Tri-Tech Calculating Capacities for

Medical Inc. Medical Vacuum Systems

Project
Information
Project Number_________________________ Approval_____________________________

SCFM Allowed per : AVG.


** Outlets Bed Room USAGE Peak x = TOTAL
AREA Min. Req’d FACTOR x Flow QTY DEMAND
Anesthetizing locations :
Operating Room 3/Room 3.5 100.00% 3.50
Open Heart & Transplant 3/Room 4.0 100.00% 4.00
Minor OR's & Cysto's 3/Room 2.0 100.00% 2.00
Delivery Rooms 3/Room 1.5 50.00% 0.75
Special Proceedures 3/Room 1.0 100.00% 1.00
Major Trauma and
Emergency Surgery 3/Room 3.0 50.00% 1.50
Other Anesthetizing 3/Room 2.0 50.00% 1.00
Anesthetic Evacuation 1/Room 1.0 100.00% 1.00
Acute Care Areas :
Medical ICU 2/Bed 2.0 75.00% 1.50
Cardiac ICU 2/Bed 1.0 75.00% 0.75
Surgical ICU 2/Bed 2.0 75.00% 1.50
Neonatal ICU 2/Bed 1.0 50.00% 0.50
Post-Op. Recovery Rm. 3/Bed 1.5 50.00% 0.75
Emergency Rm. Beds 2/Bed 2.0 50.00% 1.00
Non-Acute Care Areas :
Pre-Op Holding 1/Bed 1.5 10.00% 0.15
Respiratory Care 1/bed 1.5 5.00% 0.08
Pat. Room Med. 1/bed 1.5 10.00% 0.15
Pat Room Surg. 2/bed 1.5 20.00% 0.30
Nursery 1/Bed 1.0 10.00% 0.10
LDRP's 1/bed 1.5 10.00% 0.15
Exam / Treatment Rm's. 1.5 10.00% 0.15
Autopsy 2/room 2.0 10.00% 0.20
Workrooms 1/station 1.5 10.00% 0.15
Other Non-Acute Care Area's
(Specify) 1/station 1.0 10.00% 0.10
Special Considerations (Specify) 1.0 10.00% 0.10
Class Rooms 1.0 10.00% 0.10
Equipment Room 1.0 10.00% 0.10
Total Peak Calculated Flow in SCFM (Free Air) @ 19" HgV.
+ additions for estimated future demand (peak * 33%)
GRAND TOTAL =
** AHA Recommendations for No. of Medical Vacuum Outlets for each usage location.

Tri-Tech Medical Inc., 810 Center Road, Bldg.-E, Avon, Ohio 44011