Introduction
This article outlines the outcome of auditing of steam system conducted in process Industries. The
details of modifications / improvements carried out may be of use to other boiler users. During the
audit the operating staff had exchanged all their experiences and this had resulted in benefit of their
plant.
A detailed interaction with various level personnel in the plant resulted in a long list of the
problems that could be addressed in order to improve the plant efficiency. The list was quite
exhaustive and it included the finer details of the problems as experienced. The studies included
both the boiler and the entire steam & condensate system of the plant. For photos refer annexure.
The customer had requested for an audit of their plant to bring down the coal consumption. The
boiler was originally a husk fired. Later due to fuel price escalations, customer switched over to
coal firing most of the year.
The customer had requested for an operational audit of their boiler to bring down the fuel
consumption and to address the dust complaint from nearby factories. The boiler was originally a
wood fired boiler. Later due to non availability of wood the boiler was converted to FBC firing
with external refractory furnace walls. The biomass fuels used include rice husk, tamarind shell,
ground nut shell, coffee husk.
Clinker formation The fuels used have ash fusion The combustion temperatures were
in bed. temperatures as low as 750 deg C. adjusted for a lower bed
temperature.
There was clinker formation above the The biomass of fouling nature
bed on the wall due to high free board needs waterwall furnace enclosure.
temperature excursions & due to Only flue gas recycling is to be
presence of uncooled walls. done now to reduce the furnace
temperature.
ID fan capacity It was seen that the air / flue gas Ducting reengineering was advised
inadequate ducting is designed in a haphazard to bring down the draft loss.
manner. See photo 34.
It was seen that the ID fan is provided Customer was advised to remove
with a damper right at the fan inlet. the flap from the damper and to
Such obstructions bring down the fan provide multi flap damper in the
performance. See photo 33. MDC outlet duct.
Chimney failure This is a common phenomenon in The exhaust temperature at chimney
many plants. The cause is the high top should be over 110 deg C. This
moisture content in fuel & low can be improved by insulating the
exhaust temperature. gas ducting up to chimney inlet.
Dust complaint Though the ash content is less, due to Customer was advised for rotary
from adjourning improper combustion, improper ash ash feeder at all ash collection
factory. collection system combined with points. In addition unconventional
condensation of water vapor has dust traps as seen in photo 32 & 33
caused carbon particulate. were added.
Furnace is not provided with over-fire Customer was advised to
air arrangement. High volatile fuels incorporate secondary air system.
need a good turbulence above the bed, Seeing the CO values in the flue gas
particularly in over bed feed system. at shell outlet the over-fire air has to
This is required to burn off the be adjusted.
unburnt gases.
Frequent boiler The feed pump suction piping is with Customer was advised to remove
feed pump failure mistakes that take away the NPSH. the thermocouple & flow meter
See photo 35, 36 & 37. immediately. If problem persists,
globe valve shall be replaced with
gate valve.
Conclusion
Generally in all the plants there remains a good scope for fuel savings & for improving the steam
generating & distributing system. There are numerous cases where plant engineers & operators
have incorporated many improvements. The users could bring out their achievements in this boiler
meet in the further years.
Photo 1: Gauge glass seen eroded. This failure Photo 2: Gauge glass located close to risers.
took place every week. This causes turbulence in water level gauge.
Figure 1:
Photo 3: Excess chemicals have led to whitish Photo 4: Rear tube sheet seen with whitish
deposit seen in the shell above the tubes. deposit. If hardness salts are present, tubes
would be seen with deposits.
Photo 5: A baffle box provided at one end of the Photo 6: Steam separator seen with foaming
drum did not have level equalizer. The steam mark indicating the drum was under turbulent
water mixture would have to climb over the box. water level.
Figure 2:
Photo 7: Risers do not have a cap. Thus the Photo 8: Inlet of the I pass tubes at shell. A view
water can go directly to the steam pipe nearby. after cleaning. Old deposits could be seen.
Figure 3:
Photo 9: Compressor lined up for ash deposit Photo 10: Cleaning ports in the inspection door.
removal. Compressed air line is taken out of port.
Photo 11: Fresh air ingress to APH causes gas Photo 12: Improper APH inspection door
condensation leading to corrosion & choking. seating leads to cold ingress.
Photo 13: Shell intermittent hopper (not Photo 14: MDC cones seen coated with
insulated?)with improper flange seating condensed ash deposits. Insulation is advised.
allowing air ingress.
Photo 17: Uninsulated valves result in heat loss. Photo 18: Steam seen gushing out of trap. There
were traps downstream & hence this was closed.
Photo 20: Auditing equipment – Infrared camera
Photo 19: In accessible traps – not suited for
– for identifying defective trap, bearings &
regular check.
electrical panels.
Photo 21: Energy audit equipment – ultrasonic Photo 22: Vibratory feeder being used for coal
probe for various application feeding in an FBC boiler. Boiler designed for
husk.
Photo 23: Unburnt coal seen in the bed ash Photo 24: The Oxygen analyzer is provided to
itself. It is not practically adjust required coal ensure Oxygen is available for combustion. If
feed rate with vibratory feeder. The LOI ranged load is varying then the minimum Oxygen has
to 2% in this case. to be 3.5%.
.
Photo 26
Photo 25
Photo 27: Uninsulated areas in a bi-drum boiler Photo 28: Almost at all sealbox the temperatures
run over the stipulated ambient + 20 deg C. Max
temperature is 197 deg C.
Photo 33: A way to reduce dust emission. Photo 34. Haphazard ducting adds up to higher
Further at all ash collection points rotary feeders draft loss. Customer had gone ahead with
added. replacement of fans.
Photo 35, 36 & 37 show the mistakes made in feed pump suction piping that the frequently the
pumps fails to pump due to cavitation. Thermocouple in the line, flow meter & globe valve in pump
suction line creates loss of NPSH.