PROJECT:G+1+R villa LOCATION: GROUND FlOOR

DB NO: DB-AC-2 LOAD DISTRIBUTION SCHEDULE AREA: Jabal Ali First


FEEDING FROM: MDB PLOT: AFNBVIL071
MCB CCT ECC ROOM /AREA CONNECTED LOADS/POINTS LOAD PER CIRCUIT-WATT
RATING WIRE WIRE
RATING SL WATER
OF CIR NO RTG IN 13A 13A 15A SH REMARKS
OF ELCB NO SIZE SIZE LTG Chandlier C-FAN E-FAN W/H FCU Cooker W-AC S-AC S-ISO T-ISO PUMP/BOOS WATT/UNIT
INCOMER S/O TWIN S/O S/O
TER PUMP
AMPS mm2 mm2 R Y B
40A, 4P 1 R1 25 4 4 Bedroom 2 1 1800 1800 UVR+TIMER+CONTACTOR
100mA 2 Y1 25 4 4 Bedroom 3 1 1800 1800 UVR+TIMER+CONTACTOR
ELCB-1 3 B1 25 4 4 Bedroom 4 1 1800 1800 UVR+TIMER+CONTACTOR
40A TP ISOLATOR

40A, 4P 4 R2 25 6 4 Master Bedroom 1 2500 2500


100mA 5 Y2 20 4 4 Store and Laundry 1 1400 1400 UVR+TIMER+CONTACTOR
ELCB-2 6 B2
40A, 4P 1200
100mA
ELCB-3
7 RYB-3 25A,TP 4 4 Sitting Area 1
3600 { 1200
1200
UVR+TIMER+CONTACTOR

40A, 4P 8 R4 20 4 4 Bedroom 2 1 150 150


100mA 9 Y4 20 4 4 Bedroom 3 1 150 150
ELCB-4 10 B4 20 4 4 Bedroom 4 1 150 150
40A, 4P 11 R5 20 4 4 Master Bedroom 1 150 150
100mA 12 Y5 20 4 4 Store and Laundry 1 150 150
ELCB-5 13 B5 20 4 4 Sitting Area 100 100
TOTAL= 5,800 4,700 3,250 13,750
2 2
CABLE SIZE: 1/2/3/4C 16 mm CU.PVC/XLPE/SWA/PVC + 1*1C 10 mm CU PVC.ECC LTG - Lighting, C-FAN - Ceiling Fan, E-FAN - Exchaust Fan, SH S/O - Shaver Socket Outlet
W/H - Water Heater, H/D - Hand Dryer, W-AC - Window AC, S-AC - Split AC