You are on page 1of 1

PROJECT:G+1+R villa LOCATION: GROUND FlOOR

DB NO: DB-AC-1 LOAD DISTRIBUTION SCHEDULE AREA: Jabal Ali First


FEEDING FROM: MDB PLOT: AFNBVIL071
MCB CCT ECC ROOM /AREA CONNECTED LOADS/POINTS LOAD PER CIRCUIT-WATT
RATING WIRE WIRE
RATING SL WATER
OF CIR NO RTG IN 13A 13A 15A SH REMARKS
OF ELCB NO SIZE SIZE LTG Chandlier C-FAN E-FAN W/H FCU Cooker W-AC S-AC S-ISO T-ISO PUMP/BOOS WATT/UNIT
INCOMER S/O TWIN S/O S/O
TER PUMP
AMPS mm2 mm2 R Y B
40A, 4P 1 R1 25 4 4 Guest Bedroom 1 2000 2000 UVR+TIMER+CONTACTOR
100mA 2 Y1 20 6 4 Pantry 1 1500 1500
ELCB-1 3 B1 25 4 4 Kitchen 2500 2500
40A, 4P 4 R2 32 6 4 Dining Area 1 3000 3000 UVR+TIMER+CONTACTOR
100mA 5 Y2 20 6 4 Maid Room 1 1500 1500 UVR+TIMER+CONTACTOR
ELCB-2 6 B2 25 4 4 Parking Area 1 2500 2500 UVR+TIMER+CONTACTOR
63A TP ISOLATOR

40A, 4P 1300
100mA
ELCB-3
7 RYB-3 25A,TP 4 4 Living Room Male 1
4000 { 1400
1300
UVR+TIMER+CONTACTOR

40A, 4P 1300
100mA
ELCB-4
8 RYB-4 25A,TP 4 4 Living Room Female 1
4000 { 1400
1300
UVR+TIMER+CONTACTOR

40A, 4P 9 R5 20 4 4 Guest Bedroom 1 150 150


100mA 10 Y5 20 4 4 Pantry 1 100 100
ELCB-5 11 B5 20 4 4 Dining Area 1 150 150
40A, 4P 12 R6 20 4 4 Maid Room 1 150 150
100mA 13 Y6 20 4 4 Parking Area 1 150 150
ELCB-6 14 B6 20 4 4 Living Room Male 1 150 150
40A, 4P 15 R7 20 4 4 Living Room Female 1 150 150
100mA 16 Y7 20 4 4 Kitchen 50 150
ELCB-7 17 B7
TOTAL= 8,050 6,200 7,900 22,150
2 2
CABLE SIZE: 1/2/3/4C 16 mm CU.PVC/XLPE/SWA/PVC + 1*1C 16 mm CU PVC.ECC LTG - Lighting, C-FAN - Ceiling Fan, E-FAN - Exchaust Fan, SH S/O - Shaver Socket Outlet
W/H - Water Heater, H/D - Hand Dryer, W-AC - Window AC, S-AC - Split AC