You are on page 1of 6

GENERAL 7.

0 REINFORCEMENT
1.01 TECHNICAL SPECIFICATIONS OR SPECIFIC INSTRUCTIONS ON DRAWINGS 5.0 FOUNDATIONS
7.01 REINFORCEMENT SYMBOLS
TAKE PRECEDENCE OVER THESE NOTES. 5.01 FOUNDATIONS HAVE BEEN DESIGNED FOR THE FOLLOWING ALLOWABLE PRESSURES:
S DENOTES GRADE 250 S HOT ROLLED DEFORMED BARS TO AS
1.02 THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH AL 4671
ARCHITECTURAL AND OTHER CONSULTANTS DRAWINGS AND SPECIFICATIONS ELEMENT BEARING SHAFT N DENOTES GRADE D500 N BARS TO AS 4671 GRADE N ELEMENT SURFACE PRIME COAT SECOND COAT THIRD COAT
AND WITH SUCH OTHER WRITTEN INSTRUCTIONS AS MAY BE ISSUED DURING THE PRESSURE (kPa) ADHESION (kPa) SL &RL DENOTES GRADE 250 HOT ROLLED PLANS BARS TO AS 4671 PREPARATION
COURSE OF THE CONTRACT,ANY DISCREPANCY SHALL BE REFERRED TO THE SQUARE
WAFFLE SLAB,PAD & ABRASIVE BLAST 2 COATS R.O.Z.P
ENGINEER BEFORE PROCEEDING WITH THE WORK.CONSTRUCTION FROM THESE 150 - RECTANGULAR MESH RESPECTIVELY ALL U.N.O REFER REFER
STRIP FOOTINGS CLASS 2.5 (MIN.DRY FILM
DRAWINGS AND THEIR ASSOCIATED CONSULTANCTS DRAWINGS IS NOT TO R DENOTES GRADE 250 HOT ROLLED PLAIN BARS TO AS 4671 ARCHITECT ARCHITECT
COMMENCE UNTIL APPROVED BY THE LOCAL AUTHORITIES. PILES 300 25 THICKNESS TO 75
W DENOTES HARD-DRAWN PLAIN WIRE TO AS 4671
1.03 ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE DW DENOTES COLD ROLLED RIBBED WIRE TO AS 4671 ALL EXTERNAL MICRONS)
HOT DIP REFER REFER
RELEVANT AND CURRENTSTANDARDS AUSTRALIA CODES AND WITH BY-LAWS & STTELWORK -
5.02 THE FOUNDATION MATERIAL SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER FOR THIS GALVANISED ARCHITECT ARCHITECT
ORDINACES OF THE RELEVANT BUILDING AUTHORITIES EXCEPT WHERE VARIED NUMBER OF BARS IN BAR GRADE AND TYPE (INCL.LINTELS)
BY THE PROJECT SPECIFICATION. BEARING CAPACITY BEFORE PLACING ANY MEMBRANE,REINFORCEMENT OR CONCRETE,WHERE
GROUP
1.04 ALL DIMENSIONS SHOWN SHALL BE VERIFIED BY THE BUILDER ON NECESSARY,THE FOOTING DESIGN MAY BE ALTERED.
17N20-250
SITE.ENGINEER'S DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS 5.03 SITE CLASSIFICATION IS ASSUMED CLASS "M" IN ACCORDANCE WITH AS2870,THIS IS TO BE
CONFIRMED ON SITE ON SITE AFTER EXCAVATION HAS TAKEN PLACE. 9.12 THE BUILDER SHALL PROVIDE ALL CLEATS AND DRIL ALL HOLES
1.05 DURING CONSTRUCTION THE STRUCTURE AND ANY ASSOCIATED NECESSARY FOR FIXING STEEL TO STEEL AND TIMBER TO STEEL
EXCAVATIONS SHALL BE MAINTAINED IN A STABLE CONDITION AND NO PART 5.04 THE BUILDER SHALL BE RESPONSIBLE FOR MAINTAINING ANY EXCAVATIONS IN A STABLE CONDITION NOMINAL BAR SIZE IN mm BAR SPACING IN mm
WITHOUT ADVERSELY AFFECTING SURROUNDING PROPERTIES INCLUDING SERVICES,THIS INCLUDES WHETHER OR NOT DETAILED IN THE DRAWINGS.
SHALL BE OVERSTRESSED.TEMPORARY BRACING SHALL BE PROVIDED BY THE 9.13 FREE ALL MEMBERS FROM TWISTS AND DISTORTIONS BEFORE AND
BUILDER TO KEEP THE WORKS AND EXCAVATIONS STABLE AT ALL TIMES. OBTAINING ALL NECESSARY APPROVALS FOR SHORING AND ANCHORING SYSTEMS.
THE FIGURES FOLLOWING THE FABRIC SYMBOL IS THE REFERENCE NUMBER FOR AFTER WELDING.
1.06 UNLESS NOTED OTHERWISE,ALL DIMENSIONS ARE IN MILLIMETERS (mm) 5.05 FOOTING SHALL BE LOCATED CENTRALLY UNDER WALLS AND COLUMNS UNLESS NOTED OTHERWISE.
FABRIC TO AS 4671 9,14 ALL MEMBERS TO BE IN ONE LENGTH,UNLESS OTHERWISE
AND ALL LEVELS ARE IN METERS (m) TO AUSTRALIAN HEIGHT DATUM (AHD). 5.06 FOOTING NEAR BOUNDARIES MUST NOT BE LOCATED HIGHER OR LOWER THAN FOOTNGS OF
7.02 ALL REINFORCEMENT SHALL FIRMLY SUPPORTED ON MILD STEEL PLASTIC TIPPED APPROVED.
1.07 ALL ABBREVIATIONS ARE IN ACCORDANCE WITH AS1100.ADDITIONAL ADJACENT PROPERTIES UNLESS APPROVED.
CHAIRS OR CONCRETE CHAIRS AT NOT GREATER THAN 1 METER CENTRES BOTH
ABBRVIATIONS USED ARE AS FOLLOWS: 5.07 WHERE FOOTINGS ARE OVER-EXCAVATED,FILL OVER-EXCAVATED AREAS WITH BINDING CONCRETE
WAYS,BARS SHALL BE TIED AT ALTERNATE INTERSECTIONS.IN EXPOSURE CONSITIONS
NSOP NOT SHOWN ON PLAN GRADE SAME AS FOOTING TO A MINIMUM THICKNESS OF 50 mm.
GREATHER THAN B1 ONLY PLASTIC CHAIRS. 10.0 STRUCTURAL TIMBER
NSOE NOT SHOWN ON ELEVATION 5.08 KEEP FOOTING CLEAN AND FREE OF LOOSE MATERIAL BEFORE INSPECTION,IMMEDIATELY PRIOR TO
7.03 REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT NECESSARILY IN 10.01 ALL TIMBER DESIGN CONSTRUCTION AND MATERIAL TO BE AS
UNO UNLESS NOTED OTHERWISE POURING OF CONCRETE,AND DURING POURING.
TRUE PROJECTION. 1720.1 AND AS 1720.2 U.N.O.
U/S UNDERSIDE 5.09 DO NOT EXCEED A RISE OF 1000 mm IN A RUN OF 3000 mm FOR THE LINE UNTIL OF SLOPE BETWEEN
7.04 SLAB REINFORCEMENT SHALL EXTEND AT LEAST 75 mm ONTO MASONARY SUPPORT 10.02 AS 1684 SHALL BE APPLIED TO DOMESTIC CONSTRUCTION IN
GL GROUND LINE ADJACENT FOOTINGS OR EXCAVATIONS.
WALLS AND 50 PERCENT OF BOTTOM REINFORCEMENT SHALL BE COGGED TO ACHIVE SHELTERED LOCATIONS.
FFL FINISHED FLOOR LEVEL 5.10 DO NOT BACKFILL RETANING WALLS (OTHER THAN CANTELEVER WALLS) UNTIL FLOOR
ANCHORAGE AT SIMPLY SUPPORTED ENDS. 10.03 SOFTWOOD TO BE MINIMUM GRADE F7 U.N.O. HARDWOOD TO BE
CONSTRUCTION AT TOP AND BOTTOM IS COMPACTED.ENSURE FREE DRANING BACKFILL AND DRANAGE IN
7.05 SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN POSITIONS SHOWN OR MINIMUM GRADE F14.
2.0 DESIGN DATA PLACE.
OTHERWISE APPOROVED IN WRITTING BY THE ENGINEER.LAPS SHALL BE IN 10.04 EXTERNAL TIMBER TO BE EITHER HARDWOOD DURABILITY CLASS I
2.01 THE STRUCTURAL COMPONENTS DETAILED ON THESE DRAWINGS HAVE 5.11 FOOTINGS ARE TO BE CONSTRUCTED AND BACKFILLED AS SOON AS POSSIBLE FOLLOWING
ACCORDANCE WITH THE FOLLOWING: OR II AS PER AS 1720.2 OR IMPREGNATED PINE GRADE F7,PRESSURE
BEEN DESIGNED IN ACCORDANCE WITH THE RELEVANT STANDARDS AUSTRALIA EXCAVATION TO AVOID SOFTENING OR DRYING OUT BY EXPOSURE.
FABRIC SHALL BE LAPPED SUCH THAT THE TWO OUTERMOST WIRES OF ONE SHEET TREATED TO AS `604 AND RE-DRIED PRIOR TO USE.SUPPLEMENTARY
CODES AND LOCAL GOVERNMENT ORDINANCES FOR THE FOLOOWING 5.12 FOR FOOTINGS FOUNDED ON CONTROLLED FILL REFER TO NOTE 4.04.
OVERLAP THE TWO OUTERMOST WIRES OF THE OTHER SHEET BY 25 mm MINIMUM. TREATMENT SHALL BE APPLIED TO ALL OUT SURFACES,SUPPLY
LOADINGS,REFER TO ARCHITECTURAL DRAWINGS FOR PROPOSED FLOOR A MAXIMUM OF THREE SHEETS OF FABRIC SHALL BE LAPPED AT ANY POINT. SUPPORTING DOCUMENTATION FOR PRESERVATIVE TREATMENT.
USAGE. 6.0 CONCRETE
6.01 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 3600 CURRENT EDITION 10.05 TIMBER TRUSSES TO BE PRE-CAMBERED AN AMOUNT EQUAL TO
2.02 LIVE LOADS ARE IN ACCORDANCE WITH AS 1170.1 8.0 STRUCTURAL MASONARY DEAD LOAD DEFLECTION.THREE (3) COPIES OF SHOP DRAWINGS ARE TO
WITH AMENDMENTS,EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.
8.01 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 3700 BE SUBMITTED TO THE ENGINEER FOR APPROVAL CLEARLY SHOWING
6.02 PRE-MIXED CONCRETE SUPPLY SHALL COMPLY WITH AS 1379.
CURRENT ADDITION WITH AMENDMENTS AND OTHER RELEVANT CODES. THE DESIGN LOADS ON THE ROOF AND CEILING AND TRUSS NODE POINT
6.03 NO ADMIXTURES SHALL BE USED IN CONCRETE UNLESS APPROVED IN WRITING.
8.02 MORTAR ADMIXTURES SHALL NOT BE USED WITHOUT THE WRITTEN APPROVAL OF LOADS AND PRECAMBER.
6.04 CONCRETE MIX DESIGNS TO BE SUBMITTED FOR REVIEW PRIOR TO USE OF CONCRETE.
THE ENGINEER. 10.06 ALL BOLTS IN TIMBER CONSTRUCTION TO BE MINIMUM M12 U.N.O.
FLOOR SUPERIMPOSED LIVE LOADS 6.05 ENSURE CLEAR COVER TO REINFORCEMENT IS AS FOLLOWING UNLESS DETAILED OTHERWISE.
8.03 NON LOAD BEARING WALLS SHALL BE SEPERATED FROM CONCRETE ABOVE BY 25 BOLT HOLES TO BE DRILLED EXACT SIZE,WASHER UNDER HEADS AND
USAGE DEAD LOADS (kPa) COVER (mm) mm GAP.PROVIDE JOINT FILLER TO THE ARCHITECT'S DETAILS. NUTS TO BE AT LEAST 2.5 TIMES BOLT DIAMETER.
RESIDENTIA (kPa) 8.04 NO CHASES OR RECESSES ARE PERMITTED IN LOAD BEARING MASONARY WITHOUT
FORMED FORMED-NOT NOT FORMED- 10.07 TIMBER DIMENSIONS ON THE FINISHED WIDTH AND THICKNESS TO
L
-INTERNAL 0.50 1.50 ELEMENT THE APPROVAL OF THE ENGINEER.
EXPOSED TO EXPOSED TO CAST AGAINST BE:
-WET AREAS 1.00 1.50 WEATHER (B1) WEATHER (A1) GROUND 8.05 REINFORCED BRICKWORK SHALL COMPLY WITHT THE FOLLOWING U.N.O I) SEASONED SOFTWOOD:5,-0 mm
-BALCONIES 0.50 2.00 I) FILL ALL BED JOINTS AND PERPENDS WITH MORTAR EXCEPT AT WEEP II) UNSEASONEDSOFTWOOD : >F7:+3,-3mm OR F7:+2,-4mm
FOOTINGS & PILES - - 20 HOLES. III) SEASONED HARDWOOD : +2,-0mm
SLABS ON GROUND II) PROVIDE CLEAN-OUTS AT BASE OF REINFORCED CORES AND IV) UNSEASONED HARDWOOD : +3,-3 mm
2.03 WIND LOADS ARE IN ACCORDANCE WITH AS 1170.2-2002 AS FOLLOWS: 40 20 - CAVITIES.REMOVE MORTAR PROTRUSIONS BEFORE CORE OR CAVITY (SEE ALSO CLAUSE 1.6.2 IN AS 2082)
(TOP COVER)
REGIONAL WIND SPEED Vr = 46 m/s FILLING. 10.08 ALL TIMBER JOINTS AND NOTCHES ARE TO BE 100 mm MINIMUM
ANNUAL PROBABILITY OF EXCEEDANCE = 1:1000 III) COMPACT GROUT FILLING BY RODDING OR MECHANICAL VIBRATOR. AWAY FROM LOOSE KNOTS,SEVERE SLOPING GRAIN,GUM VEINS OR
REGION : A2 6.06 CONCRETE SIZES SHOWN DO NOT INCLUDE THICKNESSES OF APPLIED FINISHES.
IV) MAXIMUM HEIGHT OF POUR FOR CAVITY FILLED WALLS TO BE 1200 mm. OTHER MINOR DEFECTS.
TERRIAN CATEGORY: 3 6.07 DEPTHS OF BEAMS ARE GIVEN FIRST AND INCLUDE SLAB THICKNESS.
2.04 THE CONCRETE ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING 6.08 FOR CHAMFERS,DRIP GROOVES,RIGLETS ETC.REFER TO ARCHITECTURAL DETAILS,MAINTAIN COVER
8.06 WATERPROOF REAR FACE OF RETAINING WALLS AS SPECIFIED BY THE ARCHITECT.
EXPOURE CLASSIFICATIONS IN ACCORDANCE WITH AS 3600 TO REINFORCEMENT AT THESE DETAILS.
8.07 UNLESS NOTED OTHERWISE PROVIDE VERTICAL CONTROL JOINTS AT 12.0 m
6.09 NO HOLES,CHASES OR EMBEDMENT OF PIPES OTHER THAN THOSE SHOWN ON THE STRUCTURAL
MAXIMUM CENTRES AND 6.0 m FROM CORNERS IN ALL MASONARY WALLS U.N.O.
DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT THE PRIOR WRITTEN APPROVAL OF THE
ELEMENT CLASSIFICAIONS 8.08 BACKFILL TO RETAINING WALLS TO BE FREE DRAINING GRANNULAR MATERIAL
ENGINEER. SITE PREPERATIONS
EXTERIOR CONCRETE B1 U.N.O.PROVIDE SUBSOIL DRAIN OR WEEP HOLES.
6.10 CONSTRUCTION JOINTS WHERE NOT SHOWN SHALL BE LOCATED TO THE APPROVAL OF THE
INTERNAL CONCRETE A1 8.09 ALL CAVITY CONSTRUCTION TO HAVE GALVANISED WALL TIES INSTALLED AS PER CLEAR AREA UNDER SLAB OF ALL TOP SOIL CONTAINING HUMUS AND VEGETATABLE MATTER
ENGINEER.
CLAUSE 3.4 AND 4.10 AS 3700 100mm MIN.
6.11 THE FINISHED CONCRETE SHALL BE A DENSE HOMOGENEOUS MASS COMPLETELY FILLING THE
FORMWORK THOROUGHLY EMBEDDING THE REINFORCEMENT AND FREE OF STONE POCKETS,ALL PROVIDE FILL UNDER SLAB WHERE REQUIRED TO PRODUCE FINISHED LEVELS AS SHOWN ON
3.0 BULK EARTHWORKS 9.0 STRUCTURAL STEELWORK PLANS.
3.01 ALL EXCAVATION WORK TO BE CARRIED OUT TO THE SATISFACTION OF THE CONCRETE INCLUDING SLABS ON GROUND AND FOOTINGS SHALL BE COMPACTED WITH MECHANICAL
VIBRATORS. 9.01 ALL WORKMANSHIP AND MATERIAL SHALL BE IN ACCORDANCE WITH AS 4100 FILLING USED IN THE CONSTRUCTION OF A SLAB,EXCEPT WHERE THE SLAB IS SUSPENDED,
GEOTECHNICAL CONSULTANT INCLUDING INSPECTION OF STRIPPING APPROVAL EXCEPT WHERE VARIES BY THE CONTRACT DOCUMENTS. SHALL
OF FILL MATERIAL AND APPROVAL OF COMPACTION. 6.12 CURING OF ALL CONCRETE IS TO BE ACHIEVED BY KEEPING SURFACES CONTINUOUSLY WET FOR A
9.02 UNLESS NOTED OTHERWISE,ALL STEEL SHALL BE IN ACCORDANCE WITH AS 3678 CONSISTS OF CONTROLLED FILL ROLLED FILL AS FOLLOWS:
3.02 REFER TO THE GEOTECHNICAL REPORT FOR EXCAVATION PERIOD OF 3 DAYS AND PREVENTION OF LOSS OF MOISTURE FOR A TOTAL OF 7 DAYS FOLLOWED BY A
GRADE 250 OR AS 3679 GRADE 300,OR AS 1163 GRADE C350 AS APPROPRIATE. a) CONTROLLED FILL IS MATERIAL THAT HAS BEEN PLACED AND COMPACTED IN LAYERS BY
CONDITIONS,INCLUDING NATURAL WATER LEVELS AND GROUND CONDITIONS. GRADUAL DRYING OUT,APPROVED SPRAYED ON CURING COMPOUNDS THAT COMPLY WITH AS 3799 MAY
BE USED WHERE FLOOR FINISHES WILL NOT BE AFFECTED(REFER MANUFACTURER'S 9.03 TWO (2) COPIES OF WORKSHOP FABRICATION DRAWINGS SHALL BE SUBMITTED TO COMPACTION EQUIPMENT WITHIN A DEFEND MOISTURE RANGE TO A DEFINED DENSITY
3.03 REFER TO SURVEY DRAWINGS FOR EXISTING SERVICES AND LEVELS. THE ENGINEER FOR REVIEW AT LEAST 7 DAYS PRIOR TO COMMENCEMENT OF REQUIREMENT. EXCEPT AS PROVIDED BELOW, CONTROLLED FILL SHALL BE PLACED IN
3.04 ALL LEVELS SHOWN ARE TO AUSTRALIAN HEIGHT DATUM. SPECIFICATION),POLYTHENE SHEETING OR WET HESSIAN MAY BE USED TO RETAIN CONCRETE MOISTURE
FABRICATION.FABRICATION IS NOT TO COMMENCE WITHOUT ENGINEER'S APPROVAL OF ACCORDANCE WITH AS3798.
3.05 V.R.C INDICATES VERTICAL ROCK CUT,ROCK TO BE OUT NEAR VERTICAL WHERE PROTECTED WIND AND TRAFFIC.
WORKSHOP DRAWINGS.ALL DIMENSIONS AND SETOUTS TO BE OBTAINED FROM SAND FILL UP TO 0.8M DEEP, WELL COMPACTED IN NOT MORE THAN 0.3M THICK LAYERS BY A
FROM LOWER BENCH AT 90 TO 95 DEGREE WITH HORIZON UNLESS NOTED 6.13 CONSTRUCTION SUPPORT PROPPING IS TO BE LEFT IN PLACE WHERE NEEDED TO AVOID
OVERSTRESSING THE STRUCTURE DUE TO CONSTRUCTION LOADING.NO MASONARY OR PARTITION WALLS ARCHITECTURAL DRAWINGS WHERE NOT INDICATED ON STRUCTURAL DRAWINGS. VIBRATING PLATE OR VIBRATING ROLLER SHALL BE DEEMED TO COMPLY WITH THIS
OTHERWISE. 9.04 BOLT CATEGORY : COMMENTS REQUIREMENT. A SATISFACTORY TEST FOR SAND FILL NOT CONTAINING GRAVEL SIZED
3.06 OVERBURNDEN OCCURING ABOVE ROCK SHALL BE BATTERED BACK AT 2:1 ARE TO BE CONSTRUCTED ON SUSPENDED LEVELS UNTIL ALL PROPPING IS REMOVED AND THE SLAB HAS
4.6/S COMMERCIAL BOLTS OF GRADE 4.6 TO AS 1111SNUG TIGHTENED MATERIALIS THE ACHIEVEMENT OF A BLOW COUNT OF 7 OR MORE PER 0.3M USING THE
AS REQUIRED. ABSORBED ITS DEAD LOAD DEFLECTION.
8.8/S HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252 PENETROMETER TEST DESCRIBED IN AS AS1289.6.3.3. NON-SAND FILL UP TO 0.4M DEEP, WELL
3.07 SITE SURFACE CONTOURS SHOWN ARE INDICATIVE ONLY,FOR TRUE 6.14 THE ENGINEER SHALL BE GIVEN24 HOURS NOTICE FOR REINFORCEMENT INSPECTION AND CONCRETE
SHALL NOT BE DELIVERED UNTIL FINAL APPROVAL OBTAINED. SNUG TIGHTENED COMPACTED IN NOT MORE THAN 0.15M LAYERS BY A MECHANICAL ROLLER SHALL BE DEEMED
SURFACE LEVELS REFER SURVEY DRAWINGS. 9.05 UNLESS NOTED OTHERWISE ALL CLEAT PLATES SHALL BE MINIMUM 10 mm THICK. TO COMPLY WITH THIS REQUIREMENT, CLAY FILL SHALL BE MOIST DURING COMPACTION.
4.0 SLAB ON GROUND 6.15 CONDUITS PIPES ETC SHALL ONLY BE LOCATED IN THE MIDDLE THIRD OF THE SLAB DEPTH,PIPES OR
9.06 UNLESS NOTED OTHERWISE ALL BOLTS SHALL BE M20 CATEGORY 8.8/S,NO b) ROLLED FILL CONSISTS OF MATERIAL COMPACTED IN LAYERS BY REPEATED ROLLING WITH
4.01 REMOVE ALL TOP SOIL INCLUDING ROOTS AND ANY OTHER ORGANIC CONDUITS SHALL NOT BE PLACED WITHIN THE COVER TO REINFORCEMENT.
CONNECTION SHALL HAVE LESS THAN 2 BOLTS. ALL BOLTS,NUTS AND WASHERS SHALL AN EXCAVATIOR. ROLLED FILL SHALL NOT EXCEED 0.6M COMPACTED IN LAYER NOT MORE
MATTER,STORE TOP SOIL AS REQUIRED. 6.16 SLABS AND BEAMS SHALL BE CONSTRUCTED TO BEAR ONLY ON THE BEAMS,WALLS COLUMNS ETC
SHOWN ON THE DRAWINGS.ALL OTHER BUILDING ELEMENTS SHALL BE KEPT 20 mm MINIMUM CLEAR FROM BE HOT DIPPED GALVANISED,UNLESS NOTED OTHERWISE.ALL HOLDING DOWN BOLTS THAN 0.3M THICK FOR SAND MATERIAL OR 0.3M COMPACTED IN LAYERS NOT MORE THAN 0.15M
4.02 WHERE SHOWN ON THE DRAWINGS,BASE AND SAND BUNDING ARE TO BE SHALL BE M20 CATEGORY 4.6/S. ALL BOLTS,NUTS AND WASHERS SHALL BE HOT DIPPED THICK FOR OTHER MATERIAL.
PLACED AND COMPACTED AS SPECIFIED. SOFFITS OF STRUCTURE.
GALVANISED. A 50mm MIN. BASE COURSE OF PACKING SAND SHALL BE SPREAD OVER THE SUB-BASE AND TO
4.03 EXCAVATE TO THE REQUIRED FORMATON LEVEL AND PROOF ROLL 6.17 CONCRETE QUALITY SHOWN IN CONCRETE MIX DESIGN TABLE.
9.07 FABRICATION SHALL COMPLY WITH AS 4100,SECTION 14. BE THOROGHLY ROLLED AND COMPACTED TO A SMOOTH LEVEL SURFACE. THE SAND SHALL BE
FORMATION WITH 6 PASSES OF A 10 TONNE SMOOTH WHEELED ROLLER,SOFT CONCRETE MIX TABLE 9.08 ERECTION SHALL COMPLY WITH AS 4100 SECTION 15. MOISTENED PRIOR TO THE PLACEMENT OF A 0.2mm POLYTHENE MEMBRANE IN 360mm MIN.
AREAS ARE TO BE REMOVED AND REPLACED WITH SUITABLE FILL COMPACTED 9.09 UNLESS NOTED OTHERWISE,ALL FILLET WELDS SHALL BE 6 mm CONTINUOUS WIDE SHEETS LAPPED 150mm AND JOINED WITH 75mm WIDE PRESSURE SENSITIVE TAPE. THE
EXPOSURE STRENGTH (MPa)
TO THE DENSITY NOMINATED BELOW. CATEGORY GP USING E41XX ELECTRODES.ALL BUT WELDS SHALL BE COMPLETE TAPE SHALL BE LAID UNDER ALL SLABS AND WALLS IN CONTACT WITH THE GROUND.
CLASSIFICATION U.N.O
4.04 CONTROLLED FILL MATERIAL SHALL MEET THE REQUIREMENTS OF THE PENETRATION BUTT WELDS CATEGORY SP TO AS 1554.1. UNLESS NOTED OTHERWISE THE TOTAL FILL BENEATH THE SLAB PANELS MUST NOT EXCEED 300MM.i.e. THE SUM OF
GEOTECHNICAL REPORT,PLACE IN MAXIMUM 150mm.THICK LAYERS TO 98% ELEMENT (AS 3600) Pc AT 28 COVER
DAYS ALL PURLIN CLEAT WELDS SHALL BE 6 mm CONTINUOUS CATEGORY GP USING E41XX EXISTING FILL PLUS ANY NEW FILLING PLACED TOGETHER MUST NOT EXCEED 300mm MAX.
STANDARD COMPACTION IN ACCORDANCE WITH AS 1289E1.1 MAXIMUM DEPTH ELECTRODES.
OF FILL IS TO BE 400 mm FOR COHESIVE FILL AND 800 mm FOR GRANULAR FILL. FOOTINGS A1 25 50
9.10 PROVIDE SEAL PLATES TO THE ENDS OF ALL HOLLOW SECTIONS,WITH 'BREATHER'
4.05 CLAY SUBGRADE FORMATION IS TO BE MAINTAINED AT OPTIMUM MOSTURE WALLS/COLUMNS INTERNAL A1 32 40 OVER THE PROPOSED BUILDING AREA, BUILDER TO REMOVE ALL TREES AND TREE
HOLES IF MEMBERS TO BE HOT DIP GALVANISED.
CONTENT -O,+3% PRIOR TO COVERING. WALLS/COLUMNS EXTERNAL ROOTS/MATERAIL. ANY SOFT OR LOOSE MATERIAL THAT DOES NOT RESPOND TO
B1 32 40 9.11 STRUCTURAL STEELWORK NOT ENCASED IN CONCRETE SHALL HAVE THE
COMPACTION SHOULD BE EXCAVATED TO ACHIEVE A FIRM WORKING BASE. FILL HOLES WITH
SLABS ON GROUND A1 FOLLOWING SURFACE TREATMENT IN ACCORDANCE WITH THE SPECIFICATION.
25 40 NON POROUS FILL COMPACTED IN 150mm MAX. LAYERS.
INTERNAL SUSPENDED SLABS A1 32 40
EXTERNAL SUSPENDED SLABS B1 32 40
PILES A1 25 75

Sheet Title :
RASMAN Pty.Ltd. No. Description Date CLIENT:
Owner
Project Status : VERIFICATION:
DO NOT SCALE THE DRAWINGS,READ ALL DIMENSIONS
SHOWN ALL DIMENSIONS,NOTES ON PLAN & CONSENT
ABDULALLH ALLK Civil/Structure P. Eng. 1 FOR CDC APPLICATION 24-05-2022 STRUCTURAL GENERAL FOR CDC DOCUMENTS MUST BE CHECKED & VERIFIED BY THE
M.I.E (Aust.) 3281602 NOTES APPLICATION CONTRACTOR PRIOR TO ANY COMMENCEMENT OF
13 Greendale Cr. Chester hill NSW 2162 PROJECT: PROJECT: RASP034-21/22
BUILDING WORKS ON SITE TO CLARIFY ANY
DISCRIPANCIES BETWEEN ALL PLAN DRAWINGS &
Mobile 0406 674 982 SHEET NO : DOCUMENTATION RELEVANT TO THE PROPOSAL,SITE
PROPOSED ATTACHED DWELLINGS DATE: 08/25/20 WORKS,GROUND LEVELS MAY VARY DUE TO SITE
CONDITIONS.
COPY RIGHT: THIS DRAWING IS THE PROPERTY OF
RASMAN Pty Ltd CREATED BY GRID DRAFTING
PROJECT ADDRESS: DRAWN BY: PG MIEAust 4406526 S01
a.allk@yahoo.com, SERVICES AND MAY NOT BE RETAINED,COPIED IN LOT 22 & 23 SEC 49, DP753 DESIGNED BY: PG MIEAust 4406526
WHOLE OR IN PART OR USED OTHER THAN FOR THE SCALE : REVISION :
ACN 22126810273 SPECIFIC USE,LICENSED AND ISSUED WITHOUT THE 38 EVANS STREET, CHECKED BY: ALLK. MIEAust 3281602
WRITTEN CONSENT OF BOTH PARTIES.
FAIRFIELD HEIGHTS,NSW,2165
APPROVED BY: Approver
As indicated Yes
150 DIA SEWER PIPE
ZONE OF
INFLUENCE CONCRETE
ENCASEMENT

900 P1 P1 P1 P1 P1
900
P1 P1 P1

P1 P1
P1 P1 P1 P1
1
200 150 1 P1
S03 STEPS
P1 P1
200 S03
100

P1
P1 P1 P1 P1 STEPS P1 P1 P1
P1
150
100 STEPS

P1
P1

100 P1
P1 P1 100
P1

ZOI

ZOI
P1 P1 P1 P1 P1
P1
P1 P1 P1 P1 P1
STEPS

P1 P1
P1 P1
P1
P1 P1

DN 100
100
P1 P1 P1
100 P1 P1 P1 P1 P1
P1 P1
P1 P1 STEPS

P1 P1 P1 P1 P1
P1 P1

P1 P1
P1 P1 P1 P1 P1 P1

2117
ZOI 2101
LEGEND APPLIES TO ALL STRUCTURAL
ZOI DRAWINGS UNLESS NOTED OTHERWISE

FOUNDATION PLAN 100 PROPOSED SLAB THICKNESS

1 1 : 100 CONCRETE MIX TABLE


STRENGTH (MPa)
LOAD BEARING WALL UNDER
BLOCKWRORK OVER
EXPOSURE
CLASSIFICATION U.N.O BRICKWORK OVER
ELEMENT (AS 3600) Pc AT 28 COVER
DAYS FLOOR JOIST (FIRST FLOOR
FOOTINGS A1 25 50
FJ
JOIST FJ1)
WALLS/COLUMNS INTERNAL A1 32 40
WALLS/COLUMNS EXTERNAL B1 32 40
SLABS ON GROUND A1 25 40 CORNER BARS FOR SHEAR
INTERNAL SUSPENDED SLABS A1 32 40
EXTERNAL SUSPENDED SLABS B1 32 40
PILES A1 25 75 DENOTES APPROX. LOCATION OF ARTICULATION
JOINT EXACT POSITION SHOULD BE READ OFF
ARCHITECTURAL DRAWINGS AND/OR
DETERMINED BY BUILDER ON SITE. ALL
ARTICULATION JOINTS ARE TO BE PROVIDED AS
PER THE BCA LATEST EDITION.

Sheet Title :
RASMAN Pty.Ltd. No. Description Date CLIENT:
Owner
Project Status : VERIFICATION:
DO NOT SCALE THE DRAWINGS,READ ALL DIMENSIONS
SHOWN ALL DIMENSIONS,NOTES ON PLAN & CONSENT
ABDULALLH ALLK Civil/Structure P. Eng. 1 FOR CDC APPLICATION 24-05-2022 FOUNDATION PLANS FOR CDC DOCUMENTS MUST BE CHECKED & VERIFIED BY THE
M.I.E (Aust.) 3281602 APPLICATION CONTRACTOR PRIOR TO ANY COMMENCEMENT OF
13 Greendale Cr. Chester hill NSW 2162 PROJECT: PROJECT: RASP034-21/22
BUILDING WORKS ON SITE TO CLARIFY ANY
DISCRIPANCIES BETWEEN ALL PLAN DRAWINGS &
Mobile 0406 674 982 SHEET NO : DOCUMENTATION RELEVANT TO THE PROPOSAL,SITE
PROPOSED ATTACHED DWELLINGS DATE: 24-05-2022 WORKS,GROUND LEVELS MAY VARY DUE TO SITE
CONDITIONS.
COPY RIGHT: THIS DRAWING IS THE PROPERTY OF
RASMAN Pty Ltd CREATED BY GRID DRAFTING
PROJECT ADDRESS: DRAWN BY: PG MIEAust 4406526 S02
a.allk@yahoo.com, SERVICES AND MAY NOT BE RETAINED,COPIED IN LOT 22 & 23 SEC 49, DP753 DESIGNED BY: PG MIEAust 4406526
WHOLE OR IN PART OR USED OTHER THAN FOR THE SCALE : REVISION :
ACN 22126810273 SPECIFIC USE,LICENSED AND ISSUED WITHOUT THE 38 EVANS STREET, CHECKED BY: ALLK. MIEAust 3281602
WRITTEN CONSENT OF BOTH PARTIES.
FAIRFIELD HEIGHTS,NSW,2165
APPROVED BY: PRIVATE CERTIFIER
As indicated Yes
FOOTING 450dx450w 3N12
TOP & BTM WITH R10@300

100
TIES SL82 FABRIC
2

100
S03 SL82 MESH

310

450
E
U OF
100

C
EN
FL E
I N ON
NGL

450

450
NGL

Z
NGL
ZO F L U
IN

50
NE EN

450
OF CE

4N16 TOP &


50mm Compressible
2 2101 Membrane
3N12 BOT
2117 R10-300 TIES
S03 ZOI
ZOI

1150
SECTION X-X

200
2 1 : 25
200 450
MIN. MIN.
150
MIN.
450 DIA MASS
CONCRETE 450 DIA MASS
00°

45.
MIN.
PIERS CONCRETE

150
45.

00°
PIERS
MIN.

MIN.
150

150
900 900
SECTION 1-1 150mm DIA
1 1 : 30
CONCRETE
ENCASEMENT
SEWER PIPE

FOOTING DETAILS NEAR SYDNEY


WATER PIPE

100
P1 PIERS 450

450 P1 PIERS

450mm

D1=225mm

P1 PIERS 450

Sheet Title :
RASMAN Pty.Ltd. No. Description Date CLIENT:
Owner
Project Status : VERIFICATION:
DO NOT SCALE THE DRAWINGS,READ ALL DIMENSIONS
SHOWN ALL DIMENSIONS,NOTES ON PLAN & CONSENT
ABDULALLH ALLK Civil/Structure P. Eng. 1 FOR CDC APPLICATION 24-05-2022 FOUNDATION DETAILS FOR CDC DOCUMENTS MUST BE CHECKED & VERIFIED BY THE
M.I.E (Aust.) 3281602 APPLICATION CONTRACTOR PRIOR TO ANY COMMENCEMENT OF
13 Greendale Cr. Chester hill NSW 2162 PROJECT: PROJECT: RASP034-21/22
BUILDING WORKS ON SITE TO CLARIFY ANY
DISCRIPANCIES BETWEEN ALL PLAN DRAWINGS &
Mobile 0406 674 982 SHEET NO : DOCUMENTATION RELEVANT TO THE PROPOSAL,SITE
PROPOSED ATTACHED DWELLINGS DATE: 24-05-2022 WORKS,GROUND LEVELS MAY VARY DUE TO SITE
CONDITIONS.
COPY RIGHT: THIS DRAWING IS THE PROPERTY OF
RASMAN Pty Ltd CREATED BY GRID DRAFTING
PROJECT ADDRESS: DRAWN BY: PG MIEAust 4406526 S03
a.allk@yahoo.com, SERVICES AND MAY NOT BE RETAINED,COPIED IN LOT 22 & 23 SEC 49, DP753 DESIGNED BY: PG MIEAust 4406526
WHOLE OR IN PART OR USED OTHER THAN FOR THE SCALE : REVISION :
ACN 22126810273 SPECIFIC USE,LICENSED AND ISSUED WITHOUT THE 38 EVANS STREET, CHECKED BY: ALLK. MIEAust 3281602
WRITTEN CONSENT OF BOTH PARTIES.
FAIRFIELD HEIGHTS,NSW,2165
APPROVED BY: PRIVATE CERTIFIER
As indicated Yes
C1 P2

300 PFC +10mm


PLATE (B2)
300PFC +10mm
PLATE (B2)
FJ
TRUSS BY
OTHERS

UP 250 PFC+10mm 250 PFC +10mm


PLATE (B1) PLATE (B1)

250 PFC+10mm
TRUSS BY 300 PFC +10mm PLATE (B1) 250 PFC+10mm
PLATE (B2) PLATE (B1)
OTHERS

First FLoor
Partition Walls
FJ

300 PFC +10mm


PLATE (B2)

C1 Ground Floor Partion P2


Walls
FIRST FLOOR BEAM PLAN
1 1 : 100

FIRST FLOOR FRAMING MEMBER SCHEDULE


LINTEL SCHEDULE (L1) MARK MEMBER SIZE REMARKS
LEGEND APPLIES TO ALL STRUCTURAL
DRAWINGS UNLESS NOTED OTHERWISE
SPAN (mm) SECTION B1 250 PFC+10mm PLATE 100 PROPOSED SLAB THICKNESS
B2 300 PFC +10mm PLATE LOAD BEARING WALL UNDER
BLOCKWRORK OVER
900 140X45 F7 KD PINE 1L1 2/240X42 LVL 15 OR 150 PFC NAIL LAMINATED
BRICKWORK OVER
1L2 150 X42 LVL 15
FLOOR JOIST (FIRST FLOOR
1200 190X35 F7 KD PINE 2L1 2/240X42 LVL 15 OR 150 PFC NAIL LAMINATED
FJ
JOIST FJ1)

1800 190X45 F17 KD HW 2L2 150 X42 LVL 15


CORNER BARS FOR SHEAR
2L3 180 PFC +200 X 10PL CRANKED BEAM
2400 2-240X35 F17 KD HW FJ 240x45 HYSPAN LVL @450mm CRS MAX. AS PER DENOTES APPROX. LOCATION OF ARTICULATION
MANUFACTURER'S SPECIFICATION
OR 2-240X35 HYSPAN JOINT EXACT POSITION SHOULD BE READ OFF
ARCHITECTURAL DRAWINGS AND/OR
C1 90x90x6 SHS DETERMINED BY BUILDER ON SITE. ALL
3000 2-240X45 F17 KD HW ARTICULATION JOINTS ARE TO BE PROVIDED AS
P2 90X90 F7 TREATED PINE POST
OR 2-240X45 HYSPAN PER THE BCA LATEST EDITION.

Sheet Title :
RASMAN Pty.Ltd. No. Description Date CLIENT:
Owner
Project Status : VERIFICATION:
DO NOT SCALE THE DRAWINGS,READ ALL DIMENSIONS
SHOWN ALL DIMENSIONS,NOTES ON PLAN & CONSENT
ABDULALLH ALLK Civil/Structure P. Eng. 1 FOR CDC APPLICATION 24-05-2022 FIRST FLOOR JOISTS PLAN FOR CDC DOCUMENTS MUST BE CHECKED & VERIFIED BY THE
M.I.E (Aust.) 3281602 APPLICATION CONTRACTOR PRIOR TO ANY COMMENCEMENT OF
13 Greendale Cr. Chester hill NSW 2162 PROJECT: PROJECT: RASP034-21/22
BUILDING WORKS ON SITE TO CLARIFY ANY
DISCRIPANCIES BETWEEN ALL PLAN DRAWINGS &
Mobile 0406 674 982 SHEET NO : DOCUMENTATION RELEVANT TO THE PROPOSAL,SITE
PROPOSED ATTACHED DWELLINGS DATE: 24-05-2022 WORKS,GROUND LEVELS MAY VARY DUE TO SITE
CONDITIONS.
COPY RIGHT: THIS DRAWING IS THE PROPERTY OF
RASMAN Pty Ltd CREATED BY GRID DRAFTING
PROJECT ADDRESS: DRAWN BY: PG MIEAust 4406526 S04
a.allk@yahoo.com, SERVICES AND MAY NOT BE RETAINED,COPIED IN LOT 22 & 23 SEC 49, DP753 DESIGNED BY: PG MIEAust 4406526
WHOLE OR IN PART OR USED OTHER THAN FOR THE SCALE : REVISION :
ACN 22126810273 SPECIFIC USE,LICENSED AND ISSUED WITHOUT THE 38 EVANS STREET, CHECKED BY: ALLK. MIEAust 3281602
WRITTEN CONSENT OF BOTH PARTIES.
FAIRFIELD HEIGHTS,NSW,2165
APPROVED BY: PRIVATE CERTIFIER
As indicated Yes
BRACING SCHEDULE-DESIGNED IN ACCORDANCE WITH AS1684.2-2010
N2
NOTES:
All windows and door to have perforated soffit sheets above. (excluding front
door & garage doors).
temporary Bracing to be installed in accordance with AS 1684
Bracing panels positioned under-eave to be fixed as per AS1684.2 fig 8.3.6.8
**-denotes walls to be packed out (for remaining length of wall) to suit depth of
bracing panel.
PLYWOOD:
One face sheeted with structural plywood (6mm F11, 4mm F14 or 4mm F27)
closer nailing pattern with top and bottom plates and horizontal joints at 50mm
centres. Refer As1684.2 Table 8.18 (h) method B.
METAL ANGLE:
Approved metal angle brace cut into studs and fixed with approved nails
(Strapped as required). refer AS1684.2 Table 8.18 (c).
300mm to 449mm Bracing Panels:
Ply bracing panels to be as per AS1684.2, table 8.18 "H", Method "A" (c/w M12
rod to each end) & PAA Limit State Design Manual-structural plywood wall
bracing, tables 8& 9. (Value 1.28KN/m -this has a reduction factor of 0.20
aplied).

450mm to 599mm Bracing Panels:


PLY bracing panels to be as per AS1684.2,table 8.18 "H" Method "A" (c/w M12
rod to each end) & PAA Limit State Design Manual-structural wall bracing, tables
8&9. (value 1.6KN/m-this has a reduction factor of 0.25 applied).

600m to 899mm Bracing Panels:


PLY bracing panels to be as per AS1684.2,table 8.18 "H" Method "A" (c/w M12
rod to each end) & PAA Limit State Design Manual-structural wall bracing, tables
8&9. (value 6.0KN/m-the reduction factor is not applicable).

Sheet Title :
RASMAN Pty.Ltd. No. Description Date CLIENT:
Owner
Project Status : VERIFICATION:
DO NOT SCALE THE DRAWINGS,READ ALL DIMENSIONS
SHOWN ALL DIMENSIONS,NOTES ON PLAN & CONSENT
ABDULALLH ALLK Civil/Structure P. Eng. 1 FOR CDC APPLICATION 24-05-2022 BRACING DETAILS FOR CDC DOCUMENTS MUST BE CHECKED & VERIFIED BY THE
M.I.E (Aust.) 3281602 APPLICATION CONTRACTOR PRIOR TO ANY COMMENCEMENT OF
13 Greendale Cr. Chester hill NSW 2162 PROJECT: PROJECT: RASP034-21/22
BUILDING WORKS ON SITE TO CLARIFY ANY
DISCRIPANCIES BETWEEN ALL PLAN DRAWINGS &
Mobile 0406 674 982 SHEET NO : DOCUMENTATION RELEVANT TO THE PROPOSAL,SITE
PROPOSED ATTACHED DWELLINGS DATE: 24-05-2022 WORKS,GROUND LEVELS MAY VARY DUE TO SITE
CONDITIONS.
COPY RIGHT: THIS DRAWING IS THE PROPERTY OF
RASMAN Pty Ltd CREATED BY GRID DRAFTING
PROJECT ADDRESS: DRAWN BY: PG MIEAust 4406526 S05
a.allk@yahoo.com, SERVICES AND MAY NOT BE RETAINED,COPIED IN LOT 22 & 23 SEC 49, DP753 DESIGNED BY: PG MIEAust 4406526
WHOLE OR IN PART OR USED OTHER THAN FOR THE SCALE : REVISION :
ACN 22126810273 SPECIFIC USE,LICENSED AND ISSUED WITHOUT THE 38 EVANS STREET, CHECKED BY: ALLK. MIEAust 3281602
WRITTEN CONSENT OF BOTH PARTIES.
FAIRFIELD HEIGHTS,NSW,2165
APPROVED BY: PRIVATE CERTIFIER
As indicated Yes
Sheet Title :
RASMAN Pty.Ltd. No. Description Date CLIENT:
Owner
Project Status : VERIFICATION:
DO NOT SCALE THE DRAWINGS,READ ALL DIMENSIONS
SHOWN ALL DIMENSIONS,NOTES ON PLAN & CONSENT
ABDULALLH ALLK Civil/Structure P. Eng. 1 FOR CDC APPLICATION 24-05-2022 TYPICAL DETAILS FOR CDC DOCUMENTS MUST BE CHECKED & VERIFIED BY THE
M.I.E (Aust.) 3281602 APPLICATION CONTRACTOR PRIOR TO ANY COMMENCEMENT OF
13 Greendale Cr. Chester hill NSW 2162 PROJECT: PROJECT: RASP034-21/22
BUILDING WORKS ON SITE TO CLARIFY ANY
DISCRIPANCIES BETWEEN ALL PLAN DRAWINGS &
Mobile 0406 674 982 SHEET NO : DOCUMENTATION RELEVANT TO THE PROPOSAL,SITE
PROPOSED ATTACHED DWELLINGS DATE: 24-05-2022 WORKS,GROUND LEVELS MAY VARY DUE TO SITE
CONDITIONS.
COPY RIGHT: THIS DRAWING IS THE PROPERTY OF
RASMAN Pty Ltd CREATED BY GRID DRAFTING
PROJECT ADDRESS: DRAWN BY: PG MIEAust 4406526 S06
a.allk@yahoo.com, SERVICES AND MAY NOT BE RETAINED,COPIED IN LOT 22 & 23 SEC 49, DP753 DESIGNED BY: PG MIEAust 4406526
WHOLE OR IN PART OR USED OTHER THAN FOR THE SCALE : REVISION :
ACN 22126810273 SPECIFIC USE,LICENSED AND ISSUED WITHOUT THE 38 EVANS STREET, CHECKED BY: ALLK. MIEAust 3281602
WRITTEN CONSENT OF BOTH PARTIES.
FAIRFIELD HEIGHTS,NSW,2165
APPROVED BY: PRIVATE CERTIFIER
As indicated Yes