Professional Documents
Culture Documents
Typical silicone based materials for structural bonded glass corners are either the
bi-component Dow Corning® 993 or the mono-component Dow Corning® 895.
It is not permitted to exceed the maximum combined design stress of 0.14 MPa
within the structural sealant joint. Only dynamic loads like wind loads (wind suck
and wind pressure) or working loads are permitted. Permanent loads on the
structural sealant, like dead loads, are not allowed.
Four different construction types are possible for structural bonded glass corners:
Backerod
Figure 1: Glass corner example 1 - for one stepped IG unit and one standard IG unit
Explanations for example 1 - one stepped IG unit and one standard IG unit:
Backerod
Backerod material:
Recommended backerod materials are closed celled Polyethylene (PE) backerods. In
this case it is essential that the joint is fully applied without gaps or air bubbles. This is
very important because any condensation water within the gap can harm the long term
functionality of the IG unit. In this case the IG manufacturer has to explicitly approve the
structure.
Alternative silicon based hollow sections can be used. Openings on the top and on the
bottom must ensure air circulation and draining of condensation water within the joint.
Surface pretreatment:
If stepped IG units are used with backerod materials and sealants different colour
shades would be visible through the glass. To ensure a optical uniform look of the
stepped IG units it is possible to .pacify the glass steps. That means the step of the IG
unit is covered with a 1 to 2mm thick homogenous sealant layer. Cure time for the thin
sealant layer is around 24 hours under normal room conditions (+23°C / 50% r.h.).
During production of the stepped IG unit it is already possible to pacify the step of the IG
unit (position #2) with Dow Corning® 3362 or Dow Corning® 3793.
Before applying the material it must be ensured, that all surfaces are dry, clean, dust-
free and degreased. We recommend Dow Corning® R40 cleaner (additional details of
cleaning procedures are shown in the Dow Corning® Structural Glazing Manual).
In general dust, grease, oils, liquids, ice and any other possible dirt have to be avoided.
Recommended application temperature of Dow Corning® 895 or Dow Corning® 993 are
+5°C to +40°C.
Curing phase:
Proper curing for the structural sealant bonding has to be ensured. There is no stress or
movement allowed before total curing. If the application takes place on site the structure
has to be mechanically fixed to avoid any stress or movement until complete curing of
the sealing.
Calculation:
Calculations of structural bonded glass corners have to be calculated regarding linear
bedding. Dead loads of the glass have to be supported with adequate glass unit
beddings (setting blocks). The joint is not to be affected by stress.
Regarding the calculation methods of the European Guideline for Strucutural Sealant
Glazing ETAG 002 it is recommended to use calculation for vertical structural bondings.
1 W
PE = B×H × linear bedded on three sides
2 (B + H )
PE linear load impact [kN/m] – is taken over from the structural bonding
B glass width [m]
H glass height [m]
W maximum windload [kPa]
The calculation of the linear load impact of the IG unit can be separated for both single
glass panels. The maximum windload is calculated for only one glass panel. The
calculated structural sealant joint has to overtake all mentioned load impacts. Therefore
the allowed design stresses for Dow Corning® 895 and Dow Corning® 993 are shown in
the table below:
For calculation it is allowed to assume either the inner joint or the outer joint of the glass
corner. For this purpose the different impacts like pull stress or shear stress have to be
considered.
kN
PE
b[mm] > m
allowedstress[MPa ]
For structural bonded glass corners like shown in example 2 the resulting linear load
impact has to be split into the tear stress σ and shear stress τ. With these values the
comparing design stress can be calculated using the following formulas:
The linear load can be assumed to be continuous through the complete height if the
deflection is lower than H/100.
If IG units are used the secondary sealant has to be calculated to take over the wind and
climatic loads. More information for these calculations can be found in the Dow
Corning® IG Manual.
Sometimes it is not easy to take over the dead load support of the glass because of the
construction of the structural bonded glass corner. If there is no metal post integrated
into the glass corner (this could support the dead load impact) the dead load support is
only possible through the force transmission of neighboring posts.
a) mechanical solution:
Dead load caused through vertical impact is transferred through a mechanically fixed
bedding to the post. The horizontal impact caused through the torque is transferred
through mechanical fixed bedding in the top of the post. In this solution no permanent
load must be taken over by the structural bonding of the glass corner.
Dead load caused through vertical impact is transferred through mechanically fixed
bedding to the profile. Further impacts are taken over through the structural bonding to
the profiles. In this case the structural bonding has permanent shear load. The structural
bonding has to be carried out with Dow Corning® 993 which is tested and approved
regarding ETAG 002, the static dimensioning must also consider the permanet load.
To simplify the calculation it can be assumed that the post is bending resistant.
Additionally it is assumed that there are pin supported transoms fixed to the post.
3⋅G ⋅ B
Minimum width of the structural bite: jo int with ≥
τ ⋅ H (6 B + H )
3⋅G ⋅ B
Minimum structural bite for the transom: jo int with ≥
τ ⋅ H (6 B + H )
3⋅G ⋅ B G
Minimum structural bite for the post: jo int with ≥ +
τ ⋅ H (6 B + H ) τ ⋅ H
Bedding Bedding