‫راﻫﻨﻤﺎي ﻧﺼﺐ ﮐﻨﺘﺮﻟﺮ ‪InteliNano Plus‬‬

‫در ﻫﻨﮕﺎم ﻧﺼﺐ ﮐﻨﺘﺮﻟﺮ ﻧﮑﺎت ﺑﻪ ﻓﻨﯽ ذﯾﻞ ﺗﻮﺟﻪ ﻓﺮﻣﺎﯾﯿﺪ‪:‬‬

‫‪ -1‬ﺗﺮﺗﯿﺐ ﻓﺎزﻫﺎي ورودي ﺑﺮق ﺷﻬﺮ ﻣﯽ ﺑﺎﯾﺴﺘﯽ ﺑﻪ ﺻﻮرت ‪ L1,L2,L3‬ﺑﺎﺷﺪ ‪ .‬در ﺻﻮرت ﻋﺪم‬

‫رﻋﺎﯾﺖ ﺗﺮﺗﯿﺐ ﻓﺎزﻫﺎ آﻻرم ‪ MainsCCW Rotation‬ﻧﻤﺎﯾﺶ داده ﻣﯽ ﺷﻮد‪.‬‬

‫‪ -2‬ﭼﻨﺎﻧﭽﻪ ﺟﺮﯾﺎن و ﺗﻮان اﻧﺪازه ﮔﯿﺮي ژﻧﺮاﺗﻮر ﺑﻪ ﺻﻮرت ﻋﺪد ﻣﻨﻔﯽ ﻧﻤﺎﯾﺶ داده ﺷﻮد ﻧﺸﺎﻧﮕﺮ‬

‫اﯾﻦ اﺳﺖ ﮐﻪ ورودي ﻫﺎي ﺗﺮاﻧﺲ ﺟﺮﯾﺎن ) ‪ (l – k‬ﺟﺎﺑﻪ ﺟﺎ ﻣﯽ ﺑﺎﺷﺪ‪.‬‬

‫‪ -3‬ﻧﻘﻄﻪ ﻣﺸﺘﺮك ﺗﺮاﻧﺴﻬﺎي ﺟﺮﯾﺎن را ﺑﻪ ﻫﯿﭻ ﻋﻨﻮان ﺑﻪ ﺗﺮﻣﯿﻨﺎل ﻧﻮل ﻣﺘﺼﻞ ﻧﻨﻤﺎﯾﯿﺪ‪.‬‬

‫‪ -4‬ورودي ﻫﺎي دﯾﺠﯿﺘﺎل ﮐﻨﺘﺮﻟﺮ ﺑﺎ ﻣﻨﻔﯽ ﺑﺎﻃﺮي ﻓﻌﺎل ﻣﯽ ﺷﻮﻧﺪ و ﺧﺮوﺟﯽ ﻫﺎي ﮐﻨﺘﺮﻟﺮ ﺑﺮاي‬

‫ﻓﻌﺎل ﮐﺮدن رﻟﻪ ﻫﺎ ﻣﺜﺒﺖ ﻣﯽ ﺑﺎﺷﺪ‪.‬‬

‫‪ -5‬ﻧﻘﻄﻪ ﻣﺸﺘﺮك ورودي ﻫﺎي آﻧﺎﻟﻮگ ﺗﺮﻣﯿﻨﺎل ﻣﻨﻔﯽ ﺑﺎﻃﺮي ﯾﺎ اﺗﺼﺎل ﺑﺪﻧﻪ دﯾﺰل‬

‫ﻣﯽ ﺑﺎﺷﺪ‪.‬‬

‫‪ -6‬ورودي ﻫﺎي آﻧﺎﻟﻮگ ﮐﻨﺘﺮﻟﺮ از ﻧﻮع ﻣﻘﺎوﻣﺘﯽ ﺑﻮده و ﻓﻘﻂ اﻣﮑﺎن اﺗﺼﺎل ﺳﻨﺴﻮرﻫﺎي‬

‫اﺳﺘﺎﻧﺪارد ﻓﺸﺎر روﻏﻦ ‪ ،‬دﻣﺎي آب ‪ ،‬ﺳﻄﺢ ﺳﻮﺧﺖ وﺟﻮد دارد ‪.‬‬

‫‪ -6‬ﮐﻠﯿﻪ ﺗﻨﻈﯿﻤﺎت ﮐﻨﺘﺮﻟﺮ ﺑﺠﺰ ﭘﺎراﻣﺘﺮ ﻫﺎي ﻣﺮﺑﻮط ﺑﻪ ‪ ECU‬ﺗﻮﺳﻂ دﮐﻤﻪ ﻫﺎي روي ﭘﻨﻞ‬

‫ﮐﻨﺘﺮﻟﺮ ﻗﺎﺑﻞ ﺗﻨﻈﯿﻢ ﻣﯽ ﺑﺎﺷﺪ و ﻫﻤﭽﻨﯿﻦ ﻧﺮم اﻓﺰار ‪ Nano Edit‬ﺑﺮاي ارﺗﺒﺎط ﺑﺎ ﮐﺎﻣﭙﯿﻮﺗﺮ اراﺋﻪ‬

‫ﺷﺪه اﺳﺖ و ﮐﺎﺑﻞ ارﺗﺒﺎﻃﯽ ﺑﯿﻦ ﮐﻨﺘﺮﻟﺮ و ﮐﺎﻣﭙﯿﻮﺗﺮ ‪ USB‬اﺳﺘﺎﻧﺪارد اﺳﺖ‪.‬‬

‫‪ -7‬ﺗﻨﻈﯿﻤﺎت ﭘﯿﺶ ﻓﺮض دﺳﺘﮕﺎه ﺑﻬﺘﺮﯾﻦ ﺣﺎﻟﺖ ﮐﺎري ﮐﻨﺘﺮﻟﺮ را ﺗﻌﯿﯿﻦ ﻣﯽ ﮐﻨﺪ ودر ﺻﻮرت‬

‫ﻧﯿﺎز ﺑﻪ ﺗﻐﯿﯿﺮات دﻓﺘﺮﭼﻪ راﻫﻨﻤﺎي اﻧﮕﻠﯿﺴﯽ ﮐﻨﺘﺮﻟﺮ ﻣﻄﺎﻟﻌﻪ ﻓﺮﻣﺎﯾﯿﺪ‪.‬‬

‫‪1‬‬
‫ﻓﺸﺎر‬ ‫‪ -8‬ﺟﻬﺖ وارد ﺷﺪن ﺑﻪ ﮔﺮوه ﺗﻨﻈﯿﻤﺎت ‪ ،‬ﺑﺎﯾﺪ در ﺻﻔﺤﻪ اﺻﻠﯽ)‪ (1‬دﮐﻤﻪ‬

‫ﻓﺸﺎر داده ﺗﺎ‬ ‫و و‬ ‫داده و ﻧﮕﻪ دارﯾﺪ و ﺳﭙﺲ ﺑﻪ ﺗﺮﺗﯿﺐ دﮐﻤﻪ ﻫﺎي‬

‫ﺑﺮاي ﺣﺮﮐﺖ ﺑﯿﻦ ﮔﺮوه‬ ‫و‬ ‫وارد ﺻﻔﺤﻪ ﺗﻨﻈﯿﻤﺎت)‪(2‬ﺷﻮﯾﺪ و از دﮐﻤﻪ ﻫﺎي‬

‫ﺑﺮاي ﺧﺮوج‬ ‫ﺑﺮاي اﻧﺘﺨﺎب و از دﮐﻤﻪ‬ ‫ﺗﻨﻈﯿﻤﺎت و از دﮐﻤﻪ‬

‫اﺳﺘﻔﺎده ﻣﯽ ﺷﻮد‪.‬‬

‫‪2‬‬
Alarms , Events ‫ﻟﯿﺴﺖ‬

Events Alarms
Mains Warning
Return Maintenance
Mains Fail Low Battery

Manual LowFuel
Start Level
Remote External
Start Warning 1
AMF Start External
Warning 2
Manual External
Stop Warning 3
Remote ECU
Stop Comm Error
AMF Stop MCB Fail

Auto On MainsCCW
Rotation
Auto Off

Power On

Island
Operation

3
Shutdowns ‫ﻟﯿﺴﺖ‬

Emergency GCB Fail


Stop
Overspeed Generator
Overvoltage
Underspeed Generator
Undervoltage
LowOil
Pressure Generator
High Overfrequency
temperature Generator
External Underfrequency
Shutdown 1 Generator
External CCWRotation
Shutdown 2
Start Fail
External
Shutdown 3 Stop Fail
Battery Flat
Generator
Short Circuit
.

‫ﻧﻘﺸﻪ ﺳﯿﻢ ﮐﺸﯽ و ارﺗﺒﺎط ﺑﯿﻦ ﮐﻠﯿﺪ ﻫﺎي ﺷﻬﺮ و ژﻧﺮاﺗﻮر‬

4
5
‫ﻧﻘﺸﻪ ﺳﯿﻢ ﮐﺸﯽ و ارﺗﺒﺎط ﺑﯿﻦ ﮐﻠﯿﺪ ﻫﺎي ﺷﻬﺮ و ژﻧﺮاﺗﻮر‬

‫‪6‬‬
‫ﺷﺮﮐﺖ درﻧﺎ ﻣﻬﺮ‬

‫راﻫﻨﻤﺎي ﻧﺼﺐ ﮐﻨﺘﺮﻟﺮ ‪Inteli NANO PLUS‬‬

‫ﺗﻬﺮان – ﺧﯿﺎﺑﺎن ﺷﺮﯾﻌﺘﯽ – ﮐﻮي زﯾﺒﺎ – ﺷﻤﺎره ‪ -46‬واﺣﺪ ‪5‬‬

‫ﺗﻠﻔﻦ ‪22883169 -70 :‬‬

‫اﯾﻤﯿﻞ ‪GENSET-SUPPORT@DORNAMEHR.COM :‬‬

‫‪7‬‬