POWER AND ACCESSORIES

SWIMMING POOL ADDITION A SINGLE / DOUBLE 13 AMP SWITCHED SOCKET OUTLET -


ADDED AS LATER PHASE MOUNTING HEIGHT AT 450mm TO UNDERSIDE OF SOCKET
EXCEPT WHERE MARKED * WHICH ARE TO BE MOUNTED ABOVE
WORKTOP LEVEL (EXACT HEIGHT TO BE AGREED).
NOTE REQUIREMENTS FOR COMPLIANCE WITH PART M OF THE
BUILDING REGULATIONS.

EG EXTERIOR GRADE WATERPROOF POWER POINT.

PHASE 1 - MAIN FUSED SPUR

SECURITY ALARM PIR ALARM SENSOR

ENTRANCE ADDITION K
SECURITY ALARM SYSTEM KEYPAD

SECURITY ALARM SYSTEM CENTRAL PANEL


A

E.RWP
MOVEMENT
STARTER TIES
BT MASTER SOCKET
RWP

EJ MK OR EQUAL INSULATED CONSUMER UNIT - MODEL TO SUIT


E N1
FINAL WIRING ARRANGEMENT.
IP CSU
INSTALL CSU AT HEIGHT SO SWITCHES ARE BETWEEN 1350mm
E AND 1450mm ABOVE FFL
7 LS 7 DS 7 E 7 7 DS LS 7 E 7 1 LS 1 DS E 1
1

PLANT ROOM MALE CHANGING SVP DURGO


STAT PC
DIS WC/SHOWER EMERGENCY ALARM PULL CORD TO B. REGS
PART M2 5.4h
SVP DURGO
DS
HAIR DW
RECEPTION

STAT
A DIS WC/SHOWER EMERGENCY ALARM BEACON/SOUNDER TO B.

AMBULANT
DRYER

CUBICLE
CCTV DVR
gully LS 7 7 REGS PART M2 5.4h
74.72 EXISTING BT
MSH3 MSH2 MSH1 gully
74.76
MASTER TO BE
7 7 7 RELOCATED TO DIS WC/SHOWER EMERGENCY ALARM RESET BUTTON TO B.REGS
E 7 WASH E 7
HERE
E
ENTRANCE R PART M2 5.4h
LOCATION OF
ELECS MALE WC

OUTLET
MWO 6 LS 6 E 6 DH 6 LS 1
B POSSIBLE NEW B
ASHP(s) IF 7 7
DW TEA OFFICE
REQUIRED GULLY MWO INTERNAL LIGHTING
CHANNEL
FR
STATION
x2

2xLOCKERS

2xLOCKERS

2xLOCKERS

2xLOCKERS
7 * NOTE ELECTRICAL CONTRACTOR TO UNDERTAKE FULL
FR ILC ELC LIGHTING LUX DESIGN WITH LIGHT MANUFACTURER TO
E 1 DETERMINE WATTAGE REQUIREMENTS OF ALL FITTINGS, WITH
LIGHT POSITIONS TO BE ADJUSTED ACCORDINGLY AS REQUIRED

MH
MAIN BY DESIGN TO APPROVAL OF MJB ARCHITECTURE.
CL 74.61
POOL ACCESS DUCTWORK/SERVICES ROUTE EJ
COMMUNITY

DRINKS
FROM EXISTING PLANT ROOM TO K EJ
CENTRALISED INTERNAL LIGHTING CONTROL SYSTEM TO
POOLSIDE NEW CEILING VOID IN MAIN
FE
HALL ADDED AS ILC
CONTROL ALL NEW INTERNAL LIGHTING WITH TIMER, AND
OVER-RIDE ON/OFF CAPABILITIES PAIRED WITH INDIVIDUAL PIR
ENTRANCE ADDITION (VIA

IC IC
ENCASEMENT BELOW EXISTING EJ RWP LATER PHASE LIGHT SENSORS FOR EACH CIRCUIT - SYSTEM TO ALLOW FOR
FULL ADAPTATION BETWEEN USE OF EITHER TIMER OR PIR
IC IC FLAT ROOF JOISTS)
EJ SENSOR CONTROL TO EACH LIGHTING CIRCUIT.
1 1 1
IC
TV LS
PIR LIGHT SENSOR TO SWITCH LIGHTS - NUMBER DENOTES
CIRCUIT - ALL INTERNAL LIGHTS
1700mm ABOVE
FFL FOR WALL WHITECROFT MIRAGE 3 C165 IP65 DOWNLIGHTER, WARM
VIEWING/WAITING AREA MOUNTED TV WHITE 3000K, WHITE BEZEL. E DENOTES INTEGRAL 3 HOUR
LS 1 DS EMERGENCY PACK TO BS 5266 VERSION. NUMBER DENOTES
CIRCUIT. ELECTRICAL CONTRACTOR TO ARRANGE LIGHTING
LAYOUT AND DESIGN BY MANUFACTURER TO DETERMINE
WATTAGE REQUIREMENTS TO EACH FITTING - NOTE WILL
LIKELY DIFFER FOR EACH ROOM/SPACE.

EXTERNAL LIGHTING
E 1 1 1

CENTRALISED EXTERNAL LIGHTING CONTROL SYSTEM TO


SVP CONTROL ALL NEW EXTERNAL LIGHTING WITH TIMER, AND
ELC
STAT DURGO OVER-RIDE ON/OFF CAPABILITIES PAIRED WITH INDIVIDUAL PIR
LIGHT SENSORS TO CONTROL ALL NEW EXTERNAL LIGHTS ON
R ONE CIRCUIT - SYSTEM TO ALLOW FOR FULL ADAPTATION
CLEANERS BETWEEN USE OF EITHER TIMER OR PIR SENSOR CONTROL TO
3 3 LS DS CUPD ALL NEW EXTERNAL LIGHTS ON ONE CIRCUIT.
SWIMMING POOL CSU
2 DS 2 WHITECROFT MIRAGE 3 C165 IP65 DOWNLIGHTER, WARM
E GULLY WHITE 3000K, WHITE BEZEL. E DENOTES INTEGRAL 3 HOUR
VISITOR WC PC
DS 4 R EMERGENCY PACK TO BS 5266 VERSION.
2 LS
1500x1500mm WHEELCHAIR
1 TURNING SPACE
PC WHITECROFT LIGHTING KOLO IP65 HOOD 14W 3000k WARM
WHITE LED LUMINAIRE, BLACK. EMERGENCY VERSION
LS 4
THROUGHOUT. MOUNTING HEIGHT 2100mm FROM FFL TO TOP
DS LS 1 E 1 OF FITTING.
CHANGE/SWR
E E 4 EJ EJ
RWP

1500x1500mm WHEELCHAIR
MECHANICAL VENTILATION/HEATING-COOLING AND PLUMBING
TURNING SPACE

ENTIRE SYSTEM TO BE DESIGNED, DETAILED AND INSTALLED BY


1 M&E SPECIALIST. SEE SEPARATE DRAWINGS AND DETAILS.
E
SVP
SYSTEM TO INCLUDE HEATING AND COOLING AIR CONDITIONING
TO
PAIRED WITH EXTRACT AND SUPPLY MECHANICAL VENTILATION
5 ATMOS 5 5 5
E TO ALL NEW AREAS. BUILDING TO BE FULLY ZONED WITH
USE 1200mm TILES INDIVIDUAL AREAS SERVED BY SEPARATE THERMOSTATS.
ABOVE WASH HERE TO HOT WATER GENERATION TO BE PROVIDED BY HOT WATER
AID IN CENTRALISING USE 1200mm TILES HEATERS.
FITTINGS ABOVE 2x END
CUBICLES HERE TO AID
STAT AMBULANT IN CENTRALISING CEILING MOUNTED OUTLET/INLET - SIZE AND POSITION
CUBICLE
DS FITTINGS INDICATIVE ONLY. COLOUR WHITE.
POOL ACCESS
WASH FEMALE WC
C C WALL/ENCASEMENT MOUNTED OUTLET/INLET - SIZE AND
GULLY
5 LS 5 5 5 E 5 POSITION INDICATIVE ONLY. COLOUR WHITE.

BONDING
PROVIDE FULL EARTH BONDING TO LATEST IEE WIRING
E.RWP REGULATIONS ONTO ALL PLUMBING PIPEWORK AS REQUIRED.
MOVEMENT
STARTER TIES 2xLOCKERS

OUTLET EXTERNAL COLD WATER TAP


EG
FSH1 2xLOCKERS
SVP STAT
FIRE PRECAUATIONS CCTV SYSTEM 5
DURGO PROGRAMMABLE ROOM STAT.
2xLOCKERS

SYSTEM TO BE AN EXTENSION OF EXISTING/LINKED TO EXISTING, FULLY ZONED SYSTEM CCTV SYSTEM DESIGNED AND SPECIFIED BY SPECIALIST, FULL DETAILS TBA. E 5 5
WITH INDIVIDUAL CIRCUITS TO ALL AREAS WITH CENTRAL PANEL ADDRESSABLE PANEL PROVIDE PERIMETER COVERAGE EXTERNALLY AND SOME INTERNAL COVERAGE, FSH2 2xLOCKERS

TO IDENTIFY EACH AREA SEPARATELY AND PROVIDE INDIVIDUAL AND COLLECTIVE ALL AS SHOWN. 5
ACTIVATION.

CHANNEL
2xLOCKERS

FINAL DESIGN, LAYOUT AND SPECIFICATION TO BE AGREED WITH SPECIALIST. DATA AND POWER OUTLET REQUIREMENTS FOR EACH CAMERA LOCATION TBC
SYSTEM AND ALL COMPONENTS MUST COMPLY WITH BS 5839-1:2017. SYSTEM TO BE AN WITH DESIGN BY SPECIALIST, TO BE SITED IN CEILING VOIDS WHERE POSSIBLE. D D

DRYER
FSH3 EJ

HAIR
L1 SYSTEM. USE FP200 CABLING. 5
360 DEGREES ADJUSTABLE CAMERA. USE EXTERNAL GRADE WHERE LOCATED
DS/DH MAINS OPERATED INTERLINKED DETECTOR UNIT. EXTERNALLY.
FEMALE CHANGING
5 DS LS 5 E 5
DS DH DS=SMOKE, DH=HEAT.
FSH4
DETECTORS SITED THROUGHOUT TO COMPLY WITH L1 SYSTEM. CCTV DVR CCTV DIGITAL VIDEO RECORDER AND MAIN CONTROL UNIT.
5
EJ RWP
FE FIRE EXTNGUISER POINT. TYPE AND CHARGE TBA.
EJ

FIRE ALARM BELL SOUNDER

FIRE ALARM BEACON LIGHT

APPROVED DIRECTIONAL EXIT SIGN. ALL SIGNS TO COMPLY WITH


E
BS 5499 AND HEALTH & SAFETY REGULATION 1996.

FIRE ALARM BREAK GLASS POINT

IP FIRE ALARM INDICATOR PANEL

CITADEL MAINTAINED EXIT SIGN ELJSNV/8/3M


A
N1 FIRE ACTION NOTICE

Oakhurst Studio Revisions Date Revisions Date By : SB Drawing : Ground Floor Project : Phase 1 Addition to Pool at:

TENDER
Horam Electrical Layout ST. FRANICS SOCIAL AND SPORTS CLUB,
Heathfield 01825 767854 Scale : 1:50 @ A1
Dwg No. : 0815/3/1305 Lewes Road, Haywards Heath
East Sussex www.mjbarch.co.uk
TN21 0LJ admin@mjbarch.co.uk Date : March 2023 Rev : Client : St. Francis Social and Sports Club architecture