Professional Documents
Culture Documents
O V E RV I E W, E F F E C T S , M I T I G AT I O N T E C H N I Q U E S A N D E VA L U AT I O N
PRESENTED BY: DENIS R ESTRELLA, PEE-IIEE
President/Managing Director
FIRST DEERS COSNSULT INC
Partner
MEP Global Inc
OUTLINE ❑ Power System Harmonics?
❑ Why Harmonics are Troublesome?
❑ Nonlinear Loads Producing Harmonic
Currents
❑ Harmonic Distortion?
❑ Negative Effects of Sustained
Harmonics
❑ Mitigation of the Effects of Harmonics
❑ Evaluation of AC Power System
Harmonics?
❑ Conclusions
❑ References
WHAT ARE POWER
SYSTEM
HARMONICS?
Supply Voltage
HARMONICS OVERVIEW
Voltage is typically
supplied as a sine wave.
SYSTEM HARMONICS?
( )
• Fourier Series Y (t ) = ch sin ht + h
h =1
= + h=5
.. h=7
.
. ..
h=11
h=13
HOW ARE
Input Voltage Output Voltage
HARMONICS
PRODUCED ? Input Current Output Current
VFDs
❑ Power system harmonics: presenting
deviations from a perfect sinusoidal-waveform
(voltage or current waveform).
❑ The distortion comes from a Nonlinearity
caused by saturation, electronic-switching
and nonlinear electric loads,
Inrush/Temporal/Arc/Converter/Limiter/Thresh
old Type Loads
❑ Electronic lighting ballasts/Controls
❑ Saturated Inductors/Transformers
❑ LAN/Computer Networks
EFFECT
Reactive power is
wasted energy
❑ Higher reactive power
increases kVA.
❑ Higher kVA requires a larger
transformer.
❑ Higher kVA can increase utility
company demand charges.
HOW TO QUANTIFY
HARMONIC DISTORTION?
❑ Total Harmonic Distortion-THD: the
contribution of all harmonic frequency
Currents/Voltages to the fundamental
current.
• Current THD-I
• Voltage THD-V
15
NEGATIVE EFFECTS OF
HARMONICS
❑ Overheating and premature failure of distribution transformers [1]
❑ Increasing iron and copper losses or eddy currents due to
stray flux losses
❑ Overheating and mechanical oscillations in the motor-load system
[1]
❑ Producing rotating magnetic field, which is opposite to the
fundamental magnitude field.
❑ Overheating and damage of neutral ground conductors [2]
❑ Trouble sustained type Harmonics: 3rd, 9th, 15th …
❑ A 3-phase 4-wire system: single phase harmonic will add
rather than cancel on the neutral conductor
❑ Malfunction/Mal-Operation of Sensitive Tele-control and
Protection Relaying
NEGATIVE EFFECTS OF
HARMONICS
❑ False or spurious Relay operations and trips of circuit breakers [2]
❑ Failure of the Firing/Commutation circuits, found in DC motor-
drives and AC drives with silicon controlled rectifiers (SCR-
Thyristor) [1]
❑ Mal-Operation instability of voltage regulator [1]
❑ Power factor correction capacitor failure [1]
❑ Reactance (impedance)-Zc of a capacitor bank decreases as
the frequency increases.
❑ Capacitor bank acts as a sink for higher harmonic currents.
❑ The System-Series and parallel Resonance can cause
dielectric failure or rupture the power factor correction capacitor
failure due to Over-Voltages & Over-Currents.
NEGATIVE EFFECTS OF
HARMONICS
❑ False or spurious Relay operations and trips of circuit breakers [2]
❑ Failure of the Firing/Commutation circuits, found in DC motor-
drives and AC drives with silicon controlled rectifiers (SCR-
Thyristor) [1]
❑ Mal-Operation instability of voltage regulator [1]
❑ Power factor correction capacitor failure [1]
❑ Reactance (impedance)-Zc of a capacitor bank decreases as
the frequency increases.
❑ Capacitor bank acts as a sink for higher harmonic currents.
❑ The System-Series and parallel Resonance can cause
dielectric failure or rupture the power factor correction capacitor
failure due to Over-Voltages & Over-Currents.
MEAUREMENT OF HARMONICS
❑HARMONICS AND PARALLEL ❑HARMONICS AND SERIES ❑MEASURE EQUIPMENT
RESONANCE CIRCUIT RESONANCE CIRCUIT ❑Digital Oscilloscope: Wave shape,
❑Harmonic currents produced by ❑The voltage of upstream AC THD and Amplitude of each harmonic
variable speed motor-drives: can Network can be also distorted due
be amplified up to 10-15 times in ❑“True RMS” Multi-Meter: Giving correct
to series/parallel resonance formed readings for distortion-free sine waves
parallel resonance circuit formed by by capacitance of the capacitor
the capacitance bank and network and typically reading low when the
inductance [5] bank and System/load inductance : current waveform is distorted
❑Amplified/intensified harmonic Ca cause high harmonic current
currents: leading to internal circulation through the capacitors
overheating of the capacitor unit. [5] ❑Use of Harmonic Meters-Single Phase
or three Phase
❑Higher frequency currents: causing ❑Parallel Resonance can also lead
more losses than 60hz currents to high voltage distortion.
having same amplitude
3.150MVA, 13.8kV 3.150MVA, 13.8kV 3.150MVA, 13.8kV
STANDARDS FOR HARMONICS
LIMITATION IEEE/IEC
IEEE 519-1992 Standard: Recommended
Practices and Requirements for Harmonic
Control in Electrical Power Systems (Current
Distortion Limits for 120v-69kv DS)
MVAsc/
h<11 11<h<17 17<h<23 23<H<35 35<h THDi
MVAL
<20 4.0 2.0 1.5 0.6 0.3 5
20<50 7.0 3.5 2.5 1.0 0.5 8.0
50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<100
12.0 5.5 5.0 2.0 1.0 15.0
0
>1000 15.0 7.0 6.0 2.5 1.4 20.0
STANDARDS FOR HARMONICS
LIMITATION IEEE/IEC
IEEE 519-1992 Standard: Recommended
Practices and Requirements for Harmonic
Control in Electrical Power Systems (Voltage
Distortion Limits)
(Eq-4)
hr = resonant frequency as a multiple of the fundamental frequency
kVAsc = short circuit current as the point of study
kVARc = capacitor rating at the system voltage
MITIGATION OF HARMONICS
❑ Isolation-Interface Transformers
❑ The potential to “voltage match” by stepping
up or stepping down the system voltage, and
by providing a neutral ground reference for
nuisance ground faults
❑ The best solution when utilizing AC or DC
drives that use SCR/GTO/SSR.. as bridge
rectifiers
❑ Line Isolation-Reactors
❑ More commonly used for their low cost
❑ Adding a small reactor in series with
capacitor bank forms a Blocking series Filter.
❑ Use diode bridge rectifier as a front end to
avoid severe harmonic power quality
problems
MITIGATION OF HARMONICS
𝐸2
❑ Harmonic-Shunt or Trap Filters: 𝑋𝑌 =
𝑘𝑣𝐴𝑅
❑ Used in applications with a high 3𝑥𝐸 2
𝑋𝐷 =
non-linear ratio to system to 𝑘𝑣𝐴𝑅
eliminate harmonic currents
𝑋𝐷/𝑌 = 𝑋𝐿 − 𝑋𝑐
❑ Sized to withstand the RMS current
as well as the value of current for 𝑋𝑐 =
1
2𝑓𝐶
the harmonics
𝑋𝑙 = 2𝑓𝐿
❑ Providing true distortion power
factor correction
Harmonic Filter Calculations FIRST DEERS CONSULT INC
Harmonic Filter Calculations: BAY 1; KINGDOME PROJECT
Three-Phase Capacitor Bank Rating: 600 kVAr3φ Capacitor Bank Voltage Rating: 500 Voltsφφ
Rated Capacitor Bank Current: 693 Amps Capacitor Unit Frequency Rating: 60 Hz
𝐸2 Nominal Bus Voltage Rating: 400 Voltsφφ Derated Capacitor Bank Rating: 384 kVAr3φ
System Reactance for Wye Connection, 𝑋𝑌 = Capacitor Bank Current (actual): 554.3 Amps Total Harmonic Nonlinear Load: 1500 kVA3φ
𝑘𝑣𝐴𝑅 Filter Tuning Harmonic (e.g., 4.7): 8.2 th Filter Tuning Frequency (x Fundamental): 492 Hz
System reactance for Delta Connection, 𝑋𝐷 = Harmonic Filter Reactor Reactance: 0.0062 W Harmonic Filter Reactor Inductance: 0.0164 mH
Transformer Nameplate Rating: 1500 kVA3φ Utility Side Voltage Distortion (Vh): 5.00 %
Equivalent Reactance in Series, 𝑋𝐷/𝑌 = 𝑋𝐿 − 𝑋𝑐 Transformer Nameplate Impedance: 5.51 % (Utility Harmonic Voltage Source)
Nonlinear Load Harmonic Current: 63.25 % Fund Nonlinear Load Harmonic Current: 1369.4 Amps
𝑘𝑉 2 1 Utility Harmonic Current: -112.6 Amps Maximum Total Harmonic Current: 1256.8 Amps
𝑄𝑐 2𝑓𝐶 Harmonic Filter Bank RMS Current: 1377.0 Amps Capacitor Bank Voltage (Fundamental): 406.0 Voltsφφ
234.4 VoltsφG
𝑋𝐶 Harmonic Capacitor Bank Voltage: 302.3 Voltsφφ Maximum Peak Voltage (Fundamental): 708.4 Voltsφφ
Inductive reactance of harmonic Order to be trap, 𝑋𝑙 = 2 = 2𝑓𝐿 RMS Capacitor Bank Voltage:
174.6 VoltsφG
506.2 Voltsφφ
409.0 VoltsφG
Value
400 Volt Bus
ℎ2 - + Tuning Range
𝑛
xVbus
1
Capacitor Voltage, 𝑉𝐶 = ℎ2 −1 Capacitor Tolerance:
Reactor Tolerance:
0.00
2.50
10.00
2.50
ftuned = fno min al
(1 + t r )(1 + t c )
7.72
8.30
𝑛 Filter Reactor X/R Ratio: 4.00 Quality Factor: 32.80
Resulting Parallel Resonance: 5.87 (x Fundamental)
Using these formulas, the excel file for sizing the harmonic filter is generated Information contained in this document is subject to change without notice.
Electrotek assumes no responsibility for any damages resulting from use of the information contained within.
Copyright © 2022 FIRST DEERS CONSULT INC. All rights reserved.
MITIGATION OF HARMONICS
3.150MVA, 13.8kV
MITIGATION OF HARMONICS
120.00%
100.00%
𝑘 − 𝑓𝑎𝑐𝑡0 𝑟 = 𝛴 𝐼ℎ2 𝑥 ℎ2
❑ Where 60.00%
Ih = Harmonic Current
h = Harmonic Frequency 40.00%
Below is an example of how to generate the K rating and currents of
the non linear loads 20.00%
Harmonics In x (Non A k-Factor
(In)^2 A x h^2
Number Linear Loads) In/(S(In)^2) (In)^2 h^2
0.00%
1 100.00% 1.000000 0.626488 1.000000 0.626488
1 3 5 7 9 11 13 15 17 19 21 23 25
3 65.70% 0.431649 0.2704230 3.884841 2.433807
5 37.70% 0.142129 0.0890422 3.553225 2.226054
7 12.70% 0.016129 0.0101046 0.790321 0.495127 Calculation of Effective Current at k=10
9 4.40% 0.001936 0.0012129 0.156816 0.098243
0.5
25
11 5.30% 0.002809 0.0017598 0.339889 0.212936
13 2.50% 0.000625 0.0003916 0.105625 0.066173 𝐼𝑒𝑓𝑓 = 𝐼ℎ2 = 1.596199 0.5
= 1.2634
15 1.90% 0.000361 0.0002262 0.081225 0.050887
17 1.80% 0.000324 0.0002030 0.093636 0.058662 𝑛=1
19 1.10% 0.000121 0.0000758 0.043681 0.027366
21 0.60% 0.000036 0.0000226 0.015876 0.009946 THDi = 1.264 – 1 = 26.34%, using the same calculation, the
23 0.80% 0.000064 0.0000401 0.033856 0.02121
25 0.40% 0.000016 0.0000100 0.0100000 0.006265 table of k-factors below are generated
1.596199 1.0000000 10.108991 6.333165
Item Load Type K-Factor THD
1 Linear Loads
1.1 Incandescent Lamps k-1 0
MITIGATION OF HARMONICS 1.2 Heaters
1.3 Motors without Drives
k-1
k-1
0
0
1.4 Cntrol Transformers k-1 0
1.5 Generators k-1 0
❑ K-RATINGS OF Common Loads 1.6 Transformers k-1 0
❑ Linear Loads 2 Non Linear Loads, Low THD
❑ IDL 2.1 Electric Discharge Lightings' k-4 25.82
2.2 UPS k-4 25.82
❑ Heaters
2.3 Welders k-4 25.82
❑ Motors, Control Transformers, Transformer, Generators 2.4 Induction Heaters k-4 25.82
❑ Non Linear – Low THD 2.5 PLC and Solid State Controls k-4 25.82
❑ Electric Discharge Lamps 3 Non Linear Loads, Medium THD
❑ UPS 3.1 Telecommunications Equipment k - 13 57.74
❑ Welders and Induction Heaters 3.2 UPS without input filters k - 13 57.74
❑ PLC and Solid State Controls Multiwire Receptacle Outlets in
3.3 general areas od healthcare k - 13 57.74
❑ Non Linear – Medium THD facilities
❑ Telecoms 4 Non Linear Loads, High THD
❑ UPS 4.1 Main Frame Computers k - 20 80.94
❑ Multiwire outlets in Hospitals 4.2 VFD Driven <Motors k - 20 80.94
❑ Non Linear – High THD Multiwire receptacle outlets in
❑ Computers 4.3 Medical and Educational k - 30 123.54
Laboratories
❑ VFD Drives
4.4 Small Main Frame Computers k - 30 123.54
❑ Multiwire outlets in laboratories Other Loads identified with a very
❑ Others 4.5 k - 40 208.17
high harmonic Contents
SAMPLE CALCULATION
❑ Sample Calculation
❑ 69 kV Side
❑ MVA Fault : 200MVA
❑ Transformers : 2x12.5MVA, 69/13.8 kV
❑ Impedance, %IZ : 8%
❑ 13.8kV
❑ MVA Fault : 122MVA
❑ Transformer bay 1 : 4 x 3.15MVA, 13.8/0.4kV
❑ Load of 400V Side
❑ MVA Fault : 47MVA
❑ Loads
Drives : 1500kVA, k-20
Others : 1600kVA, k-13
❑ 13.8kV
❑ MVA Fault : 122MVA
❑ Transformer bay 1 : 3 x 3.15MVA, 13.8/0.4kV
❑ Load of 400V Side
❑ MVA Fault : 47MVA
❑ Loads
Drives : 2500kVA
Others : 600kV
CALCULATION
❑HARMONICS THD LIMITS AS PER ❑HARMONICS THD LIMITS AS PER ❑HARMONICS THD LIMITS AS PER
IEEE/IEC IEEE/IEC IEEE/IEC
❑69kV SIDE ❑13.8kV SIDE ❑0.4kV SIDE
𝑀𝑉𝐴𝑠𝑐 200 𝑀𝑉𝐴𝑠𝑐 122 𝑀𝑉𝐴𝑠𝑐 47
𝑅𝑎𝑡𝑖𝑜 = = =8 𝑅𝑎𝑡𝑖𝑜 =
𝑀𝑉𝐴−𝐿𝑜𝑎𝑑
=
12.5
= 𝑅𝑎𝑡𝑖𝑜 =
𝑀𝑉𝐴−𝐿𝑜𝑎𝑑
=
3.15
=
𝑀𝑉𝐴−𝐿𝑜𝑎𝑑 25
9.76 15
THDi = 5% THDi = 5% THDi = 5%
THDv = 5% THDv = 5% THDv = 5%
SAMPLE CALCULATION
SYSTEM INFORMATION:
Three-Phase Capacitor Bank Rating: 600 kVAr3φ Capacitor Bank Voltage Rating: 500 Voltsφφ
Rated Capacitor Bank Current: 693 Amps Capacitor Unit Frequency Rating: 60 Hz
Nominal Bus Voltage Rating: 400 Voltsφφ Derated Capacitor Bank Rating: 384 kVAr3φ
Capacitor Bank Current (actual): 554.3 Amps Total Harmonic Nonlinear Load: 1500 kVA3φ
Filter Tuning Harmonic (e.g., 4.7): 8.2 th Filter Tuning Frequency (x Fundamental): 492 Hz
Capacitor Bank Reactance (wye): 0.4167 W Capacitor Bank Capacitance (wye): 6366.20 mF
Capacitor Bank Reactance (delta): 1.2500 W Capacitor Bank Capacitance (delta): 2122.07 mF
Harmonic Filter Reactor Reactance: 0.0062 W Harmonic Filter Reactor Inductance: 0.0164 mH
Filter Full Load Current (actual): 562.6 Amps Fundamental Frequency Compensation: 390 kVAr3φ
Filter Full Load Current (rated): 703.3 Amps
Transformer Nameplate Rating: 1500 kVA3φ Utility Side Voltage Distortion (Vh): 5.00 %
Transformer Nameplate Impedance: 5.51 % (Utility Harmonic Voltage Source)
Nonlinear Load Harmonic Current: 63.25 % Fund Nonlinear Load Harmonic Current: 1369.4 Amps
Utility Harmonic Current: -112.6 Amps Maximum Total Harmonic Current: 1256.8 Amps
CAPACITOR BANK DUTY CALCULATIONS:
Harmonic Filter Bank RMS Current: 1377.0 Amps Capacitor Bank Voltage (Fundamental): 406.0 Voltsφφ
234.4 VoltsφG
Harmonic Capacitor Bank Voltage: 302.3 Voltsφφ Maximum Peak Voltage (Fundamental): 708.4 Voltsφφ
174.6 VoltsφG 409.0 VoltsφG
RMS Capacitor Bank Voltage: 506.2 Voltsφφ
292.3 VoltsφG Maximum Peak Current: 1819.4 Amps
CAPACITOR LIMITS: (IEEE Standard 18-2002) FILTER CONFIGURATION:
400 Volt Bus
Limit Contingency Actual Value
Peak Voltage: 100% 120% 141.7% 708
RMS Current: 100% 135% 198.8% 1377
Xl = 0.0062 W
KVAr: 100% 135% 201.2% 1207 600 kVAr @
RMS Voltage: 100% 110% 101.2% 506 500 Volts
- + Tuning Range
1
Capacitor Tolerance: 0.00 10.00 ftuned = fno min al 7.72
Reactor Tolerance: 2.50 2.50 (1 + t r )(1 + t c ) 8.30
THANK YOU