Class I Class II Class II

Earthed appliances Double insulated S.E.L.V


Plug appliance into PAT tester, switch appliance S.E.L.V
Plug appliance into PAT tester, switch appliance on on and attach earth clip to exposed metal Safety Extra Low Voltage (Under 50
and attach earth clip to exposed metal (If no exposed metal attach earth clip to cable Volts)
If no exposed metal VOID earth test only and supply entry point.
reason.

A. Lead <5M (0.1+R of lead) C. Any lead length D.

M Earth <0.1Ω Earth N/A Visual inspection only


A Insulation >1MΩ Insulation >2MΩ
N 100/200mA – IT
D 20/25A – Standard
A
T B. Lead >5M (0.1+R of lead)
O
R Earth <0.1Ω
Y Insulation >1MΩ
100/200mA – IT
20/25A – Standard
O
P Leakage test (do not attach earth clip) Leakage test (attach earth clip)
T
I <0.75mA – Class I Hand held & portable <0.25mA –Class II equipment
O <3.5mA – All other class I
N
Load/Run test –Check against serial plate Load/Run test –Check against serial plate
A
L