Request For Inspection

r
i to
Date: 17 AUG.2023
Request no. RFI-CSCEC-D01-ME-04-0125-01
Project No. & Title: E21110-0100S - Alamein Downtown Towers

Ed
Employer: Engineer: Contractor:

We request your attendance to inspect the following works :

DF
1. Type : PLUMBING (water supply ) Electrical Mechanical installations

2. Inspection Time : 10:00 AM Date : 18 AUG.2023


3. Location: Zone Road Stations Structure Other
D01 1 Raft
4. Inspection : First Second Third

rP
5. Purpose of Inspection :
1. Electrical 2. Mechanical
Setting out Light fittings Mechanical installations
Furniture elect. culvert Sub-stations Pumping stations
MV cables Civil works & finishings Civil works & finishings
Street lighting cables
te
Street lighting poles

Telephone duct Bank

TV cables
as

Others (specify) (Installation of PPR water supply system )


PPR pipes of water supply at 4th floor at zone1 exclude the (main valves ,water meter and relief valves ) & Drawings
Particular Details as follows:
(SHD-CSCEC-D01-ME-PL-01-04-00-0001-0000-04) & (SHD-CSCEC-D00-AR-ID-07-ML-00-0008-0001-01)
M

(SHD-CSCEC-D00-AR-ID-07-ML-00-0008-0007-00) & (SHD-CSCEC-D00-AR-ID-07-ML-00-0021-0001-01)

Submitted by : Ali Elkahlawy Signature:

6. Inspection report : Signature


in

Surveyor inspection is done for water supply system in 4th floor zone 1
according to approved shop drawing and detailed plans attached.
Elect. Eng. inspection is done according to the concrete spots which not
Mech. Eng. approved and the contractor is the sole responsible for any changes. Abanob Saad
labels and identifications shall be provided for all pipes.
Civil Eng. seismic supports shall be added if needed.
ed

final approval is subjected to the pressure test inspection.

Date/time of inspection :

7. Engineer's Representative Comments:


at

The works are : Approved Approved as Noted Rejected


re

Signature Khaled Shehata Date : 23/08/2023

Attach all relevant particular test forms


Approval shall not relieve Contractor of his liabilities under the Contract or constitute authorization of any change to Contract Documents.

S-PRC-SS-02(F31) Rev 2
KEY PLAN:

D01 D01 D01


NORTH

r
───── ───── ─────
T11 T12 T13

ABBREVIATIONS D01M D01

D02M D02
AAV AUTOMATIC AIR VENT

to
BV BALL VALVE
D01 D01
───── ─────
BFV BUTTERFLY VALVE
T01 ceilinglimit ceilinglimit T01
GV GATE VALVE

HB HOSE BIB
CWS Φ20 BOP+2830

150

150
CWS Φ20 BOP+2810 +3.600

195
195
HWS Φ20 BOP+3010 HWS Φ20 BOP+3010 F.F.L
CP CIRCULATION PUMP

F.F.L BP BOOSTER PUMP


Ø25 CWS ABOVE Ø25 CWS ABOVE
CEILING CEILING PG PRESSURE GAUGE
7000

KITCHEN KITCHEN +2.600 PRV PRESSURE REDUCING VALVE


TERRACE HWS Φ20 BOP+3010 MAID
ROOM
MAID
ROOM
TERRACE F.C.L CWS TO PRV

CWS Φ25 BOP+2810 HWS Φ20 BOP+3010 APARTMENTS

di
CWS Φ40 BOP+2970 CWS Φ25 BOP+2830 WM WATER METER
CWS Φ32 BOP+2945 CWS Φ32 BOP+3095 RECEPTION Ø65mm CWS,HDPE
ceilinglimit

RECEPTION LOBBY LOBBY


CWS Φ40 BOP+2820 IV T01
HWS Φ20 BOP+3010 04 WH 80 06 F/A FROM ABOVE
CWS Φ40 BOP+2800 HWS Φ20 BOP+3010 Ø65mm CWS,PPR

3600
CWS Φ20 BOP+3100 04 WH 100 12 5/4/2023
O W
04 WH 80 07 BV
Ø150mm CWP RISER,
HDPE, FA/TB Khaled Shehata F/B FROM BELOW
MAID HWS Φ20 BOP+3010 MAID HWS Φ25 BOP+3170
H W SH CH 04 WH 100 13 LAUNDRY TOILET TOILET LAUNDRY
Ø25 CWS CV WM IV
T/A TO ABOVE
CWS Φ25 BOP+3100 Ø150mm STORM STACK

150
150
20 250 UPVC,FA/TB
135
O W
HWS Φ20 BOP+3010 HWS Φ25 BOP+3140 Ø20 CWS FOR Ø100mm CWS RISER, TOWER KEY PLAN

20
CWS Φ20 BOP+2950 H W SH CH FLUSH TANK
Ø20 CWS FOR FLUSH
HDPE, FA/TB T/B TO BELOW

150
TANK
HWS Φ25 BOP+3130 CWS Φ25 BOP+2790 D01
Ø20 CWS PIPE FOR
D01
CWS Φ25 BOP+3170 150

580
TRIGGEER SPRAY
───── 150 125 150 150
HWS Φ25 BOP+2530 ───── Ø20 CWS FOR D/N DOWN

785
145
T02 CWS Φ25 BOP+2640 275
CWS Φ32 BOP+2825 T02
TRIGGEER SPRAY

180

700

480
CWS Φ40 BOP+2780 GUEST GUEST TWO OUTLETS ANGLE

620
TOILET
CWS Φ32 BOP+2805 B.V TOILET VALVE
F.F.L
H/L HIGH LEVEL
HWS Φ25 BOP+3010 CWS Φ32 BOP+2735
300 Ø110 DRAINAGE PIPE
TO SOVENT STACK
CWS Φ25 BOP+2740

600
L/L LOW LEVEL

300

230 70
CWS Φ25 BOP+2810

410

410
595

300
HWS Φ20 BOP+3010 HWS Φ20 BOP+3010

220 100115

E
CORRIDOR CORRIDOR
CWS Φ20 BOP+2890 F.F.L
U/T UNDER TILES
BEDROOM
CWS Φ20 BOP+2810 150
150
BEDROOM

D-2-E-1

D-2-E-2
HWS Φ25 BOP+3170 Provide two angle valves
ENTRANCE ENTRANCE HWS Φ25 BOP+3170
HWS Φ20 BOP+2940 LOBBY LOBBY
HWS Φ20 BOP+2940
CWS Φ32 BOP+2815 one for Hand spray and another one
CWS Φ32 BOP+2815
150 for WC douche
150
Please check with the WC manufacturer the ability of
7800

150
hidden connection to WC douche.
630 150

CWS Φ32 BOP+2815


CWS Φ25 BOP+2820 CWS Φ25 BOP+2820
CWS Φ32 BOP+2815 CWS Φ32 BOP+2815
HWS Φ20 BOP+2940 CWS φ25,BOP+2800mm
HWS Φ20 BOP+2940 BATHROOM BATHROOM
CWS Φ32 BOP+2815 CWS Φ32 BOP+2815

240
MASTER 150 MASTER
150
CWS Φ32 BOP+2815
ceilinglimit

ceilinglimit
BEDROOM BEDROOM
ELEVATION FROM F.F.L
145
50

HWS Φ20 BOP+2940


150
150

CWS Φ32 BOP+2815 BOTTOM OF PIPE


CWS Φ32 BOP+2815 +3.600
HWS Φ20 BOP+2940
DRESSING DRESSING F.F.L
CWS Φ25 BOP+2820
ROOM
MASTER MASTER
ROOM
HWS Φ20 BOP+2940 +3.600
F.F.L PIPE SIZE
BATHROOM BATHROOM

CWS Φ25 BOP+2820


SYSTEM TYPE
895

CWS Φ25 BOP+2770 HWS ABOVE CEILING HWS ABOVE CEILING

F
295

Ø25 CWS ABOVE WITH INSULATION


Ø25 CWS ABOVE WITH INSULATION
D01 HWS Φ20 BOP+2820 D01 CEILING
CEILING
CWS ABOVE CEILING
Ø20 HWS IN WALL
WITHOUT INSULATION L04-EWH_50L-05
───── ───── Ø20 CWS ABOVE CEILING
T03 CWS Φ25 BOP+2770 150 T03
RAIN SHOWER
150 +2.450 +2.600

HWS Φ20 BOP+2820 185


CWS Φ25 BOP+2760
F.C.L F.C.L
Ø20 CWS IN WALL SEQUENCE NUMBER

Height and actual location of the vertical pipes the connected


Ø20 HWS IN WALL WITHOUT
INSULATION
290 DRESSING
ROOM CWS Φ32 BOP+2755 EQUIPMENT CAPAICITY
RECEPTION Ø20 CWS IN WALL
KITCHEN & HWS Φ20 BOP+2900 EQUIPMENT TYPE

3600
HWS Φ20 BOP+2900 LEGEND
150

DINING

to the sanitary fixtures should be as per ID drawings.


MASTER
MASTER

3600
CWS Φ25 BOP+2770 BATHROOM
BEDROOM 150 127 FLOOR NUMBER
D-1-A-1

CWS Φ40 BOP+2760 Ø20 MIXED WATER


PIPE IN WALL, PPR
TERRACE CORRIDOR CWS Φ32 BOP+2755
CWS Φ25 BOP+2640 Ø25 CWS
HAND SHOWER

D
LAUNDRY
CWS Φ40 BOP+3155
150

350

350
CWS Φ40 BOP+2760
7800

185

MASTER SHOWER MIXER


310
BATHROOM
Ø20 CWS FOR SHOWER MIXER

04 WH 80 04 LAUNDRY 04 WH 80 05 Ø20 CWS FOR


FLUSH TANK 300 300
TRIGGEER SPRAY
D-1-B-1

375
CWS Φ25 BOP+3130 CWS Φ25 BOP+2760 Ø20 CWS PIPE FOR
shower mixer connection

900
Ø20 CWS FOR FLUSH
O W 150 690 150
HWS Φ20 BOP+2790
TERRACE TRIGGEER SPRAY

900
TANK
refer to the data sheet of

1000

1000
H W SH CH Ø110 DRAINAGE

600
O W PIPE TO

400
400
MASTER
HWS Φ25 BOP+3170 150 SOVENT STACK
the approved material submittal HDPE PIPE SIZE SDR (11) PN (16) BAR

300
KITCHEN &
H W SH CH

170 180

170 180
BEDROOM DINING RECEPTION
CWS Φ32 BOP+2765 60
F.F.L
pipe size Internal Diameter Wall Thickness
F.F.L
Showing in the dwg. (in mm) (in mm)

170
170
CWS Φ32 BOP+2765 (in mm)
CWS Φ25 BOP+2770 63 51.4 5.8
8.2
NOTES
CWS Φ25 BOP+2890 90 73.6
HWS Φ20 BOP+2940 110 90.0 10.0 1-ALL PIPE LEVELS ARE MEASURED FROM FINISHED FLOOR
D01 195 D01
14.6 LEVEL,AND ALL PIPE LEVELS ARE IN METER.

rP
───── 150 ───── 160 130.8
T04
150
CWS Φ32 BOP+2815 T04
HWS Φ20 BOP+3110
CWS Φ20 BOP+2820
880

CWS Φ32 BOP+2815 2-ALL EQUIPMENT ,PIPES AND FITTINGS ARE AS PER
CWS Φ32
DRESSING
BOP+2815
MASTER
BATHROOM 150 420
HWS
150
Φ25
ROOM
BOP+3110 SPECIFICATIONS AND APPROVED MATERIAL SUBMITTAL.
STAIR 03
CWS Φ25 BOP+2820 04 WH 50 10
235

HWS Φ20 BOP+3110 04 WH 100 BEDROOM


08
MASTER

CWS Φ20 BOP+2820 LAUNDRY


150

MASTER
PPR PIPES SCHEDULE
ceilinglimit

ceilinglimit

BEDROOM
150 O W
CWS Φ25 BOP+2820 CWS Φ32 BOP+2815 H W SH CH PIPE SIZE Ø (mm) OUTSIDE Ø (mm) INSIDE Ø (mm) THICKNESS (mm)
50

CWS Φ20 BOP+2820 CWS Φ40 BOP+2810


+3.600
F.F.L
+3.600
F.F.L +3.600
700 370 580 F.F.L
HWS Φ20 BOP+2970
150
HWS Φ20 BOP+3170 20 20 13.2 3.4 PROJECT NAME:
7800

MASTER CWS Φ32 BOP+2815


BATHROOM
CWS Φ20 BOP+2720 CWS Φ20 BOP+2820
BATHROOM
HWS Φ25 BOP+3110
CWS ABOVE
HWS Φ20 BOP+2970 HWS Φ20 BOP+3110 25 25 16.6 4.2
Alamein Downtown Towers
CEILING Ø20 HWP IN WALL +3.080
CWS Φ32 BOP+2815 Ø20 HWS ABOVE
CEILING WITH
WITHOUT INSULATION ELECTRIC WATER 150 F.C.L
150 CWS Φ40 BOP+2810 INSULATION
HEATER
Electric Water 32 32 21.2 5.4
D-2-A-5

Heater
HWS Φ20 BOP+2890 LOBBY
ENTRANCE
+2.600
150 F.C.L Ø20 HWS IN WALL
Ø20 CW PIPE IN
+2.450 40 40 26.6 6.7
HWS Φ20 BOP+2970 CORRIDOR
WALL
F.C.L
550 150

BEDROOM BEDROOM Ø20 CWS IN WALL


150
HWS Φ25 BOP+2970 50 50 33.4 8.3
CWS Φ32 BOP+2815 FLEXIBLE HOSE FLEXIBLE HOSE
CWS Φ32 BOP+2815
CWS Φ20 BOP+2820 150 63 63 42.0 10.5

3600
3600
GUEST

3600
TOILET
TERRACE 950 CLIENT:
50

CORRIDOR BATHROOM 75 75 50 12.5


For WM 25 mm
D01 O W D01 FLEXIBLE HOSE
90 90 60 15.0

te
150
FLEXIBLE HOSE
───── ─────
T05 H W SH CH T05
FAUCET FOR WM FAUCET FOR WM
110 110 73.4 18.3
04 WH 100 11
CWS Φ25 BOP+2820
Ministry of Housing, Utilities
Ø50 DRAINAGE
LAUNDRY V-3
PIPE IN WALL
04 WH 50 09
150 150 150 125 125 83.4 20.8
HWS Φ20 KITCHEN
BOP+3010
&

500
135 245 DINING
HWS Φ25 BOP+3130

650
Ø50 DRAINAGE

& Urban Communities


Ø50 DRAINAGE
150
S1

PIPE UNDER TILE PIPE IN WALL 140 140 93.4 23.3


130

RECEPTION
RECEPTION HWS Φ25 BOP+3170 500

550

550
200 150

528
CWS Φ25 BOP+2880 FLOOR DRAIN Ø50 DRAINAGE

550

550
925
PIPE TO FLOOR 160 160 106.8 26.6

200
CWS Φ32 BOP+2875 F.F.L
DRAIN F.F.L
CWS Φ40 BOP+2870 GUEST
F.F.L

170
TOILET
CWS Φ25 BOP+2880
D-2-B-1
7800

LOBBY
ENTRANCE

INDIVIDUAL FIXTURES PIPE SIZE TABLE New Urban Communities


CW-( PPR ) HW-( PPR )
Authority

as
KITCHEN

RECEPTION FIXTURE
OD Ø (MM) ID Ø (MM) OD Ø (MM) ID Ø (MM)
CWS Φ40 BOP+2615
CWS Φ25 BOP+2715 - -
HB 25 16.6 THE ENGINEER:
150

150 150

CWS Φ25 BOP+2715


KITCHEN &
CWS Φ25 BOP+2865
190

DINING
S1

CWS Φ25 BOP+2865 - -


WM pipe size for one bed room 40 mm,WM pipe size for 2,3 & 4 bed rooms 50 mm WC (FT+HS) 25 16.6

LAV 20 13.2 20 13.2


D01 CWS Φ32 BOP+2865 D01 Common comments should be applicable on all apartments SH
───── HWS Φ20 BOP+3010 ───── 20 13.2 20 13.2
Guest toilet Faucet is wall mounted type, check the data sheet and the height should be as per ID drawings (typical)
150
T06 CWS Φ32 BOP+2865 T06
KS 20 13.2 20 13.2 Shair & Partners
150

HWS Φ20 BOP+3030 170 CORRIDOR


CWS Φ20 BOP+2740 - -
CWS Φ20 BOP+2890 GUEST HWS Φ20 BOP+3010 DW 25 16.6
HWS Φ20 BOP+3030
MASTER
CWS
BATHROOMΦ25 BOP+2890
TOILET CWS Φ20 BOP+2870 CONTRACTOR:
130

CWS Φ50 BOP+2550 W/M 25 16.6 - -


150

MASTER
CWS Φ50 BOP+2865
CWS Φ40 BOP+2615 BEDROOM
D01
─────
D01
───── Water heater pipe size 25 mm inlet and outlet (for 50, 80, 100 L)
D01
─────
D01
─────
D01
─────
D01
─────
D-2-A-4

LOBBY
BEDROOM
04 WH 80 03 CWS Φ25 BOP+3170 ENTRANCE T14 T15 T16 T17 T18 T19
HWS Φ20 BOP+3130
150

O CORRIDOR
W LAUNDRY

H W SH CH HWS Φ20 BOP+3130


CWS Φ50 BOP+2670
7750

CWS Φ40 BOP+2930 CWS Φ40 BOP+2880


BATHROOM
M valves quantity
D-1-C-1

HWS Φ20 BOP+3030 should be verified


CWS Φ20 BOP+2730 MAIN EQUIPMENT SCHEDULE
TERRACE
555 150 HWS Φ20 BOP+3010 REFERENCE TABLE:
HWS Φ20 BOP+3020 TYPE SIZE QUANTITY
HWS Φ20 BOP+2900 150
CWS Φ32 BOP+2725
CWS Φ20 BOP+2730 LAUNDRY
MASTER
04BEDROOM
WH 50 07
TERRACE Ø 20mm 47 Type No. Ref. No. Date
150

HWS Φ20 BOP+3110 475


HWS Φ20 BOP+3130
TERRACE
KITCHEN & CWS Φ32 BOP+2725 Ø 25mm 28
RECEPTION
CWS Φ25 BOP+2940 DINING
CWS Φ50 BOP+2550 04 WH 100 09 ISOLATION VALVE Wrong quantity of WM 1 SHD-CSCEC-D01-AR-AR-01-04-00-0001-0000-01 10-10-2022
MASTER 370 O W 25
CWS Φ40 BOP+2615 BATHROOM 150 150 DRESSING
Ø 32mm
2 SHD-CSCEC-D01-ST-SC-04-04-01-0001-0000-01 01-08-2022
CWS Φ50 BOP+2670 H W SH
ROOM CH
CWS Φ25 BOP+2730 Ø 40mm 10
CWS Φ50 BOP+2875
0

DWG-CSCEC-D00-FD-AR-ID-13-ML-00-0001-00 AUG. 2022


155

3
CWS Φ50 BOP+2550 CWS Φ20 BOP+2730 ceilinglimit ceilinglimit ceilinglimit
Ø 50mm 26
150 CWS Φ50 BOP+2865 HWS Φ20 BOP+3020 4 DWG-CSCEC-D01-FD-ME-PL-01-ML-00-0001-00 AUG. 2022
D01 140
CWS Φ40 BOP+2980 D01 Ø 40mm 13
─────
150
─────
WATER METER 5 DWG-CSCEC-D01-FD-ME-PL-01-ML-00-0002-00 AUG. 2022
CWS Φ25 BOP+2820 Ø 50mm 3
T07 RECEPTION RECEPTION RECEPTION T07
HWS Φ20 BOP+2940 Drawings 6 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0001-00 AUG. 2022
PRESSURE REDUCING 1 2
CWS Φ25 BOP+2820 Ø 65mm / 8-2bar
CWS Φ32 BOP+2815 50
BEDROOM BEDROOM
25mm BEDROOM
VALVE 7 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0002-00 AUG. 2022
DRESSING
CWS Φ32 BOP+2815
ROOM
MASTER
BEDROOM
MASTER
BEDROOM
MASTER
BEDROOM RECEPTION
CWS Φ32 BOP+2815 MASTER
8 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0003-00 AUG. 2022
285

BATHROOM
HWS Φ25 BOP+3110
CWS Φ25 BOP+3130 9 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0004-00 AUG. 2022
O W
MASTER
BEDROOM CWS Φ20 BOP+2820
150
H W SH CH ELEVATOR O W 9 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0005-00 AUG. 2022
04 WH 100 06 150 HWS Φ20 BOP+2940 LOBBY-01
HOUSEKEEPING

H W SH CH
in
ROOM

CWS Φ32 BOP+2815 O W 10 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0008-00 AUG. 2022


ceilinglimit

04 WH 50 08 LAUNDRY
H W SH CH
150

CWS Φ32 BOP+2815 distance between angle valves 120 mm 04 WH 50 02 AUG. 2022
CWS Φ25 BOP+2820 O W DRESSING DRESSING DRESSING 11 DWG-CSCEC-D01-FD-ME-PL-02-ML-00-0011-00
CWS Φ40 BOP+2810 for master bathroom and common bathroom ROOM
04 WH 50 05 ROOM ROOM
04 WH 50 01
H W SH CH 04 WH 100 03 25 mm for
215

HWS Φ20 BOP+3170 BATHROOM


typical 12 DWG-CSCEC-D00-FD-ME-PL-04-00-00-0009-00 AUG. 2022
04 WH 100 05
150

04 WH 100 02

150
8600

150
CWS Φ25 BOP+3135 LAUNDRY CORRIDOR CWS Φ25 BOP+3140 CORRIDOR LAUNDRY WM LAUNDRY CORRIDOR
HWS Φ20 BOP+3200 13 DWG-CSCEC-D00-FD-ME-PL-05-00-00-0000-00 AUG. 2022
HWS Φ20 BOP+3200
150

HWSLOBBYΦ20 BOP+2960 CWS Φ25 BOP+3135 HWS Φ25 BOP+2970


HWS Φ20 BOP+3205 14
HWS Φ25 BOP+3200
LOBBY
HWS Φ25 BOP+3200 HWS Φ20 BOP+2850
LOBBY
F.F.L 31.55 M
T.O.S 31.45 M
CWS Φ32 BOP+3130
ENTRANCE
CWSENTRANCE
Φ20 BOP+2870
CWS Φ32 BOP+2775 CWS Φ25 BOP+2790 CWS Φ20
ENTRANCE
BOP+2690 25 mm pipe down
15
850

150

150
D-2-A-3

KITCHEN & KITCHEN & KITCHEN &


150

LOBBY
CWS Φ32 BOP+2845 HWS Φ20 BOP+2810 valve
150
150

150

150

150

1315
850

for WM

150
ENTRANCE CORRIDOR
CWS Φ20 BOP+2750
DINING DINING
CWS Φ32 BOP+2775 CWS Φ20 BOP+2710
DINING
CWS Φ20 BOP+2850 GUEST
16
PRV(7') 8 BAR TO 2 BAR
CWS Φ25 BOP+2850 MASTER HWS
TOILET Φ20 BOP+2970 HWS Φ20 BOP+2890 CWS Φ20 BOP+2870GUEST MASTER MASTER
GUEST
HWS Φ20 BOP+3130

785
TOILET TOILET
BATHROOM
50
BATHROOM
CWS Φ25 BOP+2850 CWS Φ25 BOP+2770 HWS Φ20 BOP+2960 BATHROOM BATHROOM BATHROOM CWS Φ40 BOP+2780
BATHROOM
HWS Φ20 BOP+2970 KITCHEN
HWS Φ20 BOP+2970 CWS Φ40 BOP+2780 HWS Φ20 BOP+2890
210

17

295

285
CWS Φ50 BOP+3025 HWS Φ25 BOP+2970 CWS Φ25 BOP+2740 HWS Φ20 BOP+2890 775
185

185

185
HWS Φ20 BOP+2990
50

GUEST
HWS Φ20 BOP+2970

150
180
CWS Φ50 BOP+2670 190
CWS Φ25 BOP+2770
290

BEDROOM
HWS Φ20 BOP+2970

375
TOILET
CWS Φ20 BOP+2850 CWS Φ25 BOP+2770 HWS Φ20 BOP+2960 CWS Φ40 BOP+2780 CWS Φ25 BOP+2890 1 SCR-CSCEC-D00-ME-ML-0006-00 10-12-2022
CWS Φ40 BOP+2615 D-2-A-1 CWS Φ25 BOP+2740 D-2-A-1 HWS Φ20 BOP+2970
HWS Φ20 BOP+2970 CWS Φ25 BOP+2890
150

150

150
150

150

150

CORRIDOR
CWS Φ50 BOP+2550 CWS Φ40 BOP+2770 D-2-A-2
CWS Φ25 BOP+2790
CWS Φ25 BOP+2960
400 235 CWS Φ25 BOP+2990
HWS
CWS
Φ20
Φ25
BOP+2970
BOP+2790 HWS Φ20 BOP+3170
DW25 mm 2 SCR-CSCEC-D00-ME-ML-0007-00 10-26-2022
CWS Φ32 BOP+2955 CWS Φ20 BOP+2870 HWS Φ20 BOP+2970 CWS Φ25 BOP+2790 150 855
HWS Φ20 BOP+2970 CWS Φ32 BOP+2845 910 930 150
Isolation valve Documents 3 SCR-CSCEC-D00-ID-13-0006-00 01-05-2023
CWS Φ20 BOP+2960 150 HWS Φ20 BOP+2960 CWS Φ20 BOP+2790
HWS Φ20 BOP+2970 HWS Φ20 BOP+2890 HWS Φ20 BOP+2970
CWS Φ50 BOP+2685 should shutoff all sanitary fixtures CWS Φ50 BOP+2925
LOBBY
CWS Φ40 BOP+2780 4 SCR-CSCEC-D00-ME-ML-0033-00 22-03-2023
CWS Φ50 BOP+2550 MECH.CLOSET FTR SPR
CWS Φ25 BOP+2850 ENTRANCE

D-3-C-1
D01 CWS Φ40 BOP+2690 D01
CWS Φ50 BOP+2550 CORRIDOR inside the bathroom CWS Φ50 BOP+2775 HWS Φ20 BOP+2690
───── CWS Φ50 BOP+2685 ─────
T08
150
CWS Φ40 BOP+2690 CWS Φ40 BOP+2550 CWS Φ32 BOP+2785 T08 COORDINATION TABLE:
CWS Φ50 BOP+2550 WM closet should be maintained as
ed

GARBAGE
CWS Φ50 BOP+2685 HWS Φ20 BOP+2970
CWS Φ40 BOP+2550 ROOM
CWS Φ25 BOP+2950 HWS Φ20 BOP+3170 Discipline Signature Date
HWS Φ20 BOP+3170
CWS Φ40 BOP+2780 valve
150 905 905 150 GUEST
CWS Φ50 BOP+2550 per IFC HWS Φ20 BOP+2970

150
CWS Φ25 BOP+2960 HWS Φ20 BOP+2890
TOILET
04 WH 80 01
CWS Φ40 BOP+2840 CWS Φ20 BOP+2800 W.M-CLOSET A.R.-A.R. Magdy Allam
CWS Φ25 BOP+2790 HWS Φ20 BOP+3020 CWS Φ40 BOP+2780

630
CWS Φ32 BOP+2845 CWS Φ25 BOP+2770 HWS Φ20 BOP+2980 HWS Φ20 BOP+2970 LAUNDRY BEDROOM
150

HWS Φ20 BOP+2890


150

150
150

CWS Φ20 BOP+2850 CWS Φ32 BOP+2795 CWS Φ32 BOP+2785 01


O W A.R.-A.I. Magdy Allam

550
D-2-A-1 HWS Φ20 BOP+2890 D-2-A-1

150
20mm H.B HWS Φ20 BOP+2970 HWS Φ20 BOP+2970 PRV(7) 8 BAR TO 2 BAR
KITCHEN &
HWS Φ20 BOP+2940 CWS Φ25 BOP+2770
375
0

CWS Φ25 BOP+2740 HWS Φ20 BOP+2970 CWS Φ40 BOP+2780 H W SH CH


175

535
DINING HWS Φ20 BOP+2970
190

CORRIDOR
CWS Φ25 BOP+2750 CWS Φ25 BOP+2770 CWS Φ25 BOP+2795 S.C.
CWS Φ25 BOP+2850 CWS Φ25 BOP+2750
1390

195
04 WH 100 01
390

MASTER MASTER
790

790

HWS Φ25 BOP+2970


150

RECEPTION
BATHROOM GUEST CWS Φ20 BOP+2850 HWS Φ20 BOP+2890 GUEST BATHROOM CWS Φ40 BOP+2790 MAID
150MAID
CWS Φ25 BOP+2850
BATHROOM
HWS Φ20 BOP+2970
BATHROOM
S.S.

150
CWS Φ20 BOP+2750
TOILET
HWS Φ25 BOP+2970 CWS Φ20 BOP+2750
TOILET
CWS Φ25 BOP+2795 HWS Φ20 BOP+2920 TOILET ROOM
CWS Φ25 BOP+2790
ELEC.ROOM SERVICE ELEVATOR
CWS Φ20 BOP+2850 CWS Φ25 BOP+2850 HWS Φ20 BOP+2870 50 mm
HWS Φ20 BOP+3090 LOBBY
HWS Φ20 BOP+2970
KITCHEN & KITCHEN &
HWS Φ20 BOP+3150 CWS Φ32 BOP+2795 HWS Φ25 BOP+3085 HWS Φ20 BOP+2890 E.L. Li YONG
150
150

150
150

DINING DINING
HWS Φ20 LOBBY
BOP+3150
150

150

CWS Φ20 BOP+2750 CWS Φ32 BOP+3155 CWS Φ20LOBBYBOP+2800 CWS Φ20 BOP+2890 CWS Φ25 BOP+2790
CWS Φ32 BOP+3205 HWS Φ20 BOP+2920
HWS Φ20 BOP+3090 HWS Φ25 BOP+3130 HWS Φ20 ENTRANCE
BOP+3150 ENTRANCE
HWS Φ25 BOP+3130 P.L. Jie YuanQing

150
120
CWS Φ32 BOP+2885 move the valve to be inside the toilet

345
8600

04 WH 100 04 150

150
CWS Φ32 BOP+2745
W.M-CLOSET
04 WH 100 06 HWS Φ20 BOP+3160 HVAC Li Yang
HWS Φ20 BOP+3070 CWS Φ25 BOP+3160 CWS Φ25 BOP+3210 32 mm
HWS Φ20 BOP+3090 150 1125 150
HWS Φ20 BOP+3070 LAUNDRY CORRIDOR CORRIDOR HWS Φ20 BOP+2890 LAUNDRY
785
150

04 WH 50 04 FAC Mo Yan
150

150 150

225
CWS Φ32 BOP+2835 CWS Φ20 BOP+2790 CWS Φ32 BOP+2785 MASTER
HWS Φ20 BOP+2890
HWS Φ25 BOP+3090 CWS Φ40 BOP+2780 DRESSING 04 WH 50 03 DRESSING BATHROOM
DRESSING
ROOM
MASTER CWS Φ25 BOP+2790 125 O W ROOM ROOM CWS Φ20 BOP+2790 CWS Φ20 BOP+2790 BATHROOM
Clamp with rubber OTHER
BATHROOM
CWS Φ32 BOP+2785
150 125
O W HWS Φ25
20BOP+2790
150 150 H W SH CH HWS Φ20 BOP+2745
04 WH 100 07 180 150 150
H W SH CH 80 mm CWS Φ25 BOP+2690 150 REVISION TABLE:

230
MASTER
in maid toilet (typical)
135 570

BEDROOM
O W
LAUNDRY 04 WH 80 02
150 495 D-3-J-1
H W SH CH 780 CWS Φ25 BOP+2790
CWS Φ40 BOP+2830 CWS Φ20 BOP+2790 MAID ELEC.ROOM
MASTER
1015

TOILET
HWS Φ20 BOP+2860
150

CWS Φ25 BOP+2840 MASTER MASTER BEDROOM


at

BATHROOM GUEST
STAIR 02 BEDROOM BEDROOM
04 FOR APPROVAL 26-03-2023
365

CWS Φ25 BOP+2840 TOILET


BEDROOM
LOBBY
ENTRANCE
MAID BEDROOM BEDROOM 02
03 FOR APPROVAL 22-02-2023
ROOM
KITCHEN HWS Φ25 BOP+3065
D01 CWS Φ25 BOP+2790 RECEPTION RECEPTION D01 02 FOR APPROVAL 06-02-2023
STAIR 01
───── ─────
T09
150 1085 150
T09 01 FOR APPROVAL 10-01-2023
00 FOR APPROVAL 26-11-2022
ceilinglimit ceilinglimit ceilinglimit

CORRIDOR
No. Description Date App.

DRAWING TITLE:
ceilinglimit
5850

RECEPTION
02
BEDROOM
re

D01 - RESIDENTIAL TOWER


01
BEDROOM

The comments are applicable on the typical apartments


4th FLOOR PLAN PLUMBING
D01
─────
D01
─────
SYSTEM LAYOUT
T10 T10

Designed Checked Approved


TERRACE

ZHANG JIE YANG

Drawn Date Scale

8300 9600 8550 7800 7800 7800 7800 9100 ZHU 26-03-2023 1:100

D01 D01 D01 D01 D01 D01 D01 D01 D01


───── ───── ───── ───── ───── ───── ───── ───── ─────
T11 T12 T13 T14 T15 T16 T17 T18 T19 SHD-CSCEC-D01-ME-PL-01-04-00-0001-0000-04
Document Part Sheet Sequence
Contractor Building Trade Discipline Elements Floor Level No. Rev.
Type No. No.
re a
te d
in
Ma
s te
rP
DF
Ed
i to
r
re
a te
di
nM
as
te r
PD
F
Ed
i to
r