2280
24 to 30 R R R NR R R R R litres LPM and two jockey 20000 NR
M
180 LPM litres

two Electric 2850


150000 LPM, one diesel 2850
above 30 R R R NR R R R R litres LPM and two jockey 20000 NR
m
180 LPM litres
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
up to 5 m R NR NR NR NR NR NR R NR NR NR NR
12 Mercantile 5 m to 10 20000 450 LPM and
m R R NR R NR R R R NR NR litres jockey 180 LPM
one electric 900
LPM , one electric
10 to 18 450 LPM and one
m R R NR R NR R R R NR NR 25000 jockey 180 LPM
One electric 2280,one
18 to 24 100000 diesel 2280 and one 10000
m R R R NR R R R R litre jockey 180 LPM litre NR
Two electric 2280,
24 to 200000 one diesel 2280,two 20000
30m R R R NR R R R R litre jockey 180 LPM Litre NR
UG Two electric 2280,
shopping 150000 one diesel 2280,two 10000
13
complex F-3 R R R NR R R R R LITRE jockey 180 LPM litre NR
Covered
area
upto 200
14 Low hazard
sqm R R NR R R NR NR NR NR NR 5000 450 LPM
industry
Covered
area 450 LPM and one
200sqm to 15000 jockey 180 LPM
500sqm R R NR R R NR NR NR NR NR litre
Covered
area 500 Two electric
sqm to 25000 900LPM , one
1000 sqm R R NR R R R R R NR NR litre jockey 180 lpm
Covered One electric 1620
area lpm, one diesel 1620
1000sqm to 50000 lpm ,one jockey 180 10000
2000sqm R R R NR R R R R LITRE lpm litre NR
Covered One electric 2280 lpm,
area more one diesel 2280
than 75000 lpm ,one jockey 180 10000
2000sqm R R R NR R R R R litres lpm litres NR

Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
Covered
area upto 10000 450 LPM and
15 Moderate 200sqm R R NR NR R R NR NR NR NR litres jockey 180 lpm
hazard Covered
industry area
200sqm to 20000 900LPM AND ONE
500sqm R R NR R R R NR R NR NR LPM JOCKEY 180 LPM
Covered
area 500 Two lectric pump
sqm to 50000 900 lpm,one
1000 sqm R R NR R R R NR R NR NR litres jockey 180 lpm
Covered
area One electric 1620
1000sqm lpm, one diesel 1620
to 2000 50000 lpm ,one jockey 180 20000
sqm R R R NR R R R R litres lpm litres 450 lpm

Covered Two lectric 2280


area more lpm,one diesel 2280
than 150000 lpm,two jockey 180 20000
2000sqm R R R NR R R R R litres lpm litres NR
Covered
High area upto 20000 450lpm and one
16 R R NR R R R R R NR NR litres jockey 180 lpm
hazards 400sqm
industry Covered One electric 1620 lpm
area , one diesel 1620 lpm
400sqm to 50000 and one jockey 180 20000
1000 sqm R R R NR R R R R litrs lpm litres 900lpm
Covered Two electric 2280
area more lpm,one diesel 2280 20000
than 150000 lpm, two jockey 180 litres
1000sqm R R R NR R R R R litres lpm NR
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
Height two electric pump
upto NR 450 lpm and one
10m R R NR R NR R NR R NR 25000 jockey 180 lpm
17 Storage
One electric 1620 lpm
10 m to 100000 ,one diesel 1620 lpm , 20000
15 m R R R NR R R R R LITRES one jockey 180 lpm litres 900lpm
Two electric
Multilevel 2280lpm,one diesel
18
car parking 150000 2280 lpm , two jockey 10000
- R R R NR R R R R litres 180 lpm litres NR
Hazardous
19
buildings As peso PESO/ CCOE guidelines and related Act and rules

Notes –
1- Sprinkler shall be required in basement, if area of basement exceeds 200 sqm .
2- The standby pump can be of electrical driven pump, if dedicated supply is provided from DG set by dedicated feeder.
3- If providing over head tank is not possible due to type of structure like typical industrial sheds or structure not capable to bear the load of water, can
shift to ground / underground tank with the consultation of Fire NOC issuing authority. Fire NOC issuing authority can grant the permission to
change the location without affecting the change in total water capacity of building.
4- Design of fire protection system shall be as given in NBC.
5- Special fire protection system like gas flooding system, foam pourer system, foam injection system, water spray , water curtain , etc as
suggested/refer NBC and specific rule .
6- In case specific act and rules already existed for specific buildings then these above rules shall not be applicable on those buildings example – petrol
pumps, CNG stations, LPG bottling plants ,petroleum depos, refineries ,LPG gas go downs, fire cracker shops storage, and manufacturing comes
under explosive act and rules like petroleum rules 2002, gas cylinder rules 2016, PNGRB rules , OISD 225, 114,115,116,117,118,179,144, etc
7- Refer NBC for following points – fire exits , norms of staircase , travel distance , dead end , location of fire control rooms in buildings , construction
and location of fire pump house, pressurization of staircase , compartmentation, smoke management system , horizontal progressive evacuation etc.
8- Refer local building by laws for Access road width or for building upto 12 m height and covered area less than 400 sqm shall be 6 m or where fire
vehicle can move easily.
9- For building upto 12 m height and covered area upto 400 sqm width of external staircase shall be 1.2 m . Staircase shall be on front side of building
on outer wall with 0.5 sqm area window on each landing for natural ventilation.
10- In case upper floors not be used by occupants and occupants seeking exemption for not used floors, exemption shall be given on the following
conditions – floors must be fully empty means no goods of any type and electric supply of those floor must be cut off or fully isolated.
11- GO order dated 7.01.2022 for low rise building ,GO Avas avam sahri niyojan vibhag for exemption in access road ,fire exit ,set back dated 20.11.2008
as per building by laws clause 3.11.3.1 , point no 3. and GO for old and new cold storage dated 18.11.2019 and 22.10.2020 shall be remain valid.
12- Building Owner/occupier/manager shall make arrangements for alternate electrical supply for electric fire pumps.
13- Covered area means – ground coverage of the biggest building of the industry .
14- Some specific buildings to be inspect according to following act and rules as given below.
A ) Petrol/diesel retail outlets – petroleum rules and OISD 225
B) CNG stations – PNGRB rules and OISD179
c) Bio diesel retail outlets – as PESO guidelines
d) LPG bottling plants – OISD 144
e) Petroleum depots – OISD 117
f) Petroleum refineries - OISD116
G) Petroleum industry – OISD 115
h) Hazardous chemicals – OISD 114
I) layout of oil and gas installations – OISD 118
j) Inspection of storage tanks – OISD 129
K) LPG gas godowns – Gas cylinder rules 2016 or as amended time to time
L) fire crackers shop , storage and manufacturing – explosive rules 2008 or as amended

You might also like