You are on page 1of 7

Daily Coating Inspection Report

Date: 28/11/2021
Day 25

Project : Maintenance of crude oil storage tank T1


Location : ABU-ATTIFEEL A 100- Field
Contractor : TIC Libyan branch
Specification: 20000. VAR.PAI.FUN Rev. 3 - March 2010/ 20552. VAR.PAI.FUN.
Rev. 0 – January 2005
Standards: ISO 8502-4/ ASTM D4285/ISO8501-1/ISO 8502-6/ISO8502-9/NACE RP0287

Activities:

1- Measure the weather condition.

2- Evaluation of surface cleanliness after sandblasting.

3- Performing roughness test

4 Performing soluble salt test (Bresle Batch Salt test - ISO 8502-6)

5- Checking equipment for abrasive blasting.

Findings:

1/- WEATHER CONDITION:

The measure of weather condition before sandblasting found acceptable; where the difference
between the steel surface and dew point temperature was greater than 3˚C and the RH is less than
85%. (See photos 1,2,3)

- Below table summarize reading results:

Date Time Ambient Steel Dew ∆T °C


Temp °C Temp °C Point °C % RH (Ts – Td) Comments
(Ta) (Ts) (Td)
8h00 21,6 °C 22,6 °C 0°C 23,6 % 22,6 °C Weather conditions are
28-11-2021 appropriate and acceptable
15h00 26 °C 27,5°C 8,9 °C 34 % 18,6 °C

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 1/7


Daily Coating Inspection Report
2/- Surface cleanliness

Random blasted areas do not comply with MOG specification. The final grade required according to
MOG specification shall be Sa 2½.

-During our inspection, we found: (See photos 4,5,6,7)

 Random areas with black stains are observed in blasted surface.

3/- Roughness test

-The surface roughness was measured on the blasted areas using Elcometer 122 Testex Replica
Tape & Elcometer 124 Thickness Gauge, which is providing a permanent peak to valley surface
profile in µm according to ISO 8503-5.
-(04) spots of roughness test was taken after sandblasting.

-Results were found acceptable and within the recommended surface profile 50-85 μm, grade
Medium G; stated in TDS. Some of the achieved profile results are listed in below table:

ROUGHNESS TEST RESULT


Acceptance criteria:
Reading, surface Level of surface
Spot N° Average, μm Result
profile, μm profile
(according to TDS*)
1 76
80,5 50-85 μm conform
2 85

*TDS: Technical data sheet.

-Some steel & weld imperfections (spatter, surface irregularity, undercut...) was found after
sandblasting. These imperfections cannot be detected before sandblasting; it is hidden by the
paint.

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 2/7


Daily Coating Inspection Report
-Damage on paint is observed in random areas of shell are due to sandblasting operation.
4/- Soluble salt test: (See photos 8,9,10)

 Soluble salts have been measured on (02) spots using the POSITECTOR SST (Soluble Salt
Tester).
 The test is done according to according to Bresle method (ISO 8502-6 & 9).
 Results are summarized in below table:

BRESLE BATCH SALT TEST RESULT


Acceptance
criteria: Level of
Spot N° Reading, Salt content, mg/m2 Result
total water-soluble
salts
1 23
30 mg/m² conform
2 20

5/- Checking air compressor

-The measured temperature of portable compressor found acceptable as per MOG specification.

-The pressure gauge of portable air compressor found damaged.

Activity Progress:

Bottom Roof
Step
Pre-cleaning 100% 100%
Sandblasting/Mechanical surface 54,75 % 0%
preparation
Paint application :First coat 20,63 % 0%
Paint application :Top coat 11,10 % 0%
Final Inspection 0% 0%

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 3/7


Daily Coating Inspection Report

Sandblasting Progress (Details):

Date Blasted surface (m2) Date Blasted surface Date Blasted surface (m2)
(m2)
Until 04/11/2021 865,78 20/11/2021 25 *** ***
05/11/2021 25 21/11/2021 40 *** ***
06/11/2021 25 22/11/2021 40 *** ***
07/11/2021 45 23/11/2021 35 *** ***
08/11/2021 55 24/11/2021 38 *** ***
09/11/2021 30 25/11/2021 8 *** ***
10/11/2021 40 26/11/2021 0 *** ***
11/11/2021 30 27/11/2021 45 *** ***
12/11/2021 0 28/11/2021 81 *** ***
13/11/2021 47 *** *** *** ***
14/11/2021 62 *** *** *** ***
15/11/2021 44 *** *** *** ***
16/11/2021 0 *** *** *** ***
17/11/2021 40 *** *** *** ***
18/11/2021 0 *** *** *** ***
19/11/2021 30 *** *** *** ***

Total surface bottom (m2) 3014,58


2
Total Blasted surface (m ) 1650,78
Progress bottom : 54,75 %
Remaing bottom surface (m2) 1363,8

Primer coat Progress:

Primer coat applied –Total surface (m2) 622,04


Progress bottom : 20,63 %
Remaing bottom surface (m2) 2392,54

Top coat Progress:

Top coat applied –Total surface (m2) 334,69


Progress bottom : 11,10 %
Remaing bottom surface (m2) 2679,89

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 4/7


Daily Coating Inspection Report

Recommendations:

1- All steel and welding imperfections should be smoothly prepared without any damage to the plate
as per MOG specification & ISO ISO 8501-3. (Further examination shall be according API inspector.

2- All fittings and accessories shall be protected as per MOG specification.

3/- More ventilation should be installed to remove dust during and after grit blasting.

4/- The no conform areas after sandblasting shall be repaired to achieve the final required grade as
per MOG specification.

5/- Contact area (between pipe support and bottom plates) shall be prepared and painted as per
MOG specification.

6/-The pipe support's extremity shall carefully prepared. (Perimeter of support on deck plates)

7/- All damage on paint in shell plates shall be repaired as per MOG specification.
8/- All used abrasive material should be removed from the tank.
9/- It is recommend to use vacuum cleaner during collect of dust.

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 5/7


Daily Coating Inspection Report

Reference Photos:

28/11/2021 28/11/2021
8:00 AM 8:00 AM

Photo No 1 Photo No 2

28/11/2021
General view of
8:00 AM blasted surface

Photo No 3 Photo No 4

Photo No 5 Photo No 6

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 6/7


Daily Coating Inspection Report

Photo No 7 Photo No 8

Photo No 9 Photo No 10

Prepared by : TIC Libyan Branch Reviewed by :


Anis BEN RABEH Ismail ASSOUAD
Coating inspector Hassan ALBAWANDI
Ahmed BENHALEEM
Ali ELMARRIMI
MOG Plant Inspection dept

DAILY REPORT INSPECTION OF CRUDE OIL STORAGE TANK T1 PAGE 7/7

You might also like