You are on page 1of 204

B ISSUE FOR APPROVAL A.S M.S. A.

F 31/05/2023
A ISSUE FOR APPROVAL A.S M.S. A.F 09/05/2023

REV ISSUED FOR BY CHECKED APPROVED DATE

KINGDOM OF SAUDI ARABIA

WATER TRANSMISSION AND TECHNOLOGIES CO

C B
Project No.
22SWCG00061
KHOBAR - HOFUF WATER TRANSMISSION SYSTEM- PH2 ,
Package B + C )

FICHTNER CONSULTING ENGINEERS CORPORATION


ENGINEER

MUTLAQ AL-GHOWAIRI CONTRACTING CO.

CONTRACTOR

HVAC TECHNICAL SUBMITTAL AHU&FFU

DOCUMENT NO: Sheet Rev


22SWCC00061-1-1EF-110MEC-1MH-DS-060610 1 of204 B

SUB-CONTRACTOR ZAMIL HVAC SUBMITTAL


TECHNICAL SUBMITTAL
PROJECT
Khobar - Hofuf Water Transmission System - PH2,
Package (B+C)

CUSTOMER: MUTLAQ AL - GHOWAIRI CO. FOR CONT.

29/05/2023
INDEX

1. COMPLIANCE STATEMENT

2. EQUIPMENT SCHEDULE

3. EQUIPMENT DESCRIPTION

4. TECHNICAL DATA WITH DRAWINGS

5. CERTIFICATES

6. COUNTRY OF ORIGIN

7. PRODUCT CATALOGUES
COMPLIANCE STATEMENT
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


4.4 Air Handling Unit
4.4.1 General Requirements
VDI 3803 is for hygenic applications.
Air Handling Units shall conform to VDI 3803, DIN EN 1363 - 1365, DIN EN 1886 and EN 13053 or equivalent. Comply as Applicable
Hygenic AHUs will be provided upon request
Each air handling unit shall be equipped with filters, heat exchanger (for energy recovery), sound attenuators,
supply and exhaust fans, cooling coils, humidifier and with motorized/manual isolation damper in supply und return Comply
air ducts.

Cooling coils shall be direct expansion refrigerant or chilled water type to meet the system requirements. Coils shall
have copper tube and aluminium fins with a fin spacing suitable for the application. Coils within a distance of 0.5 km Comply Cu tube / Cu fins with Resistec Coating are provided
to the sea shall have copper fins and copper tubes.

Units with cooling coils shall have an insulated condensate drain pan and a suitable acoustic and thermally insulated
Comply
cabinet.
For areas requiring heating, electric heating coils or electrical duct heater with suitable protection devices shall be
Comply Electric Heaters are provided in the AHUs
provided.

The unit shall be complete with sand traps, a primary filter section and a secondary filter section. The primary filter
section shall contain filter with an average efficiency of not less than 90 % (at least filter class G4) and the secondary 2" Washable MERV8 prefilter (F5) and 15" Bag filter (F9) are provided to
filter section with an average efficiency of not less than 95 % (at least filter class F7) based upon DIN EN 779 or Comply as Noted the AHUs.
equivalent. Sand louvers shall be provided for all air intakes. Sand traps shall have an efficiency of 80% with a sand Sand Trap Louver will be contractor's scope
consistency of 92% with a particle diameter of 20 microns. Maximum face velocity shall be 1.5 m/s.

Accessories such as face and bypass dampers, zone dampers, mixing boxes, and vibration isolators and economizer
Comply
for “free cooling” shall be provided for each air handling unit as required.

All air handling units shall be positions/installed on spring isolators, to minimize the potential vibration sound to the
Contractor Scope
building.
4.4.2 Weather Proof Casing
Structure
All frames shall be made of galvanized square tubes, arranged completely inside the casing to avoid thermal bridges
Comply
and to improve thermal performance of the casing.

The air conditioning unit shall be installed complete with all usual and standard equipment such as water and
refrigerant piping, valves, gauges, thermometers, etc., required for convenient operation, testing and maintenance.
Contractor Scope
Materials which are in contact with the cooling medium shall be highly resistant to corrosion by the fluid. Cooling
medium stands for chilled water and halocarbon refrigerants.

All heavy parts (30 kg and more) which must be removed for inspection, cleaning or repair shall be provided with
Comply
lifting eyes or lugs.

Outdoor units shall include a ‘technical duct’ (casing for the indicated equipment and similar to outside air duct) in
which the air handling unit control panel, necessary water and drain piping, valves, etc. are protected against the NA Not required
environmental influences like wind, sun, sand etc.
The casing walls shall be of the sandwich type with proper heat (maximum of 0.5 W/m²K) and acoustic insulation.
Comply
The unit shall be airtight according to DIN EN 1886 Class B
The coating of the unit shall be suitable for the prevalent outside conditions. Comply All AHUs are suitable for outdoor application
Base of Unit

Page 1 of 7
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


Base of unit has to be simple and quick to clean and easy for maintenance. It shall be smooth and without any
Comply Drip trap contractor scope
inaccessible corner or depression, equipped with an integrated drip tray with 80 mm slope.

Roof
The roof shall be weatherproof by UV-resistant foil and weather drips. Comply
Air Inlet/Outlet
The air inlet/outlet shall be equipped with a weatherproof hood and shall be coated. The air inlet section shall be
Comply
equipped with drain pan.
Access doors
The access doors shall be with thermal break between internal and external sheets, easy and quick to open. High
Comply
contact pressure shall guarantee extremely high air tightness.
4.4.3 AHU Equipment (Components)
Dampers
Damper shall be with profiled blades, made of galvanised steel, using high precision aluminium gears to ensure
positive accurate movement with a minimum force. Dampers shall be prepared for either manual or motorized Comply as Noted Aluminum dampers with PVC gears with better corrosion resistance
operation.
For air tightness dampers shall be selected with rubber lips on the blades. Comply special gasket inserted in both, the blades and the frame
Flexible Connectors
Connectors shall be made of coated woven polyester. Frames shall be made of EP-profile, with equipotential
Comply
bonding.
Sound Insulated Connection
Zamil AHUs does note require sound insulated connections, We are
Sound insulated connection shall be made of double U-profile-frame, airtight screwed, with equipotential bonding
Comply as Noted providing canvas connection between fan and casing (inside the unit) as
and sealed with rubber plate.
default (factory installed) , as well on fan outlet
Sand Traps/Filters

All air intakes shall be provided with sand louvers. Sand filter louvers shall be static vertical louver type and shall be
designed such, that collected sand can discharge through self emptying sand drain holes located on the bottom
edge of the unit. The casing shall be constructed of sheet metal. The sand trap louvers shall be backed by
removable washable panel type filter 25 mm thick, with a separating efficiency of the G4 filter class (DIN EN 779), a 2" Washable MERV8 prefilter (F5) and 15" Bag filter (F9) are provided to
bird screen shall be mounted on the suction side to exclude small animals. The dust collecting duct shall be made of Comply as Noted the AHUs.
sheet steel up to the secondary fan (bleed blower). The radial type secondary fan for conveying the dust laden air Sand Trap Louver will be contractor's scope
(approx. 10 % of the intake air) shall be mounted below the filter casing, and shall be equipped with a cleaning
opening and a condensate drain pipe, suction and delivery connections with flexible, reinforced PVC-collars and anti-
vibration mounts.

Screwed Filter Walls


Panel filter or wedge filter shall be used for filter walls. Comply

The filter shall consist of a standard cell frame with clamping device for fastening and sealing of the filter media.
Housing and mounting frame shall be made in galvanised steel supplied in kit form for site assembly. Parts shall be Comply
easily assembled and the screw fixing ensures shall have accurate erection and an airtight sealing.

Flat Filters
A flat filter shall be used as pre filter. The flat filters shall be of the filter class G3 to F5 based on DIN EN 779 and
Comply Prefilters of class F5 are provided
shall be with aluminium or synthetic non-woven washable media.
Bag Filters
As main and/or final filter, bag filter shall be used. The bag filters shall be of class G3 to F9 based on the DIN EN 779,
Comply Bag filters of class F9 are provided
made of synthetic glass fibre.

Page 2 of 7
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


The filter assemblies shall be housed within a purpose made box section. The filter shall comprise 50 mm thick
Comply as Noted V formation is not applicable
washable filter panels arranged in V-formation holding frames.
Plisse Filter Elements
As main/final filter suitable plisse filter elements shall be used. The filter shall be of class F6 to F9 based on the DIN
NA only 2 stage filtration is provided
EN 779, made of z- formed cellulose or glass fibre paper.
Sound Attenuators

Splitters shall be made of profiled, galvanised steel frame with mineral wool packing impregnated to prevent rotting
and provide moisture resistance. For an adequate protection against particle erosion the splitter shall be covered
Comply
with high grade glass fibre facing. The sound attenuators casing shall be made of min. 1 mm thick galvanized sheet
metal with steel angle flanges at both ends.

The best sound absorption shall be at 125 - 250 Hz. Comply

The attenuator shall be made of non-combustible material according to DIN EN 1363 – 1365 or equivalent. Comply

Plate Heat Exchanger Air/Air (Energy Recovery)


Each plate heat exchanger shall be a complete skid mounted assembly and shall conform to the applicable DIN or
Comply
AMCA Standards or equivalent.
Each heat exchanger shall have a droplet separator, a drain pan and a siphon to collect and drain the condensation Master droplet separator is provided downstream the cooling coil to
Comply
water. avoid extreme pressure drop
Heat exchanger is maade of coated aluminum beds as per vendors
The heat exchange faces shall be made of non-corroding copper plates. Comply as Noted
standards (copper is not available in market)
In case of aggressive air and if necessary all parts of heat exchanger which are directly exposed to the air stream
Comply
shall be additional coated with an applicable chemical proof material to prevent corrosion (electro tinned etc.).
The exchange plate shall be easy to inspect and to clean. The recovery efficiency of the exchanger shall be not less
Comply
than 80%.
Cooling Coils

Each cooling coil shall be complete skid mounted assembly and shall conform to DIN EN 378 or equivalent. Comply as Noted Coils conforms to AHRI410 standard

The cooling coil shall be a direct expansion type suitable for R 134a or R 407c refrigerant. Comply as Noted R-410a used
The material for fins, pipes and frames shall be applicable for humid saline air and/or saline concentrated
Comply
condensate.
Each cooling coil shall have a droplet separator, an insulated condensate drain pan and a siphon to collect and drain
Comply
the condensation water.

The cooling coil shall be constructed of copper or aluminium fins with belled collars mechanically bonded to the
seamless copper tubes. The fins spacing shall be suitable for the application. Coils for full face active or face split
operation shall have intertwined circuits for equal loading on each circuit. Suction and discharge connections shall
Comply
be on the same end. All copper coils in contact with outside air shall be electro-tinned. Coil section shall have heavy
duty coil tracks extending, the full width of the unit to provide slip-in slip-out coils for ease of maintenance and
service.

Coils shall be tested in accordance with DIN EN 764 or equivalent. After testing, coils shall be dehydrated and
Comply as Noted Tested in accordance to AHRI410 standard
charged, with dry air or nitrogen and properly sealed.
Condensing Unit, Air-Cooled
Each condensing unit shall be easy accessible and a complete skid mounted assembly, piped, wired and shall
Comply as Noted Conforms to AHRI standard
conform to DIN EN 378, DIN EN 1363 – 1365, DIN EN 1886 or ARI Standards, ANSI Standards, ASME or equivalent.

Page 3 of 7
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


The air cooled condensing unit shall be suitable for operation with refrigerant R134a or R 407c. Comply as Noted R-410a used
Each unit shall include compressors, motors, fans, coils, refrigerant piping, controls, wiring, variable frequency drive
Comply as Noted capacity control will be by compressor staging
(VFD) or capacity stage control.
Condensing units with a capacity of 150 kW to 500 kW shall be equipped with semi-hermetic type
Comply as Noted only hermetic scroll compressors proposed
scroll/reciprocating compressors and refrigeration circuits.
Smaller units may be equipped with hermetic type scroll/reciprocating compressors. Comply
Units with a capacity above 500 kW shall be equipped with semi-hermetictype turbo compressor. NA Such capacity Not required in project design
The compressor shall start operation by soft-start (e.g. Y-Δ start). NA Compressors interconnection is DOL
The compressor shall be electronically protected from temperature rise, phase failure and phase transition. Comply
The condenser shall be constructed of seamless copper tubes with copper fins. Comply
ResisTec anti corrosive coating is proposed
Coils in contact with outside air shall be electro-tinned. The fins shall not be placed closer than 10 fins per 25
Comply as Noted 12 fins per 25 mm is proposed for the ultimate heat transfer and best
millimetres.
efficiency values
Direct driven low- noise axial ventilators for low circumferential speed in a water resistant version conforming to
Comply as Noted Coil guard is provided
the IEC IP 55, class “F” utilised according to “B”, shall be used. The fan motor shall be TEAO, with rain guards.

The casing shall be constructed of weather-resistant, galvanised sheet steel, phosphated, primed and enamelled.
Comply
The external condensing units shall be effectively protected against sand, dust, humid saline air and sun.
All controls shall be completely factory wired and mounted in an enclosure. The control panels shall be complete
with all safety switches and pressure gauges. The controller shall be capable of communication over Ethernet, Comply
TCP/IP.
Each refrigerant circuit shall be complete with all necessary accessories and safety devices, including hot gas bypass
Comply
valves when used with multizone air handling units.

The refrigeration cycle shall be delivered dried, evacuated and filled with a refrigerant protection filling. NA condensing unit will be delivered fully charged with freon

The switch box (IEC IP 55) shall be equipped with following components: Comply

Compressor contactors with over-current relay and dropping relay, ventilator contactor with over- current relay,
Comply
pressure control and safety pressure control, low pressure switch and pump out relay.

Each compressor shall be provided with its individual short circuit and magnetic trips breaker. Comply

Each compressor and condenser fan motor shall be equipped with separate external over load relay. Comply

Each condensing unit shall be provided with a disconnect / MCB switch locally. Comply
Droplet Separator

The droplet separator shall be made of PP (Polypropylene) removable through maintenance door without
Comply
disassembling the cooling coils or the plate heat exchanger. Frame shall be made of stainless steel.

Each droplet separator shall be provided with a drip pan to collect the condensate and a syphon. Comply as Noted common drain pan for coil and droplet separator

Drain Pans

The drain pan shall be made of stainless steel, double wall, insulated and sloped for positive drainage. Comply

Pans shall be provided under coils, fans and humidifier sections. Comply as Noted Not applicable under fan
For stacked coils intermediate pans and copper drop tubes shall be provided. Comply as Noted PVC drop tubes shall be provided.

Page 4 of 7
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


Drain pans shall be drained by a trapped, insulated copper drainpipe that remains the full size (diameter) of the
Contractor Scope
drain pan connection to the sanitary sewer system connection. PVC drains are not acceptable.

The drain pans shall be designed for easy access and maintenance. Comply
They shall extend from upstream of the coil face continuously to 1m downstream of the coil. NA to avoid water carry over
Plug Fan
Fan shall be with open impeller and welded blades, coated as recommended by manufacturer, fixed on the motor
shaft by taper- lock- system, impellers statically and dynamically balanced, in accordance with DIN ISO 1940-1 or Comply
equivalent.
Fan/motor system shall be vibration isolated to the casing. Fan motor shall be totally enclosed fan cooled and
Comply
located out of the air stream.
Electric Heating Coils
Electric heater shall have elements made of stainless steel, fins made of galvanised steel, removable, wired and shall open wire type heater with Nickel Chromium (Ni/Cr) (80%/20%) low
provide a minimum of 4 steps of control. The heat grid shall be of the non glowing type with low surface Comply glowing material is proposed, number of stages depends on heater
temperature. Wiring shall be outside of the airflow and easy accessible by a door. capacity
Each panel shall be provided with the following accessories:
high temperature cut-out switch (thermostat), Comply
manual reset facility for high temperature cut-out Comply
heaters shall be interlocked with an air-flow switch to isolate the electrical supply when the fan is not in operation. Comply
Each heater element shall be separately fused. Near any hot areas the wiring insulation shall be of appropriate
Comply
quality.

Page 5 of 7
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


Electric Steam Humidifier for setting up outside
Carbon steel casing and Reinforced polypropylen cylinder
The steam humidifier shall consist of one casing made of stainless steel, equipped with stainless steel steam
cylinder, with integrated regulators, a steam nozzle for air moisturization in air handling unit combined with a lime
Comply as Noted lime catchment Not comply WE are providing different technology which
catchment tank prepared for the operation with potable water. The lime catchment tank shall be of low
is Openable Type Cylinder which allow the customer to remove the lime
maintenance which means collected lime shall be automatically discharged.
and the scale

Steam tubes of appropriate lengths shall be supplied as fittings as well as a measuring device for temperature and
Comply
humidity for stationary fastening (30 – 90 % relative humidity) and a pressure and differential pressure switch.
For operation the steam humidifier shall be connected to the potable water system. Also a water drain shall be
Contractor Scope
supplied.
Air control damper shall be built and installed according to chapter 4.9.9 (Air Control Damper). Contractor Scope
Weather resistant louvers shall be built and installed according to chapter 4.9.9 (Weather- Resistant Louvers). Contractor Scope
Fan
The fan section shall consist of a vane axial or centrifugal type belt or direct driven blower. The maximum noise level
Comply
at a distance of 1 m shall not exceed 85 decibel on the A scale.
The motor of belt driven blowers shall be totally enclosed fan cooled (TEFC) located out of the air stream with
Comply Direct driven fan is provided
variable pitch motor sheave. The drive assembly shall be complete with a drive cover.
For vane axial blower, the impeller shall be of the airfoil design. For centrifugal blower, the fan wheel shall be radial
Comply as Noted in case of belt driven, Axial with backward curved / airfoil
blade type or the backward curved type.
4.7 Fan/Filter Units
4.7.1 Single Fan/Filter Unit
Each fan/filter unit shall be a complete skid mounted assembly and shall conform to the applicable DIN or AMCA
Comply
Standards or equivalent.
The fan section shall consist of a vane axial or centrifugal type belt or direct driven blower. The maximum noise level
Comply Plug fan (Direct driven) is provided
at a distance of 1 m shall not exceed 85 decibel on the A scale.

The motor of centrifugal and belt driven blowers shall be totally enclosed fan cooled located out of the air stream
Comply Direct driven fan is provided
with variable pitch motor sheave. The drive assembly shall be complete with a drive cover.

For vane axial blower, the impeller shall be of the airfoil design. For centrifugal blower, the fan wheel shall be radial
Comply in case of belt driven, Axial with backward curved / airfoil
blade type or the backward curved type.

Each unit shall be complete with a filter section containing filter with average efficiency of not less than 90 % (filter
2" Washable MERV8 prefilter (F5) and 15" Bag filter (F9) are provided to
class G4) based upon DIN EN 779. Sand louvers shall be provided for all air intakes. Sand traps shall have an
Comply as Noted the AHUs.
efficiency of 90% with a sand consistency of 92% with a particle diameter of 20 microns.
Sand Trap Louver will be contractor's scope
Maximum face velocity shall be 1.5 m/s.

Page 6 of 7
Khobar - Hofuf Water Transmission System - PH2, Package (B+C) Compliance

NO. Specifications Compliance Remarks


If the fan/filter units are installed outdoors they shall be completely enclosed and must be effectively protected
Comply
against sand, dust, humid saline air and sun.
Each unit shall be complete with weatherproof intake hood (including a bird screen), automatic backdraft damper, Bird screen will be provided with the sand trap louver
Contractor Scope
disconnect switch, starters and mounted on a structural steel skid. backdraft damper will be contractor scope
The cooling coil and drain pan shall be removable as one piece, with the coil mounted inside the tray. The drain pan
shall be galvanized steel, and shall be mounted on slide rails for easy removal and to ensure that the drain pan does NA Fan/Filter Units do not have cooling coil
not rest on the unit case-work.

Cooling coils shall be fabricated using seamless copper tubes expanded into high efficiency aluminium fins to give a
mechanical bond. The copper tubes and aluminium fins shall be tin plated or blygold coated against corrosion.
NA Fan/Filter Units do not have cooling coil
Return bends shall be die formed. Header shall be heavy section seamless copper tubing. All joints shall be silver
brazed. Fittings shall include plugged vent and drain tops for each section.

Coil headers shall be fabricated from copper tube. All coil headers shall have threaded, extended pipe connections
as standard, with heavy duty PVC sealing gaskets where the connections pass through the casing, rendering the NA Fan/Filter Units do not have cooling coil
joint air–tight.
End of Section

Page 7 of 7
EQUIPMENT SCHEDULE
Project: Khobar - Hofuf Water Transmission System - PH2, Package (B+C)
Air Handling Units Schedule
Electric Heater/Heating ESP
Condensing Unit Total Cooling Capacity Sensible Cooling Capacity Air Flow Total Power Input
Ref. NO. Unit Model Coil Entering Leaving Qty
Model
KW KW KW L/S Pa Pa Temperature Temperature Supply Exhaust
Supply Return DB WB DB WB KW KW
AHU-01 TW60SP5EBD - 383.4 311.23 126 13745 450 375 37.2 23.1 18.11 16.2 33 11.6 2
ACCU-01 - CTX130N 385.48 - - - - - - - - - 165.5 -
AHU-02 TW26SP5EBD - 150 115.1 - 6761 300 300 32.4 22.1 18.03 16.4 11.6 11.6 2
ACCU-02 - CTX060N 159.73 - - - - - - - - - 74.1 - 2
EF_05 TW35P3BD - - - 161.6 8381 250 - 28 - 44.12 - 23.2 - 1
EF_01 A,B TW47P5BD - 161.6 161.6 - 10438 - - 50 26.2 36.44 22.91 - - 2
FFU-01 TW6P3BD - - - - 1440 200 - - - - - 2.8 - 5
FFU-02 TW6P3BD - - - - 1380 200 - - - - - 2.8 - 5
FFU-03 TWC2P3BD - - - - 95 150 - - - - - 0.5 - 2
FFU-04 TW3P3BD - - - - 674 150 - - - - - 1.5 - 2
FFU-05 TWC2P3BD - - - - 325 150 - - - - - 0.5 - 6
EQUIPMENT DESCRIPTION
TW Series:

TW Series Air Handling Units Central Station horizontal draw thru type Double Skin Air Handling Units are
fabricated from PENTA post heavy gauge corrosion free aluminum profile and PE corner connection.
Panels and frame are secured using internally bolted fixings and manufactured as a factory-made
combined blocks of encased individual modules assembly based upon a wide range of standard panels
with 50mm thick panels made of galvanized sheet steel, smooth walled with 48kg/m3 insulation. Unit
casing shall be externally painted. The AHU consists of filter section with 2"-thick aluminum washable filter,
coil section with DX or chilled water-cooling coil made of corrugated fins & tube and fan section with
forward curved blower driven by TEFC motor.

The Run Around Coil AHU consists of:


- Fresh Air Inlet Section with ZAC air Foil AL Dampers.
- Filter section with 2" Washable MERV8 prefilter and 15-inch bag filter (F9).
- DX cooling coil (R410a) with Cu/Cu fins with Resistec Coating and Hot Gas Bypass.
>> Stainless Steel Drain Pan
- Heating Coil.
- Electric Heater
- Steam Humidifier
- Plug Fan section, Supply and Return with EC motors.

Note: Circulating Pump is out of Zamil Scope.

The Plate Exchanger AHU consists of:

The FAHUs consist of:


- Filter section with 2" Washable MERV8 prefilter and 15-inch bag filter (F9).
- Plate Exchanger
- Double mixing box section.
- DX cooling coil (R410a) with Cu/Cu fins and Resistec Coating and with Hot Gas Bypass.
>> Stainless Steel Drain Pan
- Plug Fan section, Supply and Return with EC Motors.

Power Supply: 400V/3Ph/60Hz

The Fan units consist of:


- Filter section with 2" Washable MERV8 prefilter and 15-inch bag filter (F9).
- Plug Fan section with EC Motors.

Power Supply: 400V/3Ph/60Hz

Zamil Air Conditioners & Home Appliances Co. Ltd. Branch


Single Person Limited Liability Company
Paid-Up Capital 173,000,000
C.R. No. 4030130644
P.O. Box 4138, Jeddah23523 4138

Prince Sultan Road, Al Henaki Business Center - Kingdom of Saudi Arabia
F:+966 12 234 3652|T:+966 12 234 3640
Additional Options Added:
- Magnahelic 2000 with Contact for the filters section
- SS Drain pan from both sides
- Anti ice thermostat
- Drain second wall (for double wall drain).
- Disconnect switch for the motor connection on unit casing
- Earth Lugs
- Thermal Break profile.

Note: DDC control panels are not provided.


DDC control panels can be provided upon request with additional cost after receiving the sequence of
operation from the contractor.

CTXN (R-410a) Series Air Cooled Condensing Units consists of Dual / Hermetic Scroll compressors,
air cooled condenser coils corrugated fins & tube type,
condenser propeller fans direct driven by TEAO type motors mounted on a heavy gauge galvanized steel
sheet press
formed base, sealed type filter drier & sight glass, holding charge, Microprocessor

The selection is based on:


- Ambient Temperature 50C and Altitude 154m.

Additional Options Added:


- Condenser Coil - Copper fins
- Volt free contact
- Compressor circuit breaker
- Non fused disconnect switch
- Pump down solenoid
- Pressure Gauge
- Hot gas bypass
- Fully charged Refrigerant
- Full Guard condenser
- Electronic Thermostat
- Spring Isolators

Power Supply: 380V/3Ph/60Hz

Zamil Air Conditioners & Home Appliances Co. Ltd. Branch


Single Person Limited Liability Company
Paid-Up Capital 173,000,000
C.R. No. 4030130644
P.O. Box 4138, Jeddah23523 4138

Prince Sultan Road, Al Henaki Business Center - Kingdom of Saudi Arabia
F:+966 12 234 3652|T:+966 12 234 3640
TECHNICAL DATA
WITH DRAWINGS
1,730
1,730
L1
1,140 590
50 120
311

1,119 82.5
1,385
2 1

183.5
120

82.5
1,179.5
4,140
2,605

2,440
2,605
2,755
311
1 2 3 4 5 6

1,114.5

82.5
150

150
120 130
590 590 640 700 750 1,040
1,180 3,130
L2 L3
4,310

82.5
2,380 570
3,520

3,355
570

82.5
SURFACE CASING TOLERANCE
Supply air TW60SP5EBD P5 Exhaust air TW14SP5EBD
P5 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
CTX130N
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/29/2023 user DX3-MRE
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: AHU-01
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position AHU-01
LV DX3-MRE
web www.zamilac.com
CTX130N
Office / Agent user Print data 5/29/2023

POINT LOAD DISTRIBUTION

SECTION 1 SECTION 2 SECTION 3


o o o o o o o

o o o o o

o o o o o o o

93 93 93

Delivery sections No. Points Each load (kg)

1 Delivery Section 6 252


2 Delivery Section 6 259.5
3 Delivery Section 8 547.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/7
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position AHU-01
LV DX3-MRE
web www.zamilac.com
CTX130N
Office / Agent user Print data 5/29/2023
Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class C 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 50 °C
Type of unit External unit Unit design NRVU - BVU

Unit definition General data

Unit size TW60SP5EBD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 13,745 Length [mm] 4,310.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 450 Width [mm] 3,520.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 933 Height [mm] 2,605.0
Profiles AL

1 Simple mixing section 590.0 mm 81 Pa

Recircle air [l/s] Humidity Mixed air Temp. Humidity [%]


Fresh air [l/s] Humidity total air 13,745 Mixing Ratio [%]

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 2 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 6,873
Total Qta. Levers 2 air velocity [m/s] 9.28
Each Torque [Nm] 4.82

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 2 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 6,873
Total Qta. Levers 2 air velocity [m/s] 9.28
Each Torque [Nm] 4.82

5/29/2023 14:23
Offer R2 Page 2/7
Position AHU-01 From date 2/21/2023
CTX130N
Unit size TW60 AirCalc++ Vers. 3.8.33

2 Bag Filter section with prefilter 590.0 mm 227 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 20 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
4 x 592.0 x 287.0
Clean dP [Pa] 45
Dirty dP [Pa] 135
Airflow [l/s] 13,745 Cross section velocity [m/s] AEC [kWh] N/A
1.6

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 20 x 592.0 x 592.0
Clean dP [Pa] 87 4 x 592.0 x 287.0
592.0
Dirty dP [Pa] 187
Airflow [l/s] 13,745 Cross section velocity [m/s] 1.6
1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

3 Cooling coil 640.0 mm 76 Pa

Medium R410A
Airflow l/s 13,745
Evaporating temp. [°C] 9.44
air velocity m/s 1.91
SHR 0.81
Air in °C 37.20 Humidity [°C] 23.1
Air out °C 18.11 Humidity [°C] 16.2 Coil Suction Line 3 1/8
Tot. capacity kW 383.40 Coil Liquid Line 1 3/8
Sens. capacity 311.23
Air press. drop (wet) [Pa 76
Air press. drop (dry) [Pa] 68
2xDX-1/2"-2 4R - RH Materials:
RRows 4 Fins CU
nos. of refr.circuits 3 circuits per Slab RRows CU
Circuits (Per Slab) 36 Header CU
Fin space mm 2.1 Frames GI

1 Pcs Hot gas bypass


1 set Resistec Coating

Drain pan Double End drain Quality SS 304 Drain connection 1 1/4

1 Pcs Drain second wall (for doubl wall drain)

4 Electric heater 700.0 mm 50 Pa

HTRD-TW60-126-05-Q-C-WX Heat capacity [KW] 126.00


Entering [°C] 0.00 Voltage [V] 3x400
Leaving [°C] 20.00 Steps 5

Air volume [l/s] 5,170 Kw: Equally Divided

5/29/2023 14:23
Offer R2 Page 3/7
Position AHU-01 From date 2/21/2023
CTX130N
Unit size TW60 AirCalc++ Vers. 3.8.33

5 Steam humidifier 750.0 mm Pa


UE065XL001/DP125D40R0/1312367 voltage [V] 3x400
Temperature in [°C] 15.00 nos. of distributors 2 Nominal power [kW] 48.750
Air On Relative humidity lance length [mm] 1,250.0 Humidification [kg/h] 65.00

Drain pan Single End drain Quality SS 304 Drain connection 1 1/4

6 Plug fan Supply 1,040.0 mm 49 Pa

EC Fan 560.0 x 6
Air volume [l/s] 13,745
External press [Pa] 450
Speed [1/m] 1,553 Power [kW] 5.500 Total power [kW] 33
Tot. pres. [Pa] 933
Dynamic Pres 28
efficiency 66 Supply 3 - 380-480V/50/60HZ
Note: All Fans are running in parallel arrangement.

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 3,355.0 x 2,440.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/29/2023 14:23
Offer R2 Page 4/7
Position AHU-01 From date 2/21/2023
CTX130N
Unit size TW60 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 87.8 86.8 88.8 80.8 75.8 73.8 73.8 75.8 84.8
Outlet (db) 86.8 88.8 91.8 88.8 88.8 87.8 80.8 78.8 97.8
Casing (db) 76.3 77.8 74.3 70.0 57.2 56.1 45.6 44.3 70.5
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 73.8 72.8 74.8 66.8 61.8 59.8 59.8 61.8 70.8
Outlet (db) 72.8 74.8 77.8 74.8 74.8 73.8 66.8 64.8 83.8
Casing (db) 62.3 63.8 60.3 56.0 43.2 42.1 31.6 30.3 56.5

Unit definition General data

Unit size TW14SP5EBD Casing:


Type Exhaust air Thickness P5
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 3,307 Length [mm] 1,730.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 375 Width [mm] 3,520.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 700 Height [mm] 1,385.0
Profiles AL

1 Bag Filter section with prefilter 590.0 mm 129 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 10 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
2 x 592.0 x 287.0
Clean dP [Pa] 22
Dirty dP [Pa] 66
Airflow [l/s] 3,307 Cross section velocity [m/s] AEC [kWh] N/A
0.75

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 10 x 592.0 x 592.0
Clean dP [Pa] 42 2 x 592.0 x 287.0
592.0
Dirty dP [Pa] 126
Airflow [l/s] 3,307 Cross section velocity [m/s] 0.75
Damper: Dimensions [mm] 1,160.0 x 1,119.0 x 120.0 x 2 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 1,654
Total Qta. Levers 2 air velocity [m/s] 0.62
Each Torque [Nm] 11.005

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/29/2023 14:23
Offer R2 Page 5/7
Position AHU-01 From date 2/21/2023
CTX130N
Unit size TW60 AirCalc++ Vers. 3.8.33

2 Plug fan Return 1,140.0 mm 46 Pa

EC Fan 500.0 x 2
Air volume [l/s] 3,307
External press [Pa] 375
Speed [1/m] 1,526 Power [kW] 5.800 Total power [kW] 11.6
Tot. pres. [Pa] 700
Dynamic Pres 23
efficiency 62 Supply 3 - 380-480V/50/60HZ
Note: All Fans are running in parallel arrangement.

Fan KW may reduce

System Effect pressure drop included

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 2 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 1,654
Total Qta. Levers 2 air velocity [m/s] 2.23
Each Torque [Nm] 4.82

1 Pcs Disconnect Switch for the Motor Connection on Unit casing


1 Pcs Differential Pressure switch

5/29/2023 14:23
Offer R2 Page 6/7
Position AHU-01 From date 2/21/2023
CTX130N
Unit size TW60 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 78.0 83.0 76.0 72.0 70.0 74.0 68.0 65.0 78.6
Outlet (db) 77.0 81.0 80 79 82 77 71.0 67.0 89
Casing (db) 66.5 71.1 61.5 59.8 50.3 46.8 35.8 31.1 60.6
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 64.0 69.0 62.0 58.0 56.0 60.0 54.0 51.0 64.6
Outlet (db) 63.0 67.0 66 65 68 63 57.0 53.0 75
Casing (db) 52.5 57.1 47.5 45.8 36.3 32.8 21.8 17.1 46.6

1 set Roof top-weather proof


1 Pcs Earth Lugg
thermal break profile

SFP (int) 0 Specific Fan Power (Internal) MCA : 287.915 MOCP : 300 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

* Vertical Support is required


Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 3,520.0 1,385.0 1,730.0 1,011.00
2 3,520.0 2,605.0 1,180.0 1,037.00
3 3,520.0 2,605.0 3,130.0 2,920.00

5/29/2023 14:23
Offer R2 Page 7/7
Position AHU-01 From date 2/21/2023
CTX130N
Unit size TW60 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CK2 37.20 31 12.36 69.17 23.32 18.11 83 10.81 45.60 16.24
P2 CEE 0.00 0 0.00 0.00 -5.82 20.00 0 0.00 20.12 5.77
P3 CDB 15.00 0 0.00 15.09 3.15 15.00 10 1.05 17.75 4.56

5/29/2023 14:23
PacZAC

Condensing Unit 1.1.139.0

Customer: MUTLAQ AL - GHOWAIRI CO. FOR CONTRACTING


Done By: Rami
General Info

Project: Khobar - Hofuf Water Transmission System - Location:


PH2, Package
Hofouf
(B+C)

Ref/Tag: ACCU-01 Quantity: 2

Revision: Rev 0 Date: Wednesday, April 5, 2023

Required Capacity Required Outside Required Power Supply


Conditions
Input Conditions

Total Ambient Altitude Voltage Phases Frequency

kW °C m Volts Phase Hertz


383.40 50.00 26.0 380V (4 Wire) 3 60Hz

Selected Unit Model


CTX130N

Performance @ 50 °C Ambient Physical Data


Total Cooling Capacity 385.48 kW Fan Data Condenser Units
Total Power Input 165.5 kW
Size 760
Quantity 12
Compressor Data Air Flow 96,240.0 CFM
Output Performance

Type Hermetic Scroll Fan Speed 1100 RPM


Quantity 6 Coil Data Condenser Units

Coil Face Area 293.3 sqft


Electrical Data Coil Tube Diameter 3/8 in
Number of Rows 4
Condenser Units
Fins Per Inch 12 FPI
Power Supply 380/400-3-60Hz
(4 wire)
Fins Material Cu
Compressor RLA (Each) Amps
Compressor LRA (Each) 39.3/39.3 Amps
Fan Motor (Each) 290/290 Refrigerant
Fan Motor Speed 1.35 RPM
1100 Refrigerant R410A
Fan Motor FLA (Each) Amps
3.0 Charge Per System Oz
Unit MCA Amps
Unit MOCP 281.6 Amps
300.0 General Data
Products Certifications

1 of 1
4,740
630 980
L3 L1
630 640 340
120 120

82.5

82.5
1,692

1,692
1,995

1,995
1 2 1

220.5

220.5
3,990
4,140

82.5

82.5
2

1,830

1,830
1,995

1,995
4 3 4 6

82.5

82.5
150

150
130 130
1,080 3,130 640 450 640
1,080 3,130 1,730
L2 L4 L5
5,940
112.5

112.5
82.5

82.5
2,605
2,380
2,440

2,440
2,380
112.5

112.5
82.5

82.5
SURFACE CASING TOLERANCE
Supply air TW26SP5EBD P5 Exhaust air TW26SP5EBD
P5 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
CTX060N
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/30/2023 user DX4-MPE
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: AHU-02 fin
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position AHU-02 fin
LV DX4-MPE
web www.zamilac.com
CTX060N
Office / Agent user Print data 5/30/2023

POINT LOAD DISTRIBUTION

SECTION 1 SECTION 2 SECTION 3


o o o o o o

o o o o o o

o o o o o o

93 93 93

Delivery sections No. Points Each load (kg)

1 Delivery Section 6 174


2 Delivery Section 6 120
3 Delivery Section 6 162
4 Delivery Section 8 420
5 Delivery Section Error 0

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/7
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position AHU-02 fin
LV DX4-MPE
web www.zamilac.com
CTX060N
Office / Agent user Print data 5/30/2023
Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class B 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - BVU

Unit definition General data

Unit size TW26SP5EBD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 6,761 Length [mm] 5,490.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 300 Width [mm] 2,605.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 731 Height [mm] 1,995.0
Profiles AL

1 Bag Filter section with prefilter 630.0 mm 212 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 12 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
Clean dP [Pa] 40
Dirty dP [Pa] 120
Airflow [l/s] 6,761 Cross section velocity [m/s] AEC [kWh] N/A
1.42

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 12 x 592.0 x 592.0
Clean dP [Pa] 79
Dirty dP [Pa] 179
Airflow [l/s] 6,761 Cross section velocity [m/s] 1.42
Damper: Dimensions [mm] 1,160.0 x 816.0 x 120.0 x 4 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 6,761
Total Qta. Levers air velocity [m/s] 1.68
Each Torque [Nm] 9.9375

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/30/2023 16:31
Offer R2 Page 2/7
Position AHU-02 fin From date 2/21/2023
CTX060N
Unit size TW26 AirCalc++ Vers. 3.8.33

2 Plate exchanger - diagonal 3,130.0 mm 1 Pa


Cooling mode FI AL 20 N 2425 N 2 AE SM
Supply l/s 6,761 Pressure drop [P 1
efficiency % 100
Entering °C 50.00 Humidity [°C] 32.30
Recovery capacity [kW] 2.02
Leaving °C 46.30 Humidity [°C] 31.70

HRS pressure drop at (1.2 kg/m3) [Supply] 1


Exhaust l/s 6,423 Pressure drop [P
Entering °C 31.00 Humidity [°C] 21.60 HRS pressure drop at (1.2 kg/m3) [Exhaust
Leaving °C 50.00 Humidity [°C] 26.37

Drain pan Single End drain Quality SS 304 Drain connection 1 1/4

3 Empty section 640.0 mm Pa

4 Cooling coil 450.0 mm 50 Pa

Medium R410A
Airflow l/s 6,761
Evaporating temp. [°C] 8.33
air velocity m/s 1.74
SHR 0.77
Air in °C 32.40 Humidity [°C] 22.1
Air out °C 18.03 Humidity [°C] 16.4 Coil Suction Line 1 5/8
Tot. capacity kW 150.00 Coil Liquid Line 1 1/8
Sens. capacity 115.10
Air press. drop (wet) [Pa 50
Air press. drop (dry) [Pa] 45
DX-1/2"-2.1- 3R - RH Materials:
RRows 3 Fins CU
nos. of refr.circuits 4 circuits per Slab RRows CU
Circuits (Per Slab) 27 Header CU
Fin space mm 2.1 Frames GI

1 Pcs Hot gas bypass


1 set Resistec Coating

Drain pan Double End drain Quality SS 304 Drain connection 1 1/4

1 Pcs Drain second wall (for doubl wall drain)

5/30/2023 16:31
Offer R2 Page 3/7
Position AHU-02 fin From date 2/21/2023
CTX060N
Unit size TW26 AirCalc++ Vers. 3.8.33

5 Plug fan Supply 640.0 mm 168 Pa

EC Fan 500.0 x 2
Air volume [l/s] 6,761
External press [Pa] 300
Speed [1/m] 2,081 Power [kW] 5.800 Total power [kW] 11.6
Tot. pres. [Pa] 731
Dynamic Pres 96
efficiency 55 Supply 3 - 380-480V/50/60HZ
Note: All Fans are running in parallel arrangement.

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 2,440.0 x 1,830.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/30/2023 16:31
Offer R2 Page 4/7
Position AHU-02 fin From date 2/21/2023
CTX060N
Unit size TW26 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 82.0 80.0 88.0 79.0 74.0 76.0 69.0 70.0 83.5
Outlet (db) 81.0 81.0 91 88 87 90 81.0 79.0 98
Casing (db) 71.1 71.1 74.0 69.5 55.6 58.5 45.2 43.1 69.7
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 68.0 66.0 74.0 65.0 60.0 62.0 55.0 56.0 69.5
Outlet (db) 67.0 67.0 77 74 73 76 67.0 65.0 84
Casing (db) 57.1 57.1 60.0 55.5 41.6 44.5 31.2 29.1 55.7

Unit definition General data

Unit size TW26SP5EBD Casing:


Type Exhaust air Thickness P5
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 6,423 Length [mm] 5,190.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 300 Width [mm] 2,605.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 752 Height [mm] 1,995.0
Profiles AL

1 Filter 340.0 mm 79 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 12 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
Clean dP [Pa] 38
Dirty dP [Pa] 114
Airflow [l/s] 6,423 Cross section velocity [m/s] AEC [kWh] N/A
1.35

Damper: Dimensions [mm] 1,160.0 x 816.0 x 120.0 x 4 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 6,423
Total Qta. Levers air velocity [m/s] 1.60
Each Torque [Nm] 9.9375

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

2 Empty section 640.0 mm 72 Pa

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 2 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 6,423
Total Qta. Levers 2 air velocity [m/s] 8.68
Each Torque [Nm] 4.82

3 Plate exchanger - diagonal 3,130.0 mm 1 Pa

5/30/2023 16:31
Offer R2 Page 5/7
Position AHU-02 fin From date 2/21/2023
CTX060N
Unit size TW26 AirCalc++ Vers. 3.8.33

4 Plug fan Return 1,080.0 mm 151 Pa

EC Fan 500.0 x 2
Air volume [l/s] 6,423
External press [Pa] 300
Speed [1/m] 2,028 Power [kW] 5.800 Total power [kW] 11.6
Tot. pres. [Pa] 752
Dynamic Pres 86
efficiency 58 Supply 3 - 380-480V/50/60HZ
Note: All Fans are running in parallel arrangement.

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 2,440.0 x 1,830.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/30/2023 16:31
Offer R2 Page 6/7
Position AHU-02 fin From date 2/21/2023
CTX060N
Unit size TW26 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 78.0 78.0 84.0 74.0 68.0 70.0 64.0 65.0 78.7
Outlet (db) 80.0 80.0 90 87 86 89 80.0 78.0 97
Casing (db) 70.1 70.1 73.0 68.5 54.6 57.5 44.2 42.1 68.7
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 64.0 64.0 70.0 60.0 54.0 56.0 50.0 51.0 64.7
Outlet (db) 66.0 66.0 76 73 72 75 66.0 64.0 83
Casing (db) 56.1 56.1 59.0 54.5 40.6 43.5 30.2 28.1 54.7

1 set Roof top-weather proof


1 Pcs Earth Lugg
thermal break profile

SFP (int) 237 Specific Fan Power (Internal) MCA : 11.25 MOCP : 20.25 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 2,605.0 1,995.0 980.0 694.00
2 2,605.0 1,995.0 1,080.0 479.00
3 2,605.0 1,995.0 630.0 649.00
4 2,605.0 3,990.0 3,130.0 2,236.00
5 2,605.0 1,995.0 1,730.0 1,028.00

5/30/2023 16:31
Offer R2 Page 7/7
Position AHU-02 fin From date 2/21/2023
CTX060N
Unit size TW26 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CPTS 50.00 31 24.09 112.73 32.48 46.30 37 24.27 109.31 31.86
P2 CPTS 31.00 44 12.51 63.17 21.69 50.00 16 12.41 82.46 26.60
P3 CK2 32.40 41 12.66 65.00 22.19 18.03 86 11.15 46.38 16.50

5/30/2023 16:31
PacZAC

Condensing Unit 1.1.139.0

Customer: MUTLAQ AL - GHOWAIRI CO. FOR CONTRACTING


Done By: Rami
General Info

Project: Khobar - Hofuf Water Transmission System - Location:


PH2, Package
Hofouf
(B+C)

Ref/Tag: ACCU-02 Quantity: 2

Revision: Rev 0 Date: Wednesday, April 5, 2023

Required Capacity Required Outside Required Power Supply


Conditions
Input Conditions

Total Ambient Altitude Voltage Phases Frequency

kW °C m Volts Phase Hertz


150.00 50.00 26.0 380V (4 Wire) 3 60Hz

Selected Unit Model


CTX060N

Performance @ 50 °C Ambient Physical Data


Total Cooling Capacity 159.73 kW Fan Data Condenser Units
Total Power Input 74.1 kW
Size 800
Quantity 4
Compressor Data Air Flow 41,668.0 CFM
Output Performance

Type Hermetic Scroll Fan Speed 900|1100 RPM


Quantity 4 Coil Data Condenser Units

Coil Face Area 97.8 sqft


Electrical Data Coil Tube Diameter 3/8 in
Number of Rows 4
Condenser Units
Fins Per Inch 14 FPI
Power Supply 380/400-3-60Hz
(4 wire)
Fins Material Al
Compressor RLA (Each) Amps
Compressor LRA (Each) 30/30 Amps
Fan Motor (Each) 139/139 Refrigerant
Fan Motor Speed 2.3 RPM
900|1100 Refrigerant R410A
Fan Motor FLA (Each) Amps
4.1 Charge Per System Oz
Unit MCA Amps
Unit MOCP 143.9 Amps
150.0 General Data
Products Certifications

1 of 1
120 130

62.5

62.5
1,692
1,955

1,830
2,105
1 2 2

200.5

62.5
150
570 600 920
2,090
L1
2,090

62.5
92.5
2,565
2,380

2,440
92.5

62.5
SURFACE CASING TOLERANCE
Supply air TW35P3BD P3 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
Heating
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/30/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: EF-05
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
From date 2/21/2023
Phone +966 3 847 3333
Position EF-05
Fax
LV HW-ME Heating
web www.zamilac.com
Print data 5/30/2023
Office / Agent user

POINT LOAD DISTRIBUTION

o o o

o o

o o o

93

Delivery sections No. Points Each load (kg)

Delivery Section 8 399

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/5
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
From date 2/21/2023
Phone +966 3 847 3333
Position EF-05
Fax
LV HW-ME Heating
web www.zamilac.com
Print data 5/30/2023
Office / Agent user
Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class B 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - UVU

Unit definition General data

Unit size TW35P3BD Casing:


Type Supply air Thickness P3
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 8,381 Length [mm] 2,090.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 250 Width [mm] 2,565.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 1,026 Height [mm] 1,955.0
Profiles AL

1 Bag Filter section with prefilter 570.0 mm 252 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 12 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
Clean dP [Pa] 50
Dirty dP [Pa] 150
Airflow [l/s] 8,381 Cross section velocity [m/s] AEC [kWh] N/A
1.77

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 12 x 592.0 x 592.0
Clean dP [Pa] 97
Dirty dP [Pa] 197
Airflow [l/s] 8,381 Cross section velocity [m/s] 1.77
Damper: Dimensions [mm] 1,160.0 x 816.0 x 120.0 x 4 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 8,381
Total Qta. Levers air velocity [m/s] 2.08
Each Torque [Nm] 9.9375

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/30/2023 16:31
Offer R2 Page 2/5
Position EF-05 From date 2/21/2023
Heating
Unit size TW35 AirCalc++ Vers. 3.8.33

2 Heating coil 600.0 mm 274 Pa

Airflow [l/s] 8,381 Medium Water


air velocity [m/s] 2.16 Med. Flow [l/s] 3.6780
Air in [°C] 28.00 Med. velocity [m/s] 0.90
Air out [°C] 44.12 Med. in [°C] 45.30
Air press. Drop [Pa] 274 Med. out [°C] 34.70
Capacity [kW] 161.60 Med. pres. drop [kPa] 48.33

HW-1/2"-1.8 12R- RH Materials:

RRows 12 Fins AL
RRows CU
Fin space [mm] 1.8 Header CU
Connection in NPT 1 1/2 Frames GI
Connection out NPT 1 1/2
Water content (KG) 189.7

1 set Coating for End Plates


1 Pcs Air vent & drain connection

5/30/2023 16:31
Offer R2 Page 3/5
Position EF-05 From date 2/21/2023
Heating
Unit size TW35 AirCalc++ Vers. 3.8.33

3 Plug fan Supply 920.0 mm 100 Pa

EC Fan 450.0 x 4
Air volume [l/s] 8,381
External press [Pa] 250
Speed [1/m] 2,223 Power [kW] 5.800 Total power [kW] 23.2
Tot. pres. [Pa] 1,026
Dynamic Pres 57
efficiency 63 Supply 3 - 380-480V/50/60HZ
Note: All Fans are running in parallel arrangement.

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 2,440.0 x 1,830.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/30/2023 16:31
Offer R2 Page 4/5
Position EF-05 From date 2/21/2023
Heating
Unit size TW35 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 91.0 84.0 88.0 82.0 74.0 76.0 76.0 73.0 85.0
Outlet (db) 86.0 83.0 93 88 88 86 81.0 77.0 97
Casing (db) 80.2 75.8 74.8 69.8 57.3 55.8 53.5 42.0 70.5
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 77.0 70.0 74.0 68.0 60.0 62.0 62.0 59.0 71.0
Outlet (db) 72.0 69.0 79 74 74 72 67.0 63.0 83
Casing (db) 66.2 61.8 60.8 55.8 43.3 41.8 39.5 28.0 56.5

1 set Roof top-weather proof


1 Pcs Earth Lugg

SFP (int) 161 Specific Fan Power (Internal) MCA : 11.25 MOCP : 20.25 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 2,565.0 1,955.0 2,090.0 2,125.00

5/30/2023 16:31
Offer R2 Page 5/5
Position EF-05 From date 2/21/2023
Heating
Unit size TW35 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CH1 28.00 0 0.00 28.17 9.57 44.12 0 0.00 44.38 16.01

5/30/2023 16:31
120

82.5

82.5
2,298
2,605

2,440
2,755
1 2

224.5

82.5
150
590 790
1,380
L1
1,380

112.5

82.5
2,380

2,440
2,605
112.5

82.5
SURFACE CASING TOLERANCE
Supply air TW47P5BD P5 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
Cooling
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/30/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet

STD. Tag-no: EF_01 A,B no. OF

VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
From date 2/21/2023
Phone +966 3 847 3333
Position EF_01 A,B
Fax
LV CW-M
web www.zamilac.com
Cooling
Office / Agent user Print data 5/30/2023

POINT LOAD DISTRIBUTION

o o

o o

o o

93

Delivery sections No. Points Each load (kg)

Delivery Section 6 681

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/3
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
From date 2/21/2023
Phone +966 3 847 3333
Position EF_01 A,B
Fax
LV CW-M
web www.zamilac.com
Cooling
Office / Agent user Print data 5/30/2023
Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class E 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - UVU

Unit definition General data

Unit size TW47P5BD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 10,438 Length [mm] 1,380.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [Pa] Width [mm] 2,605.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] Height [mm] 2,605.0
Profiles AL

1 Bag Filter section with prefilter 590.0 mm 237 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 16 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
Clean dP [Pa] 46
Dirty dP [Pa] 138
Airflow [l/s] 10,438 Cross section velocity [m/s] AEC [kWh] N/A
1.66

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 16 x 592.0 x 592.0
Clean dP [Pa] 91
Dirty dP [Pa] 191
Airflow [l/s] 10,438 Cross section velocity [m/s] 1.66
Damper: Dimensions [mm] 1,160.0 x 1,119.0 x 120.0 x 4 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 10,438
Total Qta. Levers air velocity [m/s] 1.91
Each Torque [Nm] 12.2575

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/30/2023 16:31
Offer R2 Page 2/3
Position EF_01 A,B From date 2/21/2023
Cooling
Unit size TW47 AirCalc++ Vers. 3.8.33

2 Cooling coil 790.0 mm 206 Pa

Medium Water
Airflow [l/s] 10,438
Med. Flow [l/s] 3.6780
air velocity [m/s] 2.05
Med. velocity [m/s] 0.82
Air in [°C] 50.00 Humidity [°C] 26.2
Med. in [°C] 34.70
Air out [°C] 36.44 Humidity [°C] 22.91
Med. out [°C] 45.30
total capacity [kW] 161.60
Med. pres. drop [kPa] 45.72
Sens. capacity 161.60
SHR 1

No. of Rows 11 Materials:

Fins CU
Fin space [mm] 2.1
RRows CU
Connection in NPT 3
Header CU
Connection out NPT 3
Frames GI
2xCW-1/2"- 11R- RH
Water content (KG) 250.8
1 set Coating for End Plates

Drain pan Single End drain Quality SS 304 Drain connection 1 1/4

1 set Roof top-weather proof


1 Pcs Earth Lugg

SFP (int) 0 Specific Fan Power (Internal) MCA : 0 MOCP : 0 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 2,605.0 2,605.0 1,380.0 2,721.00

5/30/2023 16:31
Offer R2 Page 3/3
Position EF_01 A,B From date 2/21/2023
Cooling
Unit size TW47 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CK1 50.00 16 12.09 81.64 26.42 36.44 32 12.24 68.07 23.04

5/30/2023 16:31
120 130

62.5

62.5
816
1,040

915
1 2

1,190

161.5

62.5
150
570 820
1,390
L1
1,390

62.5
245
1,040
550

915
245

62.5
SURFACE CASING TOLERANCE
Supply air TW6P3BD P3 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/29/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: FFU-01
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-01
LV ME
web www.zamilac.com

Office / Agent user Print data 5/29/2023

POINT LOAD DISTRIBUTION

o o

o o

Delivery sections No. Points Each load (kg)

Delivery Section 4 91.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/4
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-01
LV ME
web www.zamilac.com

Office / Agent user Print data 5/29/2023


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class A 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 50 °C
Type of unit External unit Unit design NRVU - UVU

Unit definition General data

Unit size TW6P3BD Casing:


Type Supply air Thickness P3
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 1,440 Length [mm] 1,390.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 200 Width [mm] 1,040.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 678 Height [mm] 1,040.0
Profiles AL

1 Bag Filter section with prefilter 570.0 mm 260 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 1 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
2 x 592.0 x 287.0
Clean dP [Pa] 52
Dirty dP [Pa] 152
Airflow [l/s] 1,440 Cross section velocity [m/s] AEC [kWh] N/A
1.5

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 1 x 592.0 x 592.0
Clean dP [Pa] 102 2 x 592.0 x 287.0
592.0
Dirty dP [Pa] 202
Airflow [l/s] 1,440 Cross section velocity [m/s] 1.5
Damper: Dimensions [mm] 550.0 x 816.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 1,008
Total Qta. Levers 1 air velocity [m/s] 2.25
Each Torque [Nm] 4.29

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/29/2023 14:26
Offer R2 Page 2/4
Position FFU-01 From date 2/21/2023

Unit size TW6 AirCalc++ Vers. 3.8.33

2 Plug fan Supply 820.0 mm 68 Pa

EC Fan 400.0
Air volume [l/s] 1,440
External press [Pa] 200
Speed [1/m] 1,994 Power [kW] 2.800
Tot. pres. [Pa] 678
Dynamic Pres 39
efficiency 61 Supply 3 - 380-480V/50/60HZ

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 915.0 x 915.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/29/2023 14:26
Offer R2 Page 3/4
Position FFU-01 From date 2/21/2023

Unit size TW6 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 75.0 77.0 83.0 78.0 72.0 70.0 65.0 59.0 79.7
Outlet (db) 77.0 78.0 84 80 81 78 72.0 66.0 89
Casing (db) 67.1 68.5 66.5 62.1 50.5 47.6 42.8 28.8 62.5
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 61.0 63.0 69.0 64.0 58.0 56.0 51.0 45.0 65.7
Outlet (db) 63.0 64.0 70 66 67 64 58.0 52.0 75
Casing (db) 53.1 54.5 52.5 48.1 36.5 33.6 28.8 14.8 48.5

1 set Roof top-weather proof


1 Pcs Earth Lugg

SFP (int) 175 Specific Fan Power (Internal) MCA : 6 MOCP : 10.8 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 1,040.0 1,040.0 1,390.0 245.00

5/29/2023 14:26
Offer R2 Page 4/4
Position FFU-01 From date 2/21/2023

Unit size TW6 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C

5/29/2023 14:26
120 130

62.5

62.5
816
1,040

915
1 2

1,190

161.5

62.5
150
570 820
1,390
L1
1,390

62.5
245
1,040
550

915
245

62.5
SURFACE CASING TOLERANCE
Supply air TW6P3BD P3 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/29/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: FFU-02
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-02
LV ME
web www.zamilac.com

Office / Agent user Print data 5/29/2023

POINT LOAD DISTRIBUTION

o o

o o

Delivery sections No. Points Each load (kg)

Delivery Section 4 91.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/4
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-02
LV ME
web www.zamilac.com

Office / Agent user Print data 5/29/2023


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class A 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 50 °C
Type of unit External unit Unit design NRVU - UVU

Unit definition General data

Unit size TW6P3BD Casing:


Type Supply air Thickness P3
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 1,380 Length [mm] 1,390.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 200 Width [mm] 1,040.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 667 Height [mm] 1,040.0
Profiles AL

1 Bag Filter section with prefilter 570.0 mm 254 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 1 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
2 x 592.0 x 287.0
Clean dP [Pa] 50
Dirty dP [Pa] 150
Airflow [l/s] 1,380 Cross section velocity [m/s] AEC [kWh] N/A
1.44

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 1 x 592.0 x 592.0
Clean dP [Pa] 97 2 x 592.0 x 287.0
592.0
Dirty dP [Pa] 197
Airflow [l/s] 1,380 Cross section velocity [m/s] 1.44
Damper: Dimensions [mm] 550.0 x 816.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 1,104
Total Qta. Levers 1 air velocity [m/s] 2.46
Each Torque [Nm] 4.29

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/29/2023 14:26
Offer R2 Page 2/4
Position FFU-02 From date 2/21/2023

Unit size TW6 AirCalc++ Vers. 3.8.33

2 Plug fan Supply 820.0 mm 63 Pa

EC Fan 400.0
Air volume [l/s] 1,380
External press [Pa] 200
Speed [1/m] 1,950 Power [kW] 2.800
Tot. pres. [Pa] 667
Dynamic Pres 36
efficiency 61 Supply 3 - 380-480V/50/60HZ

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 915.0 x 915.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/29/2023 14:26
Offer R2 Page 3/4
Position FFU-02 From date 2/21/2023

Unit size TW6 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 74.0 76.0 82.0 77.0 71.0 69.0 64.0 58.0 78.7
Outlet (db) 76.0 77.0 83 79 80 77 71.0 65.0 88
Casing (db) 66.1 67.5 65.5 61.1 49.5 46.6 41.8 27.8 61.5
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 60.0 62.0 68.0 63.0 57.0 55.0 50.0 44.0 64.7
Outlet (db) 62.0 63.0 69 65 66 63 57.0 51.0 74
Casing (db) 52.1 53.5 51.5 47.1 35.5 32.6 27.8 13.8 47.5

1 set Roof top-weather proof


1 Pcs Earth Lugg

SFP (int) 165 Specific Fan Power (Internal) MCA : 6 MOCP : 10.8 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 1,040.0 1,040.0 1,390.0 245.00

5/29/2023 14:26
Offer R2 Page 4/4
Position FFU-02 From date 2/21/2023

Unit size TW6 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C

5/29/2023 14:26
490
1 2

640
L1
640

840

SURFACE CASING TOLERANCE


Supply air TWC 2P3BD P3 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/29/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: FFU-03 new
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-03 new
LV ME
web www.zamilac.com

Office / Agent user Print data 4/13/2023

POINT LOAD DISTRIBUTION

o o

o o

Delivery sections No. Points Each load (kg)

Delivery Section 4 12

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/4
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-03 new
LV ME
web www.zamilac.com

Office / Agent user Print data 4/13/2023

2020 Model box as declared on the Eurovent

Serie TWC Sealevel [m] 26


Execution Standard
Type of unit External unit

Unit definition General data

Unit size TWC 2P3BD Casing:


Type Supply air Thickness P3
Panel inside GI Thick [mm] 0.7
Airflow [l/s] 325 Length [mm] 640.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [Pa] 150 Width [mm] 840.0
Panel inside bottom GI Thick [mm] 0.7
Tot. pressure [Pa] 295 Height [mm] 490.0
Profiles AL

1 Filter 144 Pa

Type MERV8+MERV14
Cells pcs x size [mm] 1 x 773.0 x 360.0
Class F5 ISO ePM Coarse 55%
Clean dP [Pa] 165
Dirty dP [Pa] 126
Airflow [l/s] 325 Cross section velocity [m/s] 0.97
1 Pcs Filter.

5/29/2023 14:26
Offer R2 Page 2/4
Position FFU-03 new From date 2/21/2023

Unit size TWC 2 AirCalc++ Vers. 3.8.33

2 Plug fan Supply 520.0 mm 2 Pa

EC Fan 280.0
Air volume [l/s] 95 Protection IP54
External press [Pa] 150
Speed [1/m] 1,801 Power [kW] 0.500
Tot. pres. [Pa] 295
Dynamic Pres 1
Supply 1 -200-277V/50/60HZ

System Effect pressure drop included

5/29/2023 14:26
Offer R2 Page 3/4
Position FFU-03 new From date 2/21/2023

Unit size TWC 2 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance

sound pressure level


Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 56.0 52.0 43.0 39.0 34.0 30.0 28.0 20.0 42.1
Outlet (db) 60.0 56.0 52 49 48 47 40.0 34.0 58
Casing (db) 50.5 46.5 33.5 30.8 18.0 16.5 11.5 33.8

MCA : 2.71 MOCP : 4.88 of complete unit.

* Fan outlet position subject to change during design.


* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 840.0 490.0 640.0 33.00

5/29/2023 14:26
Offer R2 Page 4/4
Position FFU-03 new From date 2/21/2023

Unit size TWC 2 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C

5/29/2023 14:26
120 130

62.5

62.5
513
735

610
1 2

885

159.5

62.5
150
570 620
1,190
L1
1,190

62.5
195
940
550

815
195

62.5
SURFACE CASING TOLERANCE
Supply air TW3P3BD P3 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/29/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: FFU-04
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-04
LV ME
web www.zamilac.com

Office / Agent user Print data 5/29/2023

POINT LOAD DISTRIBUTION

o o

o o

Delivery sections No. Points Each load (kg)

Delivery Section 4 70.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/4
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-04
LV ME
web www.zamilac.com

Office / Agent user Print data 5/29/2023


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class A 2016, 2020 Model box as declared on the Eurovent
Certified Performance website CAL(R) L3/L3.

Serie TW Sealevel [m] 26


Execution Standard Design Outdoor Temperature 50 °C
Type of unit External unit Unit design NRVU - UVU

Unit definition General data

Unit size TW3P3BD Casing:


Type Supply air Thickness P3
Panel inside GI Thick [mm] 1.25
Airflow [l/s] 674 Length [mm] 1,190.0
Panel outside GI-P Thick [mm] 1.00
Ext. pressure [Pa] 150 Width [mm] 940.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [Pa] 541 Height [mm] 735.0
Profiles AL

1 Bag Filter section with prefilter 570.0 mm 203 Pa

Type 2" Washable MERV8


Cells pcs x size [mm] 1 x 592.0 x 287.0
Class F5 ISO ePM Coarse 55%
1 x 592.0 x 490.0
Clean dP [Pa] 37
Dirty dP [Pa] 111
Airflow [l/s] 674 Cross section velocity [m/s] AEC [kWh] N/A
1.13

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 1 x 592.0 x 287.0
Clean dP [Pa] 72 1 x 592.0 x 490.0
592.0
Dirty dP [Pa] 172
Airflow [l/s] 674 Cross section velocity [m/s] 1.13
Damper: Dimensions [mm] 550.0 x 513.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [l/s] 674
Total Qta. Levers 1 air velocity [m/s] 2.39
Each Torque [Nm] 2.68

1 Pcs Magnahelic 2000 With Contact ; 0-500 Pa

5/29/2023 14:26
Offer R2 Page 2/4
Position FFU-04 From date 2/21/2023

Unit size TW3 AirCalc++ Vers. 3.8.33

2 Plug fan Supply 620.0 mm 38 Pa

EC Fan 315.0
Air volume [l/s] 674
External press [Pa] 150
Speed [1/m] 2,130 Power [kW] 1.500
Tot. pres. [Pa] 541
Dynamic Pres 22
efficiency 56 Supply 3 - 380-480V/50/60HZ

Fan KW may reduce

System Effect pressure drop included

Flexible canvas GI Temp. [°C] 80.0 Dimensions [mm] 815.0 x 610.0 x 130.0
1 Pcs Disconnect Switch for the Motor Connection on Unit casing
1 Pcs Differential Pressure switch

5/29/2023 14:26
Offer R2 Page 3/4
Position FFU-04 From date 2/21/2023

Unit size TW3 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 65.0 67.0 75.0 71.0 68.0 66.0 62.0 56.0 73.9
Outlet (db) 67.0 68.0 76 73 75 74 71.0 64.0 84
Casing (db) 57.1 58.5 58.5 55.1 44.8 43.6 41.5 26.6 55.4
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 51.0 53.0 61.0 57.0 54.0 52.0 48.0 42.0 59.9
Outlet (db) 53.0 54.0 62 59 61 60 57.0 50.0 70
Casing (db) 43.1 44.5 44.5 41.1 30.8 29.6 27.5 12.6 41.4

1 set Roof top-weather proof


1 Pcs Earth Lugg

SFP (int) 133 Specific Fan Power (Internal) MCA : 3.81 MOCP : 6.86 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 940.0 735.0 1,190.0 187.00

5/29/2023 14:26
Offer R2 Page 4/4
Position FFU-04 From date 2/21/2023

Unit size TW3 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C

5/29/2023 14:26
490
1 2

640
L1
640

840

SURFACE CASING TOLERANCE


Supply air TWC 2P3BD P3 Type of unit External unit
Panel outside GI-P
Project:
Khobar - Hofuf Water TransmissionWN
System - PH2, Package (B+C
Panel inside GI R2 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 5/29/2023 user
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: FFU-05 new
VER: 3.8.33
DRAWING NO. Office
Classic
Air Conditioners
TEL. EMail
+966 3 847 3333 classic@zamilac.com

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-05 new
LV ME
web www.zamilac.com

Office / Agent user Print data 4/13/2023

POINT LOAD DISTRIBUTION

o o

o o

Delivery sections No. Points Each load (kg)

Delivery Section 4 12

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/4
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer R2
Phone +966 3 847 3333 From date 2/21/2023
Fax Position FFU-05 new
LV ME
web www.zamilac.com

Office / Agent user Print data 4/13/2023

2020 Model box as declared on the Eurovent

Serie TWC Sealevel [m] 26


Execution Standard
Type of unit External unit

Unit definition General data

Unit size TWC 2P3BD Casing:


Type Supply air Thickness P3
Panel inside GI Thick [mm] 0.7
Airflow [l/s] 325 Length [mm] 640.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [Pa] 150 Width [mm] 840.0
Panel inside bottom GI Thick [mm] 0.7
Tot. pressure [Pa] 294 Height [mm] 490.0
Profiles AL

1 Filter 144 Pa

Type MERV8+MERV14
Cells pcs x size [mm] 1 x 773.0 x 360.0
Class F5 ISO ePM Coarse 55%
Clean dP [Pa] 165
Dirty dP [Pa] 126
Airflow [l/s] 325 Cross section velocity [m/s] 0.97

5/29/2023 14:26
Offer R2 Page 2/4
Position FFU-05 new From date 2/21/2023

Unit size TWC 2 AirCalc++ Vers. 3.8.33

2 Plug fan Supply 520.0 mm ERROR Pa

EC Fan 280.0
Air volume [l/s] 35 Protection IP54
External press [Pa] 150
Speed [1/m] 1,796 Power [kW] 0.500
Tot. pres. [Pa] 294
Dynamic Pres
Supply 1 -200-277V/50/60HZ

System Effect pressure drop included

5/29/2023 14:26
Offer R2 Page 3/4
Position FFU-05 new From date 2/21/2023

Unit size TWC 2 AirCalc++ Vers. 3.8.33

noise calculation measureing point at 2 m Distance

sound pressure level


Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 53.0 52.0 43.0 39.0 34.0 30.0 28.0 19.0 41.9
Outlet (db) 56.0 56.0 52 50 48 47 40.0 34.0 58
Casing (db) 47.0 46.5 33.5 31.5 18.0 16.5 11.5 33.7

MCA : 2.71 MOCP : 4.88 of complete unit.

* Fan outlet position subject to change during design.


* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no.Width [mm] Height [mm] Length [mm] Weight [kg]
1 840.0 490.0 640.0 33.00

5/29/2023 14:26
Offer R2 Page 4/4
Position FFU-05 new From date 2/21/2023

Unit size TWC 2 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C

5/29/2023 14:26
CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number: 8296559 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW105
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Unducted Fan Discharge


Supply Fan Type: Plenum Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Direct-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412181296555482
Certificate of Product Ratings
AHRI Certified Reference Number: 8296647 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW47
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412180987365464
Certificate of Product Ratings
AHRI Certified Reference Number: 8296635 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW35
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412180827622488
Certificate of Product Ratings
AHRI Certified Reference Number: 8296623 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW26
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412180425457066
Certificate of Product Ratings
AHRI Certified Reference Number: 8296613 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW22
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Unducted Fan Discharge


Supply Fan Type: Plenum Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Direct-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412180287241952
Certificate of Product Ratings
AHRI Certified Reference Number: 8296601 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW17
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412180137014915
Certificate of Product Ratings
AHRI Certified Reference Number: 8296591 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW14
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412180015335695
Certificate of Product Ratings
AHRI Certified Reference Number: 8296569 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW11
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412179510678930
Certificate of Product Ratings
AHRI Certified Reference Number: 8296547 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW08
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412179318332163
Certificate of Product Ratings
AHRI Certified Reference Number: 8296537 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW06
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412179047985896
Certificate of Product Ratings
AHRI Certified Reference Number: 8296527 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW04
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412178884342945
Certificate of Product Ratings
AHRI Certified Reference Number: 8296517 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW03
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412178710872057
Certificate of Product Ratings
AHRI Certified Reference Number: 8296507 Date: 6/6/2017 †Status: Active
Product: Central Station Air-Handling Unit Supply Fan
Model Designation: TW02
Manufacturer: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
Trade/Brand name: COOLINE; ZAMIL

Rated as follows in accordance with AHRI Standard 430(I-P)-2014/431 (SI)-2014 for Central Station Air Handling
Unit Supply Fans and subject to verification of rating accuracy by AHRI-sponsored, independent, third party
testing:

Configuration Type: Ducted Fan Discharge


Supply Fan Type: Housed Fan
Geometry: Airfoil/Backwards-inclined
Drive Type: Belt-drive
Software Name: AirCalc++
Software Version: PL-AP-TWH-16-2M-E
Fan Arrays Included: No

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131412178386082139
CERTIFICATE
N° 07.04.233
Air Handling Unit / Centrales de traitement d'air
Range Name / Nom de Gamme :
TW&TW(H)
Granted on April 27, 2007 - Date 1ère admission 27 avril 2007

This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com

Participant/Titulaire

ZAMIL Central Air Conditioners


PO Box 41015 - Street 106, 2nd industrial city
31521 Dammam, Saudi Arabia

This certificate is issued by Eurovent Certita Certification Ce certificat est délivré par Eurovent Certita Certification dans
according to the certification rules: les conditions fixées par le référentiel :

ECP AHU - « Air Handling Unit » in force at ECP AHU – « Centrales de traitement d'air » en vigueur à
established date. date d’édition.

Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita
Certification, the right to use the mark ECP shall be Certification, le droit d'usage de la marque ECP, est accordé à
granted to the beneficiary company for the above Range la société qui en est bénéficiaire pour la gamme visée ci-
in the conditions defined by the certification program dessus, dans les conditions définies par le programme de
mentioned. certification mentionné.

Unless withdrawn or suspended, this certificate remains Sauf retrait ou suspension, ce certificat demeure valide tant
valid as long as the requirements for the certification que les conditions du référentiel du programme de certification
program framework are met. The validity of the sont respectées. La validité du certificat est à vérifier sur le site
certificate is to be verified on www.eurovent- Internet www.eurovent-certification.com
certification.com
CE CERTIFICAT A ÉTÉ EMIS LE 17/03/2020
THIS CERTIFICATE HAS BEEN ISSUED ON 17/03/2020 CE CERTIFICAT EST VALIDE JUSQU’AU 30/09/2020
THIS CERTIFICATE IS VALID UNTIL 30/09/2020

Organisme accrédité n° 5-0517 Paris, 17 mars 2020


Certification Produits et Services selon la
norme NF EN ISO/CEI 17065:2012
Portée disponible sur www.cofrac.fr MANAGING BOARD MEMBER / MEMBRE DIRECTOIRE
Accreditation #5-0517 Products and
Services Certification according to NF EN
ISO/CEI 17065:2012 –
Scope available on www.cofrac.fr

COFRAC est signataire des accords MLA


d’EA et MLA d’IAF,
COFRAC is signatory of EA MLA and IAF
MLA,
list of EA members is available on
www.european-accreditation.org/ea-members
list of IAF members is available on
www.iaf.nu//articles/IAF_MEMBERS_SIGNATORIES/4

1/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06 D06 TEMPLATE_ECP_RANGE_REV1.0
CERTIFICATE
N° 07.04.233

Appendix / Annexe

Granted on April 27, 2007 - Date 1ère admission 27 avril 2007

This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com

List of certified products and characteristics is displayed on:


La liste des références et caractéristiques certifiées est disponible sur le site :
www.eurovent-certification.com
This certificate is valid for the following trade names:
Ce certificat est valide pour les marques commerciales suivantes:
Trade Name / Marque Commerciale

COOLINE
ZAMIL

This certificate is valid for the following manufacturing places:


Ce certificat est valide pour les sites de production suivants:
Manufacturing Place / Site de Production

Dammam, Saudi Arabia

This certificate is valid for the following software:


Ce certificat est valide pour les logiciels de sélection suivants:
Software / Logiciel de sélection

Clim Calc 3.8.29

2/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06 D06 TEMPLATE_ECP_RANGE_REV1.0
CERTIFICATE OF COMPLIANCE
Certificate Number 20140611-SA13167
Report Reference SA13167-20140605
Issue Date 2014-JUNE-11

Issued to: ZAMIL AIR CONDITIONERS


PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA

This is to certify that HEATING AND COOLING EQUIPMENT


representative samples of Air Handling units, Series TW, followed by
2/3/4/6/8/11/14/17/22/26/35/47/60/73/90/105/120, followed
by P3/P5/P5E, followed by B/V/S, followed by D.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: Bi-National Standard for Safety for Heating and Cooling
Equipment UL1995/CSA C22.2 No. 236
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Listing Mark should be considered as being covered by UL's
Listing and Follow-Up Service.
The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the
word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category
name (product identifier) as indicated in the appropriate UL Directory.

Look for the UL Listing Mark on the product.

William R. Carney, Director, North American Certification Programs

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1
COUNTRY OF ORIGIN
Date : 31Oct2021

From : Othman Abbadi / ZAC Product Manager, DSAHU

To : Sales and Applications Department

Subject : Material Sourcing Origin (Double-Skin Air Handling Unit)

This is to inform that Zamil Air conditioners in Dammam has been designing and producing Double Skin Air
Handling Units (AHUs) for the last 47 years.

Throughout the years, thousands of AHUs have been supplied to multifarious projects involving various
contractors, consultants and clients.

The Double Skin Air Handling Units from Zamil are ranging from 2000 m3/hr to 120000 m3/hr. The
components used in all Double Skin Air Handling Units TW series are listed as follows:

Nicotra EC fans - Italy / Delta EC fans - China


EQUIPMENT CATALOGUES
Central Station
Double Skin Air Handling Units
TW / TWH Series
1400 m3/hr thru 120,000 m3/hr

Central Station Air-Handlers AH NO 07.04.233 Range TW OR TW(H)


AHRI Standard 430
Company Profile
Zamil Air Conditioners, a sector business of Zamil Industrial, is the largest manufacturer of air conditioners in the Middle East.
The company manufactures and markets the complete range of air conditioners, from room air conditioners to packaged units
to large chillers for residential, commercial and industrial applications.

Founded in 1974, Zamil Air Conditioners was one of the first air conditioning companies to be established in Saudi Arabia. Today,
the company produces about one million air conditioners per year. Aside from its head office and two manufacturing plants in
Dammam, Saudi Arabia, the company also has production facilities in India. The company supplies air conditioning products to
over 55 countries across the world, with its major markets located in the GCC, Middle East, North Africa, Europe and Asia.

Zamil Air Conditioners is the first Middle Eastern company to achieve the prestigious AHRI certification (Air-Conditioning, Heating
and Refrigeration Institute, USA). The company is also 9001:2015 Quality Management System, ISO14001:2015 (Environment
Management) and ISO 45001:2018 (Occupational Safety) certified with many of its products tested and approved by AHRI,
SASO, ESMA & UL.

Companies:
• Zamil Air Conditioners & Home Appliances Co. (L.L.C),
• Zamil Central Air Conditioners Co. (L.L.C),
• Zamil Air Conditioning and Refrigeration Services Co. (L.L.C)

Manufacturing Facilities:
The company has two factories in Saudi Arabia located in the 1st and 2nd Industrial Cities of Dammam. The company also has
production facilities in India.

Annual Production Capacity:


• Window Air Conditioners: 700,000
• Mini-Split Systems: 300,000
• Central Air Conditioners: 50,000

Core Values

VISION:
To be the partner-of-choice COMMUNITY &
for environmental control HONESTY &
PROSPERITY
INTEGRITY
solutions that are based We believe in mutual prosperity.
We believe goodwill and good
on lifetime value reputation are core to our business.
We aspire to thrive in business
while bringing progress and
We uphold honesty, integrity, prosperity to our own people and
professionalism and a high level of communities where we operate.
business ethics. We observe prudence Our culture, our ideas, our
and fairness in dealing with our practices, our environmental
MISSION: stakeholders. concern, and our teamwork lead
us to create superior values for
To make air-conditioning people and communities
Affordable, Reliable and around us.

Energy-Efficient
VALUES
LEADERSHIP &
CUSTOMER & PRUDENCE
EXCELLENCE We cultivate talent and leadership
to create sound business
We are diligent about understanding solutions, to best meet our
and fulfilling our customers’ needs. customer needs, and to develop
We strive to please our customers with markets, people and shareholder
excellence in quality and services. We value. We do so by optimizing use
listen to our customers and “go the of funds, resources, materials, and
extra mile” to satisfy them. INNOVATION & technologies. We build prudence
CHANGE and cost-effectiveness in our
leadership culture passing on
We are passionate about
benefits to our customers.
meaningful innovation. We are a
learning organization. We learn
from our experiences and global
best practices, and we innovate to
create leading local solutions
leveraging on world class
knowledge. We embrace positive
change brought forth by innovation
and aspirations to grow our
business.
Research & Development
Zamil Air Conditioners boasts of its state-of-the-art testing facilities – “Ikhtebar” which is a third party air conditioner testing
facility built by Intertek Testing Services (ITS) and certified by Electrical Testing Laboratories (ETL). Equipped to perform a wide
range of tests under many recognized local and international standards including: AHRI 210/240; AHRI 410; AHRI 310/380; AHRI
430; AHRI 440; AHRI 340/360; ASHRAE 116; ASHRAE 37;ASHRAE 41.1; AHRI 365; ISO 5151; SASO 385; SASO 2682; UL 1995
and AHRI 550/590.

Features:
• Performance test of whole range of air conditioners – consumer as well as commercial, in capacities from ½ TR to 600 TR
• Support research and development initiatives through implementation of state of the art computational programs.
• Test products for conformance to local and international certifications and standards such as SASO, AHRI, UL, AHAM etc.

Facility:
• Calorimetric Test Rooms
• Psychrometric Test Rooms
• Chiller Test Facility
• Sound Lab
• Reliability Test Facility

Parent Company
Headquartered in Dammam, Saudi Arabia, Zamil Industrial Investment Company ('Zamil Industrial') is a premier business group
engaged in the design, engineering and manufacturing of innovative products and solutions for the global building and construc-
tion industry.

Zamil Industrial offers a wide range of products and services in four sectors viz. HVAC, Steel, Insulation and Concrete. Zamil
Industrial’s key products and services include: air conditioning systems, pre-engineered steel buildings, steel structures, telecom
and transmission towers, process equipment, precast concrete building products, insulation products, installation and mainte-
nance of HVAC Solutions, and solar power solutions.

The company employs more than 15,500 people and derives about 25% of its revenues from outside Saudi Arabia. Zamil Indus-
trial products are sold in more than 90 countries around the globe, and the company operates manufacturing facilities in Saudi
Arabia, United Arab Emirates, Egypt, India and Vietnam. Zamil Industrial shares are actively traded on the Saudi Stock Exchange
(Tadawul).
INDEX

Introduction, Quality ..................................................................................................................................................... 3

Design Flexibility ........................................................................................................................................................... 4


Flexible Modular Construction, Rigid and Leak Tight Construction, Wide Range of Sizes

Nomenclature ............................................................................................................................................................... 5

Quick Unit Selection ..................................................................................................................................................... 6

Unit Cross Selections ................................................................................................................................................... 7

Unit Frame .................................................................................................................................................................... 8


Unit frame Options

Panels, Paint, Insulation ............................................................................................................................................... 9

Access Panels and Doors ........................................................................................................................................... 10


Unit Base

Roof Cover .................................................................................................................................................................. 11

Filters ..................................................................................................................................................................... 11-12


Flat Filters, Low Velocity Filters, Bag Filters, HEPA Filters, Carbon Filters, Filter Frames

Coils ............................................................................................................................................................................ 13
Drain Pan

Fans ....................................................................................................................................................................... 14-15


Centrifugal Fans, Plug Fans

Blower Motors ....................................................................................................................................................... 16-17


Drives, Vibration Eliminator

Vibration Eliminator ..................................................................................................................................................... 17


Plenum Section, Electric Heater

Dampers ..................................................................................................................................................................... 18

Energy Recovery Wheel .............................................................................................................................................. 19


Run around Coils, Plate Heat Exchanger

Heat Pipe System ....................................................................................................................................................... 20

Humidifiers .................................................................................................................................................................. 21
Steam Humidifiers, Air Washers, Adiabatic Cooling/high pressure, Humidification

Diffuser Plate .............................................................................................................................................................. 22


Sound Attenuators, Drip Eliminators

Bulk Head Light .......................................................................................................................................................... 23


Ultra Violet Lights

Power Panels .............................................................................................................................................................. 24


Starting Panel from Zamil

Variable Frequency Drivers (VFD) ............................................................................................................................... 25

Fan Array .................................................................................................................................................................... 26

Hygienic Units ....................................................................................................................................................... 27-28

Air Handling Units Selection Software "AirCalc++" ............................................................................................... 29-31

Some Air Handling Units Possible Configuration .................................................................................................. 32-34

Reference Projects ................................................................................................................................................ 35-36

‫ وﺣﺪات ﻣﻌﺎﻟﺠﻪ اﻟﻬﻮاء اﻟﺰاﻣﻞ ﻟﻠﻤﻜﻴﻔﺎت‬.......................................................................................................................... 37-38

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
INTRODUCTION

This catalogue is meant to serve as a guideline for consulting and design engineers for the selection of Zamil Air Handling Units.
Please contact your local Zamil office for assistance with any technical clarification, selection, consultancies related to the air
handling units product capabilities, features or applications.

QUALITY

The quality and reliability of any Zamil Air Handling Unit depends on the quality of the components, therefore inline with our
rigorous quality management and selection of the best suppliers, we offer you the highest quality Units. Each unit can have
designed-in flexibility to adapt to your exact requirements. This capability provides you the best overall total value based upon
life-expectancy, functionality, energy efficiency and serviceability. Zamil air handling unit designs incorporate many engineering
and performance features which maximized equipment up-time and the additional benefit of reduced equipment energy and
maintenance costs.

AH NO 07.04.233 Range TW OR TW(H)


Central Station Air-Handlers
AHRI Standard 430

3
DESIGN FLEXIBILITY

The major strength of Zamil Air Handling units, all thanks to the top of the line design software developed by the unit engineers
and designers using the latest technologies, making AHU products the best in the market.

Zamil Air Handling Units provide you the best overall total value based upon life-expectancy, functionality, energy efficiency and
serviceability. Zamil custom products and system designs incorporate many engineering and performance features that maximize
equipment up-time and the additional benefit of reduced equipment energy and maintenance costs.

FLEXIBILITY MODULAR CONSTRUCTION


Zamil Air Handling Units are manufactured as a factory-made combined blocks of encased individual modules assembly based
upon a wide range of standard panels (30mm, 50mm and 100mm). An air handling unit consists of a fan or fans and other neces-
sary sections like coil, filters,…etc. to perform one or more of the functions of circulating, cleaning, heating, cooling, humidifying,
dehumidifying and mixing of air.

Zamil Air Handling Units can be delivered in sections for indoor or outdoor installation, completely assembled or knocked
down for on site-assembly.

RIGID AND LEAK TIGHT CONSTRUCTION


Zamil Air Handling Units are fabricated from penta post heavy gauge corrosion free aluminium profile and PE corner connection.

Panels and frame are secured using internally bolted fixings. The Gasket liner between the panels and frame ensures an excellent
leak tight and also works as thermal and acoustic insulation and guarantees the tightness of the casing according to EN1886.

WIDE RANGE OF SIZES


Seventeen Standard sizes of optimally engineered Air Handling Units can be supplied by Zamil to handle air volumes from:

- 1,400 m3/h to 120,000 m3/h – Cooling duty.


- Up to 220,000 m3/h – Heating and Ventilation only.

Non-standard units can be produced for any application with much higher flow rates. For requirements in excess of the above,
please consult your nearest Zamil representative.

Dear valued customer, please go through this catalogue, if you need more detailed information, please
don’t hesitate to contact your nearest Zamil office for assistance.

4
NOMENCLATURE

SERIES PANEL THICKNESS UNIT LOCATION

TW Standard Version P3 30 mm D Roof Top Unit

TWH Hygienic Version P5 50 mm

P5E 50 mm Thermal Break

TWH 120 P5E S D

UNIT SIZE
nominal air flow PANEL DESIGN
@ 2.5 m/s face velocity

2 2,000 m3/hr B Outside Coated RAL 9002


3 3,000 m3/hr V Outside Galvanized
4 4,000 m3/hr S Special Design
6 6,000 m3/hr
8 8,000 m3/hr
11 11,000 m3/hr
14 14,000 m3/hr
17 17,000 m3/hr
22 22,000 m3/hr
26 26,000 m3/hr
35 35,000 m3/hr
47 47,000 m3/hr
60 60,000 m3/hr
73 73,000 m3/hr
90 90,000 m3/hr
105 105,000 m3/hr
120 120,000 m3/hr

**Same is applicable for TWN SERIES


-60 mm panel may used with Hygienic units

5
QUICK UNIT SELECTION

Range I = Airflow volume referring to free unit cross section and airflow velocity
from 1 m/s to 3.5 m/s.
Range II
Range II = Airflow volume referring to coil finned area and airflow velocity
Range I from 1 m/s up to 2.5 m/s.

Air flow volume [m3/h]

6
UNIT CROSS SELECTIONS

AIRFLOW RATE
UNIT SIZE
m3/hr @ 2.5 m/s
FILTER ARRANGEMENT TW TWP3 TWP5
ACROSS ACROSS
B (mm) H (mm) B (mm) H (mm) UNIT SECTION COIL

42 FILTER 1/1 120 4450 3830 146030 120582

35 FILTER 1/1 105 4450 3215 121952 104990

30 FILTER 1/1 90 3825 3215 103816 90400

20 FILTER 1/1
73 3520 2910 85932 73840
9 FILTER 1/2

20 FILTER 1/1 60 3215 2605 69723 59410

16 FILTER 1/1 47 2605 2605 56025 46890

12 FILTER 1/1 35 2565 1955 2605 1995 42328 35540

9 FILTER 1/1 26 1955 1955 1995 1995 31979 26260

6 FILTER 1/1
22 1955 1650 1995 1690 26805 21750
3 FILTER 1/2

6 FILTER 1/1 17 1955 1345 1995 1385 21630 17350

4 FILTER 1/1
14 1650 1345 1690 1385 18131 14230
2 FILTER 1/2

4 FILTER 1/1 11 1345 1345 1385 1385 14631 11195

2 FILTER 1/1
8 1345 1040 1385 1080 11131 8280
2 FILTER 1/2

1 FILTER 1/1
6 1040 1040 1080 1080 8468 5975
2 FILTER 1/2

1 FILTER 1/1
4 1040 735 1080 775 5805 3895
1 FILTER 1/2

1 FILTER 5/6
3 940 735 980 775 5207 3410
1 FILTER 1/2

1 FILTER 5/6 2 735 635 775 675 3382 2005

FILTER 1/1 = 592 x 592 mm (24" x 24") FILTER 1/2 = 287 x 592 mm (12" x 24") FILTER 5/6 = 490 x 592 mm (20" x 24")

7
UNIT FRAME

The Zamil TW-series air handling unit is constructed from framed modules manufactured from extruded anodized aluminium
profiles joined by means of 3D injected molded and reinforced PE corners to form the “Penta-post” construction. This method has
demonstrated superior mechanical characteristics and gives the unit its rigidity and design flexibility.

The unique profiles with their unique cross sections designed to give extra strength and rigidity to the unit frame and to prevent
any buckling or deformation.

For the best thermal and acoustical performance, the internal cavities of the Penta-Post frames are insulated with fiberglass that
confirms to HH-1-545B type 1, SMACNA standard for duct liners and ASTM-C-423 and NFPA90A and 90B standards for fire
resistance.

30mm Profile Penta-Post 50mm Profile Penta-Post An air handling module

Middle webs of the same material as the profiles are used to recess the panels and stiffen the case assembly.
The frame construction makes it possible to disassemble and reassemble the unit sections at site in case of access or lifting
difficulties.

Options:
- Thermal break which provides perfect isolation between the inside and outside airs.

50mm thermal break profile

8
PANELS, PAINT, INSULATION

TW-series casing panels are constructed from double wall, sandwich type panels. With this configuration, the insulation is kept
out of the air stream and thus assures better indoor quality, as well as the ease of cleaning. Panel thickness is 30 or 50mm based
on the unit size, as standard TW2 - TW35 comes with 30mm panel thick, while TW47 - TW120 comes with 50mm panel thick.
Upon client request, TW2 - TW35 units can be manufactured with 50mm panel thickness as an option.

For standard panel, the outer skin of the sandwich panel is zinc coated galvanized steel sheet metal of 24 gauge thickness
thoroughly de-greased and then phosphated before the application of an average 80 micron electrostatic polyester powder paint
oven baked in RAL 9002 color scheme, this finishing pass 1500 hr in 5% salt path at 95oF and 100% relative humidity. It complies
to ASTM B 117 standard.

The inner skin of the panel are supplied in a zinc coated galvanized finish of 18 gauge thickness.

Stiffeners inside the panel are provided to enhance the rigidity of the casing and to secure the inside insulation.

All panels are thermally and acoustically insulated for best unit performance, and are internally insulated with fiberglass insulation
of 48 kg/m3 density, the insulation confirms to HH-1-545B type 1, SMACNA standard for duct liners and ASTM-C-423 and NFPA
90A and 90B standards for fire resistance.

Double Skin Panel

Outer Skin Stiffener Insulation Inner Skin

Galvanized Galvanized
Galvanized Fiber Glass Foam Galvanized
Painted Painted
0.75 mm 1.00 mm 0.75 mm 1.00 mm 1 inch 2 inches 1 inch 2 inches 1.25 mm 1.50 mm 1.25 mm 1.50 mm

1.25 mm 1.50 mm 1.25 mm 1.50 mm

Stainless Stainless
Aluminum Rockwool Aluminum
Steel Steel
0.75 mm 1.00 mm 1.25 mm 1 inch 2 inches 1.25 mm 1.50 mm 1.25 mm

1.25 mm 1.50 mm

Double Skin Panels Combination Choices.

9
ACCESS PANELS AND DOORS

The access panels and doors of the air handling unit have exactly the same configuration of the fixed panels described previously
with same variety of choices. The access panel type is determined based on the unit size and the section which to be served.

Five types of access panels and doors can be provided:

A. Access panel with C-Clamp


B. Hinged door with C-Clamp
C. Hinged door with turn-lever
D. Hinged door with double lever lock
E. Lockable types

The table below shows the default selection of access panels and doors in the TW series AHU’s, however, the type of the
access can be changed among the alternatives upon the customer request.

Standard Access Type


Unit Section
Unit size Other Sections
Fan Section Coil Section Filter Section (if access is needed)

TW2 - TW22 B A B B
TW26 - TW120 C A C B

UNIT BASE
The unit base is a fabricated, welded galvanized sheet metal base of high gauge along the perimeter of the unit. Supports extend
across the length and width of the unit to support the internal components. The unit base construction is well painted to withstand
the most difficult weather conditions.

For the units TW2 – TW26 the unit base height as default is 80mm, the base rail can be fabricated with 150mm height.

For the units TW35– TW120 the unit base height as default is 150mm, and can be fabricated with different heights.

Air Handling Unit Base

10
ROOF COVER

For outdoor installations, TW-series air handling units are equipped with a standard roof cover to protect the unit from varying
climates. The roof cover is made with slight pitch down from the center line to the ends on both sides to avoid rain accumulation
on the unit top. For best rainwater drainage, the roof cover is extended along the unit perimeter.

Sealant application before roof Roof Cover


cover installation

FILTERS
A wide variety of filter types are available to meet any filtration requirements, including flat filters, low-velocity filters, bag filters,
HEPA filters, carbon filters and many other types of filters.

1 - Flat Filters

Aluminum Filters Synthetic Filters (MERV 8) Pleated Filters (MERV 8) Mini Pleated filter (MERV14)

2'' flat filters with Aluminium 2" flat filters with synthetic 2" flat Pleated filters with 2" or 4" Mini Pleat high
washable media, used as nonwoven media (washable) synthetic non-woven media efficiency filter can be provid-
standard in Zamil TW-series air can be provided upon request. (disposable) can be also ed upon request
handling units. 4" AL filter can provided upon request.
be provided upon request.

2 - Low Velocity Filters 3 - Bag Filters 4 - HEPA Filters

For a higher level of filtration For critical air cleaning appli-


than flat filters, bag filters with cations such as clean rooms,
95% filtration efficiency can be food factories, operation
used, the bag filters are made theaters or pharmaceutical
from ultra fine non-woven applications where a very high
To increase the filtration area, synthetic fibers, formed into degree of filtration is required
filters arranged in a vee bank: pockets and then attached to a and the efficiency needed to
2" Aluminium washable filters rigid header. Rigid bag filters be in excess of 99.995%.
or 2" synthetic filters (wash- with 12" deep or short bag HEPA filters can be provided
able) or 2" Mini-Pleated filters filters with 15" deep or long as an option.
can be provided upon request. bag filters with 22" deep are
available.

11
For all TW-series air handling units, a combination of three internationally common sizes from the above types of filters are used
(see page 7 for filter sizes combination for each model).

5 - Carbon Filters
Activated carbon is the most common material used in HVAC systems for the removal of gaseous contaminations by means of
adsorption, absorption and chemical reaction.

Based on the application, the surrounding environment carbon filters can be carefully selected and integrated in Zamil TW-series
air handling units as an option.

Filter Frames
The pre-filters and bag filters are fixed in a specially - designed galvanized steel frames, with locks to secure the filters in their
places during operation. For TW2 - TW26 models, the filter frames are fixed together and installed on a channel to enable sliding
them out complete with the filter cells for service or replacement, while for the models TW35-TW120 the filter frames are fixed
inside the filter section and service or replacement to be done inside the unit. The arrangement of filter frames designed to
minimize air bypass and allow for filter access and replacement from the access side of the air handling unit.

Withrawable Filter Frame Fixed Filter Frame

For the calculation of internal pressure drop ’’Mid-life’’ resistance is considered in the calculations for the selection of the blower
motor.

Options:
- Stainless steel filter frames
- Differential pressure switch
- Sand Inertia filters
- Gas phase filters
- Cartridge filters
- Drum filters
- Wide range of filters with MERV efficiency as per ASHRAE 52.2
- Magnehelic pressure gauge for visual indication of the filter conditions
Magnehelic Pressure Gauge

12
COILS

Zamil TW Air Handling units offer a variety of chilled water coils, direct
expansion coils (R-410a, R-134a), hot water coils and steam coils which
confirms to AHRI 410 standard and comply with Eurovent standards.

All coils designed to deliver optimum performance at all design condi-


tions and to meet a wide range of applications and requirements.

As a standard, coils are manufactured from seamless copper tubes of


½” OD, mechanically expanded into collar continuous corrugated alumi-
num fins to provide a continuous compression bond over the entire
finned length for maximum heat transfer rates.

Chilled Water Coil Direct Expansion Coil

The standard number of fins per inch is 12 FPI; however 10 and 14 FPI coils are available as an option upon the client request or
to achieve the determined indoor conditions.

Extensive cleaning is done after manufacturing each coil for optimum system cleanliness and all coils are factory tested at 300
psig air pressure under water.

Coils can be manufactured from 1 to 12 rows for both chilled water and direct expansion coils, and up to 4 rows for heating coils.

Due to the huge variety of coil input conditions, the coils calculation and selection is optimally done based on a fully wetted coil
by selection software integrated in the unit selection software to match the required conditions.

Direct expansion coils have expansion valve and distributor to ensure equal refrigerant fed to all circuits. The number of circuits is
chosen to provide optimum heat transfer and reasonable refrigerant velocity and pressure drop so as not to trap any oil in the coil
tubing.

Headers and connections for water coils and DX-coils are made of seamless copper pipes and inlet & outlet connections are
sealed against unit panels by rubber gaskets as standard wherever coil connections protrude through the casing.

Utilizing the full available unit cross section area, coils are mounted in the unit casing on non-corrosive slide rails to allow for easy
coil slide in - slide out when required. All water coils are fitted with plugged drain and vent tapping to facilitate draining and
venting.

Options:
- Stainless steel coils casing
- On stacked coils, intermediate drain pans can be fitted to provide drainage of condensate on the elevated coil block
- Copper tube – copper fins coil
- 5/8’’ tube diameter - coils.
- Coated coils (Please contact your local Zamil sales office for more details).
- Stainless steel coils.
- Steam coils.

DRAIN PAN
In order to remove the condensate formed during de-humidification, drain pan is supplied as standard under the cooling coil. The
drain pan bottom are sloped properly to ensure complete and positive drainage of condensate. The drain pan outer surface is
insulated with (1/8”) closed cell foam insulation to prevent condensation.

Options:
- Double wall drain pan assembly.
- Intermediate drain pan for small units.
- Stainless steel drain pan

Stainless Drain pan

13
FANS

Centrifugal Fans
The standard fans used in TW-series are high performance Double Width Double Inlet (DWDI) centrifugal fans, optimally
engineered for HVAC application, with high quality, and fully tested performance in accordance with DIN-24166 accuracy class-1,
ISO 5801, BS 848 Part-1 and AMCA-210 standards.

All fans are optimally selected for best performance and sound characteristics based on maximum fan efficiency.

The impellers can have forward curved, backward inclined or airfoil profile blades depending on the customer requirements and
the system static pressure.

The impeller is galvanized finished for forward curve blade, glass reinforced polymid or welded heavy gauge steel painted with
epoxy for backward and airfoil blade. All fans are statically and dynamically balanced for stable non-surging operation.

Fans are securely fixed to hardened steel shafts with high safety factor and precisely ground and polished, shafts are coated with
protective paint for added protection, the shaft ends are grooved and keyed.

Depends on fan class and size, TW-series fans equipped with self-aligned ball bearings that are greased for life or pillow block
bearings with re-greasing nipples.

The complete fan-motor assembly mounted on a common base frame entirely isolated from the unit by rubber vibration elimina-
tors or open type anti-vibration spring isolators.

As standard the fan discharge also isolated from the casing by use a flexible connection which will minimize the vibration and
accordingly the sound level.

Centrifugal Fan-motor Possible arrangements

Reinforced Forward Fan Reinforced Backward Fan

Backward Airfoil fan Smoke Fan

14
Plug Fans
Most of the energy consumed by an air handling unit is the electricity used to run the fan motor, whilst only a small percentage of
the energy goes to heat generation, so high fan efficiency means power saving, this is why the plug fans which are high fan
efficiency significantly reduces the consumption of electricity, and therefore the operation cost.

Direct Drive simplicity converts to less operating expenses also as there are no fan shafts, bearing, belts or guards to maintain.

Noise emission level of air handling units is also one of the most important environmental factors which we fine tuned our product
to reduce it, the choice of using plug fan will be ideal to achieve this goal. Plug fans are extremely quiet efficiency and quiet opera-
tion make an exceptional combination for your air handling unit.

EC Fan Plug Fan

15
BLOWER MOTORS
Fan motors are Totally Enclosed Fan Cooled (TEFC) squirrel cage type with class “F“ insulation at 50OC ambient temperature and
continuous duty. Motors are of IP55 and protect the motor from dust and water. It is mounted on an adjustable base of special
design so that the belt tension can be easily adjusted.

With a voltage tolerance ±10% and frequency tolerance ±5%, motor can operate in an ambient 0 to +50OC according to
IEC60034-1 standard.

For motor sizing the mechanical losses incurred in transmitting the load from motor shaft to the fan shaft are taken into consider-
ation along with a reasonable safety factor.

Options:
- Explosion Proof motors
- Stand by motors

Standard motors are fitted with six terminals,


and a terminal connection and wiring diagrams
are shown in the motor terminal box.

Standard Motor Mount Standard Motor

DRIVES
Transmission of power from the motor to the fan is provided by means of a set of pulleys and matching V-belts. The pulleys are
taper locked to the fan and motor shaft. TW-series air handling units are equipped with the optimized pulleys and belts, which are
sized and preinstalled by factory. Optimal selection of drives and proper installation will ensure that the fan re-stats at the required
designed speed and at same time help to optimize fan and motor bearing life. Belt guard provided as standard on the drive set
that keep operators safe.

Fan Motor Assembly

16
VIBRATION ELIMINATOR
In order to reduce the transmission of noise and vibration, the complete fan motor subbase assembly is mounted on set of anti-vi-
bration mounts. As standard for TW2 - TW22, the fan assembly is a common base frame entirely isolated from the unit by rubber
isolator while as standard in units TW26 - TW120, the frame isolated by 1” deflection open type spring isolators.

Options:
- TW6 - TW22 equipped with
the 1" deflection springs.
- 2” Deflection springs for TW 6 and above
- Seismic springs for TW 6 and above

Rubber Isolator Spring Isolator Seismic Springs

PLENUM SECTION
Empty sections can be provided upon request as an access or to facilitate the function of a component in another section or for
future use. The standard length of the plenum section is 500mm, however, custom sizes to suite any requirements can be provid-
ed.

ELECTRIC HEATER
Electrical heaters with wide range of capacities and steps are available to be supplied built-in Zamil TW-series Air handling units.

The standard electric heater is the open wire type which is provided in a stand alone section, it consists of a heavy gauge corro-
sion resistant steel frame and control compartment which contains the basic electrical components. The heating wire is a compo-
sition of 80% Nickel and 20% Chrome, via anti-thermal shock, moisture resistant steatite free floating holding ceramics. Airflow
switches are provided as standard to shut-off power to heaters in case of airflow
failure.

All heating elements are supported by corrosion resistant heavy gauge wire rack construction designed to allow for free flow of air
with lowest possible pressure drop.

Options:
- Heaters with UL Control Panel.
- Finned tubular heater type.
- Finned tubular heater, UL.

Finned Type Heater Open Type Heater

17
DAMPERS
Zamil TW series air handling units are equipped with multiple-blade, low leakage dampers to modulate and control the air flow.

Dampers can be provided with opposed blades or parallel


blades. Dampers are prepared for either manual or motorized
operation (damper actuator can be provided as an option).

As standard, Zamil dampers are entirely made of aluminum


profiles with reinforced polyamide accessories, the blades of
the damper has airfoil shape and perfectly controlled by gears
that are spaced out by special spacers located in the damper
frame.

Zamil damper has an excellent anti-corrosion features as it is


made of aluminum and polyamide which make it light in weight
and yet extremely strong because of its well engineered
design.
Whenever the damper width is exceeding 1770 mm, an intermediate profile is given to give greater rigidity for larger dimensions.
The damper’s air tightness is enhanced by special gasket inserted in both, the blades and the frame itself.

The following damper alternative can provided: Dampers can also be used as:

• Galvanized steel dampers with airfoil blades. - Full-face air intake dampers
• Stainless steel dampers with single skin blades. - Fresh, exhaust and return air dampers for two-way or
• Stainless steel dampers with airfoil blades. three-way mixing box
- Economizer control
- Multi-zone application dampers

Options:
- AMCA Dampers - Back draft dampers
- Actuators - Different Materials

Some Possible Damper Positions & applications

18
ENERGY RECOVERY WHEEL
The heat wheel is a rotating wheel consisting of an air permeable aluminum matrix with a large interior surface, the wheel consists
of two half moon sections, and it should be installed in a double deck or side by side units where the supply air flows through one
half of the rotary wheel while the exhaust air flows in counter flow through the other half, the wheel is rotating with low speed
simultaneously.

Energy wheels designed to recover either sensible heat only or both sensible and latent
to meet the requirements of the indoor air quality. The recovery of sensible heat
achieved when the sensible heat is transferred as the metallic substrate gain and stores
heat from the warmer air stream and gives it up to the cooler stream while the rotation of
the wheel.

Latent heat is transferred as the metallic substrate which is coated by a hygroscopic


coating condenses moisture from the air stream that has the higher humidity ratio
through absorption and releases moisture through evaporation into the air stream that
has a lower humidity ratio. The TW-series selection software optimizes the selection of
the energy wheel to achieve the needed indoor conditions.

- Heat wheels are ideal for applications that demand high percentage of fresh air intake.
- Wheels are Eurovent certified. Energy Recovery Wheel

RUN AROUND COILS


It is an air to water heat exchanger system, it is used to recover sensible
heat only, it consists of two coils, one located in the exhaust air stream
and the other in the supply air stream, both of them are connected with
a pump in a closed circuit (pump and piping by others), the heat trans-
fer medium is water.

When the cold air passes through the first coil of the run around system
which is located in the cold air stream, it cools down the water inside
the coil, after the water looses heat, the pump passes this cold water to
the coil in the hot air stream, heat exchange happened thus cooling the
air and warming the water, warm water returns to the coil in the cold
stream and the cycle is repeated.

Run Around coils

PLATE HEAT EXCHANGER


This type of heat recovery systems depends on the thermal conduction propriety to recover sensible heat only.

The plate heat exchanger is specially thermoformed plates, connected together via folded edges permanently bonded and sealed.
The supply and exhaust airflows pass crossways through the heat exchanger alternate aluminum layers of the plate heat exchanger.
The two air streams are totally separated by the nature of the heat exchanger construction, so to use this type of heat exchangers,
the unit shall be a double deck unit.

Plate Heat Exchanger

19
HEAT PIPE SYSTEM
This type of heat recovery system utilizes the refrigerant phase change property. It consists of two coils connected to each other
circuit by circuit independently; each circuit is filled with a refrigerant.

Two main functions can be done by using two types of heat pipes; it can be used for dehumidification or for heat recovery, accord-
ing to the arrangement of the heat pipe coils with respect to other components.

1- Heat pipes for dehumidification function may be described as having two sections: Pre-cool and reheat. The first section is
located in the incoming air stream. When warm air passes over the heat pipes, the refrigerant vaporizes, carrying heat to the
second section of heat pipes, placed downstream. Because some heat has been removed from the air before encountering the
evaporator coil, the incoming air stream section is called the precool heat pipe.

Air passing through the evaporator coil is assisted to a lower temperature, resulting in greater condensation removal. The «over-
cooled» air is then reheated to a comfortable temperature by the reheat heat pipe section, using the heat transferred from the
precool heat pipe.

This entire process of pre-cooling and reheating is accomplished with no additional energy use. The result is an air conditioning
system with superior ability to remove moisture.

Heat Pipe For Dehumidification

2 - Heat pipes for recovery function may be described as having two sections, each of them installed in an air steams, side by side
or staked depending on the unit arrangement. When warm air passes over the heat pipes the warm air will be cooled down and
the refrigerant vaporizes; carrying heat to the second section while the relatively cold air in the cold air stream will condense the
refrigerant which will return back to the first part by gravity, then this cycle repeated.

Heat Pipe For Heat Recovery

20
HUMIDIFIERS

1 - Steam humidifiers

Zamil TW-series Air handling units can be equipped with a


self-contained humidifier, Which is electronically controlled to
sense and control the humidity.

The steam is generated in a polypropylene cylinder mounted


onto the outside of the humidifier section within a special enclo-
sure. A stainless steel distributor suitable in length passes
through the unit casing to inject steam in the air stream to reach
the needed humidity conditions.

Steam Humidifier Steam Distributor


Air

2 - Air Washers
Zamil air handling units can be equipped with air washer section which mainly serve for adiabatic cooling, humidifying and air
washing.

Air washer is a section in which the air flow is brought in contact with a large quantity of sprayed water. Depending on the condi-
tion of the circulating water, air washers are forming a basic part of air conditioning plants which easily combine washing, humidi-
fying and cooling of air.

While water evaporates on the surfaces of large drops and impurities contained in the air are washed out, extremely small droplets
(Superfine aerosols) can be fully absorbed by the air and they are designed to avoid the formation of superfine aerosols as far as
possible.

Air Washer

3 - Adiabatic Cooling/high pressure humidification


Zamil adiabatic cooling/high pressure humidification is a
system which is ideal for the humidification of medium/
large industrial environments and large volumes of air.

The system atomize water into very fine water particles


that evaporate easily in the air, humidifying and cooling it.
Evaporation occurs by “absorbing” sensible heat from the
air which becomes colder and more humid.

Along with this system an electronic controller is provided


to manage the supply of water and compressed air to the
nozzles to maintain the humidity/ temperature set point.

21
DIFFUSER PLATE
The diffuser plate is a perforated, heavy gauge galvanized steel plate provided
to shutter the air and distribute it uniformly across the section.

The use of diffuser plate becomes essential when a functionally sensitive


section - like HEPA filters or an energy wheel, is facing high face velocities.

Diffuser plate

SOUND ATTENUATOR
Sound attenuators can be used where a significant reduction to fan noise is
needed. Attenuators can be provided in the supply and/or return air side with
different lengths to provide a range of attenuator performances. Sound attenua-
tors casings are produced with G-90 galvanized steel sheets formed and lock
formed seams with a sealant.

The acoustic infill materials are inert, non-flammable, non-hygroscopic and will
not sustain vermin or fungus and odorless, the infill has a glass tissue facing and
is contained behind galvanized perforated metal, which prevent infill material
damage and fiber erosion up. To reduce the pressure loss and regenerated noise,
the splitters are radiused at both ends.
Sound Attenuators

DRIP ELIMINATOR
To avoid water carry-over in humid areas or when the velocity of air across the cooling coils is high, drip eliminators are provided.

Other than in these two cases, the drip eliminator is given as an option upon the request of the customer. Drip eliminator blades
are PVC blades encased within a galvanized steel frame. The blades are designed to completely prevent water carry-over with low
pressure drop. The drip eliminator is commonly fixed directly to the coil casing, however, separate section for the drip eliminator
can be provided upon request.

Assembled Drip Eliminator

22
BULK HEAD LIGHT
Zamil TW units can be equipped with bulk head lights as an option in
different sections like fan section or filter section, to provide enough
lightening to watch the function of the component or to facilitate any
service or maintenance activities.

Head Light

ULTRA VIOLET LIGHTS


Light in a broad sense can be divided in visible, infra-red and ultraviolet rays.

The germicidal effects of the UV-C radiation destroy DNA of Bacteria, Viruses, Spores, Fungi, Moulds and Mites avoiding their
growth and proliferation.

UVGI technology is a physic disinfection method with a great costs/benefits ratio UV-C (short-wave) from 100 to 280 nm. The
absorption of a UV photon by the DNA of microorganisms causes a destruction of a link in the DNA chain, and consequently the
inhibition of DNA replication. UV Lights can be provided upon request.

FEATURE AVAILABLE
EMISSION LEVEL
BUILT-IN POWER SUPPLY
BI-PIN lamp
AERODYNAMIC REFLECTOR
MIRROR BRIGHT REFLECTOR
MAP-PATHOGEN-TIME
IP55 PROTECTION
UL CERTIFICATE
ready-to-plug
SERIAL CONNECTORS
A.H.U. WALLS FIXTURE
A.H.U. COIL FIXTURE
IN-DUCT INSTALLATION
PARALLEL TO AIR FLOW
IN-DUCT INSTALLATION
PERPENDICULAR TO AIRFLOW

23
POWER PANELS

Starting Panel from Zamil


The optional Starter panel design is equivalent to IP55 with hinged door / access panel for easy access. Internal power and control
wiring is neatly routed, properly anchored and all wires are identified with cable markers as per NEC standard applicable to HVAC
units. All components fixed in the starter panel are UL approved.

• Direct on Line
• Star delta Starting
• VFD Panel
• Panel with Volt Free Contacts
a. Start / Stop Command
b. Run & Trip Indication Status

DSW (Disconnect switch) DOL VFD

Y-Delta E BOX

24
VARIABLE FREQUENCY DRIVERS

Variable Frequency Drives or Frequency Inverters as they are sometimes called are installed on Fan motors to vary the fan speed
in applications where the supply CFM is not constant and must be varied. In applications where Variable Air Volume boxes (VAV’s),
for example, are installed throughout the occupied space, the total CFM discharged by the Air Handling Unit will depend on the
demand requested by the VAV boxes. When the space is satisfied and the VAV box closes its damper, the total required CFM will
be reduced. To avoid over pressurizing the ducting, a Variable Frequency Drive is installed to reduce the speed of the fan and
hence reduce the total CFM discharged by the unit.

A full range of Variable Frequency Drives from 1.1 kW up to 90 kW in voltage ratings of (220V-3Phase, 380/460V-3phase).

The drives are easy to configure and operate with built-in Proportional, Integral, Derivative (PID) control. Equipped with Dynamic
Brake Control, Torque Control, Dual Motor Control and Threshold Comparator. Intelligent Thermal Management functionality to
reduce tripping and motor noise.

25
FAN ARRAY

OVERVIEW
FAN ARRAY in custom air handling units using an array of smaller fans instead of a traditional single large fan. This reduces the
air-handling dimension, and easy for maintenance, lower noise and saves energy. This allow fans and motors to be fully loaded
Air flow rates can be varied through use of a variable speed drive and by using controller.

Fan arrays can be placed close to coils and filters, and still provide even airflow:

• No belts
• No pulleys
• Less maintenance
• Less lubrication required
• Eliminate belt drive losses

CONTROL
Fan system provided with variable frequency drive (VFD).

REDUNDANCY and NO FAIL MODE


Multiple fans running together, if one failed then the speed of the
remaining fans will be increased to compensate. Additionally, Fan Array
can be provided with stand-by extra fan to run in place of failed fan.

26
HYGIENIC UNITS

Zamil hygienic air-handling units incorporate the state-of-the-art technology to provide refrigeration and meet filtration, pressur-
ization, condensation control and sanitization standards required by the critical applications where ultra clean air needed.

The units are custom engineered to produce the specified psychometric conditions and to achieve the environmental design
criteria for the area being served.

Taking economic issues taken into consideration, our design engineers can design hygienic air handling units methodically and
logically to suit the ultra clean application requirements.

27
Hygienic air handling units compliance with hygienic requirements accordingto DIN 1946-4, VDI 6022-1, VDI 3803-1, and DIN EN
13053 with following main product features:

- Smooth inside surface design.


- Air tight dampers.
- Light and inspection windows in desired function modules.
- Special joint sealing with silicon-free sealants.

Zamil hygienic air handling units are the answer when clean conditioned air is needed for today’s hygienic applications like hospi-
tals, pharmaceutical sectors, food factories requirements, etc.

28
AIR HANDLING UNITS SELECTION SOFTWARE "AirCalc++"
The innovative air handling unit selection software "AirCalc++" is a powerful tool for consultants, sales and application engineers.
To activate this software and after the user enters the design parameters that reflect the customer requirements or consultants
guidelines "AirCalc++" will then configure and calculate within a very short period the air handling unit equipment. If any data
entered doesn’t correspond with the various certification standards and norms, "AirCalc++" will reject it via an error message.

"AirCalc++" is thus able to provide the security of a planning procedure that is correct in every respect.

The program performs section by section technical verification and selection until the whole unit is done. In each section, many
options related to that particular section can be selected to satisfy any air handling unit specifications.

Main Unit Input Data Screen

Unit Design Editor

Main Unit Input Data Screen

29
Once completed, AirCalc++ can generate all technical reports related to the newly created Air Handling Unit:

Main Unit Input Data Screen

Drawing Report

Psychometric Chart

30
Fan operation area and operating point Chart

Noise Level Chart

Weight Report

31
SOME AIR HANDLING UNITS POSSIBLE CONFIGURATION

Supply, Simple Units

Supply, Exhaust Inline Units

Stacked Unit with Energy Wheel

32
Stacked Unit with Plate Heat Exchanger

Side by side Unit

Stand-by duty Fan

33
Custom AHU Belt Driven Plenum Fan Double Deck Supply with Single Fan

Dehumidification AHU Twin Wheels AHU

34
REFERENCE PROJECTS

King Abdullah Sports City

Arar Domestic Airport King Faisal Specialist Hospital

Sadara Chemical Company Fairmont Hotel

35
REFERENCE PROJECTS

Princess Noura bint Abdulrahman University

Holy Haram Expansion Al Othaim Mall

Bahrain Financial Harbour

36
‫وﺣﺪات ﻣﻌﺎﻟﺠﻪ اﻟﻬﻮاء‬
‫اﻟﺰاﻣﻞ ﻟﻠﻤﻜﻴﻔﺎت‬
‫اﻟﻤﻮاﺻﻔﺎت اﻟﻤﻄﺎﺑﻘﻪ‬
‫اﻟﺠﻤﻌﻴﺔ اﻟﻮﻃﻨﻴﺔ ﻟﻠﻮﻗﺎﻳﺔ ﻣﻦ اﻟﺤﺮﻳﻖ )‪(NFPA‬‬ ‫ﻣﻌﻬﺪ ﺗﻜﻴﻴﻒ اﻟﻬﻮاء واﻟﺘﺒﺮﻳﺪ )‪(AHRI‬‬
‫‪ NFPA 90A‬اﻟﻤﻮاﺻﻔﺎت اﻟﻘﻴﺎﺳﻴﺔ ﻟﺘﺮﻛﻴﺐ أﻧﻈﻤﺔ ﺗﻜﻴﻴﻒ اﻟﻬﻮاء واﻟﺘﻬﻮﻳﺔ‬ ‫‪ AHRI 410‬ﻣﻠﻔﺎت ﺗﺴﺨﻴﻦ اﻟﻬﻮاء وﺗﺒﺮﻳﺪ اﻟﻬﻮاء ذات اﻟﺴﺮﻳﺎن اﻟﻘﺴﺮي‬
‫‪ AHRI 430‬ﻣﺮاوح ﺗﻜﻴﻴﻒ اﻟﻬﻮاء اﻟﻤﺮﻛﺰﻳﺔ‬

‫ﺟﻤﻌﻴﺔ ﺣﺮﻛﺔ اﻟﻬﻮاء واﻟﺘﺤﻜﻢ ﺑﻪ )‪(AMCA‬‬


‫‪ AMCA 300‬ﻃﺮﻳﻘﺔ ﻏﺮﻓﺔ اﻟﺘﺮدﻳﺪ ﻻﺧﺘﺒﺎر ﺷﺪة اﻟﺼﻮت ﻓﻲ اﻟﻤﺮاوح‬ ‫وﺗﻜﻴﻴﻒ اﻟﻬﻮاء )‪(ASHRAE‬‬
‫‪ AMCA 500‬ﻃﺮق اﺧﺘﺒﺎر اﻟﻠﻮﻓﺮات واﻟﺨﺎﻣﺪات واﻟﻐﺎﻟﻘﺎت‬ ‫‪ASHRAE 51‬‬
‫‪ASHRAE 52‬‬
‫‪ASHRAE 62.1‬‬
‫‪ASHRAE 90.1‬‬

‫اﻟﺸﻬﺎدات اﻟﻤﻄﺎﺑﻘﻪ ﻟﻠﻤﻮاﺛﻴﻖ اﻟﺘﺎﻟﻴﻪ ‪:‬‬


‫‪UL 1995‬‬
‫‪Eurovent 1886‬‬
‫‪Eurovent 13053‬‬
‫‪Din1946-4‬‬
‫‪VDI6022‬‬
‫‪AHRI 430‬‬
‫‪AHRI 410‬‬

‫اﻟﻐﻼف واﻟﻬﻴﻜﻞ اﻟﺨﺎرﺟﻲ‬


‫ﻳﻜﻮن اﻟﻐﻼف ﻣﺼﻨﻮع ﻣﻦ أﻟﻮاح ﻣﻦ اﻟﺤﺪﻳﺪ اﻟﻤﺠﻠﻔﻦ ﺑﺴﻤﺎﻛﺔ ﻻ ﺗﻘﻞ ﻋﻦ ‪ 0.75‬ﻣﻢ وﻳﺼﻤﻢ اﻟﻐﻼف ﻟﻴﺘﺤﻤﻞ ﺿﻐﻂ اﻟﺘﺸﻐﻴﻞ اﻟﻤﺤﺪد‪ ،‬ﻛﻤﺎ وﺗﻌﺰل‬
‫ﻣﻦ اﻟﺪاﺧﻞ ﺻﻮﺗﻴ ًﺎ وﺣﺮارﻳﺎ ﺑﺎﻟﻤﺼﻨﻊ ﺑﻌﺎزل ﺻﻮف ﺻﺨﺮي ‪ 48 kg/m3‬ﺣﺴﺐ ‪ .SMACNA standard ASTM-C-423 and NFPA90A and 90B standards‬ﻳﻜﻮن‬
‫ﻣﻦ اﻟﺪاﺧﻞ ﻣﺼﻨﻮع ﻣﻦ اﻟﺤﺪﻳﺪ اﻟﻤﺠﻠﻔﻦ ﺑﺴﻤﺎﻛﻪ ﻋﻠﻰ اﻻﻗﻞ ‪ 0.7 mm‬وﺗﻜﻮن‬
‫ﺳﻤﺎﻛﻪ ‪ 30 Panels‬ﻣﻢ او ‪ 50‬ﻣﻢ ﺣﺴﺐ اﻟﻄﻠﺐ‪.‬‬

‫ﺗﻜﻮن ﺣﺴﺐ ‪DIN 24166 accuracy class 1, ISO 5801, BS 848- Part 1, and AMCA 210 standards‬‬
‫ﺑﺎﻟﻤﺮوﺣﺔ ﺑﻮاﺳﻄﺔ ﺳﻴﺮ ﻣﺠﻬﺰ ﺑﻮاق‪ .‬ﺗﺼﻤﻢ ﺳﻴﻮر ﻧﻘﻞ اﻟﺤﺮﻛﺔ ﺑﺤﻴﺚ ﻻ ﻳﻘﻞ ﺗﺤﻤﻠﻬﺎ ﻋﻦ ‪ 150%‬ﻣﻦ ﻗﺪرة اﻟﻤﺤﺮك اﻟﻤﺘﺼﻞ ﺑﻬﺎ‪.‬‬

‫اﻟﺘﺸﺤﻴﻢ‪.‬‬

‫اﻟﻤﺤﺮﻛﺎت اﻟﻜﻬﺮﺑﺎﺋﻴﺔ‬
‫ﺗﻜﻮن اﻟﻤﺤﺮﻛﺎت اﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻃﺒﻘ ًﺎ ﻟﻠﻤﻮاﺻﻔﺎت اﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻣﻦ ﻧﻮع ‪.TEFC, IP55 , class F insulation and class B temperature rise‬‬
‫ﻳﺮﻛﺐ اﻟﻤﺤﺮك ﻋﻠﻰ ﻧﻔﺲ اﻟﻘﺎﻋﺪة اﻟﻤﺮﻛﺐ ﻋﻠﻴﻬﺎ اﻟﻤﺮوﺣﺔ وﺗﻜﻮن ﻗﺎﻋﺪة‬
‫اﻟﻤﺤﺮك ﻗﺎﺑﻠﺔ ﻟﻠﻀﺒﻂ‪.‬‬

‫اﻟﻤﻠﻔﺎت‬
‫ﻳﺮﻛﺐ اﻟﻤﻠﻒ ﻋﻠﻰ ﺣﻮض ﻟﺘﺠﻤﻴﻊ ﻣﻴﺎه اﻟﺘﻜﺜﻴﻒ وﻳﻤﺘﺪ ﺣﺘﻰ اﻟﻤﻨﻄﻘﺔ اﻟﺘﻲ ﻳﺘﻠﻘﻰ ﻓﻴﻬﺎ اﻟﻤﻴﺎه اﻟﻤﻜﺜﻔﺔ ﻣﻦ اﻟﻤﻠﻔﺎت‪ .‬ﻳﺠﺐ ﺗﺄﻣﻴﻦ وﺻﻠﺔ ﺗﺼﺮﻳﻒ واﺣﺪة ﻋﻠﻰ‬

‫‪37‬‬
‫ﻣﻠﻒ اﻟﺘﺴﺨﻴﻦ اﻟﻜﻬﺮﺑﺎﺋﻲ‬
‫ﻳﺘﺄﻟﻒ ﻣﻠﻒ اﻟﺘﺴﺨﻴﻦ اﻟﻜﻬﺮﺑﺎﺋﻲ ﻣﻦ ﺳﻠﻚ ﻣﻘﺎوﻣﺔ‬
‫وﻳﺘﻢ إﻳﺼﺎﻟﻪ ﺑﺘﻴﺎر ﻛﻬﺮﺑﺎﺋﻲ‪ .‬ﻳﻜﻮن ﺳﻠﻚ اﻟﻤﻘﺎوﻣﺔ إﻣﺎ ﻋﺎرﻳ ًﺎ أو ﻣﻐﻠﻔ ًﺎ‬
‫‪.‬ﺗﻜﻮن اﻟﻮﺻﻼت ﺑﻴﻦ اﻟﻤﻠﻒ اﻟﻜﻬﺮﺑﺎﺋﻲ وﺻﻨﺪوق اﻟﻮﺻﻞ ﻣﻦ ﻣﺎدة ﻣﻘﺎوﻣﺔ ﻟﻠﺤﺮارة )ﺳﻴﺮاﻣﻴﻚ أو ﻣﻴﻜﺎ(‬
‫‪.‬ﺗﺠﻬﺰ ﻣﻠﻔﺎت اﻟﺘﺴﺨﻴﻦ ﺑﺄﺑﻮاب ﻛﺸﻒ وﻋﺎزل ﻣﻘﺎوم ﻟﻠﺤﺮﻳﻖ‬
‫ﻳﺤﺘﻮي ﻋﻠﻰ ﺣﻤﺎﻳﺎت اوﺗﻮﻣﺎﺗﻴﻜﻴﻪ وﻳﺪﻳﻮﻳﻪ‬
‫ﻳﺤﺘﻮي ﻋﻠﻰ ﻣﻔﺘﺎح ﻓﺼﻞ ﻫﻮاﺋﻲ )‪(air flow switch‬‬
‫ﻳﺤﺘﻮي ﻋﻠﻰ اﻟﻘﻄﻊ اﻟﻜﻬﺮﺑﺎﺋﻴﻪ ﻟﺘﺸﻐﻴﻞ اﻟﺴﺨﺎن)‪(contactors‬‬

‫ﺻﻨﺎدﻳﻖ اﻟﺨﻠﻂ‬
‫ﺗﺼﻨﻊ ﺻﻨﺎدﻳﻖ اﻟﺨﻠﻂ وﺗﻜﻮن ﻛﻤﺎ ﻳﻠﻲ‪ :‬ﺑﺤﻴﺚ ﺗﺆﻣﻦ درﺟﺔ ﻛﻔﺎءة ﻋﺎﻟﻴﺔ ﻟﺨﻠﻂ ﺗﻴﺎرﻳﻦ ﻣﻦ اﻟﻬﻮاء ﻣﺨﺘﻠﻔﻴﻦ ﻓﻲ درﺟﺔ اﻟﺤﺮارة‪.‬‬
‫ﺗﺠﻬﺰ ﺑﺠﻠﺐ ﻟﺘﺮﻛﻴﺐ ﻣﺠﺮى ﻫﻮاء إذا ﻃﻠﺐ ذﻟﻚ ﻓﻲ ﻣﺴﺘﻨﺪات اﻟﻤﺸﺮوع‪.‬‬

‫ﻣﺮﺷﺤﺎت اﻟﻬﻮاء‬

‫اﻟﻤﺮﺷﺤﺎت ذات اﻟﻜﻔﺎءة اﻟﻌﺎﻟﻴﺔ‪/‬اﻟﻤﺮﺷﺤﺎت اﻟﻜﻴﺴﻴﺔ ‪bag filters‬‬

‫ﻣﻘﺎﻳﻴﺲ ﻣﺮﺷﺤﺎت اﻟﻬﻮاء‬


‫ﻳﺠﺐ ﺗﺄﻣﻴﻦ ﻣﻘﻴﺎس ﻣﺮﺷﺢ ﻫﻮاء ﻣﻦ اﻟﻤﻘﻴﺎﺳﻴﻦ اﻟﺘﺎﻟﻴﻴﻦ‪:‬‬
‫ﻣﻘﻴﺎس ﻣﺮﺷﺢ ﻫﻮاء ﻣﻦ اﻟﻨﻮع اﻟﺮﻗﻲ ﻟﻜﻞ ﻣﺠﻤﻮﻋﺔ ﻣﺮﺷﺤﺎت ﻣﺠﻬﺰ ﺑﻘﺮص ﻣﺪرج وﻣﺆﺷﺮ وﻳﻜﻮن اﻟﺘﺪرﻳﺞ ﻣﻦ ﺻﻔﺮ إﻟﻰ ‪ 500‬ﺑﺎﺳﻜﺎل‪.‬‬
‫ﻣﻘﻴﺎس ﻣﺮﺷﺢ ﻫﻮاء ﻣﻦ اﻟﻨﻮع اﻟﻤﺎﻧﻮﻣﺘﺮي ﻟﻜﻞ ﻣﺠﻤﻮﻋﺔ ﻣﺮﺷﺤﺎت وﻳﻜﻮن اﻟﺘﺪرﻳﺞ ﻣﻦ ﺻﻔﺮ إﻟﻰ ‪ 500‬ﺑﺎﺳﻜﺎل‪.‬‬

‫ﻣﺮﻃﺒﺎت اﻟﻬﻮاء‬
‫اﻟﻤﺮﻃﺒﺎت اﻟﺘﻲ ﺗﻌﻤﻞ ﺑﺎﻟﺒﺨﺎر‬

‫‪38‬‬
Zamil Central Air Conditioners
P.O. Box 41015, Dammam 31521, Kingdom of Saudi Arabia
Tel.: +966 13 812 5400 Fax: +966 13 812 1977
Customer Service: 92 0000 468

@zamilac zamilac.com

PL-AP-TWH-21-2M-E 20Z1
High Efficiency
Condensing Units
Models CTXN022-220
22 to 220 TR
60 HZ
Company Profile
Zamil Air Conditioners, a sector business of Zamil Industrial, is the largest manufacturer of air conditioners in the Middle East.
The company manufactures and markets the complete range of air conditioners, from room air conditioners to packaged units
to large chillers for residential, commercial and industrial applications.

Founded in 1974, Zamil Air Conditioners was one of the first air conditioning companies to be established in Saudi Arabia. Today,
the company produces about one million air conditioners per year. Aside from its head office and two manufacturing plants in
Dammam, Saudi Arabia, the company also has production facilities in India. The company supplies air conditioning products to
over 55 countries across the world, with its major markets located in the GCC, Middle East, North Africa, Europe and Asia.

Zamil Air Conditioners is the first Middle Eastern company to achieve the prestigious AHRI certification (Air-Conditioning, Heating
and Refrigeration Institute, USA). The company is also 9001:2015 Quality Management System, ISO14001:2015 (Environment
Management) and OHSAS 18001:2007 (Occupational Safety) certified with many of its products tested and approved by
Eurovent, AHRI, SASO, ESMA & UL.

Companies:
• Zamil Air Conditioners & Home Appliances Co. (L.L.C),
• Zamil Central Air Conditioners Co. (L.L.C),
• Zamil Air Conditioning and Refrigeration Services Co. (L.L.C)

Manufacturing Facilities:
The company has two factories in Saudi Arabia located in the 1st and 2nd Industrial Cities of Dammam. The company also has
production facilities in India.

Annual Production Capacity:


• Window Air Conditioners: 700,000
• Mini-Split Systems: 300,000
• Central Air Conditioners: 50,000

Core Values

VISION:
To be the partner-of-choice COMMUNITY &
for environmental control HONESTY &
PROSPERITY
INTEGRITY
solutions that are based We believe in mutual prosperity.
We believe goodwill and good
on lifetime value reputation are core to our business.
We aspire to thrive in business
while bringing progress and
We uphold honesty, integrity, prosperity to our own people and
professionalism and a high level of communities where we operate.
business ethics. We observe prudence Our culture, our ideas, our
and fairness in dealing with our practices, our environmental
MISSION: stakeholders. concern, and our teamwork lead
us to create superior values for
To make air-conditioning people and communities
Affordable, Reliable and around us.

Energy-Efficient
VALUES
LEADERSHIP &
CUSTOMER & PRUDENCE
EXCELLENCE We cultivate talent and leadership
to create sound business
We are diligent about understanding solutions, to best meet our
and fulfilling our customers’ needs. customer needs, and to develop
We strive to please our customers with markets, people and shareholder
excellence in quality and services. We value. We do so by optimizing use
listen to our customers and “go the of funds, resources, materials, and
extra mile” to satisfy them. INNOVATION & technologies. We build prudence
CHANGE and cost-effectiveness in our
leadership culture passing on
We are passionate about
benefits to our customers.
meaningful innovation. We are a
learning organization. We learn
from our experiences and global
best practices, and we innovate to
create leading local solutions
leveraging on world class
knowledge. We embrace positive
change brought forth by innovation
and aspirations to grow our
business.
Research & Development
Zamil Air Conditioners boasts of its state-of-the-art testing facilities – “Ikhtebar” which is a third party air conditioner testing
facility built by Intertek Testing Services (ITS) and certified by Electrical Testing Laboratories (ETL). Equipped to perform a wide
range of tests under many recognized local and international standards including: AHRI 210/240; AHRI 410; AHRI 310/380; AHRI
430; AHRI 440; AHRI 340/360; ASHRAE 116; ASHRAE 37;ASHRAE 41.1; AHRI 365; ISO 5151; SASO 385; SASO 2682; UL 1995
and AHRI 550/590.

Features:
• Performance test of whole range of air conditioners – consumer as well as commercial, in capacities from ½ TR to 600 TR
• Support research and development initiatives through implementation of state of the art computational programs.
• Test products for conformance to local and international certifications and standards such as SASO, AHRI, UL, AHAM etc.

Facility:
• Calorimetric Test Rooms
• Psychrometric Test Rooms
• Chiller Test Facility
• Sound Lab
• Reliability Test Facility

Parent Company
Headquartered in Dammam, Saudi Arabia, Zamil Industrial Investment Company ('Zamil Industrial') is a premier business group
engaged in the design, engineering and manufacturing of innovative products and solutions for the global building and construc-
tion industry.

Zamil Industrial offers a wide range of products and services in four sectors viz. HVAC, Steel, Insulation and Concrete. Zamil
Industrial’s key products and services include: air conditioning systems, pre-engineered steel buildings, steel structures, telecom
and transmission towers, process equipment, precast concrete building products, insulation products, installation and mainte-
nance of HVAC Solutions, and solar power solutions.

The company employs more than 15,500 people and derives about 25% of its revenues from outside Saudi Arabia. Zamil Indus-
trial products are sold in more than 90 countries around the globe, and the company operates manufacturing facilities in Saudi
Arabia, United Arab Emirates, Egypt, India and Vietnam. Zamil Industrial shares are actively traded on the Saudi Stock Exchange
(Tadawul).
INDEX

Contents Page

Model decoding ............................................................................................................. 2

Standard feature/option ................................................................................................. 3

Feature/options ........................................................................................................... 4-7

Standard specification .............................................................................................. 8-12

Optional items ......................................................................................................... 13-14

Physical data ........................................................................................................... 15-18

Performance data ................................................................................................... 19-20

Electrical data ............................................................................................................... 21

Refrigeration Circuit ................................................................................................ 22-26

Dimensions ............................................................................................................. 27-39

Lifting and rigging instruction ..................................................................................40-42

Installion clearance ................................................................................................. 43-45

Typical wiring diagram ............................................................................................ 46-47

Schematic diagram ................................................................................................. 48-53

Power cable entry ......................................................................................................... 54

Load distribution & mounting points ....................................................................... 55-57

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

1
CTXN MODEL DECODING- 60 HZ
1,2,3 4,5,6 7 8 9 10 11 12 13 14 15 16 17
NOMINAL
ELECTRICAL KITS KITS
COOLING SAFETY REFRIGERATION CIRCUIT REFRIGERANT CHARGE
BASIC CAPACITY VERSION NUMBER SUPPLY REFRIGERATION CIRCUIT TYPE CONDENSER COIL ELECTRICAL MECHANICAL Special electrical options GENERAL OPTIONS
AGENCY OPTIONS & Enclosure option
TONS (V-Ph-Hz) OPTIONS OPTIONS

CTX 022 N: N Version S: STD H : 230-3-60 A : STD OPTIONS A : ALUMINIUM FIN (14 FFPI) (1) A-STD OPTIONS (2) A-STD OPTIONS (4) A : STD A: STANDERD OPTIONS
D : DUAL SCROLL COMPRESSORS
A : HOLDING CHARGE (5)
(CTX022N-CTX035N) B :MUIT-STAG
025 HIGH EFFICIENCY E: ETL Listed B : PRE COATED ALUMINIUM FIN (14 FPI)
CONDENSING ELECTRONICTHERMOSTAE
B: TRAFOILTE LABELS FOR CONTROL BOX
UNIT M- REPLACEABLE CORE FILTER DRIER &
030 CONDENSING M : 400 - 3 - 60 B :COMPRESSOR SERVICE C : COPPER FIN (12 FPI) V- VOLT FREE CONTACT (3)
SHUT-OFF VALVE, F : FULLY CHARGE D : NEMA 4X ELECTRICAL PANEL
VALVES
(R-410A) 035 SERIES (4 WIRE) Q : QUADRUPLE SCROLL C: COMP CIRCUIT BREAKER.
COMPRESSORS (CTX040N-CTX050N
& CTX090N-CTX110N) D : ALUMINIUM FIN WITH ANTI CORROSIVE COATING P-PRESSURE GAUGES (SUCTION & G : CURRENT TRANSFORMAERS
040 F: 460 - 3 - 60 D: NON FUSED DISCONNECT SWITCH F: ADDITIONAL CORE FILTER DRIER
(14 FPI) DISCHARGE) FOR COMP.

E : COPPER FIN WITH ANTI CORROSIVE COATING (12 E-CIRCUIT BREAKER FOR EACH
045 H- HOT GAS BYPASS H - B + D COMBO I : SPRING ISOLATOR UNDER THE UNIT
T : SIX SCROLL COMPRESSORS C: HOT GAS MUFFLER FPI) CONDENSER FAN
(CTX060N-CTX070N & CTX130N-
050 CTX160N) R - CONDENSER PRESSURE RELIEF VALVE K - B + G COMBO E: B + F COMBO
G: HOLDING CHARGE &
060 F : ALUMINIUM FIN (12 FPI) P-PUMP DOWN SOLENOID VALVE C - H + P COMBO FULL GUARD H: B + I COMBO
CONDENSER
070 W : EIGHT SCROLL COMPRESSORS I - H + R COMBO N - D + G COMBO M: F + I COMBO
D B&C COMBO
(CTX180N-CTX220N)
080 G : PRE COATED ALUMINIUM FIN (12 FPI) F: V+C COMBO G - R + P COMBO S - B + D + G COMBO
O: B + F + I COMBO
090 W: V+D COMBO J - M + P COMBO H: FULLY CHARGE &
FULL GUARD
I : ALUMINIUM FIN WITH ANTI CORROSIVE COATING (12 N - M + H COMBO
110 FPI) I: V+P COMBO K- M + R COMBO
CONDENSER

130 M: V+E COMBO

160 Q - M + H +R COMBO
M : MICROCHANLE CONDENSER COIL (MCHX)
180 N - V + C + P COMBO T - M + P +H COMBO

220 Q: V+C+D COMBO U- M +P+R COMBO

N- MICROCHANLE CONDENSER COIL WITH ANTI O- H +P+R COMBO


CORROSIVE COATING R: V+C+E COMBO

W- M+P+ H+ R COMBO

U: V+D+P COMBO

O:V+C+D+E+P COMBO

NOTES:

1) ALUMINUM FINS WITH 14 FPI IS STANDARD FOR CTXN SERIES, OPTIONAL CU FINS WITH 12 FPI

2) STANDARD ELECTRICAL OPTIONS CONTAIN UNDER VOLTAGE MONITOR (UVM) , FIXED HIGH LOW PRESSURE SWITCHES & FAN CYCLING SWITCH

3) A COMBINATION OF VOLT FREE CONTACT SIGNAL TO INDICATE THE FOLLOWING 1. UNIT ON 2. INDIVIDUAL COMPRESSOR, RUN & TRIP 3. UNIT TRIP (WHEN ALL COMPRESSORS HAVE TRIPPED)

4) SCROLL COMPRESSOR STD OPTION CONTAIN SEALED TYPE FILTER DRIER AND SIGHT GLASS.

5) AS A STANDARD, ALL UNITS ARE SUPPLIED WITH HOLDING CHARGE ONLY.


STANDARD FEATURES/OPTIONS

STANDARD OPTIONS
DESCRIPTION
FEATURES (FACTORY INSTALLED)
Scroll compressors
Compressor circuit breakers
Compressor with external overload protection
Compressor with serivce valves
Condenser fan - direct drive, propeller type & fan Guard
Condenser motor circuit breakers
Condenser motor with external overload protection
Aluminum fin condenser coils
Copper fin condenser coils
Microchannel condenser Coils-MCHX
Anti-corrosive coating on evpaorator coils or condenser Coils
Unit full guard
Sight glass (moisture indicator)
Sealed type filter drier
Replaceable core filter drier
Hot gas bypass for main circuit
Condenser pressure relief valve
Pressure gauges
Pump down solenoid valve
High/low pressure switch (Fixed type)
Fan cycling switch ( Fixed type)
Discharge Gas Muffler
Discharge Gas Sensor
UVM (Under Voltage Monitor)
Volt free contact
Non-fused disconnect switch
Multiple stage thermostat

3
FEATURES AND BENEFITS

* R-410A environmentally friendly refrigerant (HFC refrigerant).


* Nominal gross cooling capacity from 22.0 TR up to 220.0 TR for 60Hz.
* EER meets ASHRAE 90.1 and SASO- 2874 standards.
* Independent refrigeration circuits with scroll compressors for efficient cooling process.
* Unit’s cooling operating range from 55ºF (12.7ºC) up to (52ºC) 125.6ºF ambient temperature.
* Sealed type filter drier kit and sight glass (moisture indicator) as standard.
* Copper tubes and aluminum fins for condenser coils.
* Microchannel condenser coil (MCHX) is available as an option for all models.
* Compact unit design with smaller unit footprint at lower installation cost.
* Rigging holes in base rail for easy lifting & Installation.
* High-pressure switch and low-pressure switch protection.
* Fan cycling switch as standard.
* Single power point connection to reduce filed wiring cost.
* Easy access to all components for excellent serviceability.
* Condenser coil is provided with Integral sub-cooling circuits to increase overall unit efficiency.
* High efficient permanently lubricated condenser fan motors (TEAO) with class 'F' insulation.
* Microprocessor controller with 220V control voltage protected with control fuse.
* Quality assurance according to ISO 9001:2015, which guarantees high and constant product quality.

COOLING RATING TABLE

COOLING
MODEL No. EER
STAGES
CTX022N 2 10.5
CTX025N 2 10.5
CTX030N 2 10.5
CTX035N 4 10.5
CTX040N 4 10.5
CTX045N 4 10.5
CTX050N 4 10.5
CTX060N 4 10.5
CTX070N 6 10.5
CTX080N 6 10.5
CTX090N 4 10.5
CTX110N 4 10.5
CTX130N 6 10.5
CTX160N 6 10.5
CTX180N 8 10.5
CTX 220N 8 10.5
NOTES:
1. Rated in accordance with AHRI 365 & SASO2874 Standards
2. Ratings are based on: 95OF DB Outdoor (Ambient) Temperature & 45OF Saturated Suction Temperature .
3. EER : Energy Efficiency Ratio.

4
ZAMIL AIR COOLED CONDENSING UNITS

The CTXN Series air cooled condensing units from Zamil Air Conditioners are produced in an
ISO 9001:2015 certified facility. They are designed to provide engineering excellence on com-
fort air conditioning and industrial cooling with a superior combination of high energy efficien-
cy & energy saving, high performance, application flexibility, ease of service & maintenance
and the ability to withstand extreme ambient temperatures found in the climate of the Gulf
region. The CTXN series are consists of scroll compressor(s), cooling coil, condenser coil,
fans, control wiring and inter connecting piping. These units are suitable for mounting on the
roof or ground with easy installation and excellent serviceability. The unit features an integral
weather resistant control panel, ready for field connection to utilities and Indoor AHU.

CTXN035N WITH OPTIONAL FULL GUARD

The CTXN series units are designed to use ozone friendly HFC R-410A refrigerant. HFC
R-410A is highly efficient thermodynamic proprieties, created to serve as one of the key sub-
stitutes for HCFC based refrigerants. R-410A is environmentally safer for long term use, no
chlorine and does not contribute to Ozone depletion. There is no phasing out and no replace-
ment costs for the life of the equipment.

5
R-410A CHARACTERISTICS

* Ozone friendly- HFC compound, No Chlorine & have zero ODP.


* R-410A has a significantly higher liquid heat transfer coefficient than R-22.
* R-410A has lower density than R-22.
* Higher Pressure Range, 50% to 70% higher than R-22.
* It’s a Blended Refrigerant (50% R-32 and 50% R-125).
* This blend is a Near-Azeotrope thus; it acts very much like a single compound refrigerant.
* No Fractionation problems.
* Temperature glide less than 0.2°F over it’s operating range.
* Critical temperature is 161°F.
* Critical pressure is 700 Psig.
* R-410A utilizes Polyol Ester (POE) based oils.
* R-410A cylinders are rose colored.
* Environmentally safer for long-term usage.
* No phase out & no replacement cost.
* Low toxicity & non-flammable.
* Compatible with steel, copper, aluminum and brass.

6
SCROLL COMPRESSORS
The scroll compressors are consists of two involutes or Archimedean spirals. One spiral is positioned inside the other to form
a series of crescent-shaped pockets. During compression the upper spiral remains stationary and the lower one, being eccen-
trically mounted on the drive shaft, describes an orbital rather than a simple rotary motion.

Compressor working principle Scroll compressor

1. Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. A refrigerant enters the
outer openings as one of the spirals orbits.

2. The open passages are sealed off as gas is drawn into the spiral.

3. As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets.

4. By the time the gas arrives at the center port, discharge pressure has been reached.

5. During operation, all six gas passages are in various stages of compression at all times, resulting in nearly continuous suction
and discharge.

Refrigerant enters the compressor at the suction connection and flows around the motor’s housing and enters at the bottom
side through the openings and oil droplets separate from the refrigerant and fall into the oil sump. All suction refrigerant passes
through the electrical motor, ensuring full motor cooling, after that the refrigerant enters the scroll elements.

Scroll compressor involutes Pockets arrangement

7
STANDARD SPECIFICATION

A. UNIT CONSTRUCTION

BASE: The base rail is constructed of heavy gauge galvanized steel with lifting holes for ease in rigging and lifting. It also
includes mounting holes suitable to affix with neoprene pads or spring isolators.

CABINET: The unit cabinet is a modular construction design with a base frame and panels made of heavy gauge galvanized
steel. All panels, top panel, vertical posts, cross channels and supporting brackets are joined together and bolted. The steel
sheet panels are zinc-coated and galvanized by the hot dip process of lock-forming quality conforming to ASTM A 653
commercial weight G-90, followed by a baked on electrostatic polyester dry powder coat, capable of withstanding 1500 hours
of salt spray test in accordance with ASTM B-117.

B. COMPRESSOR
All compressors used in the CTXN series are hermetically scroll design type with a high energy efficiency ratio, low noise and
quite operation. All compressors conform to AHRI 540 standard and are equipped with internal motor protection, factory
installed crankcase heaters and rubber vibration isolators for quiet and efficient operation. Each compressor has lockout devic-
es to protect it from short cycling when tripped by safety controls. Each compressor has a separate condenser coil with its own
safety controls. Sight glass, filter drier and under voltage monitor are standard on all models.

Cooling Capacity Stage Table

NO .OF
MODEL COOLING CAPCITY STAGE COMPRESSORS

CTX022N 0-50-100% 2
CTX030N 0-50-100% 2
CTX035N 0-50-100% 2
CTX040N 0-25-50-75-100% 4
CTX045N 0-25-50-75-100% 4
CTX050N 0-25-50-75-100% 4
CTX060N 0-25-50-75-100% 4
CTX070N 0-16.5-33-49.5-66-82.5-100% 6
CTX080N 0-16.5-33-49.5-66-82.5-100% 6
CTX090N 0-25-50-75-100% 4
CTX110N 0-25-50-75-100% 4
CTX130N 0-16.5-33-49.5-66-82.5-100% 6
CTX160N 0-16.5-33-49.5-66-82.5-100% 6
CTX180N 0-12.5-25-37.5-50-62.5-75-87.5-100% 8
CTX220N 0-12.5-25-37.5-50-62.5-75-87.5-100% 8

C. AIR COOLED CONDENSING UNIT


• Open design permits unrestricted condenser airflow, access to
compressors, refrigeration components and piping.
• High efficiency scroll compressors are standard.
• Each compressor has a separate condenser coil.
• Each refrigerant circuit is furnished with an accessible sight glass,
filter drier, high-pressure switch, low-pressure switch
& Fan cycling switch.
• Each compressor has a crankcase heater as standard.
• The compressor motor is provided with built-in thermal protection
during winding.
• Vertical air discharge minimizes condenser fan noise.
Three phase condenser fan motors eliminate reverse rotation failures.

Condensing Cabinet

8
D. CONDENSER FAN
Condenser fans are constructed of die cast aluminum blades / hubs with direct driven motors. All fans are statically and dynam-
ically balanced to operate at minimum noise and vibration. Fan blades are designed with appropriate pitch angle which result
in maximum airflow through the condenser coil. Condenser fan, the impeller and motor are constructed to form one integral
unit. All fan motors are equipped with IP55 ingress protection, three phase with class "F" winding insulation and ball bearings
for high ambient application. These fan motors are of the totally enclosed air over type (TEAO) with inherent thermal protection
of the automatic reset type. As options, Zamil Air Conditioners can offer:

1. UL/ETL recognized condenser fan


2. Fan with protective coating

Condenser Fan

E. CONDENSER COIL:
Condenser coil is of the fin and tube type, constructed of seamless (3/8" OD) inner grooved copper tube, mechanically bonded
to enhanced aluminum fins for maximum heat transfer efficiency. The fins have full self spacing collars, which completely cover
each tube while the staggered tube design improves the thermal efficiency. The number of circuits is chosen to provide
optimum heat transfer and reasonable refrigerant velocity and pressure drop. End plates and tube support sheets are made of
18 gauge galvanized steel, formed to provide structural strength Condenser coils is leak tested by charging H2N2 tracer gas in
the factory at 650 psig.

As an option, Zamil Air Conditioners can offer:

1. Copper Fins (12 FPI)


2. Pre-coated Aluminum Fins
3. Anti-Corrosive Coating for Aluminum & Copper fins

F. REFRGERATION KIT
FILTER DRIER (SUPPLIED-LOOSE ITEM): Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil contami-
nating particles by the filter drier. Sealed type is standard on all models while replaceable core filter drier is optional. SIGHT
GLASS (SUPPLIED-LOOSE ITEM): The moisture indicating sight glass is installed in the liquid line and its color indicator shows
moisture contents and provides a means for checking the system’s refrigerant charge.

FILTER DRIER SIGHT GLASS

9
G. SUCTION & LIQUID ISOLATION VALVES (FACTORY-INSTALLED ITEM): Both suction and liquid service valves are brass,
back-seating type with sweat connections. Valves are externally located so refrigerant piping connections can be made quickly
and easily.

H. FAN CYCLE SWITCH HEAD PRESSURE CONTROL


The capacity of air-cooled condensers varies with the difference between condensing temperature and condenser entering air
temperature (ambient temperature). It increases as this difference increases. For a given capacity, a drop in the ambient
temperature will lower the condensing temperatures and if the ambient temperature drops below a given limit, head pressure
control is required. Control shall be set for a minimum of 95°F (35°C) saturated refrigerant condensing temperature, or to suit
the specified application.

I. CONTROL PANEL

4 3 5 2 1

Description
1.Controller
2. 24V Control Transformer
3. Under voltage Monitor
4. Control Fuse
6
5. Auxiliary terminal block
6. Control Relays
7 7. DI from DDC or Therrmostat (Aux Terminal block)
11
8. Heater Contactor

12 9 & 10. Compressor Contactor


8 11. High Voltage Terminal Block (HVTB)
12. Neutral Terminal Block

13 13. Earth Terminal Block

10 9

10
G. ADVANCED MICROPROCESSOR CONTROLLER

* CONTROL FEATURES:

• Balance loading of compressors


• Pump down solenoid outputs
• Compressor trip outputs and global alarm
• Error / warning indications
• Compressor high- and low-pressure protection
• Compressor recycle protection (anti-short cycle timer)
• Low pressure bypass timer
• Built-in condenser fan staging control
• Remote ON/OFF
• Connection to any digital thermostat
• Connection to DDC
• Connection to BMS system with different communication protocols (optional)
• Advanced programmable thermostat with error indicator (optional)
• Advanced display with programmer (optional)

* CONTROL FUNCTIONS:
• Unit On-Off
The unit can be switched On-Off with the following mode:
1. From display or thermostat
2. From digital input
3. From BMS

• Clock and time bands


Condensing unit control is fitted with an internal clock with backup battery that stores the time and date for all the
associated functions. In the condensing unit control it is possible to manage the time bands using the advanced
thermostat.

1
• Regulation by inputs
Condensing unit control can manage up to 4 digital inputs for cooling request. Each digital input request one step of
capacity in cooling mode.
a. Cooling by input
In case of request of cooling, the digital input decide the number of the compressors to switch ON, but the
condensing unit control decide which compressors switch ON according to the rotation logic.

•Temperature Control
Condensing unit control can manage temperature probes from analogue input or from thermostat. The unit can work
in the following mode:
a. Cooling: The compressors will follow the set-point.
b. Auto: According to set-point and room temperature, the mode of the unit will change automatically. A delay is
settable to avoid continue automatic change.

• Compressors and Rotation


All the following timings, typical of ON-OFF compressors, are managed by condensing unit
control:
a. Minimum on time
b. Minimum off time
c. Minimum time between consecutive starts d. Delay between ON different compressors
e. Delay between OFF different compressors (fixed as 10s)

The following rotation type is managed by unit control:


a. Rotation by time b. FIFO rotation
c. LIFO rotation
d. Custom rotation

•Pump-Down (Optional)
Condensing unit control can manage the digital output for the pump-down valve for each compressor. There is a fixed
operating procedure at start-up of the unit: the pump down valve must start settable time before the condenser fan,
then the condenser fan must start settable time before of the compressors, then the compressors can start. It is
possible to configure the pump-down at shut-down. Where the valve will be OFF while compressor is ON to pump
down the gas in the evaporator.

• Condenser Fan Control (Optional)


The condenser fan can work with or without the condensing temperature and controlling or not the status of the
compressor, like the table below:

Compressor ON Compressor OFF


Follow compressor Condenser fan switch ON Condenser fan switch OFF

Follow condensing temperature Condenser fan switches ON in case Condenser fan switches OFF (The
the compressor is ON and Condenser fan can switch ON during
temperature is higher than set-point. high condensing temperature protection).

2
• Supervisory System (Optional)
Condensing unit control can be connected to various supervisory systems, using several BMS communication protocols.
The various connection protocols are managed using the optional cards like: Carel RS485 or Modbus RS485.

• High/low Pressure Alarms


The High- or Low-pressure alarm is managed by condensing unit control with a digital input. The high- or Low-pressure
alarm can be reset as Semi-Automatic function such that if the number of alarms activated more than 3 times per
hour, then the alarm changes to manual reset. The other compressor will continue running in case it is healthy.

• PGD Display (Optional)

• 4X20 Character Liquid Crystal


• User Configurable
• Temperature Anticipation
• Current Unit Mode Status
• Operating Range ( -20 °C to 65 °C)
• IP65

3
OPTIONAL ITEMS

A. Microchannel Condenser Coils (MCHX)


Microchannel coils are an aluminum construction coil and composed of:
1. Extended flat tubes with many small flow channels.
2. Flat fins that are brazed to adjoining tubes.
3. Two refrigerant manifold headers.

Advantages of MCHX:
1. MCHX coils have more heat transfer per square foot than traditional
coils and require much less refrigerant charge.
2. No galvanic corrosion (100% aluminum).
3. Reduction in refrigerant charge compare to normal finned and tube
coils.
4. Long life alloy for very aggressive environments.
5. Improving the unit energy efficiency ratio (EER).
6. MCHX is lighter in weight, smaller in volume.

As an option, Zamil Air Conditioners can offer:


*Anti-Corrosive Coating is recommended for seacoast or
other corrosive applications and ambient environments.

B. HOT GAS BYPASS CONTROL (FACTORY-INSTALLED ITEM):


Hot gas bypass control can be provided on the lead circuit to permit operation of the system down to 80% of its unloaded
capacity. Under low ambient conditions, it controls temperature by eliminating the need to cycle the compressor on and off,
ensuring narrow temperature swing and lengthening the life span of the compressor.

C. PUMP DOWN SOLENOID VALVE (SUPPLIED-LOOSE ITEM):


A pump down solenoid valve is installed in the liquid line. When the room thermostat is satisfied, the valve closes and the
compressor continues to run until a substantial portion of the refrigerant has been pumped out from the evaporator coil. The
low-pressure switch will cycle off the compressor at a predetermined evaporator pressure.

D. PRESSURE GAUGES (FACTORY-INSTALLED ITEM):


This option is used for monitoring and inspecting the suction and discharge pressure, it is installed on the condensing units,
which allows inspection of refrigerant system performance

E. COMPRESSOR SERVICE VALVES (FACTORY-INSTALLED ITEM):


Both suction and liquid service valves are brass, back seating type with sweat connections. Valves are externally located so
refrigerant piping connections can be made quickly and easily.

F. DISCHARGE LINE MUFFLERS (FACTORY-INSTALLED ITEM):


Discharge line mufflers are installed to eliminate noise due to refrigerant pulsation.

G. UNIT FULL GUARD (FACTORY-INSTALLED ITEM):


The guard is mounted on the condensing section only, which protects the condenser coil from physical damage.

13
H. CIRCUIT BREAKER FOR COMPRESSORS OR CONDENSER MOTOR
This feature protects against branch circuit fault. When tripped (manually or automatically), the breaker cut-off the power supply
to the compressor /condenser motor /blower motor and disable its control through the breaker's auxiliary contacts

I. MOTOR EXTERNAL OVERLOAD PROTECTION


Motors are provided with overload relays or a built-in thermal winding device or both for its overload protection

J. DISCONNECT SWITCH
A single non-fused disconnect switch is provided for disconnecting electrical power at the
unit. The disconnect switch is mounted internally on the control panel and operated by an
externally mounted handle.

K. ELECTRONIC THERMOSTAT Disconnect Switch


Electronic thermostat can control up to four cooling stages and four heating stages depending
on the number of compressors and electric heaters.

The thermostat normally displays room temperature and mode of operation. The temperature
can be set by up/down buttons for both cooling and heating cycles. The thermostat also
allows you to select continuous fan operation or have the fan on intermittent operation with the
equipment. The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a
partition wall (not an outside wall), and should not be exposed to direct light from lamps, sun
etc. It should be in return air stream, away from supply air registers/diffusers.

Electronic Thermostat

L. ANTI-CORROSIVE COATING
: A single component of aluminum impregnated coating applied on the fins of heat exchanging coils. The product has
been designed for Middle East climate conditions. A high chemical, abrasion and UV resistance has been proven in both
laboratories and on field environment. The coating can be applied at the factory as well as in the field for maintenance or rejuve-
nation purposes.

Multi : A two component coating system that withstands the extreme climate conditions. The coating can be applied to
all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pre- treatment and layer
build up. Please check ResisTec product information sheets, the heat exchangers can not be coated using this type. The
coating can be applied at the factory as well as in the field for maintenance or rejuvenation purposes.

14
CTXN- PHYSICAL DATA - 60Hz
MODEL NUMBER CTX 022N 025N 030N 035N 040N 045N 050N 060N
COOLING CAPACITY (F&T @ 95⁰ F DB AMBIENT & 45⁰F EVAPORATING TEMP.)(1) 264 285 329 404 456 528 570 658
COOLING CAPACITY (MCHX 95⁰ F DB AMBIENT & 45⁰F EVAPORATING TEMP.)(1) 271 293 339 412 465 542 586 677
NUMBER OF REFRIGERATION CIRCUIT 2 2 2 2 4 4 4 4
TYPE HERMETIC SCROLL
OIL TYPE POE OIL
COMPRESSOR
OIL PER SYSTEM OZ 110 114 114 114 110 110 114 114
REFRIGERANT R-410A
TYPE PROPELLER WITH DIRECT DRIVEN MOTOR
QTY. EA 2 2 2 4 4 4 4 4
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION & IP56
MOTOR SIZE KW 1.35 1.35 2.4 1.35 1.35 1.35 1.35 2.4
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)
CONDENSER COIL FINS SPACING(2) FPI 14 14 14 14 14 14 14 14
TOTAL FACE AREA SQ. FT. 48.9 48.9 48.9 97.8 97.8 97.8 97.8 97.8
TYPE MICROCHANNEL COIL (MCHX)
CONDENSER COIL(3) FINS SPACING FPI 20 20 20 20 20 20 20 20
TOTAL FACE AREA SQ. FT 48.9 48.9 48.9 97.8 97.8 97.8 97.8 97.8
OPEN PSIG 650±15 650±15 650±15 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE PSIG 500±22 500±22 500±22 500±22 500±22 500±22 500±22 500±22
OPEN PSIG 50±7 50±7 50±7 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE PSIG 90±7 90±7 90±7 90±7 90±7 90±7 90±7 90±7
SOUND PRESSURE LEVEL , ( 1 m /3m / 5m )(4) dBA 73.2/67.2/63.6 74.2/68.2/64.6 74.9/68.9/65.4 76.2/70.2/66.6 74.2/68.2/64.6 76.2/70.2/66.6 77.2/71.2/67.6 77.9/71.9/68.4

(1) Cooling Capcity in (1000 Btuh)

(2) Optional 12 FPI Condenser Coil


(3) Microchannel Condenser Coil (MCHX) is optional

(4) Based on Free Field area at AHRI conditions. Tolerance ± 2 dB(A)


CTXN- PHYSICAL DATA - 60Hz
MODEL NUMBER CTX 070N 080N 090N 110N 130N 160N 180N 220N
COOLING CAPACITY (F&T @ 95⁰ F DB AMBIENT & 45⁰F EVAPORATING TEMP.)(1) 793 879 1017 1269 1525 1903 2033 2537
COOLING CAPACITY (MCHX 95⁰ F DB AMBIENT & 45⁰F EVAPORATING TEMP.)(1) 812 904 1039 1304 1558 1956 2078 2609
NUMBER OF REFRIGERATION CIRCUIT 6 6 4 4 6 6 8 8
TYPE
OIL TYPE
COMPRESSOR
OIL PER SYSTEM OZ 110 110 152 152 152 152 152 152
REFRIGERANT
TYPE
QTY. EA 6 6 8 8 12 12 16 16
CONDENSER FAN
MOTOR TYPE
MOTOR SIZE KW 1.35 2.4 1.35 2.4 1.35 2.4 1.35 2.4
TYPE
(2)
CONDENSER COIL FINS SPACING FPI 14 14 14 14 14 14 14 14
TOTAL FACE AREA SQ. FT. 146.6 146.6 195.5 195.5 293.3 293.3 391.0 391.0
TYPE
CONDENSER COIL(3) FINS SPACING FPI 20 20 20 20 20 20 20 20
TOTAL FACE AREA SQ. FT. 146.6 146.6 195.5 195.5 293.3 293.3 391.0 391.0
OPEN PSIG 650±15 650±15 650±15 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE PSIG 500±22 500±22 500±22 500±22 500±22 500±22 500±22 500±22
OPEN PSIG 50±7 50±7 50±7 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE PSIG 90±7 90±7 90±7 90±7 90±7 90±7 90±7 90±7
(4)
SOUND PRESSURE LEVEL , ( 1 m /3m / 5m ) dBA 78/72/68.4 79.7/73.7/70.2 84.2/78.1/74.6 87.3/81.3/77.8 86/79.9/76.4 89.1/83.1/79.6 87.2/81.1/77.6 90.3/84.3/80.8
(1) Cooling Capcity in (1000 Btuh)

(2) Optional 12 FPI Condenser Coil


(3) Microchannel Condenser Coil (MCHX) is optional

(4) Based on Free Field area at AHRI conditions. Tolerance ± 2 dB(A)


CTXN PERFORMANCE DATA - 60 Hz
AMBIENT TEMPERATURE
SST 85°F 95°F 105°F 115°F 125°F
MODEL
(ºF) TC PI TC PI TC PI TC PI TC PI
(KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW)
22 280 20.2 264 22.1 247 24.2 229 26.6 210 29.2
25 303 22.9 285 24.9 267 27.1 249 29.6 229 32.3
30 348 27.8 329 30.0 309 32.4 288 35.0 266 38.0
35 426 30.6 404 32.9 380 35.6 354 38.6 328 41.9
40 481 34.5 456 37.7 429 41.3 401 45.3 371 49.8
45 560 40.5 528 44.2 494 48.5 457 53.3 421 58.4
50 605 45.9 570 49.9 534 54.2 497 59.2 459 64.5
45 °F 60 696 55.6 658 60.0 617 64.8 576 70.0 532 75.9
70 840 60.7 793 66.2 740 72.7 686 79.9 631 87.6
80 933 72.4 879 78.3 825 84.8 767 92.2 707 100.4
90 1072 79.7 1017 86.3 958 93.9 897 102.5 835 111.6
110 1339 106.1 1269 114.4 1196 123.8 1118 134.7 1037 147.0
130 1608 119.6 1525 129.5 1437 140.9 1345 153.7 1253 167.4
160 2009 159.2 1903 171.7 1794 185.7 1677 202.1 1555 220.4
180 2143 159.4 2033 172.6 1916 187.9 1794 205.0 1670 223.2
220 2678 212.2 2537 228.9 2392 247.6 2236 269.4 2073 293.9
LEGEND:
SST-Saturated Suction Temperature ; TC - Total Capacity ; PI -Total Power Input

AMBIENT TEMPERATURE
SST 85°F 95°F 105°F 115°F 125°F
MODEL
(ºF) TC PI TC PI TC PI TC PI TC PI
(KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW)
22 289 20.4 273 22.2 256 24.4 237 26.8 218 29.3
25 313 23.1 295 25.1 276 27.3 257 29.8 238 32.4
30 360 28.1 340 30.2 319 32.7 298 35.3 275 38.2
35 441 30.9 418 33.2 393 35.9 367 38.8 340 42.1
40 497 34.8 471 37.9 444 41.5 415 45.5 385 50.0
45 578 40.8 546 44.5 511 48.8 474 53.6 436 58.7
50 625 46.3 589 50.3 553 54.6 515 59.6 475 64.9
47 °F 60 719 56.1 679 60.5 638 65.3 596 70.5 550 76.4
70 868 61.2 820 66.7 767 73.2 711 80.4 655 88.0
80 964 73.0 909 78.8 854 85.3 795 92.7 733 100.9
90 1108 80.4 1051 87.0 990 94.6 928 103.1 865 112.2
110 1384 107.1 1311 115.4 1235 125.0 1158 135.6 1074 147.7
130 1662 120.6 1576 130.4 1486 141.9 1392 154.7 1297 168.3
160 2076 160.7 1967 173.1 1853 187.5 1736 203.4 1612 221.6
180 2216 160.8 2102 173.9 1981 189.2 1856 206.2 1730 224.4
220 2768 214.3 2623 230.8 2471 250.0 2315 271.2 2149 295.5
22 303 20.6 287 22.6 269 24.7 250 27.0 230 29.6
25 328 23.5 309 25.5 290 27.6 271 30.1 251 32.7
30 378 28.5 357 30.6 335 33.0 313 35.6 289 38.5
35 463 31.4 439 33.6 413 36.3 386 39.2 358 42.5
40 523 35.2 496 38.3 467 41.9 437 45.9 406 50.3
45 607 41.3 573 45.1 538 49.3 499 54.1 460 59.2
50 656 46.9 618 50.9 581 55.3 541 60.2 501 65.5
60 755 56.9 713 61.2 670 66.1 626 71.3 579 77.1
50 °F 70 910 61.9 860 67.7 807 74.0 749 81.1 690 88.9
80 1012 73.8 955 79.7 898 86.1 837 93.4 774 101.6
90 1163 81.5 1104 88.0 1041 95.6 976 104.1 908 113.5
110 1452 108.8 1377 117.0 1298 126.5 1218 137.0 1132 149.0
130 1745 122.2 1656 132.0 1561 143.4 1463 156.2 1362 170.2
160 2178 163.2 2066 175.4 1947 189.7 1827 205.4 1699 223.5
180 2326 163.0 2208 176.0 2082 191.2 1951 208.2 1817 226.9
220 2904 217.6 2754 233.9 2596 252.9 2436 273.9 2265 298.1
LEGEND:
SST-Saturated Suction Temperature ; TC - Total Capacity ;
PI -Total Power Input ; EER - Energy Efficiency Ratio

19
CTXN PERFORMANCE DATA (MCXH) - 60 Hz
AMBIENT TEMPERATURE
SST 85°F 95°F 105°F 115°F 125°F
MODEL
(ºF) TC PI TC PI TC PI TC PI TC PI
(KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW)
22 288 19.4 271 21.4 252 23.6 232 26.2 211 29.2
25 313 22.0 293 24.1 273 26.5 253 29.2 230 32.2
30 360 26.6 339 29.0 317 31.5 294 34.4 269 37.7
35 435 29.9 412 32.2 386 35.0 359 38.2 330 41.8
40 493 33.3 465 36.6 437 40.4 406 44.8 373 49.8
45 576 38.8 542 42.8 505 47.3 465 52.5 422 58.5
50 625 43.9 586 48.2 547 52.9 505 58.3 461 64.4
45 °F 60 720 53.3 677 57.9 634 63.0 588 68.8 538 75.4
70 864 58.2 812 64.1 757 70.9 697 78.7 632 87.7
80 963 69.6 904 75.8 844 82.7 781 90.6 715 99.6
90 1100 77.0 1039 84.0 976 91.9 909 101.1 839 111.5
110 1381 102.1 1304 110.6 1225 120.5 1139 132.3 1047 145.9
130 1650 115.4 1558 126.0 1464 137.9 1364 151.6 1258 167.3
160 2072 153.1 1956 165.9 1837 180.8 1708 198.4 1571 218.8
180 2200 153.9 2078 167.9 1952 183.8 1819 202.2 1677 223.0
220 2762 204.1 2609 221.2 2449 241.1 2278 264.5 2094 291.7
LEGEND:
SST-Saturated Suction Temperature ; TC - Total Capacity ; PI -Total Power Input

AMBIENT TEMPERATURE
SST 85°F 95°F 105°F 115°F 125°F
MODEL
(ºF) TC PI TC PI TC PI TC PI TC PI
(KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW) (KBTUH) (KW)
22 298 19.5 280 21.5 261 23.8 241 26.4 219 29.3
25 323 22.1 303 24.3 283 26.6 262 29.3 239 32.4
30 373 26.9 350 29.2 328 31.7 304 34.6 278 37.9
35 450 30.1 426 32.5 400 35.2 371 38.4 341 42.1
40 510 33.5 482 36.9 452 40.6 421 44.9 387 50.0
45 596 39.1 560 43.0 523 47.5 482 52.8 438 58.7
50 646 44.3 606 48.6 566 53.3 523 58.6 478 64.7
47 °F 60 745 53.7 701 58.3 656 63.4 608 69.2 557 75.8
70 893 58.6 841 64.6 784 71.3 723 79.1 657 88.0
80 996 70.1 936 76.2 874 83.1 810 91.0 742 100.0
90 1138 77.6 1074 84.6 1010 92.5 941 101.6 868 112.1
110 1428 103.0 1349 111.5 1268 121.3 1180 133.0 1086 146.5
130 1707 116.3 1611 126.9 1515 138.7 1412 152.4 1303 168.1
160 2142 154.5 2024 167.2 1901 182.0 1770 199.5 1629 219.8
180 2276 155.1 2149 169.1 2020 184.9 1883 203.3 1737 224.2
220 2856 205.9 2698 223.0 2535 242.7 2360 266.0 2172 293.1
22 313 19.7 295 21.7 275 24.0 254 26.6 231 29.5
25 339 22.4 318 24.6 298 26.9 276 29.6 252 32.6
30 392 27.2 368 29.5 345 32.0 320 34.9 293 38.2
35 473 30.6 448 32.9 420 35.6 391 38.8 359 42.4
40 537 33.9 507 37.2 476 40.9 443 45.2 408 50.2
45 625 39.5 589 43.5 551 48.0 508 53.1 463 59.0
50 679 44.8 636 49.2 595 53.8 551 59.1 505 65.2
60 784 54.4 737 59.0 690 64.1 640 69.9 586 76.4
50 °F 70 938 59.2 884 65.2 826 72.0 763 79.7 694 88.5
80 1047 70.8 984 77.0 920 83.8 854 91.7 783 100.7
90 1196 78.5 1129 85.5 1062 93.4 991 102.5 915 113.0
110 1500 104.5 1418 112.9 1333 122.6 1243 134.2 1146 147.6
130 1794 117.8 1694 128.3 1593 140.0 1486 153.7 1372 169.4
160 2250 156.7 2127 169.3 2000 183.9 1864 201.3 1718 221.5
180 2392 157.1 2258 171.0 2124 186.7 1981 205.0 1829 225.9
220 3000 208.9 2835 225.8 2667 245.3 2485 268.4 2291 295.3
LEGEND:
SST-Saturated Suction Temperature ; TC - Total Capacity ;
PI -Total Power Input ; EER - Energy Efficiency Ratio

20
ELECTRICAL DATA
MODEL LEAD COMPRESSOR OTHER COMPRESSOR CONDENSER FAN MOTOR
SUPPLY VOLTAGE
RLA LRA RLA LRA
FLA (amps.) LRA (amps.) MCA MOCP
COND. UNIT NOMINAL (V- QTY. QTY. QTY.
MIN. MAX. (ea.) (ea.) (ea.) (ea.) (each) (each)
Ph-Hz)
CTX022N 207 253 1 37.1 239 1 37.1 239 2 5 19.2 93 125
CTX025N 207 253 1 53.6 245 1 53.6 245 2 5 19.2 131 175
CTX030N 207 253 1 57.1 300 1 57.1 300 2 6.8 32 142 175
CTX035N 207 253 1 62.1 340 1 62.1 340 4 5 19.2 160 200
CTX040N 207 253 1 33.6 225 3 33.6 225 4 5 19.2 163 175
CTX045N 207 253 1 37.1 239 3 37.1 239 4 5 19.2 178 200
CTX050N 207 253 1 53.6 245 3 53.6 245 4 5 19.2 248 300
CTX060N 207 253 1 57.1 300 3 57.1 300 4 6.8 32 270 300
230-3-60
CTX070N 207 253 1 37.1 239 5 37.1 239 6 5 19.2 262 300
CTX080N 207 253 1 53.6 245 5 53.6 245 6 6.8 32 376 400
CTX090N 207 253 1 80.7 538 3 80.7 538 8 5 19.2 383 450
CTX110N 207 253 1 95.0 605 3 95.0 605 8 6.8 32 458 500
CTX130N 207 253 1 80.7 538 5 80.7 538 12 5 19.2 564 600
CTX160N 207 253 1 95.0 605 5 95.0 605 12 6.8 32 675 700
CTX180N 207 253 1 80.7 538 7 80.7 538 16 5 19.2 746 800
CTX220N 207 253 1 95.0 605 7 95.0 605 16 6.8 32 893 1000

MODEL LEAD COMPRESSOR OTHER COMPRESSOR CONDENSER FAN MOTOR


SUPPLY VOLTAGE
RLA LRA RLA LRA
FLA (amps.) LRA (amps.) MCA MOCP
COND. UNIT NOMINAL (V- QTY. QTY. QTY.
MIN. MAX. (ea.) (ea.) (ea.) (ea.) (each) (each)
Ph-Hz)
CTX022N 342 418 1 26.4 145 1 26.4 145 2 3 10.4 65 90
CTX025N 342 418 1 26.4 145 1 26.4 145 2 3 10.4 65 90
CTX030N 342 418 1 30.0 139 1 30.0 139 2 3.9 19 75 100
CTX035N 342 418 1 37.9 196 1 37.9 196 4 3 10.4 97 125
CTX040N 342 418 1 21.4 140 3 21.4 140 4 3 10.4 103 125
CTX045N 342 418 1 26.4 145 3 26.4 145 4 3 10.4 124 150
CTX050N 342 418 1 26.4 145 3 26.4 145 4 3 10.4 124 150
CTX060N 380/400-3-60 342 418 1 30.0 139 3 30.0 139 4 3.9 19 143 150
CTX070N (4 WIRE) 342 418 1 26.4 145 5 26.4 145 6 3 10.4 183 200
CTX080N 342 418 1 26.4 145 5 26.4 145 6 3.9 19 188 200
CTX090N 342 418 1 39.3 290 3 39.3 290 8 3 10.4 191 225
CTX110N 342 418 1 57.9 380 3 57.9 380 8 3.9 19 277 300
CTX130N 342 418 1 39.3 290 5 39.3 290 12 3 10.4 282 300
CTX160N 342 418 1 57.9 380 5 57.9 380 12 3.9 19 409 450
CTX180N 342 418 1 39.3 290 7 39.3 290 16 3 10.4 372 400
CTX220N 342 418 1 57.9 380 7 57.9 380 16 3.9 19 540 600

MODEL LEAD COMPRESSOR OTHER COMPRESSOR CONDENSER FAN MOTOR


SUPPLY VOLTAGE
RLA LRA RLA LRA
FLA (amps.) LRA (amps.) MCA MOCP
COND. UNIT NOMINAL (V- QTY. QTY. QTY.
MIN. MAX. (ea.) (ea.) (ea.) (ea.) (each) (each)
Ph-Hz)
CTX022N 414 506 1 20.0 125 1 20.0 125 2 2.85 13.5 51 70
CTX025N 414 506 1 20.7 125 1 20.7 125 2 2.85 13.5 52 70
CTX030N 414 506 1 25.7 150 1 25.7 150 2 3.8 20 65 90
CTX035N 414 506 1 30.0 173 1 30.0 173 4 2.85 13.5 79 100
CTX040N 414 506 1 18.6 114 3 18.6 114 4 2.85 13.5 90 100
CTX045N 414 506 1 20.0 125 3 20.0 125 4 2.85 13.5 96 110
CTX050N 414 506 1 20.7 125 3 20.7 125 4 2.85 13.5 99 110
CTX060N 414 506 1 25.7 150 3 25.7 150 4 3.8 20 124 150
460-3-60
CTX070N 414 506 1 20.0 125 5 20.0 125 6 2.85 13.5 142 150
CTX080N 414 506 1 20.7 125 5 20.7 125 6 3.8 20 152 175
CTX090N 414 506 1 34.3 229 3 34.3 229 8 2.85 13.5 169 200
CTX110N 414 506 1 42.1 320 3 42.1 320 8 3.8 20 209 250
CTX130N 414 506 1 34.3 229 5 34.3 229 12 2.85 13.5 249 300
CTX160N 414 506 1 42.1 320 5 42.1 320 12 3.8 20 309 350
CTX180N 414 506 1 34.3 229 7 34.3 229 16 2.85 13.5 329 350
CTX220N 414 506 1 42.1 320 7 42.1 320 16 3.8 20 408 500

21
2 SYSTEM - REFRIGERATION CIRCUIT

22
3 SYSTEM - REFRIGERATION CIRCUIT

23
4 SYSTEM - REFRIGERATION CIRCUIT

24
6 SYSTEM - REFRIGERATION CIRCUIT

25
8 SYSTEM - REFRIGERATION CIRCUIT

26
DIMENSIONS

CTX022N, 025N

27
DIMENSIONS

CTX030N

28
DIMENSIONS

CTX035N

29
DIMENSIONS

CTX040N, 045N, 050N

30
DIMENSIONS

CTX060N

31
DIMENSIONS

CTX070N

32
DIMENSIONS

CTX080N

33
DIMENSIONS

CTX090N

34
DIMENSIONS

CTX110N

35
DIMENSIONS

CTX130N

36
DIMENSIONS

CTX160N

37
DIMENSIONS

CTX180N

38
DIMENSIONS

CTX220N

39
LIFTING AND RIGGING INSTRUCTION

ATTENTION TO RIGGERS
Hook rigging sling thru the holes on the lifting plates, as shown below.
Lifting plates or holes on the base rail are centered around the unit's center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging to prevent the slings from damaging the unit.

CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings if necessary.

1. STEEL BAR
2. LIFTING CABLE OR CHAIN
3. CHAIN SLING
4. BOLT & NUT
5. SPREADER BAR

NOTE: STEEL BAR MUST BE 2.50" NOMINAL PIPE THROUGH UNIT FOR SLINGS TO AVOID BASE DAMAGE

40
LIFTING AND RIGGING INSTRUCTION

NOTE: STEEL BAR MUST BE 2.50" NOMINAL PIPE THROUGH UNIT FOR SLINGS TO AVOID BASE DAMAGE

41
LIFTING AND RIGGING INSTRUCTION

NOTE: STEEL BAR MUST BE 2.50" NOMINAL PIPE THROUGH UNIT FOR SLINGS TO AVOID BASE DAMAGE

42
INSTALLATION CLEARANCE (MULTIPLE)

Note: 1. If unit is installed in special pit, please observe same tolerance for walls. Pit height should not exceed unit height.
2. No obstruction above condenser fan.

43
INSTALLATION CLEARANCE (MULTIPLE)

CTXN180N-CTXN220N

Note: 1. If unit is installed in special pit, please observe same tolerance for walls. Pit height should not exceed unit height.
2. No obstruction above condenser fan.

44
INSTALLATION CLEARANCE (SINGLE)

CTXN180N-CTXN220N

Note: 1. If unit is installed in special pit, please observe same tolerance for walls. Pit height should not exceed unit height.
2. No obstruction above condenser fan.

45
LOAD DISTRIBUTION (KG) & MOUNTING POINTS

FINNED TUBE CONDERSER COIL (AL/CU)


MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 TOTAL WT.
CTX022N 136 133 133 133 - - - - - - - - 535
CTX025N 140 135 135 135 - - - - - - - - 545
CTX030N 181 173 173 173 - - - - - - - - 700
CTX035N 231 223 223 223 - - - - - - - - 900
CTX040N 272 266 266 266 - - - - - - - - 1070
CTX045N 276 268 268 268 - - - - - - - - 1080
CTX0S0N 277 271 271 271 - - - - - - - - 1090
CTX060N 296 288 288 288 - - - - - - - - 1160
CTX070N 244 244 238 238 238 238 - - - - - - 1440
CTX0B0N 279 279 273 273 273 273 - - - - - - 1650
CTX090N 374 374 368 368 368 368 - - - - - - 2220
CTX110N 393 392 385 385 385 385 - - - - - - 2325
CTX130N 326 326 321 321 321 321 321 321 321 321 - - 3220
CTX160N 342 342 337 337 337 337 337 337 337 337 - - 3380
CTX180N 380 380 372 372 372 372 372 372 372 372 372 372 4480
CTX220N 400 400 389 389 389 389 389 389 389 389 389 389 4690

FINNED TUBE CONDERSER COIL (CU/CU)


MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 TOTAL WT.
CTX022N 165 160 160 160 - - - - - - - - 645
CTX025N 169 162 162 162 - - - - - - - - 655
CTX030N 207 201 201 201 - - - - - - - - 810
CTX035N 284 277 277 277 - - - - - - - - 1115
CTX040N 325 320 320 320 - - - - - - - - 1285
CTX045N 329 322 322 322 - - - - - - - - 1295
CTX0S0N 330 325 325 325 - - - - - - - - 1305
CTX0B0N 349 342 342 342 - - - - - - - - 1375
CTX070N 299 298 292 292 292 292 - - - - - - 1765
CTX0B0N 334 333 327 327 327 327 - - - - - - 1975
CTX090N 446 445 441 441 441 441 - - - - - - 2655
CTX110N 464 464 458 458 458 458 - - - - - - 2760
CTX130N 391 391 386 386 386 386 386 386 386 386 - - 3870
CTX160N 407 407 402 402 402 402 402 402 402 402 - - 4030
CTX180N 453 452 444 444 444 444 444 444 444 444 444 444 5345
CTX220N 473 472 461 461 461 461 461 461 461 461 461 461 5555

55
LOAD DISTRIBUTION (KG) & MOUNTING POINTS

MCHE CONDENSER COIL


MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 TOTAL WT.
CTX022N 121 118 118 118 - - - - - - - - 475
CTX025N 127 121 121 121 - - - - - - - - 490
CTX030N 168 159 159 159 - - - - - - - - 645
CTX035N 199 192 192 192 - - - - - - - - 775
CTX040N 242 236 236 236 - - - - - - - - 950
CTX045N 248 239 239 239 - - - - - - - - 965
CTX0S0N 249 242 242 242 - - - - - - - - 975
CTX060N 269 262 262 262 - - - - - - - - 1055
CTX070N 215 214 209 209 209 209 - - - - - - 1265
CTX0B0N 251 250 246 246 246 246 - - - - - - 1485
CTX090N 335 334 329 329 329 329 - - - - - - 1985
CTX110N 357 356 348 348 348 348 - - - - - - 2105
CTX130N 293 292 285 285 285 285 285 285 285 285 - - 2865
CTX160N 309 309 304 304 304 304 304 304 304 304 - - 3050
CTX180N 343 342 333 333 333 333 333 333 333 333 333 333 4015
CTX220N 365 365 352 352 352 352 352 352 352 352 352 352 4250

56
LOAD DISTRIBUTION (KG) & MOUNTING POINTS

57
Zamil Central Air Conditioners
P.O. Box 41015, Dammam 31521, Kingdom of Saudi Arabia
Tel.: +966 13 812 5400 Fax: +966 13 812 1977
Customer Service: 92 0000 468

@zamilac zamilac.com

PL-AP-CTXN-60Hz-21-2M-E 21Z1

You might also like