) The beam shown carries a uniform load of 30 KN/m including its weight and a
concentrated P acting at the mid span. Assuming the beam to be laterally unsupported,
determine the safe value of P if Fy = 250 MPa when:
a.) when L = 3 m.
0.20 𝑏𝑓
Lc =
√𝐹𝑦
.20 (261)
Lc = = 3.28 > L
√250
Used allowable bending stress Fb = 0.66 Fy
Fb = 0.66 (250) = 165 MPa
𝑀 𝑀
Fb= ; 165=
𝑆 2200000
M = 363000000 N-mm = 363 KN-m
Considering the loading and condition of supports.
𝜔𝐿2 𝑃𝐿
M= +
8 4
(30)(3)2 𝑃(3)
363 = +
8 4
P= 439 KN.
b.) when L = 6 m.
.20 (261)
Lc = = 3.28 < L
√250
139
Lu= 𝐹𝑦𝑑
𝐴𝑓
139
Lu= (250)(420) =6.68 > L
(261)(19.33)
Used allowable bending stress Fb = 0.60 Fy
Fb = 0.60 (250) = 150 MPa
𝑀 𝑀
Fb= ; 150=
𝑆 2200000
M = 330000000 N-mm = 330 KN-m
Considering the loading and condition of supports.
𝜔𝐿2 𝑃𝐿
M=
8
+ 4
(30)(6)2 𝑃(6)
330 = +
8 4
P= 130 KN.
C.) When L = 8
L > Lc > Lu
𝑳 𝟕𝟎𝟔 𝒙 𝟏𝟎𝟑 𝑪𝒃
Then verify if , >√
𝒓𝑻 𝑭𝒚
𝑳 𝟑𝟓𝟒𝟎 𝒙 𝟏𝟎𝟑 𝑪𝒃
And <√
𝒓𝑻 𝑭𝒚
Determine firt rt
½𝐼
rT = √ 1
𝐴𝑓+ 𝐴𝑤
6
½(57.2 𝑥106 )
rT = √ 1 = 71.06 mm
(251∗19.33)+ (420∗11.6)
6
𝐿 8000
= = 112.58
rT 71.06
6 6
706 𝑥 10 𝐶𝑏 706 𝑥 10 (1)
√
𝐹𝑦
= √ 250
= 53.14< 112..58
6 6
√3540 𝑥 10 𝐶𝑏
= √
3540 𝑥 10 (1)
= 119 > 112.58
𝐹𝑦 250
𝟐
𝟐 𝑭𝒚(𝑳⁄𝒓𝑻 )
Therefore Used allowable bending stress Fb = [𝟑 − 𝟏𝟎.𝟔 𝒙𝟏𝟎𝟔𝑪𝒃] 𝑭𝒚 in MPA
𝟐 𝟐𝟓𝟎(𝟏𝟏𝟐.𝟓𝟖)𝟐
Fb = [𝟑 − 𝟏𝟎.𝟔 𝒙𝟏𝟎𝟔(𝟏) ] 𝟐𝟓𝟎 = 91.94 MPA
82700 𝐶𝑏
Also check: Fb = 𝐿𝑑
Af
82700 (1)
Fb = (8000)∗(420) = 124.17 MPa
(261)∗(19.33)
Use the biggest of the two Fb but < 0.60Fy
Therefore use Fb = 124.17 MPa
𝑀 𝑀
Fb= ; 124.17=
𝑆 2200000
M = 273174000 N-mm = 273.17 KN-m
Considering the loading and condition of supports.
𝜔𝐿2 𝑃𝐿
M= +
8 4
(30)(8)2 𝑃(8)
273.17 = +
8 4
P= 16.59 KN.
d.) When L= 10 m.
𝐿 10000
= = 140.73
rT 71.06
6 6
√706 𝑥 10 𝐶𝑏
= √
706 𝑥 10 (1)
= 53.14< 140.73
𝐹𝑦 250
6 6
√3540 𝑥 10 𝐶𝑏 = √3540 𝑥 10 (1) = 119 <140.73
𝐹𝑦 250
1170 𝑥 103 𝐶𝑏
Therefore use Fb = 2
𝐿
(r )
T
1170 𝑥 103 (1)
Fb =
(140.737)2
= 59.08 MPa
82700 𝐶𝑏
Also check: Fb = 𝐿𝑑
Af
82700 (1)
Fb = (10000)∗(420) = 99.34 Mpa
(261)∗(19.33)
Therefore use Fb= 99.34 MPa
𝑀 𝑀
Fb= ; 99.34=
𝑆 2200000
M = 218548000 N-mm = 218.54 KN-m
Considering the loading and condition of supports.
𝜔𝐿2 𝑃𝐿
M= +
8 4
(30)(10)2 𝑃(10)
218.54 = +
8 4
P= -62.58 KN. (The negative result indicates that the 10 m. length of that beam
cannot carry the given 30 KN/m load or P must be acting upward to carry the
given load.)
2.The simply supported beam W 16 x 67 (English system)
carries a u niform load of 9 KN/m including its own
weight. Assuming the beam to be laterally un-supported
throughout its 9 meters length. Determine the equal
concentrated load at its one-third points. Fy= 250 MPa
Use AISC specification.
W A d tw bf tf rt Ix Sx rx Iy Sy
Designation
kg/m mm2 mm mm mm mm mm ×103 mm4 ×103 mm3 mm ×103 mm4 ×103 mm3
W 16 × 77 114.69 14,581 419.60 11.60 261.50 19.30 70.36 462,017 2,202 178.01 57,440 439 62.76
W 16 × 67 99.97 12,710 414.80 10.00 260.00 16.90 69.85 397,085 1,915 176.75 49,532 381 62.43
W 16 × 57 85.26 10,839 417.30 10.90 180.80 18.20 47.24 315,503 1,512 170.61 17,940 198 40.68
solution:
.20 𝑏𝑓
Lc =
√𝐹𝑦
.20 (260)
Lc = = 3.28 < L
√250
139
Lu= 𝐹𝑦𝑑
𝐴𝑓
139
Lu= (250)(414.78) =5.89 < L
(260)(16.9)
½𝐼
rT = √ 1
𝐴𝑓+ 𝐴𝑤
6
½(49.53 𝑥106 )
rT = √ 1 = 69.78 mm
(260∗16.9)+ (414.78∗10)
6
𝐿 9000
= = 128.97
rT 64.78
6 6
√706 𝑥 10 𝐶𝑏
= √
706 𝑥 10 (1)
= 53.14< 128.97
𝐹𝑦 250
6 6
√3540 𝑥 10 𝐶𝑏
= √
3540 𝑥 10 (1)
= 119 < 128.97
𝐹𝑦 250
1170 𝑥 106 𝐶𝑏
Therefore use Fb = 2
𝐿
(r )
T
1170 𝑥 106 (1)
Fb =
(128.97)2
= 70.34 MPa
82700 𝐶𝑏
Also check: Fb = 𝐿𝑑
Af
82700 (1)
Fb = (9000)∗(414.78) = 97.34 Mpa
(260)∗(16.9)
Therefore use Fb= 97.34 MPa
𝑀𝑐 𝑀
Fb = =
𝐼 𝑆𝑥
M =( 97.34 ) (1.92 x106)
M = 186.9 x106 N-mm =188 KN-m
𝑤𝐿2 𝑃𝐿
From the given length of beam and support condition ; M= +
8 3
(9)(9)2 𝑃(9)
186.9 = +
8 3
P = 31.93 KN.
3. A W16x31 beam section consisting of A 36 steel. Fy=250 MPa , Fu=400 MPa has two
holes for 22 mm diameter bolts in its tension flange. Fb=0.66Fy .
W 16 × 36 53.79 6,839 402.80 7.50 177.40 10.90 45.47 186,472 926 165.12 10,198 115 38.62
W 16 × 31 46.2 5,890 403 7.00 140 11.20 35.31 156,087 773 162.87 5,161 74 29.62
W 16 × 26 38.98 4,955 398.50 6.40 139.70 8.80 34.54 125,286 629 159.01 3,992 57 28.38
3 3
d = 403 mm bf= 140 mm tw= 7.0 mm Sx =773 x 10 mm
A = 5890 mm2 tf =11.2 mm w= 46.2 kg/m Ix = 156 x 106 mm4
5𝐹𝑢 𝐴𝑓 𝑛
Effective flange area , Afe =
6𝐹𝑦
5(400)(1008)
Afe = = 1344 mm2
6(250)
4. Find the safe concentrated load acting at midspan of W200 x 42 A36 steel having a simple
span of 6mtr. Assumed that the beam is laterally supported. Use AISC Specifications. Indicate
whether this section is a compact or non compact section. Neglect deflection of the beam.
Properties of W 200 x 42
A = 5310 mm2 tw= 7.2 mm Iy = 9 x 106 mm4
d = 205 mm Ix = 40.9 x 106 mm4 Sy = 108 x 103 mm3
bf = 166 mm Sx = 399 x 103 mm3 ry = 41.2 mm
tf = 11.80 mm rx = 87.7 mm w = 41.7 kg/m
bf 170 d 1690
Check if the section is Compact not: 2tf Fy and tw Fy
(0.412)(6)2 𝑃(6)
65.31 = +
8 4
P = 42.3 KN