Kindly elaborate the reply and clarify for which stair natural
ventilation considered? And for which stair mechanical
1 HVAC layout General Comments Incorporate Staircase pressurisation If natural ventilation considered , cross ventilation to be
Noted & incorporated. Planned as per natural ventilation & accordingly Fire NOC received. Noted & accordingly Fire NOC received. pressurisation considered? Becacuse in the drawing at
considered for staircase
DBR page no 35 showing mechanical some of place pressurisation shown and at some of place
pressurisation for stair. Also for above levels ,if it is missing and not shown.
natural ventilation considered , cross ventilation
to be considered for staircase
Required at this satge.
Developer to submit the PHE performance sheet at Partload performance data of Sondex & Alfa Laval at
PHE's generally does not perform at part loads below
100%, 75% , 50% and 25% load condition and Required at this stage. Developer can submit two 25%,50%,75% & 100% for 850 TR PHE submitted, we
2 Page 23 - DBR It will be submitted after the vendor / OEM is finalized 30% due to reduction in velocity creating laminar flow It will be submitted after the vendor / OEM is finalized
temperature & flow as per the DBR for approval. ,three OEM part load performance sheets confirm to provide data for final selection during
conditoon across the plates. Hence part load As per the DBR ,PHE capacity is 550 TR. Kindly submit
procurement stage.
performance is required for review. the details accordigly.
Kindly elaborate the reply and clarify for which stair natural
If natural ventilation considered , cross ventilation to be ventilation considered? And for which stair mechanical
Please clarify which staircase will be pressurised and There are Two Staircases in each of two towers, One Fire Tower
3 Page 28 - DBR which will be naturally ventilated. considered for staircase. Planned as per natural ventilation & accordingly Fire NOC received. Noted and as discussed during last joint meeting, Fire NOC received. pressurisation considered? Becacuse in the drawing at
Staircase is Pressurized while another is Naturally Ventilated.
Please mention the same in DBR & drawings. The staircase ventilation/ pressurization shall be as some of place pressurisation shown and at some of place
per NBC 2016. it is missing and not shown.
Services : ELECTRICAL(6 Nos)
Sr. Point no./
Comments from PDA (07-03-2023) Response from ATOMEP (06-04-2023) PDA REPLY-17.04.2023 Response from ATOMEP (26-04-2023) PDA REPLY-15.05.2023 Response from ATOMEP (20-05-2023) PDA REPLY-05-06-2023
No. Drawing No.
NO LIGHT ON UPS POWER / DURING POWER ups panel o/g feeder 1ph / 3ph pl. mention in SLD / As per
All common area Load considered on Backup power During
4 S-263/LPS/CC/001/002 basment layout Emg. Lighting not shown FAILURE TILL BACK UP POWER START TOTAL Noted and updated. OK CLOSE SLD passage / lobby lighting add in UPS panel / stariase
Emergency. We will apply for backup power accordingly.
DRAKNESS IN BUILDING lighting not shown in UPS panel pl. clerify