There are 4 model consider with same geometry and same loading data only slab define as

1) Membrane

2) shell with auto mesh

3) Shell with fine mesh20x20

4) Shell with auto mesh and bending and membrane all are 0.001

The Details results are in next page

1) Membrane 2) shell with 3) Shell with 4) Shell with auto


auto mesh fine mesh and bending
mesh25x25 and membrane all
are 0.001
Load pattern Tributary area 3 point load 19 point load 3 point load
method
Right side Mb 9.20 kN-m 8.75 kN-m 9.16 kN-m 7.017 kN-m
Moment

Conclusion: 1) Membrane and fine shell results nearly match. 2) During beam design, shell and
membrane both method beam is rectangular, so beam design method will follow in both condition
as a similar because beam parameter and loading parameter is similar steel always same, if any
loading deference then only reinforcement change possible

Details sketch refer in 2nd to 5th page


1) Membrane
2) shell with auto mesh
3) Shell with fine mesh 20x20
4) Shell with auto mesh and bending and membrane all are 0.001