You are on page 1of 25

Réf : PR2-SP1/ENG/060

Version 01

REPUBLIC OF CÔTE D'IVOIRE

Union - Discipline - Labor

----------------------------------
MINISTRY OF EQUIPMENT AND ROAD MAINTENANCE
----------------------------------

FEEDBACK INFRA
-------------------------------
GEOTECHNICAL SURVEY FOR SOLAR ENERGY
PROJECT OF 25 MW IN ODIENNE

GEOTECHNICAL SURVEY REPORT


Folder No. 2019/DGC/SF/0153 / Quotation No. 0263/2019/DGC-SF-04
MARCH 2019
Version 01
-------------------------------

LABORATOIRE DU BATIMENT ET DES TRAVAUX PUBLICS


E T U D E ‒ E X P E R T I S E ‒ R E C H E R C H E – E N E R G I E

Siège : 2, rue Clément Ader – Zone IV – 04 B.P. 3 Abidjan 04 – Téléphone (225) 21 21 23 23 – Fax : (225) 21 25
36 71. Email : lbtp@aviso.ci
No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

DOCUMENT QUALITY INFORMATION

GENERAL INFORMATIONS

Organization LBTP

Project title GEOTECHNICAL SURVEY FOR SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE

Document title GEOTECHNICAL SURVEY REPORT

Date 03/21/2019

Version 01

Quotation No. 0263/2019/DGC–SF–04

Folder No. 2019/DGC/SF/0153

Number of pages Report : 12 pages / Appendices : 13 pages

CHANGE HISTORY

Version Date Written by Verified by Observations

01 03/21/2019 BINZEME ALBERT FOTTO HUGUES

TO

Organization Last name and first names Observations


FEEDBACK INFRA

LBTP SAPFPM remains at your disposal to give you all the useful information to the good understanding of this report. Also,
at your request, the LBTP can participate in site meetings to clarify this document. Without our prior consent, the partial or
complete reproduction of this report is prohibited.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 2 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

SUMMARY

I INTRODUCTION..................................................................................................................... 4
II MISSION OF LBTP .................................................................................................................. 4
III SITUATION OF THE SITE ......................................................................................................... 4
IV GEOLOGICAL AND TOPOGRAPHIC OVERVIEW ........................................................................ 5
V PROGRAMME DE SONDAGE .................................................................................................. 5
VI IMPLANTATION OF SURVEY POINTS ...................................................................................... 6
VII SURVEY EQUIPMENT ......................................................................................................... 6
VIII GEOTECHNICAL SURVEY RESULTS....................................................................................... 7
VIII.1 Nature of soils ................................................................................................................... 7
VIII.2 Water table.......................................................................................................................... 8
VIII.3 Compactness of soils ........................................................................................................... 8
VIII.4 Laboratory tests................................................................................................................... 8
VIII.5 Soil resistivity tests .............................................................................................................. 9
IX FOUNDATION POSSIBILITIES .................................................................................................. 9
IX.1 Type of foundation .................................................................................................................. 9
IX.2 Allowable stress....................................................................................................................... 9
IX.3 Settlements ........................................................................................................................... 10
X CONCLUSION ...................................................................................................................... 11

LIST OF PICTURES

Picture 1: Situation of the site ................................................................................................................. 4


Picture 2: Geological overview of the site............................................................................................... 5
Picture 3: FORDIA Penetrometer on the site .......................................................................................... 7
Picture 4: Trial pits PM9 .......................................................................................................................... 8

LIST OF TABLES

Table 1: Coordinates of survey points ..................................................................................................... 6


Table 2: Allowable stress on the soil (PD1 to PD4) ................................................................................. 9
Table 3: Allowable stress on the soil (PD5 à PD8) ................................................................................... 9
Table 4: Allowable stress on the soil (PD9 à PD12) ............................................................................... 10

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 3 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

I INTRODUCTION
As part of the project of construction of a solar power plant of 25 MW capacity in Odienné on
an area of 50 ha, the Laboratory of Building and Public Works (LBTP) was consulted by the
company FEEDBACK INFRA, to carry out a geotechnical survey.

II MISSION OF LBTP
The intervention will cover G1 geotechnical engineering missions in accordance with the
French standard NFP 94-500 of November 2013.
This mission will permit to determine the lithology of the soil in place, the compactness of the
layers, the estimate of the admissible stress and eventually the level of the water table.

III SITUATION OF THE SITE


The geotechnical survey took place in the town of Odienné in northwestern Côte d'Ivoire at
about 867 km from the economic capital Abidjan.

Picture 1: Situation of the site

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 4 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

IV GEOLOGICAL AND TOPOGRAPHIC OVERVIEW


According to the geological map at 1/2,000000th scale developed by the Society for Mining
Development in Côte d'Ivoire (SODEMI), the area concerned by the geotechnical survey is in
the space of biotite heterogeneous granitoids in the inferior Proterozoic.

Picture 2: Geological overview of the site

V PROGRAMME DE SONDAGE

The geotechnical investigations program defined by the customer consists of the execution
of:
- 12 dynamic penetrometer test down to 6 m depth or refusal ;
- 12 trial pits down to 1 m depth with soil sampling for laboratory tests (Particles size
analysis, Atterberg Limits, Water content, Proctor test) ;
- 12 soil resistivity measurement.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 5 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

VI IMPLANTATION OF SURVEY POINTS


The different survey points have been implanted by customer and the GPS coordinates
found by LBTP are in the table below :

Table 1: Coordinates of survey points

Positions X Y
PD1 660460 1050774
PD2 660692 1050772
Dynamic penetrometer

PD3 660956 1050744


PD4 661216 1050737
PD5 661445 1050723
PD6 661700 1050702
PD7 661612 1050507
PD8 661437 1050574
PD9 661307 1050555
PD10 661055 1050545
PD11 660804 1050505
PD12 660548 1050540
PM1 660460 1050773
PM2 660293 1050773
PM3 660954 1050744
PM4 661215 1050736
PM5 661448 1050722
Trial pits

PM6 661698 1050704


PM7 661611 1050506
PM8 661493 1050573
PM9 661307 1050554
PM10 661048 1050549
PM11 660803 1050506
PM12 660547 1050537

VII SURVEY EQUIPMENT


The technical equipment used for the execution of the surveys consists of:
One (01) FORDIA penetrometer;
Stems;
A manual auger.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 6 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

Picture 3: FORDIA Penetrometer on the site

VIII GEOTECHNICAL SURVEY RESULTS

VIII.1 Nature of soils


The trial pits (PM1 to PM12) made during our intervention in March 2019 permited to identify
the soil layers on the first meter. These layers are constituted successively by a topsoil of 10
cm thick, followed by lateritic gravelly of various colors.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 7 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

Picture 4: Trial pits PM9

VIII.2 Water table


During our intervention in March 2019, the water table was not encountered. It is likely
located beyond the surveyed depth.

VIII.3 Compactness of soils


The graphs representing the variation of the soil resistance versus depth are at the end of
this report (see appendices).

The analysis of these graphs permit to determine the compactness of soils. In general, the
values on these graphs are decreasing.

On the two first meters the soils compactness goes from very compact to compact. These
soils are probably the same than lateritic gravelly obtained when doing the trial pits of 1 m
depth. Beyond 2 m depth, the soils are compact to medium compact.

VIII.4 Laboratory tests


Laboratory tests results will be presented in the final report.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 8 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01
VIII.5 Soil resistivity tests
The soil resistivity tests are being done on the site. The results will be presented in the next
report.

IX FOUNDATION POSSIBILITIES

IX.1 Type of foundation

The nature of the soil in place and the type of building (Solar panel) permit us to consider the
hypothesis of shallow foundations.

IX.2 Allowable stress


The usual operation of the dynamic penetration test is to admit that the allowable stress on
the soil for shallow foundations is between 1/15 and 1/20 of the resistance obtained by
making the penetrometer test.

The application of this rule permits to determine as a first approximation and for foundations
between 1 and 2 m deep the allowable stress on the soil as presented in the following tables:

Table 2: Allowable stress on the soil (PD1 to PD4)

Test PD1 PD2 PD3 PD4

Anchoring depth of the


Rd qa Rd qa Rd qa Rd qa
foundation /
(MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
Ground surface (m)
1.00 4 0.26 3 0.20 4.2 0.28 (*)
1.50 4 0.26 3 0.20 4.2 0.28 (*)
2.00 4 0.26 3 0.20 4.2 0.28 (*)

(*) : Premature refusal when doing the PD4 penetrometer test

Table 3: Allowable stress on the soil (PD5 à PD8)

Test PD5 PD6 PD7 PD8

Anchoring depth of the


Rd qa Rd qa Rd qa Rd qa
foundation /
(MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
Ground surface (m)
1.00 4.4 0.29 4.5 0.3 3.9 0.26 5.8 0.37
1.50 4.4 0.29 4.5 0.3 3.9 0.26 5.8 0.37
2.00 4.4 0.29 4.5 0.3 3.9 0.26 5.8 0.37

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 9 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

Table 4: Allowable stress on the soil (PD9 à PD12)

Test PD9 PD10 PD11 PD12

Anchoring depth of the


Rd qa Rd qa Rd qa Rd qa
foundation /
(MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
Ground surface (m)
1.00 3.3 0.22 4.2 0.28 2.9 0.19 4.4 0.29
1.50 3.3 0.22 4.2 0.28 2.9 0.19 4.4 0.29
2.00 3.3 0.22 4.2 0.28 2.9 0.19 4.4 0.29

Rd: resistance of the soil obtained by making the test

qa: allowable stress on the soil

By analyzing the tables above, we can note as allowable stress on the soil for shallow
foundations with an anchoring depth between 1.00 m and 2.00 m from the ground surface
the value of 0.19 MPa.

IX.3 Settlements
The dynamic penetration test does not permit to determine the amplitude of settlements.
Nevertheless, given the nature, the compactness of the soil encountered and the type of
structure to build (solar panel), the settlement should be admissible under the allowable
stress restained.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 10 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01
X CONCLUSION
The geotechnical survey carried out in Odienné and as part of the construction of solar
panels allowed us to have the following results:

- Nature of soils
The trial pits (PM1 to PM12) made during our intervention in March 2019 allowed to identify
soil layers on the first meter. These layers are constituted successively by a topsoil of 10 cm
thick, followed by lateritic gravelly of various colors.

- Water table depth

During our intervention in March 2019, the water table was not encountered. It is likely
located beyond the surveyed depth.

- Compactness of soils

On the two first meters the soils compactness goes from very compact to compact.
Beyond 2 m depth, the soils are compact to medium compact.

- Allowable stress

We can note as allowable stress on the soil for shallow foundations with an anchoring depth
between 1.00 m and 2.00 m from the ground surface the value of 0.19 MPa.

- Settlements
The dynamic penetration test does not permit to determine the amplitude of settlements.
Nevertheless, given the nature, the compactness of the soil encountered and the type of
structure to build (solar panel), the settlement should be admissible under the allowable
stress restained.

The conclusions of this report remain valid subject to the following important observations :

HEAD OF SPECIAL HEAD OF SOILS AND


FOUNDATIONS SERVICE FOUNDATIONS DIVISION

BINZEME ATCHO ALBERT FOTTO N’GOLE HUGUES

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 11 sur 12


No.2019/DGC/SF/0153 Réf : PR2-SP1/ENG/060
Version 01

IMPORTANT REMARKS

This report and its appendices constitute an indissociable whole. The improper use that
could be made of a communication or partial reproduction without the written consent of
L.B.T.P. can not engage the responsibility of this one.

Changes in the layout, design or significance of the constructs in relation to the data in
this study may lead to changes in the conclusions and requirements of the Report and
should, therefore, be brought to the attention of L.B.T.P..

Likewise, new elements highlighted during the execution of the foundations and that could
not be detected during the reconnaissance operations (for example: localized heterogeneity,
water coming, etc ...) may render obsolete the whole or part of the conclusions of the report.

These new elements as well as any major incident occurring during the works (sloping of
the embankment, landslide of the excavations, damage caused to existing constructions,
etc ...) must be immediately reported to L.B.T.P. to enable him to reconsider and eventually
adapt solutions initially recommended.

L.B.T.P. can not be held responsible for the changes made to his study only to the extent
that he has given, in writing, his agreement on the said modifications..

It is strongly recommended to the client to make proceed at the time of the opening of the
excavations or the realization of the first piles, to a site visit by a specialist L.B.T.P..

The purpose of this visit is to verify that the nature of the soils and the depth of the
foundation horizon are consistent with the data of the study. It gives rise to the drawing up of
a report.

Customer: FEEDBACK INFRA SOLAR ENERGY PROJECT OF 25 MW IN ODIENNE Page 12 sur 12


01235067859

969
139

d 4127997# e->fgCeCQCeefhefP g/TmE *


 iCCQj-HCQjC>kfHhlPC 7KM17#574K7;U92LM7#
 ! fee-OhCe OT0/
J4M3#V7#J3467K#
1W29RK8VV8K249#
"#$ %%&'%&(&&& 1W7973527#R4V8237#17#
OG/G.D )#$ *&+&,,'(&&& =+#:X
PQH ! >GDD/E -./0/ 123454#6789#:83;
<#$ '=&(&&& >0.?0 *=@&A@=&*B
=&*B@15;@RS@&*+A
CDDE J1* >0F *=@&A@=&*B
YZ[\]^_`aZbc j.DD0ojH
& * *& *&&
&(*& Kpqqp#rstsuvwp &
&(A& 5qvrpwpxy#wvusqzuz{xp#|qx} *&(%
*'('
5qvrpwpxy#wvusqzuz{xp#|vqz~ws *A('
+(n
*(&&
* +(n
,(*
B(n
n(B
n(B
= n(B
B(=
n(A
n(A
n(A
A n(A
n(%
n(%
,(n
,(n
' ,(n
+(=
+(=
'('
A(,
+ A(,
+(%
+(%
'(B
+(%
% +(%
-?D/0GD J797K34:7K37#
H0./I0ID. 1)98:2LM7#K)J7#N

€‚0€ƒ‚„0 …†€ƒ„‡ ƒ ƒ… 8ƒ0€€†ˆ5†„‰8ƒ 369696Š


6Š‹€ˆ696ŒŠŽ9
01235067859

969
139

G 5238::8# H.?IJCHCKCHHILHIM J0TUE (


 NCCKO.PCKOC?QIPLRMC 8Z[28#685Z8<\:3][8#
 ! IHH.SLCH ST10
Y5[4#^8#Y4578Z#
2_3:WZ9^^9Z35:#
"#$ %%&%'()&&& 2_8:84638#W5^9348#28#
SV0V/D *#$ +&,&--()&&& (,#;`
MKP ! ?VDD0E ./010 234565#789:#;94<
=#$ >(,)&&& ?1/@1 +(A&BA(&+'
(&+'A26<AWXA&+,B
CDDE Y2( ?1F +(A&BA(&+'
cdefghijkdlm O/DD1oOP
& + +& +&&
&)+& Zpqqp#rstsuvwp &
+B)>
6qvrpwpxy#wvusqzuz{xp#|qx} (B)&
&)-& (%)'
6qvrpwpxy#wvusqzuz{xp#|vqz~ws (B)&
+)&&
+ (B)&
+&)-
n)&
n)&
n)'
( n)&
%)-
,)n
,)&
,)&
B ,)&
>)-
()>
()>
B)+
> B)+
B)&
B)&
B)&
B)-
, B)-
>)'
>)(
>)(
>)(
% >)(
.@D01VD Y8:8Z45;8Z48#
P1/0a1aD/ 2*:9;3][8#Z*Y8#b

€‚0€ƒ‚„0 …†€ƒ„‡ ƒ ƒ… 8ƒ0€€†ˆ5†„‰8ƒ 369696Š


6Š‹€ˆ696ŒŠŽ9
01235067859

969
139

G 5238::8# H.>IJCHCKCHHILHIM J0TUE B


 NCCKO.PCKOC>QIPLRMC 8Z[28#685Z8<\:3][8#
 ! IHH.SLCH ST10
Y5[4#^8#Y4578Z#
2_3:WZ9^^9Z35:#
"#$ %%&'(%)&&& 2_8:84638#W5^9348#28#
SV0V/D *#$ +&(&,--)&&& @(#;`
MKP ! >VDD0E ./010 234565#789:#;94<
=#$ --&)&&& >1/?1 +@A&BA@&+'
@&+'A26<AWXA&+(B
CDDE Y2B >1F +@A&BA@&+'
O/DD1oOP
cdefghijkdlm & + +& +&&
&)+& Zpqqp#rstsuvwp &
%),
++)(
6qvrpwpxy#wvusqzuz{xp#q|xtp}uqp n)%
+&)%
+)&&
+ +&)%
++)%
n)'
n)&
%)B
@ ,)+
%),
()n
%),
%),
B %),
()(
()(
,)+
,)+
- %)B
()@
-)-
-)-
-)-
( -)-
-)@
-)@
-)'
-)@
% -)@
.?D01VD Y8:8Z45;8Z48#
P1/0a1aD/ 2*:9;3][8#Z*Y8#b

~€0‚ƒ0 „…€‚ƒ† ‚ ‚„ 8‚0…‡5…€~ƒˆ8‚ ~369696‰


6‰Š‡696‹‰Œ9
01235067859

969
139

G 5238::8# H.?IJCHCKCHHILHIM J0TUE >


 NCCKO.PCKOC?QIPLRMC 8Z[28#685Z8<\:3][8#
 ! IHH.SLCH ST10
Y5[4#^8#Y4578Z#
2_3:WZ9^^9Z35:#
"#$ %%&'&%())) 2_8:84638#W5^9348#28#
SV0V/D *#$ &)+),-,())) '+#;`
MKP ! ?VDD0E ./010 234565#789:#;94<
=#$ >>>())) ?1/@1 &-A)-A')&B
')&BA26<AWXA)&+-
CDDE Y2> ?1F &-A)-A')&B
jklmnopqrkst O/DD1vOP
) & &) &))
)
)(-) 6wxyz{z|}#{x~w€~€|z#‚w|ƒ ,(,
&)(%
6wxyz{z|}#{x~w€~€|z#w„|…z†~wz &>(>
'u(u
&())
& ->(%
-+(,
uB(-

'

>

%
.@D01VD OFD//10V a10b Ucdefg 0VFV0 Y8:8Z45;8Z48#
P1/0h1hD/ 2*:9;3][8#Z*Y8#i

‡ˆ‰Š0ˆ‹ŠŒ0 Ž‰ˆ‹Œ ‹ ‹ 8‹0ˆˆŽ5Ž‰‡Œ‘8‹ ‡369696’


6’“ˆ696”’•–9
01235067859

969
139

G 6349;;9# H/?IJCHCKCHHILHIM J1TUE (


 NCCKO/PCKOC?QIPLRMC 9Z[39#796Z9=\;4][9#
 ! IHH/SLCH ST21
Y6[5#^9#Y5689Z#
3_4;WZ:^^:Z46;#
"#$ %%&''()*** 3_9;95749#W6^:459#39#
SV1V0D +#$ &*(*,-.)*** -(#<`
MKP ! ?VDD1E /0121 345676#89:;#<:5=
>#$ ''-)*** ?20@2 &.A*.A-*&B
-*&BA37=AWXA*&(.
CDDE Y3( ?2F &.A*.A-*&B
cdefghijkdlm O0DD2oOP
* & &* &**
*
*).* 7pqrstsuv#tqwxpywyzus#{pu| &*)%
n)%
7pqrstsuv#tqwxpywyzus#p}u~swps &*)%
&-)(
&)**
& n)%
&,)B
&,)B
&,)B
-()B
- &,)B
&%),
&-)(
B)-
n).
. n).
,)n
%).
%).
()(
' ()(
()B
()-
')'
')'
( ()-
')-
')-
')B
')-
% ')-
/@D12VD Y9;9Z56<9Z59#
P201a2aD0 3+;:<4][9#Z+Y9#b

€‚ƒ0„ƒ…0 †‡‚„…ˆ „ „† 8„0‡‰5‡‚€…Š8„ €369696‹


6‹Œ‰696‹Ž9
01235067859

969
139

G 4127997# H->IJCHCKCHHILHIM J/TUE %


 NCCKO-PCKOC>QIPLRMC 7Z[17#574Z7;\92][7#
 ! IHH-SLCH ST0/
Y4[3#^7#Y3467Z#
1_29WZ8^^8Z249#
"#$ %%&'(()((( 1_7973527#W4^8237#17#
SV/V.D *#$ &(+('(,)((( ,+#:`
MKP ! >VDD/E -./0/ 123454#6789#:83;
<#$ ==')((( >0.?0 &@A(@A,(&B
,(&BA15;AWXA(&+@
CDDE Y1% >0F &@A(@A,(&B
cdefghijkdlm O.DD0oOP
( & &( &((
(
()@( 5pqrstsuv#tqwxpywyzus#{pu| &&)+
&()%
5pqrstsuv#tqwxpywyzus#p}u~swps &=)=
&B),
&)((
& &,)+
&,)+
&&)%
&()'
&@)=
, &+),
&@)=
&()(
n)@
n)@
@ n)@
n)%
n)%
&(),
n)%
= ')&
%)%
%)%
+)B
+)B
+ +),
=)B
=),
=),
=),
% =),
-?D/0VD Y797Z34:7Z37#
P0./a0aD. 1*98:2][7#Z*Y7#b

€‚ƒ0„ƒ…0 †‡‚„…ˆ „ „† 8„0‡‰5‡‚€…Š8„ €369696‹


6‹Œ‰696‹Ž9
01235067859

969
139

G 4127997# H->IJCHCKCHHILHIM J/TUE ,


 NCCKO-PCKOC>QIPLRMC 7Z[17#574Z7;\92][7#
 ! IHH-SLCH ST0/
Y4[3#^7#Y3467Z#
1_29WZ8^^8Z249#
"#$ %%&%&'())) 1_7973527#W4^8237#17#
SV/V.D *#$ &)+)+),())) '+#:`
MKP ! >VDD/E -./0/ 123454#6789#:83;
<#$ ==)())) >0.?0 &=@)A@')&B
')&B@15;@WX@)&+A
CDDE Y1, >0F &=@)A@')&B
cdefghijkdlm O.DD0oOP
) & &) &))
)(&+ 5pqrstsuv#tqwxpywyzus#{pu| )
&+(=
&'(+
5pqrstsuv#tqwxpywyzus#p}u~swps &+(=
&n('
&())
& &B('
&+('
&,()
&,()
&=(A
' &=(A
&)()
n(A
+(n
+(n
A +(n
+(+
=(,
=(,
=(,
= =(,
A(,
=(=
=(=
=(=
+ =(=
A(+
'(n
A(+
'(n
% '(n
-?D/0VD Y797Z34:7Z37#
P0./a0aD. 1*98:2][7#Z*Y7#b

€‚ƒ0„ƒ…0 †‡‚„…ˆ „ „† 8„0‡‰5‡‚€…Š8„ €369696‹


6‹Œ‰696‹Ž9
01235067859

969
139

G 5238::8# H.>IJCHCKCHHILHIM J0TUE V


 NCCKO.PCKOC>QIPLRMC 8[\28#685[8<]:3^\8#
 ! IHH.SLCH ST10
Z5\4#_8#Z4578[#
23̀:X[9__9[35:#
"#$ %%&'()*+++ 28̀:84638#X5_9348#28#
SW0W/D ,#$ &+-+-)'*+++ A-#;a
MKP ! >WDD0E ./010 234565#789:#;94<
=#$ ''+*+++ >1/?1 &'@+(@A+&B
A+&B@26<@XY@+&-(
CDDE Z2V >1F &'@+(@A+&B
defghijklemn O/DD1oOP
+ & &+ &++
+*&- [pqqp#rstsuvwp +
&+*%
&(*'
6qvrpwpxy#wvusqzuz{xp#q|xtp}uqp ((*%
%)*A
&*++
& 'A*A
A%*V
A(*A
&V*V
&(*'
A &-*A
%*)
-*V
%*)
V*(
( )*-
%*(
)*&
)*V
)*V
' )*V
V*&
)*'
)*'
%*%
- %*%
)*+
%*(
%*(
%*(
% %*(
.?D01WD Z8:8[45;8[48#
P1/0b1bD/ 2,:9;3^\8#[,Z8#c

~€0‚ƒ0 „…€‚ƒ† ‚ ‚„ 8‚0…‡5…€~ƒˆ8‚ ~369696‰


6‰Š‡696‹‰Œ9
01235067859

969
139

G 4127997# H->IJCHCKCHHILHIM J/TUE B


 NCCKO-PCKOC>QIPLRMC 7Z[17#574Z7;\92][7#
 ! IHH-SLCH ST0/
Y4[3#^7#Y3467Z#
1_29WZ8^^8Z249#
"#$ %%&'()*((( 1_7973527#W4^8237#17#
SV/V.D +#$ &(,(,,,*((( A,#:`
MKP ! >VDD/E -./0/ 123454#6789#:83;
<#$ =')*((( >0.?0 &=@('@A(&B
A(&B@15;@WX@(&,'
CDDE Y1B >0F &=@('@A(&B
cdefghijkdlm O.DD0oOP
( & &( &((
(*&( Zpqqp#rstsuvwp (
&A*,
,*n
5qvrpwpxy#wvusqzuz{xp#q|xtp}uqp ,*n
=*n
&*((
& ,*n
=*,
=*,
'*%
'*%
A '*%
'*'
'*'
'*'
'*'
' '*'
'*&
'*B
'*B
'*B
= '*B
,*A
,*A
=*=
,*A
, ,*A
=*B
=*B
=*B
=*B
% =*B
-?D/0VD Y797Z34:7Z37#
P0./a0aD. 1+98:2][7#Z+Y7#b

~€0‚ƒ0 „…€‚ƒ† ‚ ‚„ 8‚0…‡5…€~ƒˆ8‚ ~369696‰


6‰Š‡696‹‰Œ9
01235067859

969
139

F 3016886# G,>HIBGBJBGGHKGHL I.STD &'


 MBBJN,OBJNB>PHOKQLB 6YZ06#463Y6:[81\Z6#
 ! HGG,RKBG RS/.
X3Z2#]6#X2356Y#
0^18VY7]]7Y138#
"#$ %%&'(()''' 0^6862416#V3]7126#06#
RU.U-C *#$ &'('(+()''' A(#9_
LJO ! >UCC.D ,-./. 012343#5678#972:
;#$ +<=)''' >/-?/ &+@'<@A'&=
A'&=@04:@VW@'&(<
BCCD X0&' >/E &+@'<@A'&=
N-CC/oNO
bcdefghijckl ' & &' &''
')&' Ypqqp#rstsuvwp '
')<( 4qvrpwpxy#wvusqzuz{xp#|qx} &m)<
&+)+
4qvrpwpxy#wvusqzuz{xp#q~xtpuqp &+)+
&n)A
&)''
& AA)&
&=)%
A')(
&%)&
()+
A ()+
()'
()'
+)A
+)A
< ()'
+)m
<)=
+)m
+)m
+ +)m
+)+
()A
()A
()=
( %)%
%)<
%)<
m)'
%)<
% %)<
,?C./UC X686Y2396Y26#
O/-.`/`C- 0*8791\Z6#Y*X6#a

€‚ƒ0„ƒ…0 †‡‚„…ˆ „ „† 8„0‡‰5‡‚€…Š8„ €369696‹


6‹Œ‰696‹Ž9
01235067859

969
139

H 4127997# I-?JKDIDLDIIJMIJN K/UVF ++


 ODDLP-QDLPD?RJQMSND 7[\17#574[7;]92^\7#
 ! JII-TMDI TU0/
Z4\3#_7#Z3467[#
12̀9X[8__8[249#
"#$ %%&'&()&&& 17̀973527#X4_8237#17#
TW/W.E *#$ +&,&,&,)&&& =,#:a
NLQ ! ?WEE/F -./0/ 123454#6789#:83;
<#$ (=>)&&& ?0.@0 +(A&BA=&+C
=&+CA15;AXYA&+,B
DEEF Z1++ ?0G +(A&BA=&+C
defghijklemn P.EE0oPQ
& + +& +&&
&)+, [pqqp#rstsuvwp &
+&)%
+C)=
5qvrpwpxy#wvusqzuz{xp#q|xtp}uqp =C)'
+%)B
+)&&
+ +()(
')&
')&
')&
>)+
= >)+
%)>
,)'
B)B
=),
B %)>
%)B
,),
%)B
>)+
( %)B
%)%
,)C
%)%
%)%
, %)%
%)B
%)B
%)B
,)%
% ,)%
-@E/0WE Z797[34:7[37#
Q0./b0bE. 1*98:2^\7#[*Z7#c

~€0‚ƒ0 „…€‚ƒ† ‚ ‚„ 8‚0…‡5…€~ƒˆ8‚ ~369696‰


6‰Š‡696‹‰Œ9
01235067859

969
139

G 4127997# H->IJCHCKCHHILHIM J/TUE ,=


 NCCKO-PCKOC>QIPLRMC 7Z[17#574Z7;\92][7#
 ! IHH-SLCH ST0/
Y4[3#^7#Y3467Z#
1_29WZ8^^8Z249#
"#$ %%&'()*&&& 1_7973527#W4^8237#17#
SV/V.D +#$ ,&'&'(&*&&& ='#:`
MKP ! >VDD/E -./0/ 123454#6789#:83;
<#$ (=,*&&& >0.?0 ,(@&A@=&,B
=&,B@15;@WX@&,'A
CDDE Y1,= >0F ,(@&A@=&,B
cdefghijkdlm O.DD0oOP
& , ,& ,&&
&*,& Zpqqp#rstsuvwp &
&*A& 5qvrpwpxy#wvusqzuz{xp#|qx} =&*=
=,*,
5qvrpwpxy#wvusqzuz{xp#q~xtpuqp ,%*A
,,*'
,*&&
, ,,*'
'*(
%*A
n*,
n*,
= n*,
)*A
)*A
%*n
%*n
A %*n
(*n
(*n
(*n
(*n
( (*n
(*(
(*(
(*(
(*(
' A*n
(*=
A*'
(*=
A*'
% A*'
-?D/0VD Y797Z34:7Z37#
P0./a0aD. 1+98:2][7#Z+Y7#b

€‚ƒ0„ƒ…0 †‡‚„…ˆ „ „† 8„0‡‰5‡‚€…Š8„ €369696‹


6‹Œ‰696‹Ž9

You might also like