PROJECT EAST WEST PIPE PUMP STATION-10

LOCATION : RESIDENTIAL BUILDING -TYPE 1&2


FRESH AIR / EXHAUST AIR FLOW RATE CALCULATION
DECK TO COND. FA / EA SELECTED
FLOOR DECK SPACE OCCUPANCY MIN. OUTDOOR AIR CONSIDERING AS PER ASHRAE 62.1-2013 [Note-1) SELECTED
AS PER DOC. NO FRESH AIR EXHAUST
K06-K-CAL- FLOW RATE FLOW RATE
AREA AREA VOL.. Nof of person Breathing ventilation air Minimum Exhaust air HV101-Rev.00 [Note-2]
SL.NO ROOM / SPACE REMARKS

No. of l/s per l/s per Air flow Kitchen/Pantry/ Kitchen L/s per WC No of WC per WC & Shower
[m2] [m] [m3] Store /Pantry/store [l/s] [l/s] [l/s]
People person m2 (l/s) [l/s] per m2 [l/s] & Shower shower [l/s]

RESIDENTIAL BUILDING -TYPE 1&2


BREATHING VENTILATION AIR
Living Room (TYP) 19.3 3.3 63.69 1 1 2.5 0.3 8 1.5 28.95 - - - 25 25 25 -

Bedroom (TYP) 23.9 3.3 78.87 1 1 2.5 0.3 10


1.1
- - 25 1 25 25 25 25 -
Bedroom Toilet (TYP) 4.5 3.3 14.85 - - - - -

Common TV Room (TYP) 41.1 3.3 135.63 20 20 2.5 0.3 62 - - - - - 70


1.2 70 70 -
Kitchen (TYP) 11.3 3.3 37.29 1 1 2.5 0.3 6 1.5 16.95 - - - -

Common tv room toilet (F/F) 2.78 3.3 9.174 - - - - - - - 25 1 25

25

1.3 Centre Corridor, Lift Lobby, Store (FF) 57.4 3.3 189.42 - - - 0.3 17 - - - - - 87 87 -

EWH / Janitor (F/F) 7.2 3.3 23.76 - - - - - 5 36 - - - 62

Centre Corridor, Lift Lobby,Store -01,


Store-02 (S/F) 69.2 3.3 228.36 - - - 0.3 21 - - - - - -

1.4 65 65 -

EWH / Janitor (S/F) 7.2 3.3 23.76 - - - - - 5 36 - - - 65

1.5 Corridor Left (F.F/S.F) 40.2 3.3 132.66 - - - 0.3 12 - - - - - 25 25 N/A -

1.6 Corridor Right (F.F/S.F) 40.2 3.3 132.66 - - - 0.3 12 - - - - - 25 25 N/A -

1.7 Trash 2.457 3.3 8.1081 - - - - - - - - - - 56 - 56 -

Reference:
Doc. No: xxxx

Note:-

1 Space fresh air requirement is selected based on the highest value amongst the calculation method indicated above
2 Fresh air requirements for each space shall be selected based on the ASHRAE 62.1 as a minimum ventilation design requirements for Indoor Air Quality
3 N/A = Not Applicable