Fire Fighting Equipment Table
Fire Fighting Equipment Table
above
24m but
not two Electric 2280
exceding 200000 LPM, one diesel 2280
30 m in R R R NR R R R R lires LPM and two jockey 20000 NR
height 180 LPM litres
9 D-6
two Electric 2850
Mall 200000 LPM, one diesel 2850
R R R NR R R R R Litres LPM and two jockey 20000 NR
180 LPM litres
D-7
10
As NBC per annexure J and K of NBC -2016
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
up to 4 m R NR NR NR NR NR NR NR NR NR NR NR
4 to 7 m 5000 450 lpm and one
R R NR R NR NR R R NR NR
jockey 180 lpm
11 Business
7 to 12 m 15000 450lpm and one
building
R R NR R NR NR R R NR NR
litres jockey 180 lpm
Sr Building Height Extinguishers Hose Wet Down Yard Automatic MOEFA Automatic UG UG fire pumps Terrace terrace pump
No type reel riser comer hydrant sprinkler detection tank tank
system system
Covered
area upto 10000 450 LPM and
15 Moderate 200sqm R R NR NR R R NR NR NR NR litres jockey 180 lpm
hazard Covered
industry area
200sqm to 20000 900LPM AND ONE
500sqm R R NR R R R NR R NR NR LPM JOCKEY 180 LPM
Covered
area 500 Two lectric pump
sqm to 50000 900 lpm,one
1000 sqm R R NR R R R NR R NR NR litres jockey 180 lpm
Covered
area One electric 1620
1000sqm lpm, one diesel 1620
to 2000 50000 lpm ,one jockey 180 20000
sqm R R R NR R R R R litres lpm litres 450 lpm
Notes –
1- Sprinkler shall be required in basement, if area of basement exceeds 200 sqm .
2- The standby pump can be of electrical driven pump, if dedicated supply is provided from DG set by dedicated feeder.
3- If providing over head tank is not possible due to type of structure like typical industrial sheds or structure not capable to bear the load of water, can
shift to ground / underground tank with the consultation of Fire NOC issuing authority. Fire NOC issuing authority can grant the permission to
change the location without affecting the change in total water capacity of building.
4- Design of fire protection system shall be as given in NBC.
5- Special fire protection system like gas flooding system, foam pourer system, foam injection system, water spray , water curtain , etc as
suggested/refer NBC and specific rule .
6- In case specific act and rules already existed for specific buildings then these above rules shall not be applicable on those buildings example – petrol
pumps, CNG stations, LPG bottling plants ,petroleum depos, refineries ,LPG gas go downs, fire cracker shops storage, and manufacturing comes
under explosive act and rules like petroleum rules 2002, gas cylinder rules 2016, PNGRB rules , OISD 225, 114,115,116,117,118,179,144, etc
7- Refer NBC for following points – fire exits , norms of staircase , travel distance , dead end , location of fire control rooms in buildings , construction
and location of fire pump house, pressurization of staircase , compartmentation, smoke management system , horizontal progressive evacuation etc.
8- Refer local building by laws for Access road width or for building upto 12 m height and covered area less than 400 sqm shall be 6 m or where fire
vehicle can move easily.
9- For building upto 12 m height and covered area upto 400 sqm width of external staircase shall be 1.2 m . Staircase shall be on front side of building
on outer wall with 0.5 sqm area window on each landing for natural ventilation.
10- In case upper floors not be used by occupants and occupants seeking exemption for not used floors, exemption shall be given on the following
conditions – floors must be fully empty means no goods of any type and electric supply of those floor must be cut off or fully isolated.
11- GO order dated 7.01.2022 for low rise building ,GO Avas avam sahri niyojan vibhag for exemption in access road ,fire exit ,set back dated 20.11.2008
as per building by laws clause 3.11.3.1 , point no 3. and GO for old and new cold storage dated 18.11.2019 and 22.10.2020 shall be remain valid.
12- Building Owner/occupier/manager shall make arrangements for alternate electrical supply for electric fire pumps.
13- Covered area means – ground coverage of the biggest building of the industry .
14- Some specific buildings to be inspect according to following act and rules as given below.
A ) Petrol/diesel retail outlets – petroleum rules and OISD 225
B) CNG stations – PNGRB rules and OISD179
c) Bio diesel retail outlets – as PESO guidelines
d) LPG bottling plants – OISD 144
e) Petroleum depots – OISD 117
f) Petroleum refineries - OISD116
G) Petroleum industry – OISD 115
h) Hazardous chemicals – OISD 114
I) layout of oil and gas installations – OISD 118
j) Inspection of storage tanks – OISD 129
K) LPG gas godowns – Gas cylinder rules 2016 or as amended time to time
L) fire crackers shop , storage and manufacturing – explosive rules 2008 or as amended