You are on page 1of 21

Solution Cantilever

Project: Microsoft JKT05

Submitted by: -

Phone Mobile/Office:
E-mail:
Date: 13/02/2023

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 2

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Media Interface
1.5 Gliders
1.6 Release Definition
2 Part list
2.1 Channels
2.2 Base Connectors
2.3 System Connectors
2.4 Accessories
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
3.5 Seismic Load Definition
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 3

1 Geometry and Application

Modular Support Spacing


Main Support Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used?

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 4

1.1 Supports

Concrete supports:

Support No. Orientation Thickness [mm] Concrete grade


- -

Steel supports:

Support No. Orientation Profile Steel grade Rotation


2 Vertical IPE 200 ASTM A36/A36M 0.00°
4 Vertical IPE 200 ASTM A36/A36M 0.00°
6 Vertical IPE 200 ASTM A36/A36M 0.00°

1.2 Nodes

Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
2 1200.00 3650.00 -1000.00Base connector 1 MT-B-O2 MT-B-O2 (C_DF)
4 1200.00 3650.00 -1300.00Base connector 2 MT-B-O2 MT-B-O2 (C_DF)
6 1200.00 3650.00 -1600.00Base connector 3 MT-B-O2 MT-B-O2 (C_DF)

1.3 Members

Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2268506 MT-40 1 2 - - 0.00
2 2268506 MT-40 3 4 - - 0.00
3 2268506 MT-40 5 6 - - 0.00

1.4 Media Interface

No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation

1.5 Gliders

No. Glider No. Position on bar [mm] Travel [mm] Start [mm] End [mm] Custom Load

1.6 Release Definition

Member Releases Member Spring Constants


Release No Ux Uy Uz φx φy φz Cu,x Cu,y Cu,z Cφx Cφy Cφz

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 5

2 Part list

2.1 Channels

Quantity Description Item No. Weight [kg] Length [mm] Cutting type Member No. Price
3 I.-Channel MT-40 2268506 7.28 1190.90 N - None 1, 2, 3 0.00

2.2 Base Connectors

Quantity Description Item No. Weight [kg] Length [mm] Cutting type Node No. Price
3 2-hole Baseplate MT-B-O2 2272094 3.08 - - 2, 4, 6 0.00

2.3 System Connectors

Quantity Description Item No. Weight [kg] Length [mm] Cutting type Node No. Price

2.4 Accessories

Quantity Description Item No. Weight [kg] Length [mm] Cutting type Member No. Price
6 Hexagon bolt MT-TLB 2273254 0.15 - - - 0.00
6 Twist-Lock MT-TL M10 2272080 0.21 - - - 0.00
Threaded stud X-BT-MR M10/15
6 2194340 0.06 - - - 0.00
SN 8
Flat washer 10 10,5x20x2 ISO
6 2184477 0.02 - - - 0.00
7089 A4 200

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 6

3 Load Types

3. Loads

3.1 Loading objects

2D objects:

Allowable Intermediate Actual


No. Description Size [mm] Waterfilled Insulation
spacing [mm] Supports Spacing [mm]
1 Custom Point load - - - - - -
2 Custom Point load - - - - - -
3 Custom Point load - - - - - -
4 Custom Point load - - - - - -
5 Custom Point load - - - - - -
6 Custom Point load - - - - - -
7 Custom Point load - - - - - -
8 Custom Point load - - - - - -
9 Custom Point load - - - - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 7

3.2 Point Loads

No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Seismic (+x) 1 400.00 1.40 -0.00 -0.00 -0.00 -0.00 -0.00
2 Seismic (-x) 1 400.00 -1.40 -0.00 -0.00 -0.00 -0.00 -0.00
3 Seismic (-x) 2 400.00 1.40 -0.00 -0.00 -0.00 -0.00 -0.00
4 Seismic (+x) 2 400.00 -1.40 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (-x) 3 400.00 1.40 0.00 0.00 0.00 0.00 0.00
6 Seismic (+x) 3 400.00 -1.40 -0.00 -0.00 -0.00 -0.00 -0.00
7 Cables 1 600.00 0.00 0.00 -0.44 0.00 0.00 0.00
8 Cables 2 600.00 0.00 0.00 -0.44 0.00 0.00 0.00
9 Cables 3 600.00 0.00 0.00 -0.44 0.00 0.00 0.00
10 Self Weight Support 1 1200.00 0.00 0.00 -0.01 0.00 0.00 0.00
11 Self Weight Support 2 1200.00 0.00 0.00 -0.01 0.00 0.00 0.00
12 Self Weight Support 3 1200.00 0.00 0.00 -0.01 0.00 0.00 0.00

3.3 Distributed loads

Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
13 Self Weight Support 1 0.00 1200.00 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 2 0.00 1200.00 0.00 0.00 -0.02 0.00 0.00 0.00
15 Self Weight Support 3 0.00 1200.00 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

No. Load Type Loading object Load applied to surface Pressure load kN/m²

3.5 Seismic Load Definition

3.5.1 Seismic load factors

3.5.2 Seismic Load Case Weight Activation

Load Case Load Case Name Load Type Seismic


4 Cables Permanent ☑
1 Self Weight Support Permanent ☑

☑All loads in these load cases are converted to seismic in +/-X, +/-Y and +/-Z
☐Loads not considered for seismic load conversion

No. Object Support Spacing Weight


(x) [mm] (y) [mm] (z) [mm] (x) [kN] (y) [kN] (z) [kN]

3.5.3 Horizontal Seismic Design Force

Seismic Forces in: ☑ ☑ ☐


No. Object Seismic Response Coefficient Seismic Load (+/-)
x [-] y [-] z [-] Fx [kN] Fy [kN] Fz [kN]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 8

4 Load Combinations

Design base: Eurocode 1993

Load combination design base: Eurocode 1990

4.1 Ultimate Limit State

Design base: Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC4
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.50 * LC4
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic
1.00 * LC1 + 1.00 * LC4 + 1.00 * LC13
(-z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC4 + 1.00 * LC14
z) + Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic
1.00 * LC1 + 1.00 * LC4 + 0.30 * LC13
(-z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC4 + 0.30 * LC14
z) + Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC4 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC4 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC4 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC4 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC4

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 9

5 Results
5.1 Calculation summary

5.1.1 Members

No Members ULS SLS Status


1 MT-40 56.55% 87.44% OK
2 MT-40 56.55% 87.44% OK
3 MT-40 56.55% 87.44% OK

5.1.2 Base Connectors

No Base connector ULS Status


2 MT-B-O2 84.94% - OK
4 MT-B-O2 84.94% - OK
6 MT-B-O2 84.94% - OK

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 10

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40 Members: 1, 2, 3
5.2.1.1.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 214.00 6.12 57717.48 -2652.65 65876.44
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
259.85 129.92 -2652.65 -3099.95 2782.31 3099.77

5.2.1.1.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
Steel S 280 GD 305.00 210000.00 80769.00 1.10 1.10 1.10

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Member
Type Load Combination: σ[N/mm²] τ[N/mm²]σeqv[N/mm²]σ[N/mm²]limitτ[N/mm²]limitUtilization
No.
1 MT-40 1.35 * LC1 + 1.50 * LC4 156.76 -5.06 156.81 277.27 160.08 56.55%
2 MT-40 1.35 * LC1 + 1.50 * LC4 156.76 -5.06 156.81 277.27 160.08 56.55%
3 MT-40 1.35 * LC1 + 1.50 * LC4 156.76 -5.06 156.81 277.27 160.08 56.55%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 11

5.2.2.2 Governing Member Loading

Beam No. 1

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.50 * LC4 0.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 240.00 kN/kNm 0.00 0.00 0.01 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 480.00 kN/kNm 0.00 0.00 0.01 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 600.00(-) kN/kNm 0.00 0.00 0.02 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 600.00(+) kN/kNm 0.00 0.00 0.68 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 720.00 kN/kNm 0.00 0.00 0.68 0.00 0.09 -0.00
1.35 * LC1 + 1.50 * LC4 960.00 kN/kNm 0.00 0.00 0.69 0.00 0.25 -0.00
1.35 * LC1 + 1.50 * LC4 1200.00 kN/kNm 0.00 0.00 0.69 0.00 0.42 -0.00

Beam No. 2

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.50 * LC4 0.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 240.00 kN/kNm 0.00 0.00 0.01 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 480.00 kN/kNm 0.00 0.00 0.01 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 600.00(-) kN/kNm 0.00 0.00 0.02 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 600.00(+) kN/kNm 0.00 0.00 0.68 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 720.00 kN/kNm 0.00 0.00 0.68 0.00 0.09 -0.00
1.35 * LC1 + 1.50 * LC4 960.00 kN/kNm 0.00 0.00 0.69 0.00 0.25 -0.00
1.35 * LC1 + 1.50 * LC4 1200.00 kN/kNm 0.00 0.00 0.69 0.00 0.42 -0.00

Beam No. 3

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.50 * LC4 0.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 240.00 kN/kNm 0.00 0.00 0.01 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 480.00 kN/kNm 0.00 0.00 0.01 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 600.00(-) kN/kNm 0.00 0.00 0.02 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 600.00(+) kN/kNm 0.00 0.00 0.68 0.00 0.00 -0.00
1.35 * LC1 + 1.50 * LC4 720.00 kN/kNm 0.00 0.00 0.68 0.00 0.09 -0.00
1.35 * LC1 + 1.50 * LC4 960.00 kN/kNm 0.00 0.00 0.69 0.00 0.25 -0.00
1.35 * LC1 + 1.50 * LC4 1200.00 kN/kNm 0.00 0.00 0.69 0.00 0.42 -0.00

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 12

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 13

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 14

Moment around Z

5.2.3 Stability Analysis

Buckling ratio

Max. lateral torsional


Set Max. buckling under
Length [mm] Buckling Length [mm] Buckling ratio buckling under Max. interaction
No. compression
bending
1 1200.00 2400.00 2.00 0.00% 20.51% 20.51%
2 1200.00 2400.00 2.00 0.00% 20.51% 20.51%
3 1200.00 2400.00 2.00 0.00% 20.51% 20.51%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 15

5.2.4 Deflection Analysis


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by
the user.

Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview

Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 + 1.00 * LC4 Relative(Cantilever) 1200.00 L/150 7.00 87.44
2 1.00 * LC1 + 1.00 * LC4 Relative(Cantilever) 1200.00 L/150 7.00 87.44
3 1.00 * LC1 + 1.00 * LC4 Relative(Cantilever) 1200.00 L/150 7.00 87.44

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 16

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC4

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 17

5.3 System Connectors


5.3 Connectors

5.3.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 18

5.4 Base Connectors


5.4 Bases

5.4.1Overview

Base connector 2 - MT-B-O2 Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: 0.00 -0.00 -0.71 0.00 0.42 0.00
Resistance: 12.60 2.43 7.34 0.06 0.55 0.23
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(My.ed/
My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 84.94 % OK

Governing Load
1.35 * LC1 + 1.50 * LC4
Combination

5.4.2 Steel Fastener results

Node no. 2. Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: 1.40 -0.00 -0.47 0.00 0.28 0.00
Anchors X-BT-MR M10/15 SN 8
Base material ASTM A36/A36M
Thickness 8.50 [mm]

Governing Load
1.00 * LC1 + 1.00 * LC4 + 1.00 * LC14
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 19

Anchor Design Checks


abs(Fx.ed/Fx.rd) ⋜ 1;abs(Fy.ed/Fy.rd) ⋜ 1;abs(Fz.ed/Fz.rd) ⋜ 1;abs(Mx.ed/Mx.rd) ⋜ 1;abs(My.ed/My.rd) ⋜
1;abs(Mz.ed/Mz.rd) ⋜ 1;
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(My.ed/My.rd)+abs(Mz.ed/Mz.rd) ⋜
1.2;

Resistance:
Anchor no. Vy Vz
1 ✔ -
2 Friction Lock ✔

Anchor resistance values


NRd[kN] VRd[kN] VRd,fr[kN] α
5.00 6.00 0.28 1

Anchor no. N [kN] Vy [kN] Vz [kN] Vres [kN] N+V


2 Force 0.25 -0.00 -0.47 0.47
2 Utilization 5.07% -0.00% -7.91% 7.91% 10.82%
1 Force 2.45 -0.00 0.00 0.00
1 Utilization 49.01% -0.00% 0.00% 0.00% 49.01%

Node no. 4. Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: 1.40 -0.00 -0.47 0.00 0.28 0.00
Anchors X-BT-MR M10/15 SN 8
Base material ASTM A36/A36M
Thickness 8.50 [mm]

Governing Load
1.00 * LC1 + 1.00 * LC4 + 1.00 * LC13
Combination

Anchor Design Checks


abs(Fx.ed/Fx.rd) ⋜ 1;abs(Fy.ed/Fy.rd) ⋜ 1;abs(Fz.ed/Fz.rd) ⋜ 1;abs(Mx.ed/Mx.rd) ⋜ 1;abs(My.ed/My.rd) ⋜
1;abs(Mz.ed/Mz.rd) ⋜ 1;
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(My.ed/My.rd)+abs(Mz.ed/Mz.rd) ⋜
1.2;

Resistance:
Anchor no. Vy Vz
1 ✔ -
2 Friction Lock ✔

Anchor resistance values


NRd[kN] VRd[kN] VRd,fr[kN] α
5.00 6.00 0.28 1

Anchor no. N [kN] Vy [kN] Vz [kN] Vres [kN] N+V


2 Force 0.25 -0.00 -0.47 0.47
2 Utilization 5.07% -0.00% -7.91% 7.91% 10.82%
1 Force 2.45 -0.00 0.00 0.00
1 Utilization 49.01% -0.00% 0.00% 0.00% 49.01%

Node no. 6. Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 19 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 20

Local Forces: 1.40 -0.00 -0.47 0.00 0.28 0.00


Anchors X-BT-MR M10/15 SN 8
Base material ASTM A36/A36M
Thickness 8.50 [mm]

Governing Load
1.00 * LC1 + 1.00 * LC4 + 1.00 * LC13
Combination

Anchor Design Checks


abs(Fx.ed/Fx.rd) ⋜ 1;abs(Fy.ed/Fy.rd) ⋜ 1;abs(Fz.ed/Fz.rd) ⋜ 1;abs(Mx.ed/Mx.rd) ⋜ 1;abs(My.ed/My.rd) ⋜
1;abs(Mz.ed/Mz.rd) ⋜ 1;
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(My.ed/My.rd)+abs(Mz.ed/Mz.rd) ⋜
1.2;

Resistance:
Anchor no. Vy Vz
1 ✔ -
2 Friction Lock ✔

Anchor resistance values


NRd[kN] VRd[kN] VRd,fr[kN] α
5.00 6.00 0.28 1

Anchor no. N [kN] Vy [kN] Vz [kN] Vres [kN] N+V


2 Force 0.25 -0.00 -0.47 0.47
2 Utilization 5.07% -0.00% -7.91% 7.91% 10.82%
1 Force 2.45 -0.00 0.00 0.00
1 Utilization 49.01% -0.00% 0.00% 0.00% 49.01%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 20 / 21
Version: 1.11.0

Cu.no./ Company: Contact: -


Address: , Solution: Solution Cantilever
Phone Mobile/Office: Date: 13/02/2023
E-mail: Page: 21

6 Remarks, Your Cooperation Duties

Warning messages for manual adjustment of sets of members


The reference length and/or buckling ratio for the stability evaluation in this project was manually adjusted by the user.

Warning messages for manual adjustment of sets of members


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by the user.
General design note
Buckling and LTB checks must always be controlled separately by the responsible designer engineer.
Channel design computation is carried out by the calculation engine from the RSTAB 8.04.0131.84645 framework software by Dlubal, analogous to the
elastic-elastic method inconformance with EC/DIN 18800 for Europe, AISIS100 for the US and SP 16. 13330 for Russia. The connector design method is
based on a combination of serval calculation models following:
for Europe the principles of either DIN 18800 or EC3 and tests carried out by an independent institute (HTL Rankweil, Austria)
for US the principles of AISC360 13th Edition and tests carried out an independent institute (HTL Rankweil, Austria)
for Russia the principles of SP16. 13330 and tests carried out an independent institute (HTL Rankweil, Austria)
XBT threaded bolts and pipe fittings must be calculated separately according to the manual / Hilti FixPoint Calculator.
Local stress and deformation of members at places where load is manually entered is not considered.
Relative deflection evaluation and stability checks: For the relative deflection evaluation and stability checks PROFIS MSE uses a reference length
based on a set of members. A member is a connection form one node to the next on a beam. Members can be connected to a set of members if the
nodes in between do not reduce the reference length. Tis connection of members to a set of members is done automatically based on the assumption
that a node with very low global displacement is eithera support or can be regarded as a support. The global displacement limit to define a node as a
support is 0.1 mm for relative deflection evaluation and 0.005 for stability checks. The connection of members to a set of members can also be done by
the user. The user can also decide manually if a set of members is a single-/multispan beam or a cantilever. The buckling ratio can also be manually
changed. The user can finally also decide to exclude a set of members from the relative deflection evaluation. In case of any manual adjustment you will
find a remark in the report.
The static analysis performed on the basis of a stationary system. 2nd - Order analysis due to possible eccentricities or deflections in the design
(deformation according to DIN 18800 or EC 3 for Europe, ASCE7-05 for the US and SP 20. 13330 for Russia) must be considered separately by the
appropriate personnel.
The maximum distance between supports suggested in Profis MSE is a recommendation based on Hilti experience, standards or specifications from
manufacturer. The installer shall always verify with the pipes, cable trays or air-ducts manufacturer the maximum allowed distance between the supports.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 21 / 21