This document discusses the design of confinement bars for a concrete structure. It determines that confinement bars are needed based on the calculated concrete and bar shear resistances. It then calculates the required area, spacing, and maximum spacing of the confinement bars. However, it finds that the calculated bar spacing of 0.47mm does not meet the maximum allowed spacing of 250mm. Therefore, confinement bars cannot be used since the requirements are not met.
This document discusses the design of confinement bars for a concrete structure. It determines that confinement bars are needed based on the calculated concrete and bar shear resistances. It then calculates the required area, spacing, and maximum spacing of the confinement bars. However, it finds that the calculated bar spacing of 0.47mm does not meet the maximum allowed spacing of 250mm. Therefore, confinement bars cannot be used since the requirements are not met.
This document discusses the design of confinement bars for a concrete structure. It determines that confinement bars are needed based on the calculated concrete and bar shear resistances. It then calculates the required area, spacing, and maximum spacing of the confinement bars. However, it finds that the calculated bar spacing of 0.47mm does not meet the maximum allowed spacing of 250mm. Therefore, confinement bars cannot be used since the requirements are not met.
Reduction Factor of Shear Strength φ= 0.60 Yield Stress, fy = 320 MPa Concrete Shear Force, Vc = (√ fc') / 6 * b * d * 10 -3 = 12.075 kN Concrete Shear Resistance, φ ∗ Vc = 7.245 kN need confinement rebar Confinement bars shear resistance φ ∗ Vs = Vu - φ ∗ Vc = 6708.593 kN Confinement Bars Shear Force Vs = 11180.988 kN Use 2 P 8 Av = ns * π / 4 * P = 100.53 mm 2 2 Ast Confinement Bars Distance needed between bars s = Av * fy * d / ( V s * 103 ) = 0.47 mm Maximum distance between bars smax = d / 2 = 81.00 mm Maximum distance between bars smax = 250.00 mm Distance used s= 0.47 mm Take distance s= 0 mm Use 2 P 8 0
Hence, confinement bars cannot be used since no eligible requirements