Request For Inspection

Date: 20-Feb-2023
Request no. RFI-CSCEC-12-D01-ME-M1-0973-00
Project No. & Title: E18066-0200S - The Central Business District of the New Administrative Capital of Egypt

Employer: Engineer: Contractor:

We request your attendance to inspect the following works : Duct work installation and test of corridor for M1 floor

1. Type : Electrical Mechanical installations


2. Inspection Time : 10:00 Date : 21-Feb-2023
3. Location: Zone Road Stations Structure Other

M1 floor corridor

First Second Third


4. Inspection :

5. Purpose of Inspection :
1. Electrical 2. Mechanical

raceways and boxs for electrical system Light fittings Mechanical installations
Furniture elect. culvert Sub-stations Pumping stations
MV cables Civil works & finishings Sleeves installations
Street lighting cables
Street lighting poles
Telephone duct Bank
TV cables

MIR-CSCEC-12-D01-ME-HD-0268-00
MIR-CSCEC-12-D01-ME-HD-0570-00
MIR-CSCEC-12-D01-ME-HD-0571-00
MIR-CSCEC-12-D01-ME-HD-0572-00
MIR-CSCEC-12-D01-ME-HD-0573-00
Others (specify) MIR-CSCEC-12-D01-ME-HD-0574-00
Duct work installation and test of corridor for M1 floor
Particular Details

Submitted by : Li Jian Ming Signature: Li Jian Ming


6. Inspection report : Signature
1. Alignment & levels has been checked. However, levels of the duct shall match with approved shop drawing and to be co-ordinate with all other trades.
Surveyor 2. Span between supports, galvanized angle size and rod diameter has shall be according to approved calculations approved material submittal.
3. All dampers(volume, fire & smoke) & Expansion Jointsand Insulation works are not installed yet and shall be submitted separately after installation.
Elect. Eng. 4. Sleeves through penetrated walls has not installed yet and filling material to be as per approved material submittal.
5. Seismic supports to be submitted for approval at separate inspection.
6. Co-ordination with all other trades is contractor sole responsibility & Contractor shall be held responsible for any corrective action required without any extra cost or time.
Mech. Eng. 7. Contractor to ensure all duct boxes connections are properly tightened.
8. Any change in duct routing to be implemented in as As-Built drawings so final approval is subjected to as built drawings approval A.Adel-Reda Elsayed / 26/02/2023
Civil Eng.

ITS

Date/time of inspection :

7. Engineer's Representative Comments:

The works are : Approved Approved as Noted Rejected

Signature Hassanein Ali Date : 26-02-2023


Attach all relevant particular test forms
Approval shall not relieve Contractor of his liabilities under the Contract or constitute authorization of any change to Contract Documents.

S-PRC-SS-02(F31) Rev 2
'  
  

 
 
#
 3#  
 0 
 +. +1 23




  
 

 
     !"#$%& '( !)*(



&( *
*
 )
)
)
)
   

+ ,(&
  7  #-3 8#$  9:&:+$+;77&$: '9<=>?/)>+@
      $  :++=++   ?*+A*+
      
! " 7  #-3 8#$ $1& :'(&/0,

+!  -%
   $ 
 #  $  
  "   %  %"
  &&'( $  )*+*+
$,&-   ,
$ #" .#  . $ %   

.(  ( 
/*0 ' 
1." #%2  
  % 3  3  2  
  4 .  3#  2  
  *    ##2  

  
The contractor is requested stick with the requirement of delivering and storage as mentioned method of statement and specification.
-All galvanization coating shall be G90 Z275 negative tolerance shall not accepted.
-Contractor is responsible for any damage for during storage or installation and it is required to change the damage piece if requested by engineer.
&5 -Final approval based on the quality of collecting duct and installation and leak test
A. Adel- Reda .Elsayed 11/10/2022

/ ) -( ' &&


. 3  .    #   #  #       

 

       .   4 5

$ %  
Hassanein Ali   11-10-2022
 3   .  3   .            .6 5 ".   .  
   "4 . .  

$1& $$+97?@&3
Project No. P2&P6 Date 10/9/2022

Computed by Checked by

Subject D01-MZF Total


T t l Air Conditioning System
Galvanised Steel Rectangular Medium Pressure Fresh Air Duct

Results

Gross Weight Duct Area Insulation Area


(kg) m2 m2
424 50 55

Weight Area
Strait Duct 373 43
Elbow 13 2
Reducer 7 1
Take Off 31 4
Plenum 0
Ring 0 0
End Cap 0 0
'    

 
 
#
 3#  
 0 
 +. +1 23/




  

 

 
     !"#$%& '( !)*(


&( *
*
 )
)
)
)
   

+ ,(&
  7  #-3 8#$  97+$+:;7-&-<=$,69<>?@/@?+A
      $  =++:++   B*+@*+
      
! " 7  #-3 8#$ $1& ='(&/0,

+!  -%
   $ 
 #  $  
  "   %  %"
  &&'( $  )*+*+
$,&-   ,
$ #" .#  . $ %   

.(  ( 
/*0 ' 
1." #%2  
  % 3  3  2  
  4 .  3#  2  
  *    ##2  

  

The contractor is requested stick with the requirement of delivering and storage as mentioned method of statement and specification.
&5 -All galvanization coating shall be G90 Z275 negative tolerance shall not accepted.
-Contractor is responsible for any damage for during storage or installation and it is required to change the damage piece if requested by engineer.
-Final approval based on the quality of collecting duct and installation and leak test
A. Adel- Reda .Elsayed 11/10/2022

/ ) -( ' &&


. 3  .    #   #  #       

 

       .   4 5

$ %   Hassanein Ali   11-10-2022


 3   .  3   .            .6 5 ".   .  
   "4 . .  

$1& $$+97BA&3
Project No. P2&P6 Date 10/9/2022

Computed by Checked by

Subject D01-MZF Total


T t l Air Conditioning System
Galvanised Steel Rectangular Low Pressure Fresh Air Duct

Results

Gross Weight Duct Area Insulation Area


(kg) m2 m2
35 5 6

Weight Area
Strait Duct 28 4
Elbow 7 1
Reducer 0 0
Take Off 0 0
Plenum 0
Ring 0 0
End Cap 0 0
'  
  
 
 #
  3#  
 0 
 +. +1 234


 

  
 
 

 
 
 

     !"#$%& '( !)*(

&(
( *
* )
)
 )
)    

+ ,(&
  7  #-3 8#$  97+$+:7;' <0=<$'9=>?@/+?AB
      $  <++>++   @*+A*+
      
! " 7  #-3 8#$ $1& <'(&/0,

+!  -%
   $ 
 #  $  
  "   %  %"
  &&'( $  )*+*+
$,&-   ,
$ #" .#  . $ %   

.(  ( 
/*0 ' 
1." #%2  
  % 3  3  2  
  4 .  3#  2  
  *    ##2  

  
The contractor is requested stick with the requirement of delivering and storage as mentioned method of statement and specification.
-All galvanization coating shall be G90 Z275 negative tolerance shall not accepted.
-Contractor is responsible for any damage for during storage or installation and it is required to change the damage piece if requested by engineer.
&5 -Final approval based on the quality of collecting duct and installation and leak test
A. Adel- Reda .Elsayed 11/10/2022

/ ) -( ' &&


. 3  .    #   #  #       

 

       .   4 5

$ %   Hassanein Ali  


11-10-2022
 3   .  3   .            .6 5 ".   .  
   "4 . .  

$1& $$+97@B&3
Project No. P2&P6 Date 10/9/2022

Computed by Checked by

Subject D01-MZF Total


T t l Air Conditioning System
Galvanised Steel Rectangular Medium Pressure Fresh Air Duct

Results

Gross Weight Duct Area Insulation Area


(kg) m2 m2
279 33 36

Weight Area
Strait Duct 255 29
Elbow 21 3
Reducer 0 0
Take Off 3 1
Plenum 0
Ring 0 0
End Cap 0 0
'  
  

 
 
#
 3#  
 0 
 +. +1 23




  

 

 
     !"#$%& '( !)*(


&( *
*
 )
)
)
)
   

+ ,(&
  7  #-3 8#$  9:&:+$+;7,'<:$'9<=>?/+>@A
      $  :++=++   B*+@*+
      
! " 7  #-3 8#$ $1& :'(&/0,

+!  -%
   $ 
 #  $  
  "   %  %"
  &&'( $  )*+*+
$,&-   ,
$ #" .#  . $ %   

.(  ( 
/*0 ' 
1." #%2  
  % 3  3  2  
  4 .  3#  2  
  *    ##2  

  
The contractor is requested stick with the requirement of delivering and storage as mentioned method of statement and specification.
-All galvanization coating shall be G90 Z275 negative tolerance shall not accepted.
&5 -Contractor is responsible for any damage for during storage or installation and it is required to change the damage piece if requested by engineer.
-Final approval based on the quality of collecting duct and installation and leak test
A. Adel- Reda .Elsayed 11/10/2022

/ ) -( ' &&


. 3  .    #   #  #       

 

       .   4 5

$ %   Hassanein Ali   11-10-2022


 3   .  3   .            .6 5 ".   .  
   "4 . .  

$1& $$+97BA&3
Project No. P2&P6 Date 10/9/2022

Computed by Checked by

Subject D01-MZF Total


T t l Air Conditioning System
Galvanised Steel Rectangular Medium Pressure Fresh Air Duct

Results

Gross Weight Duct Area Insulation Area


(kg) m2 m2
530 60 66

Weight Area
Strait Duct 463 52
Elbow 48 5
Reducer 7 1
Take Off 12 2
Plenum 0
Ring 0 0
End Cap 0 0
01235678
9331131 3233
 


! """""""""""#$%&#%'&'#
‹Œ‰
Ž‘ˆ‰Š‘’“”•–‘—˜‘ˆ™
012345679 9 647.# #
41547455924 216 0(4417
!6217 "
 7#$%4641&
'7'14'(6(&41'0!)*+!97, -)0(7, -
89:;9<=>?

@:A9BCDEC<F9CGH:IJHCKLM?
@:N OCP;Q >CP;Q RCP;Q S:DE<
T UVWXXT? YWYYY? TWTZ[?
[ U\WXZT? YWYYY? TWTZ[?
Z U\WXZT? YWYYY? TW\Z]?
\ UVWZYX? YWYYY? YW]^[?
V UVWZYX? YWYYY? TWTZ[?
X U\W_VX? YWYYY? YW]^[?
] U\W_VX? YWYYY? TWTZ[?
`J=BM?
@:N @:A9B `J=BCB<Daa9E9ACDE `J=CB9b<D:E c9EG<FC
de df de df P;Q
Tg?hijklmnop [?qrs? Z?qrs? tuu tuu \Tv\Tv[WV? YWZYV?
[g?hijklmnop \?qrs? V?qrs? tuu tuu w^ ˆ‰Š YWZVY?
Zg?hijklmnop T?qrs? V?qrs? tuu tuu \TvX[v[WV? YWZVV?
\g?hijklmnop \?qrs? X?qrs? tuu tuu \Tv[TvTWV? YWZVY?
Vg?hijklmnop X?qrs? ]?qrs? tuu tuu w^ ˆ‰Š YWZVY?
Xg?hijklmnop V?qrs? ]?qrs? tuu tuu \TvX[v[WV? YWZVY?
]g?hijklmnop ]?qrs? [?qrs? tuu tuu \TvX[v[WV? YWZ[V?
Lxyy:=<BCJEACBxyy:=<CB9<<H9;9E<BCDEC<F9CGH:IJHCb::=ADEJ<9CB>B<9;?
@:N =O => =R zO > R |{H O
JB<DbD<D9BCP|@};Q
|> |R
{HJB<DbD<D9BCP|@}=JAQ
aO a> aR
e ~? ~? ~? ~? ~? ~?
 ~? ~? ~? ~? ~?
c:JACG=:xyBM?
8=:xyCEJ;9 @:N c:JAC<>y9 KFJ=Jb<9= ;DE ;JO {EJIH9A
€li‚ti‚ T €li‚ti‚ ƒli‚ti‚ TWYY? TWYY? „
r‚kmƒ‚mko?o†j‡‚ [ €li‚ti‚ ƒli‚ti‚ TWYY? TWYY? „
c:JABM?
"/ /"/ %$!19! &206912&$3$02
354&40217*1414!9&6153$3$963 7
€‚
012345679 9 647.# #
41547455924 216 0(4417.
!6217 "
 7#$%4641&
'7'14'(6(&41'0!)*+!97, -)0(7, -

†‡ˆ‰ƒ„‰Š‹‡ŒˆŽ‰‰ƒ‘
89:;<=>?@A@?B9:CD><:DE?FDG
H<EE?=I?BD;9J<DE?I=J?:=BH<>9@?8KLL=J;
<MNO BPQNR @NSTUVWMVPX YMZ KXVM
 [, ,/[, " 61694%\[#\#$,/61&  
# 9,,/%%  21694%\%\#$,/61& % 
# 9,,%#  21694%\#\$,/61& /, 
/ 9[[,]] % 616464^*45_ # 05^&_
% 9[[,]]#` ` 4(1449245621a*45_  05^&_
[ [ `]/bc 4 b\bc12(26!521 % 05^&_
. 9//]#% *4\(226#\%  % 05^&_
] 9]]] # 61646# d 05^&_
` 9//## '64&41# % 05^&_
 9[[,]] ] e 44&41] ƒ„ d 05^&_
 9]]] ] 61646] ƒ„ f 05^&_
# 9// ] 144"2] ƒ„  
/ 9// ] *4\(26] ƒ„ g 05^&_
% 9[[,]]  e 44&41 h 05^&_
, 9]]]  61646 h 05^&_
[ 9//  144"2 % 
. 9// *4\(26 i 05^&_
] "#, #, "41 216&416 # 05^&_
` 9%%%] e269 )#j # 05^&_
# 9##,klmb 94&*(41%j  05^&_
# 9.. /,  12419 j  05^&_
## 9#, [/klmc 34 69 ^[/[[_  05^&_
#/ nopggiqqrsft utvwxyz{t|x}wz~tosft s 05^&_
#d giggrdst 9 &%\% s 05^&_
#i giggrfst 9 &%\f # 05^&_

"/ /"/ %$!19! &206912&$3$02


354&40217*1414!9&6153$3$963 7
s‰WY
012345679 4562 647/## #
41547455924216 Švxmnkxhxph‹mjlu‹mlhq~qhjmhxphvmuqhŒmlhxphjunluvhkuhŽVZh 0'4417
6217!4" xm‘p’pl“hŽŠ}hoplŒml”hpouluph‹xp‹•hujqhŒmnjqhmh–phu~Œu‹ml—W
7#!$4641
%&7%14%'6'41(%0 (61)04* +,-. 97* +,
0'7* +
9:;<:=>?

ZW[X

@;A:BCDEC=F:CGH;IJHCKLM
@;N OCP<Q ?CP<Q RCP<Q S;DE=
T UVWXVY ZWZZZ ZWZTX
[ U\W]^_ ZWZZZ ZWZTX
Y U\W^]Y ZWZZZ UZW\T^
\ U\W^]Y ZWZZZ ZWZTX
V UVWY[Y ZWZZZ UZW\T^
X UVWY[Y ZWZZZ ZWZTX
_ UVWXVY ZWZZZ ZWY[T
] U\W]^_ ZWZZZ ZWY[T
`J>BM
@;N @;A:B `J>BCB=Daa:E:ACDE `J>CB:b=D;E c:EG=F
de df de df P<Q
Tghijklmnopq \hrst Yhrst uvv uvv wxlpuqpqhlmqhyTZ ZW\YV
[ghijklmnopq \hrst [hrst uvv uvv \Tz\Tz[WVh{|sh}uo~qsln ZWZ]X
Yghijklmnopq Yhrst Vhrst uvv uvv \Tz[TzTWVh{|sh}uo~qsln ZWY\Z
\ghijklmnopq Vhrst Xhrst uvv uvv wxlpuqpqhlmqhyTZ ZW\YV
Vghijklmnopq Thrst Xhrst uvv uvv \Tz\Tz[WVh{|sh}uo~qsln ZWYYZ
Xghijklmnopq Xhrst \hrst uvv uvv \Tz\Tz[WVh{|sh}uo~qsln ZWY\Z
_ghijklmnopq Thrst _hrst uvv uvv wxlpuqpqhlmqhyTZ ZWYZV
]ghijklmnopq [hrst ]hrst uvv uvv wxlpuqpqhlmqhyTZ ZWYZV
L€;>=BCJEACB€;>=CB:==H:<:E=BCDEC=F:CGH;IJHCb;;>ADEJ=:CB?B=:<
@;N >O >? >R ‚O ? R „ƒH O
JB=DbD=D:BCP„@<Q
„? „R
ƒHJB=DbD=D:BCP„@>JAQ
aO a? aR
† ‡ ‡ ‡
ˆ ‡ ‡ ‡
01 101 $! 19 22693"!3!02
454422175!.614-2'!.!74#8
abcd
012345679 4562 647$"" "
41547455924216 0'4417/
6217 !
7"#$4641
%&7%14%'6'41(%0 (61)04* +,-. 97* +,0'7
* +

hijkefgklminjopkqrkesc

RSTU:VWXSYSX>STZ[W:T[\
]:\\XV^X>[US_:[\XTV>]:WSBXRK``V_U
:;<= >?@<A B<CDEFG;F?H I;J KHF;
 9**$$ 21694$L$L"#*061 M* 
" 9**$" 21694$L"L#*061 $ 
* N0 5 64126521 " 05
N 9NN*MM M O4541M efg $ 05
/ 9MMM M 66164(6M efg " 05
M 900 M P144!2M efg Q 
Q 900"M %6541M efg " 05
 900M -4L'2(6M efg N 05
 9MMM 66164(6  05
" 9NN*MM O4541 0 05
0 900 P144!2  
$ 900" %6541 $ 05
* 900 -4L'2(6 / 05
N !6"*"* !412166416 " 05
/ 9$$$M O269 " 05
M 9"*N0 0 4469N0NN  05

!0 0!0 $# 19 216923#3#02


45441217-1514966174#4#984 9
5 4 3 2 1 Client:

**NOTE :- LEVELS INDICATED IN SECTION AND PLANS ARE


**NOTE :- LEVELS INDICATED IN SECTION AND PLANS ARE
MEASURED FROM + 330.75
MEASURED FROM + 330.75 Ministry of Housing, Utilities
D01 D01 D01 D01 D01
X04 X04' X05 X06' X06 & Urban Development

F.F.L+328.25
C.L. +328.15 OPEN TO BELOW

FCU-D01-08 FCU-D01-08 New Urban Communities


Model No. : 00000 Model No. : 00000
OPEN TO BELOW A. Flow : 237 L/S A. Flow : 237 L/S
B.O.U 2665 B.O.U 2665 Authority
FCU-D01-04 FCU-D01-04 OPEN TO BELOW
Total Air Gap Total Air Gap
Model No. : 00000 Model No. : 00000
Length: 7515 mm Length: 7515 mm
A. Flow : 421 L/S A. Flow : 421 L/S
B.O.U 2770 B.O.U 2770

D01 D01
Y08 Y08 Main Consultant:
FCU-D01-08 FCU-D01-08

M5x25
M5x25

D D
F.F.L+330.75 F.F.L+330.75
C.L. +330.65 C.L. +330.65
FCU-D01-04 FCU-D01-04

F.F.L+330.75
C.L. +330.65

Shop drawing-Consultant:

3B-D01-M-A3
D01 D01
Y09 Y09

FCU-D01-01

FCU-D01-01
ѣᔰ‫ޡ‬ቶㅢӂᔰ䇴ᴿ䲆‫ޢ‬ਮ
THE SECOND CONSTRUCTION LIMITED COMPANY OF CHINA
CONSTRUCTION EIGHTH ENGINEERING DIVISION
FCU-D01-01 FCU-D01-01
Model No. : 00000 Model No. : 00000
A. Flow : 171 L/S A. Flow : 171 L/S
B.O.U 2685 B.O.U 2685 Contractor:
General Comments - Ductwork CODE-B
D01 D01 1- Drawings of General standard installations details shall be submitted separately for review and approval. Details provided with building plans are indicative only.
Y10 Y10

3B-D01-M-A3
F.F.L+330.75
C.L. +330.65
2- Show the fire rated walls on the drawings and provide sectional detail for pipe sleeves penetration for walls and slab clarifying: material, size, invert level, sealant, escutcheon plates…etc.; noting that the

FCU-D01-01

FCU-D01-01
sealant and Sleeve/box out penetrating fire rated wall, shaft, slab or mechanical room shall have the same rating of the wall / slab.
FCU-D01-01 F.F.L+330.75 FCU-D01-01
F.F.L+330.75
C.L. +330.65 3- Provide fire damper on all ducts penetrating fire rated wall, shaft, slab or mechanical room.
Model No. : 00000 C.L. +330.65 Model No. : 00000
A. Flow : 171 L/S A. Flow : 171 L/S
B.O.U 2720 B.O.U 2720 4- Contractor to ensure that equipment installed are fit and/or accommodate the available space.
5- Provide installation benchmark/mockups for all items on site prior commencement of installation for final approval. Project Name:
6- Duct elbows should be provided with turning vanes as per SMACNA standards.
7- Volume dampers to be added wherever necessary for proper air test & balancing. Central Business District
8- Riser diagram shall be provided.
9- Coordinated shaft details drawings (including longitudinal sections from basement to roof) showing, supporting details and branches at each floor to be provided to ensure that shafts will accommodate all
Of the
services inside. New Administrative Capital
D01 FCU-D01-03 FCU-D01-03 D01 10- All FCU, IU, VD, FD, MD, valves, VAV, fans, filters, controllers…etc. shall be accessible. Provisions shall be provided for easy accessibility of MEP services and all access doors shall be as per
Y11 Model No. : 00000 Model No. : 00000 Y11
FCU-D01-03 FCU-D01-03
A. Flow : 290 L/S A. Flow : 290 L/S CBD EAST - PHASE 1
B.O.U 2767 B.O.U 2770
approved RCP plans.
11- Ducts, pipes, equipment and false ceiling levels and air outlets locations, size, color, shape… etc. shall be as per RCP plans and ID approval.
12- Contractor is required to provide a table for ducts clarifies: duct material (black steel, galvanized, aluminum… etc.), duct construction, traverse and longitudinal joint, duct thickness, duct reinforcement, Key Plan:
hangers and supports span versus duct size, total weight, area of application (Supply, Return, Exhaust …..Etc.).
D01 D01 13- Contractor is requested to show/Indicate on duct routing air flowrate, velocity and pressure drop at each section.
Y12 Y12
14- Provide duct installation detail for flexible connection at building expansion joint.
NORTH
FCU-D01-02 15- Contractor is requested to provide coordinated sectional detail at all corridors clarifying: false ceiling level and all other trades invert levels.
Model No. : 00000
FCU-D01-02 A. Flow : 230 L/S
FCU-D01-07 B.O.U 2685
16- Contractor must submit shop drawings signed and sealed by a qualified professional engineer for multiple equipment supports and trapeze hangers. Include seismic calculations relevant to the life safety
Model No. : 00000

FCU-D01-07
A. Flow : 154 L/S FCU-D01-03
system and design calculations as per project specifications (Section 230548).
B.O.U 2815 Model No. : 00000
FCU-D01-03 17- Any deviation from original IFC drawing should be highlighted/clearly identified and addressed to engineer review and approval.
A. Flow : 290 L/S
B.O.U 2742
18- Coordination with other trades has not been checked, Contractor shall be held responsible for any corrective action if required without any extra time/cost.
19- All open-ended ducts on roof shall be provided with wire mesh screen & Goose Neck.

1B-D01-M-A
20- Show thermostats on the drawings.
FCU-D01-02

1B-D01-M-B
FCU-D01-02
Model No. : 00000
A. Flow : 230 L/S FCU-D01-03
B.O.U 2717 Model No. : 00000
A. Flow : 290 L/S
Sheet Cuts:
B.O.U 2745 Part-8 Part-7

F.F.L+330.75
C.L. +330.65
FCU-D01-03

D01 FCU-D01-07 D01


STAIRS
D01M1 013 10
C Y13 F.F.L+330.75 F.F.L+330.75 Y13 C
C.L. +330.65 C.L. +330.65 FCU-D01-07
Model No. : 00000
Part-5 Part-6
A. Flow : 154 L/S
B.O.U 2820

D01 D01
Part-4 Part-3
Y14 Y14 -contractor to clarify the resons for shop drawing resubmission however is approved before
FCU-D01-02
-for any correction at REV 0 make all modified area clouded with rev 01
Model No. : 00000 FCU-D01-02
A. Flow : 230 L/S Model No. : 00000 - contractor to submit drawing for corridor and apartments separately Part-1 Part-2
B.O.U 2717 FCU-D01-02 A. Flow : 230 L/S **NOTE :- LEVELS INDICATED IN SECTION AND PLANS ARE
B.O.U 2685

SHAFT ARRANGMENT
MEASURED FROM + 330.75

SEE DETAILS SHAFT No. ME-20


SHAFT ARRANGMENT
SEE DETAILS SHAFT No. ME-19
NOTES:-

1B-D01-M-A

FCU-D01-02
FCU-D01-03
Model No. : 00000
A. Flow : 290 L/S
B.O.U 2742
FCU-D01-03

FCU-D01-07
FCU-D01-02

FCU-D01-07
D01 Model No. : 00000 D01
Y15 FCU-D01-02 Y15 ahmed adel 14/03/2022
Model No. : 00000 A. Flow : 154 L/S

A. Flow : 230 L/S B.O.U 2818


B.O.U 2717

D01 D01
Y16 Y16

FCU-D01-02
Model No. : 00000
FCU-D01-02 A. Flow : 230 L/S
B.O.U 2685

ABBREVIATION
D01 D01 D01 D01 D01 D01 D01 D01 D01
X07 X08 X09 X10 X11 X12 X13 X14 X15
FCU-D01-04

2B-D01-M-B2
FCU-D01-04
Model No. : 00000

1B-D01-M-A
A. Flow : 421 L/S
B.O.U 2745

FCU-D01-03
Model No. : 00000
A. Flow : 290 L/S
B.O.U 2742
FCU-D01-03
LEGEND
FCU-D01-07

F.F.L+330.75
C.L. +330.65
FCU-D01-07
FCU-D01-07 FCU-D01-07
Model No. : 00000
Model No. : 00000
A. Flow : 154 L/S A. Flow : 154 L/S

B.O.U 2740 B.O.U 2818

D01 D01
Y17 Y17

FCU-D01-02
Model No. : 00000
A. Flow : 230 L/S
B.O.U 2720
FCU-D01-02

F.F.L+330.75
C.L. +330.65

B OPEN TO BELOW B

1B-D01-M-A2
CORRIDOR
D01M1 019 -
F.F.L+330.75
C.L. +330.65
FCU-D01-03
Model No. : 00000
A. Flow : 290 L/S
B.O.U 2740

FCU-D01-03

FCU-D01-07

FCU-D01-07
Model No. : 00000

A. Flow : 154 L/S


B.O.U 2825 Reference Table:
D01 D01 Type No. Ref. No. REV. Date
Y18 Y18
FILING ROOM
PRINTING ROOM
FCU-D01-02 D01 01 024 -
D01 01 023 - 01 E18066-0103D-FD-12-D01-MH-1-M1-001 01 30.05.2019
Model No. : 00000
HOUSE KEEPING
A. Flow : 230 L/S D01M1 006 09
F.F.L+330.75
02 E18066-0103D-FD-12-D01-MH-7-00-009 01 30.05.2019
B.O.U 2720 C.L. +330.65
OFFICE
OPEN TO BELOW OPEN TO BELOW OFFICE E18066-0103D-FD-12-D01-MH-7-00-010
D01 01 022 - D01 01 021 -
03 00 31.03.2019
FCU-D01-02 FCU-D01-23 Drawings 04
Model No. : 00000
AIR Flow : 180L/S
B.O.U 2705
05
OPEN TO BELOW OPEN TO BELOW
ENTRANCE LOBBY
D01GF 023 - 06
07

OPEN TO BELOW 08
ELEVATOR LOBBY
D01M1 005 -
F.F.L+330.75 01 SCR-CSCEC-12-'0(*/ 00 03.08.2019
C.L. +330.65 FCU-D01-23
Documents 02 SCR-CSCEC-12-'0(*/ 00 02.09.2019
FCU-D01-01
Model No. : 00000
A. Flow : 171 L/S
FM-FTR
B.O.U 2785 D01 01 026 02

SHAFT ARRANGMENT
Coordination Table:
SHAFT ARRANGMENT
SEE DETAILS SHAFT No. ME-32
SEE DETAILS SHAFT No. ME-31
STORE MECH CLOSET FM-FTR

2B-D01-M-A6
D01M1 012 01 D01M1 011 01 D01M1 010 02 SP-FTR
FCU-D01-01 D01M1 007 02 ELEC. CLOSET
Discipline Signature Date
Architecture
OPEN TO BELOW
Structure C.
OPEN TO BELOW CORRIDOR
D01 01 027 - Structure S.
D01 D01
Y19 Y19
SHAFT ARRANGMENT Electrical
FCU-D01-02 SEE DETAILS SHAFT No. ME-14
BMS CLOSET MECH. CLOSET
Model No. : 00000 D01 01 047 01 D01 01 029 01
SHAFT ARRANGMENT Plumbing
A. Flow : 230 L/S SEE DETAILS SHAFT No. ME-37
CORRIDOR SHAFT ARRANGMENT
D01M1 019 - SEE DETAILS SHAFT No. ME-07
B.O.U 2740
F.F.L+330.75 HVAC
C.L. +330.65

GARBAGE ROOM
SHAFT ARRANGMENT
Other
D01 M1 018 06
SEE DETAILS SHAFT No. ME-04
FACILITY MANAGEMENT OPEN SPACE
020 01 020 -

FCU-D01-02
Total Air Gap LOBBY
FCU-D01-07 D01M1 015 04
Length: 5340 mm Revision Table:
FCU-D01-23
FCU-D01-07
Model No. : 00000
Model No. : 00000 STORE
SHAFT ARRANGMENT

A. Flow : 154 L/S A. Flow : 180 L/S D01 M1 016 01


SERVICE ELEVATOR LOBBY
ELECTRICAL ROOM
D01 M1 009 04
SEE DETAILS SHAFT No. ME-02

B.O.U 2800 B.O.U 2806 D01M1 014 01


F.F.L+330.75
F.F.L+330.75

FCU-D01-23
C.L. +330.65
STAIRS C.L. +330.65
OFFICE OFFICE
D01M1 008 10 SHAFT ARRANGMENT D01 01 018 - D01 01 019 -
SEE DETAILS SHAFT No. ME-03
REFER TO SCR-CSCEC-
12-D01-ME-GL-0049-00

SHAFT ARRANGMENT
SEE DETAILS SHAFT No. ME-12 OPEN TO BELOW

FCU-D01-02
ELECTRICAL ROOM
01 RESUBMIT AS PER CONSULTANT COMMENTS 2022-02-27 L.W.
D01 01 017 01

00 APPROVED ISSUED 2021-11-20 L.W.


STAIRS Description Date App.
A OPEN TO BELOW OPEN TO BELOW A No.
FCU-D01-02
Model No. : 00000 Drawing Title:

FCU-D01-08
A. Flow : 230 L/S
B.O.U 2720
SHAFT ARRANGMENT
SEE DETAILS SHAFT No. ME-40

FCU-D01-05
D01 FCU-D01-03 D01 RESIDENTIAL TOWER D01
Y20 Y20
F.F.L+330.75
C.L. +330.65 DUCT WORK LAYOUT
FIRST FLOOR MEZZANINE (M1)
OVERALL PLAN
FCU-D01-03
Model No. : 00000
A. Flow : 290 L/S
B.O.U 2830

Designed Checked Approved


FCU-D01-02

FCU-D01-02 FCU-D01-05
Model No. : 00000 Model No. : 00000 A.S D.S. L.W.
A. Flow : 230 L/S A. Flow : 582 L/S
B.O.U 2730 B.O.U 2660
D01 D01
Y21 Y21 Drawn Date Scale

FCU-D01-08 W.T 1:100


Model No. : 00000
2022-02-27
3B-D01-M-C A. Flow : 237 L/S
B.O.U 2740

SHD CSCEC 12 D01 ME HD 02 M1 00 1275 0000 01


D01 D01 D01 D01 D01 D01 D01 D01 D01 D01 D01 D01 D01 D01
X04 X04' X05 X06' X06 X07 X08 X09 X10 X11 X12 X13 X14 X15 Packa. Build. Sub Elemt. Floor Part Sheet Sequnc. Rev.
Type Contractor Discp
5 4 3 2 1 No. Type Discp Type Level No. No. No. No.