Professional Documents
Culture Documents
This excitation current could be as large 3 to 12 as possible of transformer rating current and results
in nuisance tripping of protective devices and creates large mechanical forces within the transformer
core and windings.
From the factors mentioned above electrically, transformer size, system grounding and X/R ratio are
investigated using ETAP and Simulink and differences discussed to get a better clarification why this
synthetic inrush can have impact on the undervoltage and under frequency protection units.
Conclusion: ETAP does not consider the ungrounded sources where Simulink takes it into the
calculation and observed from plots, red grounded & orange ungrounded sources, the inrsuh current at
instant 0.1 (s) reaches to 1206.50 (A) while for an effective grounded system the inrsuh at 0.1
switching close, does not exceed more than 738.95 (A).
In compliance with the grid code, the voltage drop at POC of the network will have impact on
undervoltage relay settings and it helps to adjust relay settings based on voltage variations.
X/R ratio, MVA fault levels and source impedances are the factors mentioned above which increases
the DC offset and prolongs decay when it gets higher.
To get better results manufacturer data sheets including the inrush currents, saturation values and flux
percentages are required.
Inrush Current Inrush Current
1.20E+03 8.00E+02
1122.34667 (A) 738.9588363 (A)
7.00E+02
1.00E+03
6.00E+02
8.00E+02
5.00E+02
6.00E+02 4.00E+02
3.00E+02
4.00E+02
2.00E+02
2.00E+02 1.00E+02
0.00E+00
0.00E+00
-1.00E+02
-2.00E+02
30 MVA X/R 7 D1/Yg source grounded 15 MVA X/R 7 Yg/Yg source grounded
4.00E+02 6.00E+02
4.00E+02
2.00E+02
2.00E+02
0.00E+00
0.00E+00
-2.00E+02 -2.00E+02
15 MVA X/R 15 D1/Yg source grounded 30 MVA Yg/Yg X/R 15 source ungrounded
Fig 1: Simulink plots for four cases grounded and ungrounded sources
ETAP Inrush Current ETAP Inrush Current
900 500
450
800
400
700
350
600 300
500 250
200
400
150
300
100
200 50
100 0
1
41
81
121
161
201
241
281
321
361
401
441
481
521
561
601
641
681
721
761
801
841
881
921
961
1001
1041
1081
1121
1161
1201
1241
1281
1321
1361
1401
1441
1481
0
ETAP Inrush current 30 MVA X/R 7 D1/Yg source grounded ETAP Inrush current 15 MVA X/R 7 D1/Yg source grounded
76300
100
76200
95
76100
76000 90
75900
85
75800
80
75700
75600 75
Simulink Model Volatge drop at POC 10% ETAP Model Volatge drop at POC 13%
Fig 2: ETAP & Simulink bus volatges drop and Inrush currents
Fig 3: ETAP distribiuted network model 132kV, 33kV, 6.6 kV
Fig 4: Simulink distributed network model