Location of Non- COLO 1 Grid 1.1 ` 1.2 / B-B2 NCR [ ] Critical [x] Major [ ] Minor
Conformance Classification
Description of Non-Conformance
During site inspection on 1st November 2022, it was found that the intumescent paint
thickness (DFT) did not meet requirement.
• type S7- Pipe 216.3x8.2 - GL: B/1.2~B2/1.1 (2hr FR) req. DFT 5.185 mm
Actual DFT on site: 3.240; 3.220; 2.160; 3.140
• Type: S1- Pipe 165.1x3.5 - GL: 1.1~1.2/B2 (2hr FR) req. DFT 4.446 mm
Actual DFT on site: 2.520; 2.480; 2.880 and 3.720
Reference:
o Submittal #JKT02-JO-SUB-CSS-750 Revision 2: Steel Structure Finishing Detail
Demarcation for Admin and Colo1
o Submittal JKT02-MTP-CSS-141 Revision 0: Intumescent Paint by International
Paint
Page 1
Turner & Townsend
International Financial Centre Tower 2,
Lt. 26 Jl. Jend. Sudirman Kav. 22-23
Kuningan Jakarta Selatan 12920, Indonesia
t: +62 21 252 3895 | m: +62 (0) 813 89 616 747
www.turnerandtownsend.com
Specification Ref. Steel Structural Work Technical Drawing Refs Nos JKT02-S-D-402-0
Specification - 1.33 Intumescent Paint
Actions Proposed by Contractor (To be filled out by Contractor and returned to Originator)
Root Cause of Non-Conformance the tool has not been calibrated regularly so it is necessary to check the
dft again after recalibration by the paint manufacturer
Proposed Correction Recalibrate DFT equipment for paint manufacture dan recheck DFT after
repair onsite
Page 2
Turner & Townsend
International Financial Centre Tower 2,
Lt. 26 Jl. Jend. Sudirman Kav. 22-23
Kuningan Jakarta Selatan 12920, Indonesia
t: +62 21 252 3895 | m: +62 (0) 813 89 616 747
www.turnerandtownsend.com
Attachments
Description / Image / Drawing approval / etc
Page 3
Turner & Townsend
International Financial Centre Tower 2,
Lt. 26 Jl. Jend. Sudirman Kav. 22-23
Kuningan Jakarta Selatan 12920, Indonesia
t: +62 21 252 3895 | m: +62 (0) 813 89 616 747
www.turnerandtownsend.com
Page 4
Turner & Townsend
International Financial Centre Tower 2,
Lt. 26 Jl. Jend. Sudirman Kav. 22-23
Kuningan Jakarta Selatan 12920, Indonesia
t: +62 21 252 3895 | m: +62 (0) 813 89 616 747
www.turnerandtownsend.com
Page 5
Marking Calibration on DFT Tools