Bearing Capacity Conformation
Bearing Capacity Conformation
ـ ا
وا
اد او
Hassan Al Amir
Soil Analysis E- mail: hasa.lab1@gmail.com
To : Al Jethoor Engineering Consultants Date : 07/02/2015
Address : Dubai – UAE. Ref. No. : HASA/TL/261014/3576/01
Subject : Technical letter. Rev. No. :0
Project : Villa (G + 1)
Owner : Mr. Abdulla Ahmad Al SAyed Mohammad Al Qurash.
Location : Plot No. 367-253, Um Al Sheif – Dubai.
Dear Sir,
It is much pleasure for us to introduce the following information for the project mentioned above:
Based on your request on 07th February 2015 and HASA soil investigation report No.
HASA/261014/3576 dated on 3rd November 2014 the following must be considered:
Allowable
Depth of Soil Foundation
Bearing
Excavation, Replacement, Level, Type of Foundation
Capacity,
m m m
kN/m2
1.0 - 1.0 150 (Isolated /Conventional Strip Footing)
up to 3.0m width.
1.0 - 1.0 165 (Isolated /Conventional Strip Footing)
up to 2.0m width.
1.0 - 1.0 175 (Isolated /Conventional Strip Footing)
up to 1.5m width.
Levels are from TBM established at the adjacent asphalt road level.
• Bottom of excavation must be compacted to at least 95% of the modified proctor maximum dry
density of soil using a heavy roller. The compacted surface should then be protected by
immediately covering with a layer of concrete blinding.
• The expected total settlement for isolated/strip footing will be ≤25mm.
• All other recommendation will be as of HASA soil report No. HASA/261014/3576 dated on 3rd
November 2014.
Yours faithfully,
HASA LAB
UAE – Dubai – P.O. Box 510, Dubai & د510 . ب.رات ا اة – د& – ص#$%ا
Tel 04 – 341 6086 Fax 04 – 341 6096 04 – 341 6096 8آ#: 04 – 341 6086 ن4567
(Document No. L01, Issue No. 01, Rev. No. 0 - Issued on 01.05.2012)
Page 1 of 1