You are on page 1of 4

ER.R. PERIYASAMY. ME(STRUCT),M.SC(VALUATION), (PHD),MIE.,FIV.,PGDQSYV.

CHARTERED ENGINEER &REGISTERED VALUER

APPROVED VALUER OF INCOME TAX DEPT.-PANEL VALUER OF BANKS-STRUCTURAL CONSULTANT-


CONSULTANT FOR FLAT BUYERS-PANEL ENGINEER FOR LSSUING STABILITY CERTIFICATES FOR PUBLIC
BUILDINGS AND FACTORY BUILDINGS.

PERS/ITV/6056/21-22

16.02.22

PAGES 1OF5

STRUCTURAL ENGINEER’S CERTIFICATE

PURSUANT TO THE REQUEST FROM MR. VINODH, (+918056273269) M/S.INDUSAL CORP HAVING THEIR
OFFICE AT NO: 3E JEVARATHINAM 1ST STREET, KSR NAGER, MTH ROAD,AMDATTUR,CHENNAI,TMAIL
NADU, 600053, I CHECKED THE DRAWING PREPARED BY M/S.INDUSAL CORP FOR THE PROPOSED MS
STRUCTURAL STAGING WITH HORIZONTAL PLATFORM IN MS CHEQUERED PLATE ON WHICH TWO AC
CHILLER UNITS HAVING WEIGHT OF 1500 KG EACHARE PROPOSED TO BE MOUNTED, INSIDE THE
FACTORY SHE OF THEIR CLINE M/S BONFIGLIOLI TRANSMISSIONS PRIVATE LIMITED, AC7/AC11, SIDCO
INDUSTRIAL ESTATE, THIRUMUDIVAKKAM, CHENNAI 600044 FOR THE ISSUING STABILITY CERTIFICATE
FOR THE STRUCTURAL STAGING.

DESCRIPTION OF THE STRUCTURE

THIS MS SUPPORTING STRUCTURE IS HAVING SIX MS COLUMNS PROVIDED IN ISMB 150IN TWO ROWS
HAVING A SPAN OF 1050MMWITH THREE COLUMNS OF 2000MM HIGH IN EACH ROW SPACED AT A
EQUAL SPACING OF 2500M. THESE COLUMNS HAVE BEEN ANCHORED TO THE RCC FLOORWITH MS BASE
PLATES AND ANCHOR BBOLTS. ALLTHREECOLUMNS IN TWO ROWS HAVE BEEN CONNECTED WITHTWO
BEAMS PROVIDED IN ISMB 150MM LONGIN LONGER DIRECTION OF THE STRUCTURE. IN THE OTHER
DIRECTION AISO THREE BEAMS HAVE PROVIDED WITH SAMEISMB150 CONNECTING COLUMNS AT
1050MM AND PROJECTING 725 MM ON ONE SIDE BEYOND THE COLUMNS AS CANTILEVER TO MAKE
THE SIZE OF THE PLATFORM 5000X1775MM. ALL THE THREE PROJECTED ISMB 150 HAVE BEEN
CONNECTED WITH ISMC100. THUS, AFTER PROVIDING THE ABOVE SIX BEAMS OVER THE SIX COLUMNS,
TWO BAYS OF 2500X1050 WITHIN THE SIX COLUMNS AND TWO BAYS OF 2500X725 IN THE PROJECTED
AREA BEYOND THE COLUMNS LINE. IN THESE FOUR BAYS , IN EVERY BAY FOUR SECONDARY BEAMS
HAVE BEEN PROVIDED WITH 1050MM AND 725MM ONG ISMC 100.THESE BEAMS 5MM THICK
CHEQUERED PLATE HAS BEEN PROVIDE FOR THE ENTIRE DECK SIZE OF 5000X1775MM.SAFETY RAILING
HAS BEEN PLANNED WITH MS TUBES AROUND THE PLATFORM OVER THE DECK TOP .IN THE DRAWING
PROVIDED TO ME, NO PERMANENT STAIR/ LADDER HAS BEEN PLANNED FOR.
TECHNICAL DETAILS

SIZE OF THE PLATFORM : 5000X1775MM

HEIGHT OF THE PLATFORM FROM GL : 2000MM

NUMBER OF CHILLERS : TWO

WEIGHT OF EACH CHILLER : 1500KGS

COLUMN SUPPORTINGBASE (FOUNDATION) : RCC FACTORY FLOOR OF 225MM THICK

SUPER STRUCTURE :MS COLUMNS WITH MS DECK

OLD NO. 15, NEW NO.33,8TH CROSS STREET, SHENOY NAGAR WEST CHENNAI 600030.

PH: 45506087,26286087/MOBILE 9840046087

EMAIL: RPERIYASAMY@REDIFFMAIL.COM/PERIYASAMY@CHENNAIENGINEER.COM

WWW.CHARTEREDENGINEER.IN

ER.R. PERIYASAMY. ME(STRUCT),M.SC(VALUATION), (PHD),MIE.,FIV.,PGDQSYV.

CHARTERED ENGINEER &REGISTERED VALUER

APPROVED VALUER OF INCOME TAX DEPT.-PANEL VALUER OF BANKS-STRUCTURAL CONSULTANT-


CONSULTANT FOR FLAT BUYERS-PANEL ENGINEER FOR LSSUING STABILITY CERTIFICATES FOR PUBLIC
BUILDINGS AND FACTORY BUILDINGS.

PERS/ITV/6056/21-22

16.02.22

PAGES 2OF5

CERTIFICATE

IT IS CERTIFIED THAT BASED ON STRUCAL DRAWINGS PROVIDED TO ME PREPARED DY M/S.INDUSAL


CORP. INFORMATION PROVIDED BY CORPAND ASLO BASED ON THE ANALYSIS AND CALCULATIONS
MADE BY ME AS PER INDIAN STANDARD CODES. THE PROPOSED MS STRUCTURAL OVERHEAD
PLATFORM FOR SUPPORTING TWO AC CHILLER UNITS HAVING TOTAL WEIGHT OF 3000 KG
(2X1 500KG) TO BE FABRICATED AND ERECTED AS PER THE STRUCTURAL DRAWINGS PROVIDED TO ME
IN ABOVE MENTIONED ADDRESS WILL BE STRUCTURALLY SOUND AND SAFE FOR CARRYING THE LOAD
DUE TO THE SELF-WEIGHT OF THE CHILLERS AND OTHER INCIDENTAL AND OPERATING LOADS DUE TO
THE OPERATING AND SERVICE PERSONS USING THE PLATFORAM.

(R. PERIYASAMY)

CHARTERED ENGINEER & STRUCTURAL CONSULTANT

ER.R. PERIYASAMY

ME(STRUCT),M.SC(VAL).(PHD) PGDQSYV MIE.,FIV,MIGS

CHARTERED ENGINEER & GOVT. REGD VALUER, C ENG NO. 121991-4

AUTHORIZED ENGINEER TO ISSUE STABILITYCERTIFICATES FOR


PUBLIC & FACTORY BUILDINGS OLD NO.15,NEW NO.33,8 TH CROSS STREET, SHENOY NAGAR ,
CHENNAI-600030.

NOTE:

1. ADDITONAL LOAD SHOUD NOT BE PUT UP ON THE PLATFORM OR TO THE SUPPORTING


COLUMNS
2. ALL JOINTS, SECTIONS, BOLTS. PLATES, WELDING AND CONNECTIONS SHOULD CONFIRM IS
STANDARDS
3. MODIFICATION OR ALTERATION SHOULD NOT BE DONE TO THE STRUCTURE / PLATFORM/
DRAWING
4. PLEASE ENSURE THAT THE EXISTING RCC FLOOR IS HAVIING SUFFICIENT STRENGTH, THICKNESS
AND VOID FREE BASE BELOW.
5. THREE DRAWINGS PROVIDED TO ME BY M/S.INDUSAL CORP HAVE BEEN SIGNED BY ME AND
ANNEXED TO THIS CERTIFICATE
6. ALL STRUCTURAL MEMBERS SHOULD BE MAINTAINED PROPERLY, PERIODICALLY AND
PROTECTED FROM CORROSION TO HAVE STRUCTURAL SLABILITY AND BETTER LIFE.
7. THOUGH THE STRUCTURAL DRAWINGS PROVDED TO ME ARE SATISFYING THE STRUCTURAL
DESIGN REQUIREMENTS, THIS CERTIFICATE DOESN’T COVER / CERTIFY THE STRUCTURAL
STABILITY OF THE PLATFORM AT THE SITE.